FIR2024-00025 Taylor Shellfish Fire Alarm - FIR Plot / Site Plans - 6/24/2024
TAYLOR SHELLFISH WET PROCESSING FACILITY FIRE ALARM SYSTEM SHELTON, WASHINGTON Ai Mason Co Fire Marshal wir Approved with Conditions 08/12/2024 9:22:52 AM CONDITIONS: -Prior to scheduling acceptance test, the fire dept. (Knox) key box shall be installed. - To schedule an inspection, email: rcollins@masoncountywa.gov SH -T SHEET TITL FA- 01 SYSTEV I \ FO R V ATI O \ FA-02 TYPICAL WIRI\G D IAG RAV S FA-02A TYPICAL V OUNTING DETAILS FA-O3 SYSTEV CALC U LATI O \ S FA-04 FLOOR FRE ALARM LAYOUT FA-05 RIS DIAGRAM SHEET INDEX TYPE OF WOR<: 3UILD \G FRE ALARV SYSTEV INSTALL NEW SIEMENS FIRE A_ARN SYSTEM WITH COM v1UNICATOR. SCOPE OF WORK GUARDIAN SECURI-Y 1743 1ST AVE. S., SEATTLE, WA 98134 1-(206) 622-6545 MONITORING COMPANY W SCHE3LE A\3 COND T FILL C AT WIRE DESIGNATION SYMBOL DESCRIPTION NUMBER OF CONDUCTORS SIZE TYPE COLOR CODE D DATA LINE - ADDRESSABLE LOOP TWISTED PAIR WITH SHIELD #16 FPL/FPLR RED (JACKET) S SIGNALING CIRCUIT - FEED TWO #14 FPL/FPLR RED (JACKET) S' SIGNALING CIRCUIT - RETURN TWO #14 FPL/FPLR RED (JACKET) CONDUIT FILL CHART NO. OF CONDUCTORS VOLTS WIRE SIZE TYPE DIMENSIONS AREA TWO 600V #12 AWG THHN/THWN .244 0.D. .0467 TWO 600V #14 AWG THHN/THWN TWISTED .210 0.D. .0346 TWO CONDUCTOR 300V #18 AWG FPL TW CABLE .156 0.D. .0191 CONDUIT FILL CALCULATE THE TOTAL AREA OF THE WIRE BEING RUN IN THE CONDUIT FROM THE TABLE ABOVE. CHOOSE THE SIZE OF CONDUIT BASED ON THE MAXIMUM FILL DIMENSION FROM THE TABLE BELOW THAT DOES NOT EXCEED THE TOTAL AREA OF THE WIRE. CONDUIT SIZE MAXIMUM FILL 1/2" .12 SQUARE INCH 3/4" .21 SQUARE INCH 1" .34 SQUARE INCH 1-1/4" .60 SQUARE INCH 1-1/2" .82 SQUARE INCH 2" 1.34 SQUARE INCH FIGURES ARE BASED ON 40% CONDUIT FILL AND ARE TAKEN FROM N.E.C., CHP. 9, TABLE 4. SHIELDED WIRE TO BE GROUNDED AT POINT OF ORIGIN PUNCHED THROUGH EACH DEVICE WRAPPED WITH TAPE AND TAPED AT END FOR SIEMENS SYSTEM: DO NOT INSTALL ADDRESSABLE INITIATING DEVICES UNTIL PREPROGRAMMED WITH DEVICES ADDRESS. 1. NUMBERS ADJACENT TO DEVICE SYMBOL DENOTE DEVICE CIRCUIT/ADDRESS DEVICE 01-1-02 WOULD BE THE SECOND DEVICE ON ADDRESSABLE LOOP 1. 2. DETECTOR AND AUDIBLE CIRCUIT POLARITY SHALL BE OBSERVED. 3. AUDIBLE/VISUAL CIRCUIT WIRING IS SUPERVISED. NO PARALLEL BRANCHING IS PERMISSIBLE 4. INSTALLATION SHALL BE IN STRICT CONFORMANCE WITH THE NATIONAL ELECTRIC CODE, NFPA 72, LOCAL CODE(S), AND/OR AUTHORITY HAVING JURISDICTION. 5. INSTALLATION MATERIALS (LE. CONDUIT, WIRE, FITTINGS, HANGERS, STANDARD BOXES, FIBER OPTICS CABLE, FITTINGS, AND ASSOCIATED EQUIPMENT) ARE NOT SUPPLIED BY SIEMENS CERBERUS DIVISION. 6. DETECTORS SHALL NOT BE MOUNTED IN DIRECT AIR STREAM OF AIR SUPPLY OUTLETS. PER NFPA 72 2-3.5.1 7. WIRING SHALL BE PER PLAN WITH RESPECT TO CONDUCTOR SIZE, & OR CABLE TRAY, TYPE, QUANTITY AND COLOR CODE. CONDUCTORS SHALL BE PERMANENTLY, AND UNIQUELY MARKED FOR FUTURE IDENTIFICATION. 8. INSTALLING CONTRACTOR SHALL RETURN ONE SET OF ACCURATELY MARKED DRAWINGS FOR "AS BUILT" PURPOSES. 9. FOR ADDITIONAL INSTALLATION INSTRUCTIONS, REFER TO CATALOG CUT SHEETS AND/OR INSTALLATION INSTRUCTIONS. 10. THE 120vac POWER ELECTRICAL WORK SUPPLYING FIRE ALARIV SYSTEM PANELS MUST COMPLY WITH ARTICLE 725 AND 760 OF NFPA 70, N.E.C. AND NFPA 72, SPECIFICALLY SECTION 1-5.2.5.2: IN REFERENCE TO DEDICATED BRANCH POWER SOURCES. 120vac POWER SHALL NOT BE APPLIED TO FIRE ALARM PANEL WITHOUT DIRECT SUPERVISION OF FIRE ALARM TECHNICIAN. 11. ALL HORN/STROBE AND STROBE DEVICES SHALL BE MOUNTED AT A HEIGHT OF 80" A.F.F. OR 6" BELOW DROPPED CEILING, WHICHEVER IS LESS. 12. ALL MANUAL PULL STATIONS SHALL BE MOUNTED AT 48" A.F.F. TO THE ACTIVATION DEVICE. 13. ALL PANEL NUMBERS AND CIRCUITS WILL BE ON THE RECORD DRAWINGS SET. 14. ALL 120VAC CIRCUITS ARE FROM DEDICATED CIRCUITS FROM THE EMERGENCY GENERATOR. 15. PER NFPA 72 SECTION 5-3.6.1.3 DETECTORS SHALL NOT BE INSTALLED UNTIL AFTER THE CONSTRUCTION CLEAN-UP OF ALL TRADES IS COMPLETE AND FINAL. EXCEPTION: WHERE REQUIRED BY THE AUTHORITY HAVING JURISDICTION FOR PROTECTION DURING CONSTRUCTION. DETECTORS THAT HAVE BEEN INSTALLED PRIOR TO FINAL CLEAN-UP BY ALL TRADES SHALL BE CLEANED OR REPLACED IN ACCORDANCE WITH NFPA 72 CHAPTER 7. 16. WIRING SHALL RUN CONTINUOUS FRO' FACP TO FIRST DEVICE ON A CIRCUIT AND THEN FROM DEVICE TO DEVICE WITHOUT SPLICING IN PULL BOXES OR OTHER BACK BOXES OF DIFFERENT CIRCUITS. 17. ALL WIRING SHALL BE METERED, VERIFIED TO BE CONTINUOUS, FREE OF GROUND AND FREE OF SHORTS BETWEEN CONDUCTORS AND OTHER CIRCUITS PRIOR TO FINAL EQUIPMENT TRIM. 18. ALL CABLES SHALL BE MARKED AS INDICATED ON FIRE ALARM RISER WITH A PERMANENT LABEL AT ALL DEVICES, JUNCTION BOXES AND FACP. 19. THE ELECTRICAL CONTRACTOR SHALL CLEAN ALL DIRT AND DEBRIS FROM THE OUTSIDE AND INSIDE OF THE FIRE ALARM BACK BOXES AND JUNCTION BOXES AFTER COMPLETION OF THEIR INSTALLATION. 20. DETECTORS MUST BE RATED FOR TEMPERATURE IN THE ENVIRONMENT IN WHICH IT IS LOCATED. 21. ALL WIRING BETWEEN FLOORS SHALL BE LOCATED IN CONDUIT. 22. NFPA, 72 2007 6.4.2.2.2 ALL STYLES OF CLASS A CIRCUITS USING PHYSICAL CONDUCTORS (E.G., METALLIC, OPTICAL FIBER) SHALL BE INSTALLED SUCH THAT THE OUTGOING AND RETURN CONDUCTORS, EXITING FROM AND RETURNING TO THE CONTROL UNIT, RESPECTIVELY, ARE ROUTED SEPARATELY. THE OUTGOING AND RETURN (REDUNDANT) CIRCUIT CONDUCTORS SHALL NOT BE RUN IN THE SAME CABLE ASSEMBLY (I.E., MULTI -CONDUCTOR CABLE), ENCLOSURE, OR RACEWAY. 23. NFPA 72 2007 A.6.4.2.2.2 A GOAL OF 6.4.2.2.2 IS TO PROVIDE ADEQUATE SEPARATION BETWEEN THE OUTGOING AND RETURN CABLES. THIS SEPARATION IS REQUIRED TO HELP ENSURE PROTECTION OF THE CABLES FROM PHYSICAL DAMAGE. THE RECOMMENDED MINIMUM SEPARATION TO PREVENT PHYSICAL DAMAGE IS 305 MM (1 FT) WHERE THE CABLE IS INSTALLED VERTICALLY AND 1.22 M (4 FT) WHERE THE CABLE IS INSTALLED 24. LOCKOUT SHALL BE INSTALLED ON THE MAIN POWER DISCONNECT CIRCUIT BREAKER. NFPA 72.10.6.5.4 25. THE MAIN POWER DISCONNECT CIRCUIT BREAKER SHALL HAVE A RED MARKING. NFPA 72.10.6.2.3 26. MOUNT A SIGN STATING "FIRE ALARM CONTROL ROOM" ON OUTSIDE OF DOOR LEADING TO FIRE PANEL. IFC 509-1 QUANTITY SYMBOL DESCRIPTION 1 1 2 3 5 1 MODEL MANUFACTURER BACKBOX MOUNTING HEIGHT FACP FIRE ALARM CONTROL PANEL FC901 -U3 SIEMENS FH901 -U3 66" A.F.F. TO TOP DOC DOCUMENT ENCLOSURE SS000674 SIEMENS 60" A.F.F. TO CENTER 0 SMOKE DETECTOR 00H941 W/ SIEMENS (ADDRESSABLE -PHOTO) DB-11 BASE 4S DEEP W/ 1G RING CEILING HEAT DETECTOR (ADDRESSABLE) H1921 W/ SIEMENS DB-11 BASE 4S DEEP W/ 1G RING CEILING oH , HEAT DETECTOR, F135 (ADDRESSABLE) DT-135WP W/ XTRI-M MINIMODULE SIEMENS W.P. J-BOX W/ CEILING 4S DEEP BOX g MANUAL PULL STATION XMS-S (ADDRESSBLE) SIEMENS 4S DEEP W/ 1G RING 48" A.F.F. TO CENTER 111 wP METAL PULL STATION (ADDRESSBLE) MSM-K-WP W/ XTRI-M SIEMENS MINIMODULE PROVIDED 48" A.F.F. TO CENTER moo' c FIRE ALARM HORN/STROBE SLHSCR-F SIEMENS 4S DEEP W/ 1G RING CEILING FIRE ALARM STROBE SLSCR-F SIEMENS 4S DEEP W/ 1G RING CEILING ,o. FIRE ALARM HORN/STROBE (WEATHERPROOF) AS-75-R-WP SIEMENS 80' A.F.F. TO BOTTOM OR U.O.S. FIRE ALARM STROBE (WEATHERPROOF) ST-75-R-WP SIEMENS WPSBBS-R 80" A.F.F. TO BOTTOM 1111111 E wP J-BOX - - END -OF -LINE RESISTOR 0 1 1 BATTERY 12V 12AH SLA1 104 BATTERY TG7 FIRE ALARM COMMUNICATOR AD-TG7FSV TELGUARD PROVIDED 66" A.F.F. TO TOP BATTERY 12V 8AH SLA1 075 BATTERY 6 MM INTERFACE MINI MODULE XTRI-M MINI MODULE SIEMENS 4S DEEP BOX VERIFY IN FIELD SYMBOLS LEGEND OUTPUT INPUT ACTIVATE NOTIFICATION APPLICATIONS TRANSMIT ALARM SIGNAL TO CENTRAL STATION TRANSMIT TROUBLE SIGNAL TO CENTRAL STATION ANY SMOKE/HEAT/PULL X X ANY FIRE PANEL TROUBLE X STEVE SENDLAKOWSKI NICET LEVEL III CERT. #115442 EXP. 01 /01 /2027 CO 1743 1ST AVE. SO., SEATTLE, WASHINGTON FAX (206) 628-4990 TEL. (206) 622-6545 1 RELEASE/REVISIONS REV. BY: W 0 CLE DESCRIPTION SHOP DRAWINGS FIRE MARSHALL CORRECTIONS DATE st N N, N 0 N 0 07/24/24 2<aaaa J_ U LL 0 z_ (/) U) w 0 w Q co 8 cc co cc cm 0'cnv� � oCJz O Q wJ _cw cco ♦ )LLT v,J J J w 0 J cZ cr Ems 0 (1) } N SCALE: NOT TO SCALE DRAWN BY: C. ENGSTFELD DESIGNED BY: M. WADE DATE: 06/24/2024 BACKROUND PLAN PROVIDED BY: \,0B NUMBER:71788-3} SHEET FA-01 WIRE DESIGNATION GENERAL NOTES SEQUENCE OF OPERATIONS MATRIX 7P,t2 ctot7 Proprietary & Confidential, Copyright 2013 by Guardian Security Systems, Inc. All Rights Reserved TO FC901 FACP s FROM FACP 0 G Gam", CC SMOKE/HEAT DETECTORS HORN STROBE D + 2 + /11/1 XMS-M MANUAL PULL STATION TYPICAL DATA LOOP WIRING DETAIL STROBE WEATHERPROOF HORN STROBE HORN STROBE TYPICAL NAC CIRCUIT WIRING DETAILS TO SLC FIELD DEVICES TO ANNUNCIATOR POWER DATA 2 3 0 0 XTRI-M 8 7 6 ,&\o °/2 HORN STROBE TO NEXT DEVICE EOL CAT.5 WIRE (IN CONDUIT) ALARM TROUBLE -9911. 00 0 11 11 1 eee 00 e 00 ee 00 ee eoeeeee� n u T n u T q 0 0 ®ete 0 ❑ ❑ 0 0 O 0 0 CO 000 0 00 ®00 00 FC901-U3 CONTROL PANEL DETAILS #1 6/2C WIRES (IN CONDUIT) n TROUBLE EXDL-O OMNIDIRECTIONAL ANTENNA NOTE: IF ANTENNA IS TO INSTALL OUTDOOR, ANTENNA CABLE SHALL BE IN FLEXIBLE CONDUIT NEW TELGUARD TG-7FS LTE RF COMMUNICATOR R 0 0 T SIM 1 0 2 0 1 ❑ System Status 2 ❑ LEDs 3 ❑ 4 ❑ 5 ❑ Power LED LED Mode Toggle Button TELGUARD Digital TG-7FS LTE U 0 1 2 3 4 0 0 0 0 5 6 0 0 0 2 3 1 2 0 0 0 ALARM TYPICAL WIRING DETAILS FLAG NOTE: TO AC TRANSFORMER (12V 800mA) PLUGGED INTO UNSWITCHED OUTLET DEDICATED BRANCH CIRCUIT. AC TRANSFORMER LINES IN FLEXIBLE CONDUIT. z z STEVE SENDLAKOWSKI NICET LEVEL III CERT. #115442 EXP. 01 /01 /2027 1 C"Z W CO3 tg 1,0 CO 0' 1ST AVE. SO., SEATTLE, WASHINGTON FAX (206) 628-4990 TEL. (206) 622-6545 IREV. BY: I W J U W J 0 DESCRIPTION SHOP DRAWINGS FIRE MARSHALL CORRECTIONS DATE N 07/24/24 N 0 n 0 —J Z E5 w 0 0 oC 0_ w rI v L J J w cc 0 J r �CALE: NOT 1' ui J Zt. LU EE U TO SCALE DRAWN BY: C. ENGSTFELD DESIGNED BY: M. WADE DATE: 06/24/2024 BACKROUND PLAN PROVIDED BY: _JOB NUMBER:71788-3} Proprietary & Confidential, Copyright 2013 by Guardian Security Systems, Inc. All Rights Reserved SHEET FA-02 CEILING TILE SUPPORT BRIDGE 4S BOX CEILING STROBE OR HORN/STROBE STROBE MOUNTING (DROP CEILING) HORN STROBE/STROBE 7 80" A.F.F. TO BOTTOM MANUAL PULL STATION -T--- 48" A.F.F. TO CENTER L J 4S BOX 4" SQUARE DEEP BACK BOX WITH 1G TRIM RING STROBE & MANUAL STATION MOUNTING DETAILS HARD LID -\ CEILING SUPPORT BRIDGE 4S BOX CEILING STROBE OR HORN/STROBE STROBE MOUNTING (HARD LID) JUNCTION BOX MOUNTED ON \ CEILING FLEX JUNCTION BOX MOUNTED AGAINST CEILING SUPPORT 1 / // / 7 / / / 0 0 0 0 TO NEXT DEVICE SMOKE/HEAT DETECTOR 2= SUSPENDED ILLUMINATED CEILING SMOKE/HEAT DETECTOR MOUNTING DETAILS TYPICAL MOUNTNG DETAILS STEVE SENDLAKOWSKI NICET LEVEL III CERT. #115442 EXP. 01 /01 /2027 RELEASE/REVISIONS rO CO ON 1743 1ST AVE. SO., SEATTLE, WASHINGTON FAX (206) 628-4990 (206) 622-6545 REV. BY: CLE W J 0 DESCRIPTION SHOP DRAWINGS FIRE MARSHALL CORRECTIONS DATE 07/02/24 07/24/24 i r (if J U Q u_ 0 z u) cn 0 CC a_ I— LU /_^J v / u_ J J W cc 0 J Q WQ� CD cco U� CC>-Z O Q WIZ! LU W CC col U_ T Q 1-• w 0 0 Hi D 2 Q 0 II j 1 2 `/CALE: NOT TO SCALE DRAWN BY: C. ENGSTFELD DESIGNED BY: M. WADE DATE: 06/24/2024 BACKROUND PLAN PROVIDED BY: ...JOB NUMBER:71788-3) Proprietary & Confidential, Copyright 2013 by Guardian Security Systems, Inc. All Rights Reserved I- SHEET FA-02A} SIEMENS FC901 BATTERY CALCULATION Project: Panel TAYLOR SHELLFISH WET ID: FACP Date: July 24, 2024 Standby (C) PROCESSING Alarm (D) Minute s= Hours= 24 5 Device Description Qty Standby Total Standby Alarm Total Alarm (mA) (mA) (mA) (mA) Main Board 1 178 178 203 203 Modules FSD901 Remote Annunciator FCA City Tie 1 20 20 85 85 1 0 40 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 cZ z NAC Circuit 1 (Max Load) NAC Circuit 2 0 0 0 1200 0 0 0 1424 2 o HFP-11 Smoke Detector HFPO-11 Smoke Detector 00H941 Smoke Detector OH921 Smoke Detector OP921 Smoke Detector 00HC941 Fire/Carbon Monoxide Detector HFPT-11 Heat Detector HI921 Heat Detector FDCI0422 Quad Interface Module XMS-S,D Manual Pull Station XTRI-S Intelligent Single Input Module XTRI-D Intelligent Dual Input Module XTRI-R Intelligent Relay Module XTRI-M Intelligent Single Input MiniModul- HZM Remote Conventional Zone Module HCP Control Point Module ILED-HC,HW Intelligent Remote Lamp 1.4 0 1.4 0 1.4 0 1.4 0 2 0.68 1.36 0.68 1.36 0.3 0 0.3 0 0.3 0 0.3 0 0.75 0 0.75 0 1.4 0 1.4 0 3 0.28 0.84 0.28 0.84 1.2 0 1.2 0 1 0.5 0.5 0.5 0.5 0.5 0 0.65 0 0.5 0 0.95 0 0.5 0 0.75 0 6 0.5 3 0.5 3 1.4 0 1.4 0 1.4 0 1.4 0 1 1.4 0 1.4 0 Total(A)= 203.7 Total(B)= 2917.7 Battery Capacity:1.2x (AxC)+((.0167xD)xB) divided by 1000 6.16 8.0 Amp Hour RECOMMENDED MINIMUM BATTERY SIZE = 12VDC 7.0 AMP -HOUR Notification Appliance Circuit Detail PROJECT: TAYLOR SHELL FISH WET PROCESSING Panel: NEW FACP Date: June 25, 2024 Wire Resistance 3.07 CURRENT TOTAL= 2624.00 1 SLHSCR @15Cd 3 SLSCR @15Cd 40 1 AS-75-R-WP @30Cd 178 4 AS 75-R W P @110Cd 178 1 ST-75-R WP @15Cd 146 DEVICES 10 TOTAL mA= Total Wire Resistance (R ) 120 178 712 146 1200 14 400 21.05 1200 ( WL *2 )*(R/ft) 2.46 Total Device Load, Amps (I) (Total Cct Load) 1.20 Voltage Drop (E ) (E= I * R) EOL Voltage 24-E) SLHSCR @15Cd 44 SLSCR @15Cd 40 1 AS-75-R-WP (a,30Cd 178 7 AS-75-R-W P @110Cd 178 ST-75-R-WP @15Cd 146 DEVICES 8 TOTAL mA= 0 178 1246 0 1424 14 415 2.95 21.05 20.37 1424 Total Wire Resistance (R ) Total Device Load, Amps (I) Voltage Drop ( E ) ( WL *2 )* (Rift) (Total Cct Load) (E=I*R) EOL Voltage 24-E) SYSTEM CALCULAT!ONS 2.55 1.42 3.63 20.37 STEVE SENDLAKOWSKI NICET LEVEL III CERT. #115442 EXP. 01 /01 /2027 O I GUARDIAN SECURITY 1743 1ST AVE. SO., SEATTLE, WASHINGTON 98134 FAX (206) 628-4990 (206) 622-6545 W I-- 1 REV. BY: W J U CLEJ z 0 F= 0_ Ly U up w 0 SHOP DRAWINGS FIRE MARSHALL CORRECTIONS in F- a 07/02/24 07/24/24 2<aaaa 1 J U I11 ��Z vJ w 0C8O) Fr'c U� 1- w a lei _CCw COI U (/) T -J J w CC 0 J �i- SCALE: NOT TO SCALE DRAWN BY: C. ENGSTFELD DESIGNED BY: M. WADE DATE: 06/24/2024 BACKROUND PLAN PROVIDED BY: Q0B NUMBER:71788-3j Proprietary & Confidential, Copyright 2013 by Guardian Security Systems, Inc. All Rights Reserved L FA-03 MECHANICAL ROOM (107) WOMEN RESTROOM 103 MEN RESTROOM 104 c JANITOR 105 RAIN GEAR ROOM 106 FLAGNOTE: MINI MODULE IS MOUNTED BEHIND WEATHERPROOF INITIATING DEVICES. 0 ■ �,:�� l.T.�� !.T=11 !i.1 _. �R■� � j 35 27 1 0 J 34 WP S2-6 ♦ wp 110Cd SLOPE DOWN •� S2-7 WP 110Cd S2-8 A _ Q TRR11Q WP EOL 1 ••� DRAIN 1 1� D,S 5 ' I D,S EQUIPMENT PAD SLOPE DN • WP SLOPE DOWN 1 DS 33 EQUIPMENT PAD o- D,S SLOPE DN Ud S1-0 P� 110Cd ♦ WP w►: D,S ,S D,S .� © w���ui� 1 Y 12 •14\ S1 6 5Cd 1 /4" / 12" SLOPE DOWN w V7 S2-4 110Cd WP CROSS BRACING BY D,S METAL BUILDING SUPPLIER 20 WP S2-3 110Cd D,S S2-2 110Cd 0■ D,S D,S SLOPE DN 3/16" / 12" SLOPE DN SLOPE DN HALF SHELL PACKING ZONE SPECIALTY PACKING ZONE TRENCH DRAIN 1 TRENCH DRAIN 1/8" / 12" SLOPE DN J D,S DE4j0 ELECTRICAL ROOM TG7 110Cd FLOOR FIRE ALARM LAYOUT SCALE: 1/8" = 1'0" F o- D,S *ci)r 86 4.Q4 D,S TRENCH DRAIN WET PROCESSING AREA (10o ) r L r- N4L4X1 S1-5 110Cd 9 D,S —C. L L \ WP S1-3 30Cd DS 0 OPEN RECEIVING DOCK AND LOADING AREA 0 STEVE SENDLAKOWSKI NICET LEVEL III CERT. #115442 EXP. 01 /01 /2027 RELEASE/REVISIONS FAX (206) 628-4990 TEL. (206) 622-6545 REV. BY: J 0 J 0 DESCRIPTION SHOP DRAWINGS FIRE MARSHALL CORRECTIONS DATE N 07/24/24 N 0 n 0 J u_ 7V 'z 0) u_i 0 0 cc 0 W rZ J J W U) 0 11� W < V) CC0) cn U� �z —1O QCC co WJ LU W T 0 } W CC 0 0 J CALE: NOT TO SCALE DRAWN BY: C. ENGSTFELD DESIGNED BY: M. WADE DATE: 06/24/2024 BACKROUND PLAN PROVIDED BY: .0B NUMBER:71788-3i SHEET FA-04 Proprietary & Confidential, Copyright 2013 by Guardian Security Systems, Inc. All Rights Reserved EOL S2 WP S2-8 11 0Cd S WP S2-7 110Cd S WP S WP S WP S WP S WP S2-5 S2-4 S2-3 S2-2 30Cd 110Cd 110Cd 27 23 11 0Cd S WP S S2-1 11 0Cd 20 D S D FACP TG7 WP 11 0Cd 1 S D S D 2 WP S1-3 30Cd 4 S D WP S WP S1-5 110Cd 110Cd S S1-6 1 5Cd S 30 D � 31 p �32 p WP WP WP 6 RISER DIAGRAM SCALE: NTS 9 12 13 S D WP S S1-8 S1-9 110Cd 15Cd 14 D 15 S "c S1-10 1 5Cd EOL S1 FLAGNOTE: MINI MODULE IS MOUNTED BEHIND WEATHERPROOF INITIATING DEVICES. STEVE SENDLAKOWSKI NICET LEVEL III CERT. # 115442 EXP. 01 /01 /2027 CO FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: CLE W 0 DESCRIPTION SHOP DRAWINGS FIRE MARSHALL CORRECTIONS w 07/02/24 07/24/24 F- a 0 'SCALE: NOT TO SCALE DRAWN BY: C. ENGSTFELD DESIGNED BY: M. WADE DATE: 06/24/2024 BACKROUND PLAN PROVIDED BY: SOB NUMBER:71788-3} Proprietary & Confidential, Copyright 2013 by Guardian Security Systems, Inc. All Rights Reserved ( SHEET FA-05 /F,Arte Ss ✓ . (G✓1rLAA. Svt etc itvir pg„, gc/A: 5(:(Lt— d u "p.m& /A-kv,-L4v (44- eN'l lile;Td:/-atozr..5- fa./40-c-~ <�