HomeMy WebLinkAboutFIR2024-00003 - FIR Plot / Site Plans - 2/26/2024Mason Co Fire Marshal Approved with Conditions 02/26/2024 7:38:11 AM BEAM CLAMP RETAINING STRAP JOI ST/BEAM- 3/8" NUT %" TOP BEAM CLAMP I"-4" PIPE V TOP BEAM CLAMP 6" PIPE 3/a' ALL THREAD ROD ADJUSTABLE RING HANGER —SPRINKLER PIPE HANGER DETAILS SCALE: N.T.S. CONDITIONS: - The calc plate shall be amended to reflect the hydraulics of the new system - Discs from welded pipe shall be provided - a hydro of 200PSI & 2 hrs shall be performed - Drops to offices shall be provided with an auxiliary drain Z PURLIN MINIMUM 14 GAUGE CADDY PH- FP Z PURLIN HANGER PIPE 3/8" ALL THREAD ROD ADJUSTABLE RING HANGER SPRINKLER PIPE MAXIMUM 3" In m Ln 8-0 717 BUILDING SECTION 1 - SCALE: I/5"=I'-0" 4 HYDRAULIC REMOTE AREA: 101- SOUTH STORAGE .15 GPM/SQ. FT. OVER 2000 SQ. FT. TOTAL DEMAND OF 17 SPRINKLERS CALCULATED 336 GPM AT 30 PSI AT BASE OF RISER 4-6 .z•IQtv I LJ- 8 26'-II" 20' -4" 17' -3" 0'-0" 4" METRAFLEX SEISMIC LOOP SEISMIC BREAKAWAY HANGER WILL BE USED TO SUPPORT METRALOOP 150' RETURN WHEN INSTALLED IN ANY ORIENTATION OTHER THAN HANGING DOWN FLEXIBLE COUPLINGS ON BRANCH LINE RISERS AS REQUIRED PER NFPA 13, TYPICAL 4 12-6 1 0 26'-7' AFF 20'-I0' \AFF \ 6'O_ ' 6 60' 12-6\ a 4-0 II NG" 8-4 nN II-6 O 11 O O T 0 0 Buz O • A 0 A. cr T 7-6 " 5-0 N 20'-10' AFF \'� 26'-7" BLR _ AFF 6 12-6 \7-6 20'-10' AFF N 6 6" METRAFLEX SEISMIC LOOP BLR LNG 4 SEISMIC BREAKAWAY HANGER WILL BE USED TO SUPPORT METRALOOP 180' RETURN WHEN INSTALLED IN ANY ORIENTATION OTHER THAN HANGING DOWN TOR c!) 5 R EXISTING RISER SCALE: N.T.S. KEYNOTES 1 EXISTING 6" UNDERGROUND FIRE SERVICE. 2 EXISTING 6" WILKINS MODEL 375ADA REDUCED PRESSURE ZONE DETECTOR CHECK ASSEMBLY WITH TAMPER SWITCHES. 3 EXISTING 6" GROOVED CHECK VALVE. 4 EXISTING 6" FIRE SERVICE TO FIRE DEPARTMENT CONNECTION. 5 EXISTING 2" MAIN DRAIN. 6 EXISTING PRESSURE GAUGE. 7 EXISTING 6" WATERFLOW SWITCH. TOLCO FIG. 1001 FAST CLAMP STEEL PIPE LATERAL BRACE TOLCO FIG. 980 UNIVERSAL SWAY BRACE FITTING TOLCO FIG. 980 UNIVERSAL SWA BRACE FITTING STEEL PIPE LATERAL BRACE TOLCO FIG, 4L SWAY BRACE ASSEMBLY SEISMIC BRACING DETAILS SCALE: N.T.S. WALL SLEEVE WALL SLEEVE FIRE SPRINKLER PLAN SCALE: I/8"=I'-0" O 6' 14 -;T„O ti D.I. fr- LF UG HYDRAULIC REFERENCE SCALE: N.T.S. =STING BURDMG 7,7.4 VICINITY MAP SCALE: N.T.S. LNG 4.0'. 4 12-6 20— F m 1 AFF 2-7 .4-5-5 � I 26' -7" 20'-10'' LNGGA 2-6 O ~ SCOT = OF nOR< KNIGHT FIRE PRCTECTION TO EXTEND THE EXISTING NET PIPE FIRE SPRINKLER SYSTEM THROUGHOUT THE NEN ADDITION PER NFPA 13. HYDRAULIC REMOTE AREA: 121- SOUTH STORAGE .20 GPM/SQ. FT. OVER 1500 SQ. FT. TOTAL DEMAND OF 13 SPRINKLERS CALCULATED 333 GPM AT 3 i P51 AT SASE OF RISER T 5-0 4-6 cl -i4-0 " 5-6+ N 20'—I0' AFF 20'-10i 4-0-6 aN II-6 SUPPLEMENTAL HYDRAULIC REFERENCE SCALE: 1/5"=I'-0" LNG 4.0 p f-/A'26T‘o3 4 6-0 WASHINGTON STATE CERTIFICATE OF COMPETENCY FIRE PROTECTION SPRINKLER SYSTEMS Randy Knighton 2789-0791-CG Level 3 Knight Fire Protection KNIGHFP044LK Signature GENERAL NOTES 7.OWNER TO PROVIDE ADEQUATE REFER TO THE NFPAI113, 2010 EDITION HEAT TO PREVENT WATER IN I. MATERIAL TO BE NEW AND PIPES FROM FREEZING IN AREAS UL LISTED. PROTECTED BY A WET PIPE 2. PIPING SHALL BE PER NFPA I3. SPRINKLER SYSTEM.(MINIMUM 40'F 3. EARTHQUAKE BRACING SHALL BE REQUIRED) PER NFPA 13. B. ALL WIRING OF ELECTRICAL 4. JOINING OF PIPE AND FITTINGS, DEVICES TO BE Sr OTHERS. THREADED, GROOVED, PLAIN END, 9. PAINTING OF PIPE AND AND WELDED SHALL , PER NFPA 13. EQUIPMENT (IF REQUIRED) BY 5. PIPE HANGERS AND METHOD OF OTHERS. HANGING TO BE PER NFPA 13. 10. FURRING OF PIPE AND EQUIPMENT 6. PIPING DIMENSIONS ARE CENTER (IF REQUIRED) BY OTHERS. Tn n=,.IT=n HANGER LEGEND J WEDGE ANCHOR FITTING LEGEND APPROVALS QTY SPRINKLERS USED SYSTEM DEMAND WATER FLOW INFO OUAUTY MK CONTROL DATE BY: BY DATE: REVISIONS CONTRACT WTH: General Mechanical 2316 S. State St. Tacoma, SPA 98405 �i it. -, t roN 44 XOURS Y KNIGHT FIRE PROTECTION, INC - ►. 9702 LATHROP INDUSTRIAL DR. SW OLYMPIA, WA 98512-9188 i° t (360) 786-8606 �/�p LICENSE N0. SNIGHFP044L% A a01 A ALL THREAD ROD K TRAPEZE ST STRAP TEE srreoL scwrxLoz MAKE / MODEL S.I1L K ��� SPRiM,1ER FINISH ESCUr61EQ1 FlNSH Tam arr REQUIRED PRESSURE 50 p.s.i. STATIC PRESSURE MASON COUNTY OWNER/ARCHITECT 2 2 JP Per 11 14 23 comments on ••Ions, talcs, & cutsheets 3 TOP BEAM CLAMP y SAMMY SCREW S SOCK —IT •p' O TTCO TT-B SR 55P TY3251 I/2° 5.6 BRASS BRASS 2l)0• 64 69 s iMEI " KH RELIABLE SR HSW RA1455 I/2° 5.6 BRASS BRA55 207 4 AVAILABLE PRESSURE 66 p.s.i. RESIDUAL PRESSURE 52 ps FLOW 1410 g.p.m. ._- C SWIVEL CLAMP ■ MT MECHANICAL TEE ._. KNIG!-IT FIRE I • RELIABLE OR 55P RAI414 I/2' 56 . CHROME CHROME 200' 2 TOTAL DEMAND 583 g.p.m. HOSE 250 g.p.m. D FLUSH SHELL EARTHQUAKE BRACING P PIPE—O—LET ���__�� ---__-M ---__- TrITAI 70 DESIGN CRITERIA CONTRACT NAME: JP B e I co -Port of Shelton 1890 East Johns Prairie Road Shaltnn WA ARSRet DATE TESTED 5/9/23 E CEILING FLANGE -.--,-2 WAY EARTHQUAKE BRACE 4 WAY EARTHQUAKE BRACE SN SHAPED NIPPLE ■_ STANDARD HAZARD MAX NFPA 13 (2013) �- TOTAL 5 CLASSIFICATION: SQ. FT. / HEAD STORAGE — ORDINARY HAZARD GROUP 2 - JOB NUMBER O F SIDE BEAM BRACKET [AI WELD FITTING 124 DENSITY GPM/ 2000 S0. FT. .20 = 23-033 OF n