Fire Alarm Certification/Final Test
FIR Location: 69 w /3
Contractor: / y Phone
Contact: ;�rMG�. UJS/,M Test Date: /y/Z�
CHECKLIST
Verify panel is in "Normal" condition and clear of any signals
Kill Power At Electrical Panel
AC Trouble/ No Power,panel & verify dedicated circuit, red breaker& lockout
`V Activate device(s), verify it activates the alarm and shows correctly on the panel
Check the Notification Alarm Circuit(NAC)for activation of devices. Walk building while
alarm is activated under battery load. Check for all lights and sounds to be in-sync
Silence Alarm
Activate a few other devices in different areas to verify alarm reactivates after being silenced
✓ Reset Alarm
Does panel still show trouble (due to AC power)?
Disconnect Signal Loop Circuit(SLC) to create/verify a trouble for each device on circuit
�L Reconnect SLC. System should reset& only AC trouble showing
Disconnect the communication line & verify communication trouble,
Do batteries AMP/HR match plans? 6 4011/f,Q " ,o/h� g- 1�i'/'✓P1M9 �a 4;xe-")r
FACP Sign on Door(s) leading to panel location?
Notification Device Device Test Log
Time Comments
Smoke detector at FACP y
Waterflow Inspector's Test A1,,4
Tamper Switch ,y
Manual pull at � �� G
Manual pull at
Manual pull at
Heat Detector
Heat Detector
Heat Detector
Heat Detector
Heat Detector
Smoke Detector
Smoke Detector
Smoke Detector
Punch List/Comments: �� �w� �✓ifi�G �9«✓ ��St�/�
t/1srh, J4-17f)
Passed Final Test? Yes No
=�
TG - 7FS
• M M U N I C A T •
TELGUARD FOR
THE ALARM COMMUNICATION EXPERTS
d COMMERCIAL FIRE
Part of the full line of Telguard universal fire communicators, the
TG-7FS can augment or replace legacy Telco lines with reliable
cellular signal reporting. AHJs know that the TG-7FS meets all UL
and ULC standards, and works in virtually every installation.
PRODUCT FEATURES
SG LTE-M I• Powers directly from a 12 or 24VDC alarm panel — no electrician
needed for an outlet. Or, for AC, use included plug-in adapter.
F Operates on LTE-M networks, for 5G longevity, lower power
consumption, and better in-building penetration.
F Interfaces with fire panels using a single DACT connection for
universal compatibility. No DACT is no problem — just add a
TG-PEM accessory to the TG-7FS.
F American made, and backed by award-winning, U.S.-based
tech support.
This is the communicator dealers have loved for over a decade, updated with a more modern 5G LTE-M cellular
radio, more efficient use of power, and more options.
You're in control when setting up and installing the TG-7FS. Apply desired settings when you're in the office or on
the road using the Telguard online dealer portal. Signals can be reported to your central station of choice.
UL Listings (AT&T and Verizon) Size (without antenna) Specifications
864 Commercial Fire 7.5 H x 11.5 W x 3.5 D in Power Consumption
• Central Station (19.05 x '' Standby:
Only)ULC Listings (AT&T Package Contents ••
S559 Commercial Fire TG-7FS universal communicator Transmit: •
•4 Commercial Burglary Antenna with extension cable ••
adapterAC • blocks
Compatible
Models .
...
Verizon(US only):TG-7FS-V TG-PEM to connect .• panels
Range of antenna cable lengths
External antenna 11STEU
For the most current product specifications and UL Listings visit telguard.com/tg-7fs.In Canada.cellular data may be carried by Rogers,Bell.Telus or SaskTel.
CHOOSE THE COMMUNICATOR THAT BEST FITS THE NEEDS OF YOUR UPGRADE, TAKEOVER, OR NEW INSTALL PROJECT.
HARDWARE OPTIONS
INPUT POWER OPTIONS
FIRE PRODUCTS M112
i MODEL
TG-7UB d
800,229.2326 13225 Cumberland Blvd SE•Suite 300•Atlanta,GA 30339•USA I telguard.com Ke
,�'2021 Telguard I Telguard and the Telguard Logo are registered trademarks of Telular Corporation.I Telular is a business unit of AMETEK,Inc.All Rights Reserved.
(E) POTTER PAD300-PD
The Symbol of Protection Photoelectric Smoke Detector
Features
• Low profile,less than 2 inches with the base
• Wide selectable sensitivity range of 1.1 to 3.50/o/foot
• Detector commimicates sensitivity to control panel Ng' W
• UL listed smoke calibration and sensitivity
• Optional locking tab to prevent unwanted removal
• Simple DIP switch address setting,no programming tool
required
• Magnetic test switch
• LED alarm indicator
• Product includes 5-year warranty
• UUKL Listed for Smoke Control
• UL268 7th edition compliant u ° '
q
0328-0541
Description Technical Specifications
The Photoelectric Smoke Detector is a listed Analog Addressable
smoke detector compatible with fire alarm control panels that utilize Operating Voltage 24 VDC
the Potter Addressable Device(PAD)protocol.The PAD300-PD is a
low profile smoke detector with a wide sensitivity range.The detector Detector Current Draw 300 µA
and base are made of a durable plastic in an off-white color to blend
in with the ceiling. Alarm Indicator I LED
The PAD300-PD has a sensitivity range of LI to 3.5%per foot and is Alar n Set-point Range 1.1 to 3.50/o/ft(3.6 to I 1%/m)
UL listed.The PAD300-PD features drift compensation and has built
in dirty detector warning as well. The PAD300-PD and the control Installation Temperature Range 32 to 120°F(0 to 49°C)
panel communicate over a proven and robust digital communication
path and the system analyzes the information at the particular device. Operating Relative Humidity Doi°to 93%(Non-condensing)
The total polling speed is less than five(5)seconds,well under the UL range
requirements.
Start-up Time Max. l sec.
The detector is compatible with any of the PAD300 series detector
bases and simply twists on.The PAD300-PD is addressed using DIP Maximum Number of Addresses 127
switches in the rear of the detector and can be easily programmed in Per Loop
the field without special tools. Maximum Number of Lighted
Indicators in Alarm Per Loop 30
Setting the Address
Each addressable device on the SLC loop must have a unique address Color Eggshell White
from 1 to 127 to function properly. The address is set using DIP
switches. Weight(without base) 9 1 g(3.2oz)
Before connecting a device to the SLC loop, take the following Dimensions(without base) Ileight: 1.42 in(36mm)
precautions to prevent potential damage to SLC or device. Verify the Diameter:3.93 in(100 mm)
following:
1.Power to the device is removed.
2.Field wiring is correctly installed.
3.Field wiring has no Open or short circuits.
Potter Electric Signal Company, LLC St. Louis, MO Phone: 800-325-3936 www.pottersignal.com
8830216-REV B 2/23 PAGE I OF 2
(E) POTTER PAD300-H D
The Symb7l of P,mfer7 rn Heat Detector
Features
• Selectable Rate of Rise and/or Fixed Heat Detector
• Low Profile
• Reliable Detection Technology
• LED Alarm Indicator
• Ambient Temperature Listing of 32°F to 150°F
• Simple DIP Switch Address Setting,No Programming Tool k7* •
Required •
• Magnetic Test Switch •
• Product includes 5-year warranty
• UUKL Listed for Smoke Control
0328-0538
Description Technical Specifications
The PAD300-HD is a listed analog addressable rate of rise and/or Operating Voltage 24 VDC
fixed temperature heat detector compatible with any fire alarm control
panel that has the Potter Addressable Device(PAD)protocol.The heat Detector Current Draw �cu1 µA
sensing portion utilizes a proven thermistor for accurate and reliable Alarm Indicator 1 LED
heat detection. The detector and base (not included) are made of a Alarm Set-point Range I",� F to 185°F(57°C to 85°C)
durable plastic in an off-white to blend in with the ceiling.
Rate of Rise Detection 1 5°F/min. 8.3°C/min.)
The PAD300-HD is UL listed with a selectable fixed temperature (Selectable Option)
point from 135° to 185° Fahrenheit and can be used for rate of rise
applications. See detector spacing limitations below. This flexibility Installation Temperature Range 32°F to 150°F(0°C to 66°C)
allows the installer to cover a wide variety of applications with a single
unit. Operating Relative Humidity o 0
The PAD300-HD and the control panel communicate over a proven
Range 0!o to 93/o(Non-condensing)
and robust digital communication path and the system analyzes the Start-up Time Max. 1 sec.
information at the particular device.The total polling speed is less than Maximum Number of Addresses
five(5)seconds,well under the UL requirements. Per Loop 127
The detector is compatible with any of the PAD300 series detector
bases and simply twists on.The PAD300-HD is addressed using DIP Maximum Number of Lighted 30
switches in the rear of the detector and can be easily programmed in Indicators in Alarm Per Loop
the field without special tools.
Color Eggshell White
Setting the Address Weight(Without Base) 68g(2.4oz)
Each addressable device on the SLC loop must have a unique address Height: 1.5 in(38 mm)
from I to 127 to function properly. The address is set using DIP Dimensions(Without Base) Diameter 3.93 in(100nun)
switches.
Before connecting a device to the SLC loop, take the following
precautions to prevent potential damage to SLC or device.Verify the
following:
1. Power to the device is removed.
2. Field wiring is correctly installed.
3. Field wiring has no open or short circuits.
Potter Electric Signal Company, LLC St. Louis, Mn Phone: 800-325-3936 www.pottersignal.com
8830210-RED'C 6/23 PAGE I OF 2
SYSTEM
SENSOR
1 '
r
Indoor Selectable- �f3
Output Strobes and '"rF
Horn Strobes for
Ceiling Applications
System Sensor L-Series audible visible notification
products are rich with features guaranteed to cut
installation times and maximize profits with lower
current draw and modern aesthetics.
Features The System Sensor L.Series offers the most versatile and
• Plug-in design with minimal intrusion into the back box easy-to-use line of horns,strobes,and horn strobes in the industry
with lower current draws and modern aesthetics.With white and red
• Tamper-resistant construction plastic housings,wall and ceiling mounting options,System Sensor
• Automatic selection of 12-or 24-volt operation L-Series can meet virtually any application requirement.
at 15 and 30 candela
Field-selectable candela settings on ceiling units: The entire L-Series product line of ceiling-mount strobes and horn
• 15,30,75,95, 115, 150,and 177 strobes include a variety of features that increase their application
versatility while simplifying installation.All devices feature a plug-in
• Horn rated at 88+dBA at 16 volts design with minimal intrusion into the back box,making installations
• Rotary switch for horn tone and two volume selections fast and foolproof while virtually eliminating costly and time-
Universal mounting plate for ceiling units consuming ground faults.
• Mounting plate shorting spring feature checks wiring continuity To further simplify installation,the L-Series utilizes a universal
before device installation mounting plate so installers can mount them to a wide array of back
• Electrically Compatible with legacy SpectrAlert and SpectrAlert boxes.With an onboard shorting spring, installers can test wiring
Advance devices continuity before the device is installed.
• Compatible with MDL3 sync module
Installers can also easily adapt devices to a suit a wide range of
• Listed for ceiling mounting only application requirements using field-selectable candela settings,
automatic selection of 12-or 24-volt operation,and a rotary switch
for horn tones with two volume selections.
Agency Listings
SIGNauNs
4vvrrove0
LISTED
-m dpv--j eMcepl 712551653W
LERT
S40t 1 for A models 7135.1653.M
3057383
AVDS868-02.121D1/2017•Page 3
L-Series Specifications
Arch itect/Engi neer Specifications
General
L-Series ceiling-mount strobes and horn strobes shall mount to a standard 4 x 4 x 11/2-inch back box,4-inch octagon back box,or double-
gang back box.Two-wire products shall also mount to a single-gang 2 x 4 x 17/8-inch back box.A universal mounting plate shall be used
for mounting ceiling and wall products.The notification appliance circuit wiring shall terminate at the universal mounting plate.Also,L-Series
products,when used with the Sync•Circuit"Module accessory,shall be powered from a non-coded notification appliance circuit output
and shall operate on a nominal 12 or 24 volts.When used with the Sync•Circuit Module, 12-volt-rated notification appliance circuit outputs
shall operate between 8.5 and 17.5 volts;24-volt-rated notification appliance circuit outputs shall operate between 16.5 and 33 volts.Indoor
L-Series products shall operate between 32 and 120 degrees Fahrenheit from a regulated DC or full-wave rectified unfiltered power supply.
Ceiling strobes and horn strobes shall have field-selectable candela settings including 15,30,75,95, 115, 150,and 177.
Strobe
The strobe shall be a System Sensor L-Series Model listed to UL 1971 and shall be approved for fire protective service.The strobe
shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible
signaling appliances,flashing at 1 Hz over the strobe's entire operating voltage range.The strobe light shall consist of a xenon flash tube and
associated lens/reflector system.
Horn Strobe Combination
The horn strobe shall be a System Sensor L-Series Model listed to UL 1971 and UL 464 and shall be approved for fire protective
service.The horn strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act
requirements for visible signaling appliances,flashing at 1 Hz over the strobe's entire operating voltage range.The strobe light shall consist
of a xenon flash tube and associated lens/reflector system.The horn shall have two audibility options and an option to switch between a
temporal three pattern and a non-temporal(continuous)pattern.These options are set by a multiple position switch.The horn on horn strobe
models shall operate on a coded or non-coded power supply.
Synchronization Module
The module shall be a System Sensor Sync•Circuit model MDL3 listed to UL 464 and shall be approved for fire protective service.The module
shall synchronize L-Series strobes at 1 Hz and horns at temporal three.Also,while operating the strobes,the module shall silence the horns
on horn strobe models over a single pair of wires.The module shall mount to a 4 11/16 x 4 11/16 x 2 1/8-inch back box.The module shall also
control two Style Y(class B)circuits or one Style Z(class A)circuit,The module shall synchronize multiple zones.Daisy chaining two or more
synchronization modules together will synchronize all the zones they control.The module shall not operate on a coded power supply.
Physical/Electrical Specifications
Standard Operating Temperature 320F to 120OF(0°C to 49°C)
Humidity Range 10 to 93%non-condensing
Strobe Flash Rate 1 flash per second
Nominal Voltage Regulated 12 VDC or regulated 24 DC/FWR1
Operating Voltage Range 8 to 17.5 V(12 V nominal)or 16 to 33 V(24 V nominal)
Operating Voltage Range(MDL3) 8.5 to 17.5V(12 V nominal)or 16.5 to 33 V(24V nominal)
Input Terminal Wire Gauge 12 to 18 AWG
Ceiling-Mount Dimensions(including lens) 6.8"diameter x 2.5"high(173 mm diameter x 64 mm high)
Ceiling-Mount Surface Mount Back Box Skirt Dimensions 6.9"diameter x 3.4"high(175 mm diameter x 86 mm high)
(SBBCRL,SBBCWL)
Notes:
1. Full Wave Rectified(FWR)voltage is a non-regulated,time-varying power source that is used on some power supply and panel outputs.
2.P,S,PC,and SC products will operate at 12 V nominal only for 15 and 30 cd.
AVOS88602.12l01f2017•Page 2
v v v v v v v c v
> r N N N N N N N N Q
U
O V co V (N7 m It N "It It 'O
y p r- .: O (D M N M t-
to N N CO N N cliN N N N - <
Llf
n
r U
O 00 M M a1 d1 N M N •O
ab G M N V N M N V N N V V V
f` LOr- O V' LO N r` n (D N c0 N tT O 0) O
M OD 00 r\ co co O OD 0000 N 0000 N ONO N ccoo N
m D O O LM O O O L:)) LT
V Ln LO CO LO V LO O ;1- O V 0) LO 0) LO 0)
o (0 Owl (D (D (0 (O (0 LO (D LO w LO N LO N LO N LO N
r N N N N N N N N
O O
Q Q
R) RS
C O O O N )
o oE E 0 0 o u M r` v r` CO y Li CO 0) co 0) LO LO (D
O O- O- ♦- H z z U to IT V' N V V M r N O N 0) N N N 0)
a 7 N E E - r N - N N N O) M 00 00 N 0) M
= = 2 -O _ OD co ao 00 ao 00
0 O o g F 2
a O- CL E Y Y Y Y 0 Y
O O OF IL r
N F- z z (*i C, ri ri UO ri (f
O O O V 0o V co Lff m tl- m f-- O O r- (n
0) m 0o 0) c0 M r - N N .-
rn Uco It o O > 0 ccoo 00 gi coo 000o ccoo cor coo
� tC
N V 00 V (+) 0
(OO Opp V p O) N N CO)II V 0 0) 0) � 0) O 0) CD
W (D LA R V 41 IT M V w r p n p n LO LO ++
r r t` p r LO (D LO CO LO ti Ln
w J 0 OO � co r- W � 00 r-
0
r V (MD M LO M N
t) (D LO M (D (D M N M C1 LO LO LO LO
M - - - - - - - - � co O M O M O M
O
+�- U co Q Q Q Q Q r4 0
r` n u M cD M r M f9 0 rl- r- M w
ab 0 M 10
Z z z z Z W- o � o � o o Lb - o ago o m o m o r m m
E E Q
N m �
o `o
3 a °) o �' o = o o E E o 0
cc H a m m
c p h S J S J (0 Q a
td LO O LO tO LO L 3 L L 3 L . N N N N N
0) J = J O O O J = J 0 0 S c a 0 H F 2 2 2 S
= o) 3 m ro m E E o 3 6 @ E E O o 0 0 0 0 T
2 J O O O O H F� �' 2 J O O O O H H !/� F- H Z Z M M M M
as 3TumEEEEoo mFOEEEEoo N c
U v rn a Q F ~ z z — Q Q t� z z O s o
_ u
E E 0 0 Y_ Y Y_ Y_ ¢ E E o o O _ C
(,� 0 z z M M m c) z z m M M M = a N co LO (O tv M
SYSTEM
SENSOR®
E F
I
Outdoor Selectable- s R
E
Output Horns,
Strobes, and `
Horn Strobes for
Wall Applications
SPECT . rt
SpectrAlertO Advance outdoor audible visible products a Iv v a IN c E
are rich with features that cut installation times and
maximize profits.
Features SpectrAlert Advance offers the broadest line of outdoor horns,
• Weatherproof per NEMA 0, IP56 strobes,and horn strobes in the industry.With white or red plastic
housings,wall or ceiling mounting options,and plain or FIRE-printed
• Listed to UL 1638(strobe)and UL 464(horn) devices,SpectrAlert Advance can meet virtually any application
• Compatible with System Sensor synchronization protocol and requirement,including indoor,outdoor,wet,and dry applications in
legacy SpectrAlert products temperatures from-40°F to 151 OF.
• Field-selectable candela settings: 15. 15/75,30,75,95, 110, 115,
135, 150, 177,and 185 Like the entire SpectrAlert Advance line,outdoor horns,strobes,
• Automatic selection of 12-or 24-volt operation at 15 and and horn strobes for wall applications include a variety of features
15/75 candela that increase application flexibility and simplify installation. First,
• Rotary switch for horn tone and three volume selections field-selectable settings,including candela,automatic selection of
12-or 24-volt operation, horn tones,and three volume options enable
• Horn rated at 88+dBA at 16 volts installers to easily adapt devices to meet requirements.
• Rated from-40°F to 151 IF
• Universal mounting plate with an onboard shorting spring that Next,SpectrAlert Advance devices use a universal mounting plate
tests wiring continuity before devices are installed for both wall and ceiling applications.This mounting plate includes
• Plug-in design with minimal intrusion into the back box an onboard shorting spring that ensures wiring continuity before
Tamper-resistant construction devices are installed,so installers can verify proper wiring without
•
mounting the devices and exposing them to potential construction
• Listed for ceiling or wall mounting damage.Once the plates are mounted,all SpectrAlert Advance
devices utilize a plug-in design with a single captured screw to
speed installation and virtually eliminate costly ground faults.
Outdoor devices ship with weatherproof plastic back boxes(metal
back boxes are available separately)that accommodate in-and-
Agency Listings out wiring for daisy chaining devices. Plastic back boxes feature
removable side flanges and improved resistance to saltwater
corrosion. Knock-outs located on the back eliminate the need to drill
SIGNALING
® holes for screw-in mounting.Plastic and metal weatherproof back
& boxes come with 3/4-inch top and bottom conduit entries and 3/4-inch
F M MEA 7300-1653:187(OWCO rstrobes) knock-outs at the back.A screw-in NPT plug with an O-ring gasket
LISTED 7125-1653 188(horn strobes.
S4011(fir,. _.'I" n0lnechirne strobes) for a watertight seal is included with each back box.
S3593(ow-) ai'o,ier 3023572 MEA452-05-E 7135-1653 189(horns,chimes)
AVDS115-02.1J3/2019•Page 1
SpectrAlert Advance Outdoor Horn, Strobe, and Horn StrobeSpecifications
Architect/Engineer Specifications
General
SpectrAlert Advance outdoor horns,strobes,and horn strobes shall mount to a weatherproof back box.A universal mounting plate shall
be used for mounting ceiling and wall products.The notification appliance circuit wiring shall terminate at the universal mounting plate.
Also,SpectrAlert Advance products,when used with the Sync•CircuitT"Module accessory,shall be powered from a non-coded notification
appliance circuit output and shall operate on a nominal 12 or 24 volts.When used with the Sync•Circuit Module, 12-volt-rated notification
appliance circuit outputs shall operate between 8.5 and 17.5 volts;24-volt-rated notification appliance circuit outputs shall operate between
16.5 and 33 volts.Outdoor SpectrAlert Advance products shall operate between-40 and 151 degrees Fahrenheit from a regulated DC or full-
wave rectified unfiltered power supply.Strobes and horn strobes shall have field-selectable candela settings including 15, 15/75,30,75,95,
110, 115, 135, 150, 177,and 185.
Strobe
The strobe shall be a System Sensor SpectrAlert Advance Model listed to UL 1971 and shall be approved for fire protective service.
The strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for
visible signaling appliances,flashing at 1 Hz over the strobe's entire operating voltage range.The strobe light shall consist of a xenon flash
tube and associated lens/reflector system.The strobe must be installed with its weatherproof back box in order to remain outdoor approved
per UL.The strobe shall be suitable for use in wet environments.
Horn Strobe Combination
The horn strobe shall be a System Sensor SpectrAlert Advance Model listed to UL 1971 and UL 464 and shall be approved for
fire protective service.The horn strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with
Disabilities Act requirements for visible signaling appliances,flashing at 1 Hz over the strobe's entire operating voltage range.The strobe
light shall consist of a xenon flash tube and associated lens/reflector system.The horn shall have three audibility options and an option to
switch between a temporal three pattern and a non-temporal(continuous)pattern.These options shall be set by a multiple position switch.
On four-wire products,the strobe shall be powered independently of the sounder.The horn or horn strobe models shall operate on a coded or
non-coded power supply.The horn strobe must be installed with its weatherproof back box in order to remain outdoor approved per UL. The
horn strobe shall be suitable for use in wet environments.
Physical/Electrical Specifications
Operating Temperature -401F to 151IF(-40'C to 661C)
Strobe Flash Rate 1 flash per second
Nominal Voltage Regulated 12 DC/FWR or regulated 24 DC/FWR1
Operating Voltage Range2 8 to 17.5 V(12 V nominal)or 16 to 33 V(24 V nominal)
Operating Voltage with MLD3 Sync Module 8.5 to 17.5 V(12 V nominal)or 16.5 to 33 V(24 V nominal)
Input Terminal Wire Gauge 12 to 18 AWG
Wall-Mount Dimensions(including lens) 5.6'L x 4.7-W x 2.5-D(142 mm L x 119 mm W x 64 mm D)
Horn Dimensions 5.6"L x 4.7"W x 1.3-D(142 mm L x 119 mm W x 33 mm D)
Wall-Mount Weatherproof Back Box Dimensions(SA-WBB) 5.7`"L x 5.1W x 2.0"D(145 mm L x 130 mm W x 51 mm D)
Notes:
1, Full Wave Rectified(FWR)voltage is a non-regulated,time-varying power source that is used on some power supply and panel outputs.
2.2.P.S,PC,and SC products will operate at 12 V nominal only for 15 and 15/75 cd.
AVDS 115 0?•12131?019•Page 2
UL Current Draw Data
UL Max.Strobe Current Draw(rnA RMS) UL Max.Horn Current Draw(rnA RMS)-
8-17.5 Volts 16-33 Volts 8-17.5 Volts 16-33 Volts
Candela DC FWR DC FWR Sound Pattern dB DC FWR DC FWR
Standard 15 123 128 66 71 Temporal High 57 55 69 75
Candela 15175 142 148 77 81 Temporal Medium 44 49 58 69
Range 30 NA NA 94 96 Temporal Low 38 44 44 48
75 NA NA 158 153 Non-Temporal High 57 56 69 75
95 NA NA 181 176 Non-Temporal Medium 42 50 60 69
110 NA NA 202 195 Non-Temporal Low 41 44 50 50
115 NA NA 210 205 Coded High 57 55 69 75
High 135 NA NA 228 207 Coded Medium 44 51 56 69
Candela 150 NA NA 246 220 Coded Low 40 46 52 50
Range 177 NA NA 281 251
185 NA NA 286 258
Strobe,UL Max.Current Draw(rnA RMS),2-Wire Horn .. .
8-17.5 Volts 16-33 Volts
DC Input 15 15l75 15 15/75 30 75 95 110 115
Temporal High 137 147 79 90 107 176 194 212 218
Temporal Medium 132 144 69 80 97 157 182 201 210
Temporal Low 132 143 66 77 93 154 179 198 207
Non-Temporal High 141 152 91 100 116 176 201 221 229
Non-Ternporal Medium 133 145 75 85 102 163 187 207 216
Non-Temporal Low 131 144 68 79 96 156 182 201 210
FWR Input
Temporal High 136 155 88 97 112 168 190 210 218
Temporal Medium 129 152 78 88 103 160 184 202 206
Temporal Low 129 151 76 86 101 160 184 194 201
Non-Temporal High 142 161 103 112 126 181 203 221 229
Non-Temporal Medium 134 155 85 95 110 166 189 208 216
Non-Temporal Low 132 154 80 90 105 161 184 202 211
UL Max.Current • Candela16-33 Volts 16-33 Volts
DC Input 135 150 177 185 FWR Input 135 150 177 185
Temporal High 245 259 290 297 Temporal High 215 231 258 265
Temporal Medium 235 253 288 297 Temporal Medium 209 224 250 258
Temporal Low 232 251 282 292 Temporal Low 207 221 248 256
Non-Temporal High 255 270 303 309 Non-Temporal High 233 248 275 281
Non-Temporal Medium 242 259 293 299 Non-Temporal Medium 219 232 262 267
Non-Temporal Low 238 254 291 295 Non-Temporal Low 214 229 256 262
Candela Derating Horn Tones and Sound Output Data
For K series products used at low temperatures, listed Horn and Horn Strobe Output
candela ratings must be reduced in accordance with ,8-17.5 16-33 24-Volt Nominal
this table. Switch Sound Volts Volts Reverberant Anechoic
Strobe • Position Pattern dB DC FWR DC FWR DC FWR DC FWR
Listed Candela Candela rating at-40°F 1 Temporal High 78 78 84 84 88 88 99 98
15 2 Temporal Medium 74 74 80 80 86 86 96 96
15/75 Do not use below 320F 3 Temporal Low 71 73 76 76 83 80 94 89
30 4 Non- High
75 44 Temporal 82 82 88 88 93 92 100 100
95 70 5 Non- Medium
110 110 Temporal 78 78 85 85 90 90 98 98
115 115 6 Non- Low 75 75 81 81 88 84 96 92
135 135 Temporal
150 150 7t Coded High 82 82 88 88 93 92 101 101
177 1177 81 Coded Medium 78 78 85 85 90 90 97 98
185 1185 9t Coded Low 75 75 81 81 88 85 96 92
tSettings 7,8,and 9 are not available on 2-wire horn strobe.
R
f'
Randy Collins
From: Randy Collins
Sent: Tuesday, September 17, 2024 2:12 PM
To: 'JIANXIONG CHEN'
Cc: mheinrich@cmfe.org
Subject: RE: Inspection of 50 Westfield Ct Shelton, Building A
Hi Michael,
G/osad l s� �c!►r c. , cp�o�,s� /)i, r\
I appreciate you taking my phone call and allowing me to conduct the reinspection of your facility at 50 Westfield
Ct Bldg A. I want to thankyou for placing the covers back on the circuit breaker panels and installing sheetrock on
the ceiling in the hallway traversing the building. However, as I alluded in our phone conversation, despite your
efforts to contract with an alarm company to fix the fire alarm, it was still in the same trouble mode when I
inspected the facility on July 31.
To that end, it will be necessary for a licensed firm to return to fix the system and I would ask once this has been
done to please let me know.
Respectfully,
Randy Collins,
Fire Marshal
From:JIANXIONG CHEN <perfectplant98@gmail.com>
Sent:Tuesday, August 27, 2024 8:43 AM
To: Randy Collins<RCollins@masoncountywa.gov>
Cc: mheinrich@cmfe.org
Subject: Re: Inspection of 50 Westfield Ct Shelton, Building A
Caution: External Emait Warning!This email has originated from outside of the Mason County
Network. Do not click links or open attachments unless you recognize the sender, are expecting the
email, and know the content is safe. If a link sends you to a website where you are asked to validate
using your Account and Password, DO NOT DO SO! Instead, report the incident.
Good morning Randy,
We have fixed the sheetrock as your request. Please feel free to inspect if needed. Thanks
On Mon, Aug 5, 2024, 1:49 PM JIANXIONG CHEN <perfectp1ant98PgmaiLcom> wrote:
Hi Randy,
Confirmed with the Landlord and the tenant. The key is the same in the Knoxbox.We will let you know
once the corrections are made.
I Thankyou,
1
Randy Collins
From: JIANXIONG CHEN <perfectplant98@gmail.com>
Sent: Tuesday,August 27, 2024 8:43 AM
To: Randy Collins
Cc: mheinrich@cmfe.org
Subject: Re: Inspection of SO Westfield Ct Shelton, Building A
Caution: External Email Warning!This email has originated from outside of the Mason County
Network. Do not click links or open attachments unless you recognize the sender, are expecting the
email, and know the content is safe. If a link sends you to a website where you are asked to validate
using your Account and Password, DO NOT DO SO! Instead, report the incident.
Good morning Randy,
We have fixed the sheetrock as your request. Please feel free to inspect if needed.Thanks
On Mon,Aug 5, 2024, 1:49 PM JIANXIONG CHEN <perfectplant98CEbgmaiLcom>wrote:
Hi Randy,
Confirmed with the Landlord and the tenant. The key is the same in the Knoxbox.We will let you know
once the corrections are made.
Thankyou,
On Mon, Aug 5, 2024 at 12:29 PM Randy Collins <RCollinsPmasoncountywa.gov>wrote:
i
Michael,
F
I appreciate your response. I would like to conduct a reinspection once the items I identified in my email below
are complete so please let me know when those items are corrected.Also,your building already has a Knox Box
so it will not be necessary to purchase one but only contact Deputy Fire Marshal Matt Heinrich at Centrat Mason
Fire (cc'd here)so he can install the keys in the box.
Since you indicated you have only leased out Building A, I will contact the property owner regarding the other
buildings.
Respectfully,
q
10 Randy Collins
From: Randy Collins L�// 2� r�� vc,��
Sent: Monday, August 5, 2024 12:29 PM /1
To: 'JIANXIONG CHEN' � G
Cc: mheinrich@cmfe.org
Subject: RE: Inspection of 50 Westfield Ct Shelton, Building A
Michael,
I appreciate your response. I would like to conduct a reinspection once the items I identified in my email below are
complete so please let me know when those items are corrected.Also,your building already has a Knox Box so it
will not be necessary to purchase one but only contact Deputy Fire Marshal Matt Heinrich at Central Mason Fire
(cc'd here)so he can install the keys in the box.
Since you indicated you have only leased out Building A, I will contact the property owner regarding the other
buildings.
Respectfully,
Randy Collins,
Fire Marshal
From:JIANXIONG CHEN<perfectplant98@gmail.com>
Sent:Wednesday,July 31, 2024 2:23 PM
To: Randy Collins<RCollins@masoncountywa.gov>
Subject: Re: Inspection of 50 Westfield Ct Shelton, Building A
Caution: External Email Warning!This email has originated from outside of the Mason County
Network. Do not click links or open attachments unless you recognize the sender, are expecting the
email, and know the content is safe. If a link sends you to a website where you are asked to validate
using your Account and Password, DO NOT DO SO! Instead, report the incident.
Randy,
Please see my replies below and thankyou for your visit this morning.
• Working with a licensed fire alarm company to restore the monitoring for the fire alarm.This includes all
the other buildings as well.Yes,we are working with Smith Fire System.All other buildings are belong to
someone else.We only occupy#A
• Installing sheetrock on the ceilings of the hallway,electrical room and any other rooms I was unable to
access that do not have sheetrock lids.This is necessary to maintain a fire separation between the attic
and occupied spaces below and ensure the proper operation of your fire alarm system.Well noted. It will
be installed within a month.
• Provide keys that access all buildings and the fire alarms to Central Mason Fire Department so they can be
placed in your fire department key(Knox) boxes.We will order one. Please let me know if the model
below will work and what 1 should choose for question 2 and 3.
Comrnardal KmWoaes
KnoxBox®3200
Standard Capacity Model-3261
MSRP:66W-
Price:S487.00
ii
7.color 2.Mount Type
Alu ri— Recessed Mount
J Black +: surface Mount
.^.. Dark&ooze
7.Tamper switch Type
w- None
Fre Alarm/Panel
J Securlty Alarm
• Installing the cover panels on each of the main electrical panels in the hallway. It will be installed within a
month.
Since I was unable to occupy the other buildings at this location, I would like to schedule a time to meet
with you to perform an inspection of these as well.Would 9 AM Monday August 5 or 9 AM Wednesday Aug
7 work for you? In regard to all other buildings, you may contact the land tord Sean Kirby(360-789-3694)
On Wed, Jut 31, 2024 at 12:17 PM Randy Collins <RColtins masoncountywa.gov>wrote:
Michael,
I appreciate you taking my phone call to discuss fire safety for your facility. Per our conversation, I am
sending you this email to bring to your attention the fire code issues that will need to be corrected in
Building A, some of which you indicated you may be working on.These include:
• Working with a licensed fire alarm company to restore the monitoring for the fire alarm. This
includes all the other buildings as well.
• Installing sheetrock on the ceilings of the hallway,electrical room and any other rooms I was
unable to access that do not have sheetrock lids.This is necessary to maintain afire separation
between the attic and occupied spaces below and ensure the proper operation of your fire alarm
system.
• Provide keys that access all buildings and the fire alarms to Central Mason Fire Department so
they can be placed in your fire department key (Knox) boxes.
• Installing the cover panels on each of the main electrical panels in the hallway.
Since I was unable to occupy the other buildings at this location, I would like to schedule a time to meet
with you to perform an inspection of these as well. Would 9 AM Monday August 5 or 9 AM Wednesday
Aug 7 work for you?
2
Randy Collins
From: Randy Collins
Sent: Monday, August 5, 2024 3:37 PM
To: 'Jean Bray'
Subject: RE:About What I Have Called About
Jean,
I can appreciate your concerns and having a generator run continuously would annoy me incredibly too. However,
since you alluded below and in our phone conversation you have not heard it since July 30 and there may have
been an ownership change, I will defer following up for now unless you let me know that they have resumed
running it.
Any questions, please let me know.
Randy Collins,
Fire Marshal
From:Jean Bray<jmbraywa@gmail.com>
Sent: Monday,August 5, 2024 3:23 PM
To: Randy Collins<RCollins@masoncountywa.gov>
Subject:About What I Have Called About
Caution: External Emait Warning!This email has originated from outside of the Mason County
Network. Do not click links or open attachments unless you recognize the sender, are expecting the
email, and know the content is safe. If a link sends you to a website where you are asked to validate
using your Account and Password, DO NOT DO SO! Instead, report the incident.
August 5, 2024
Randy,
I am sorry I seem to have missed your return telephone call.
I hate to put this "matter" into writing.
_About what I had called about_Neighbors of mine ran an exterior generator night and day_for going-on
eight months, daily,—around-the-clock.
They were buying gasoline, like 20 gallons at a time to fuel. I guess they would purchase gas every other
day, or, in some instances,_practically,_daily.
It was a loud generator. I live "in a neighborhood."And the whole time, there was power going into the
house.
I think the state and counties should do more mitigation for these circumstances. The decibels were just
_frankly_outrageous, and I have tinnitus.
i
A Commissioner from the Mason County Commission Board says "this was perfectly fine to do." I beg to
differ.
I got nothing from out of the State Fire Marshall's offices, either, "except to contact you,"
In the past several weeks the occupants removed the generator to aback area, which, was hidden from
view. There is a lot of debris on the property, making this even more dangerous.
To my knowledge the previous last night the generator was run was July 30.
1 wanted to submit this information to you, and,
just for reference I will give my address and other contact information. Please do not give it out.
I am truly disgusted with the Timberlake Community Club for their failure to remediate this matter, when
requested to do so. I guess the person in charge of the affairs of this property has resided here longer
than me and their word took precedence over mine. This is all I can think of-what"was happening" my
comments and those of others going unanswered, for many months."
Jean Bray
160 E Park Loop
Shelton WA 98584
360 229 8739
jmbravw�maiLcom
2