June 20, 2011
MS. Tevan Riedel
AMERICOVER
2067 Wineridge Place
Suite F
Escondido, CA 92029
Reference : Laboratory Test Report
Lab Identification No. 8159
Invoice No. 29675 (Attached)
Dear Ms. Riedel :
One (1) sample, identified as 4 MIL WHITE FR POLYETHYLENE, was received and
tested in accordance with the National Fire Prevention Association No. 701,
"Standard Methods of Fire Tests for Flame Propagation of Textiles and Films, 2010
Edition, (Test 1, Small Scale) " . The results are as follows:
Specimen Number Residual Flame Weight Loss
(seconds) (percent)
1 0.0 1. 19
2 0.0 1. 64
3 0.0 4.43
4 0.0 6.00
5 0. 0 26.36
6 0. 0 1.60
7 0.0 1.92
B 0. 0 21. 60
9 0.0 4.99
10 0A 4.10
AVG. 0.0 7.39
The sample submitted meets the minimum requirements of the above standard. The
average percent weight loss cannot exceed 40.6 and the weight loss of individual
specimens cannot exceed mean value plus three standard deviations. The average
residual flame cannot exceed 2.0 seconds.
If there are any questions or when we can be of further assistance, please let us
know.
Sin rely,
Ka n S. Matkins
KSM/mr
Attachment
OUR LETTERS AND REPORTS ARE FOR THE EXCLUSIVE USE OF THE CLIENT TO WHOM THEY ARE ADDRESSED.ANY COMMUNICATION TO OTHERS OR THE USE OF OUR COMPANY NAME MUST
RECEIVE PRIOR APPROVAL.OUR TEST RESULTS APPLY ONLY TO THE SAMPLE TESTED AND ARE NOT NECESSARILY INDICATIVE OF THE QUALITIES OF APPARENTLY IDENTICAL OR SIMILAR
PRODUCTS.SAMPLES NOT DESTROYED IN TESTING ARE RETAINED A MAXIMUM OF THIRTY DAYS.THE LETTERS.REPORTS OR NAME OF DIVERSIFIED TESTING LABORATORIES.INC.MAY NOT
BE USED IN ADVERTISING TO THE GENERAL PUBLIC.