HomeMy WebLinkAboutFIR2023-00010 - FIR Inspections - 8/16/2023 STAND-ALONE 13-D SPRINKLER SYSTEM INSPECTION REPORT FIR ADDRESS FIRM iar A;e- ROUGH-IN/HYDRO INSPECTION InspectorlCe' ,s Date 1 . Piping Installed per approved plans? Yes No 2. Hydro test (At normal operating pressure for 2 hours) 11.2.1.1 Start time 7 End time 8l6 Z� 3. Are hangers sufficient to secure pipe? 7.4 Yes ✓ No 4. Is attic piping tented with insulation (min R-15)? 7.7 Yes No 5. Did plans deviate enough to require "As Builts"? Yes ✓ No 6. If required, did Bucket Test deliver GPM needed? Heads 1)/D.. �-(2)i��.- NA 7. Hydro/Rough-In Inspection Passed Yes V No Date Corrected Comments I-2 e., isti ��v FINAL INSPECTION Date 91167123 Inspector 1 . Spare Heads & Wrench with BOX (2 of each when 2 or more are used) Yes i% No 2. Main drain (min '/2") valve present? 7.2.1 Yes No 3. Covers removed from concealed heads? Yes No 4. Shut-off valve also controls domestic 7.1.1(separate domestic valve ok) Yes No ✓ 5. Does shut-off valve have required sign? 6..3.4 Yes No ✓ (Permanent metal"Sprinkler System Shut-off Valve") 6. Is shut-off valve "locked" in open position w/zip-tie? Yes No ✓ 7. Heads unobstructed by lights, ceiling fans, beams, etc. Yes ✓ No 8. "Calc" plate present with required pressures/K-factor? Yes ✓ No 9. Pass Final Inspection Yes / No If no, pass date Comments 7 J� ,����(v`i�1� �;'r/ia�dol�GS�YG/ylaintiy�' �S��i�.� .4io✓i� cZ�Z� Page / of 7i CALCULATION WORKSHEET Contractor Phone 3007/lMs Job Location Begin Node 0 End Node J Flow in GPM /y Pipe Type/Size G�yL FITTINGS & PIPE Quantities ft/equiv. Total 90 El = Start Pressure.............................. "d T-Bend = Loss to Elev. ft.x.434 = T-Run = Pressure Loss to Flow Switch Coupling - Pressure Loss to Water Meter Total Fitting Length Total Pipe Length �X q Subtotal �U x 0/8 (factor) - 370 Total Node Pressure Loss Proceed to Next Node Begin Node Q End Node O M Flow in GPM Pipe Type/Size FITTINGS & PIPE Quantities ft/equiv. Total 90 El = Z/ Start Pressure 6/ 3 T-Bend Loss to Elev. ft. x.434 � T-Run - ell, Pressure Loss to Flow Switch _- /Z l Coupling = Pressure Loss to Water Meter Total Fitting Length 37 �U Total Pipe Length ��, Subtotal x " vwy (factor) Total Node Pressure Loss Page of CALCULATION WORKSHEET Contractor Phone Job Location '60/e/rl,.,*1 Begin Node �_-/ End Node L Flow in GPM Pipe Type/Size /'1Lope. FITTINGS & PIPE Quantities ftlequiv. Total 90 El = Start Pressure............................ R, T-Bend - Loss to Elev. ft.x.434 = 1- 74 T-Run Z = _ Pressure Loss to Flow Switch Coupling �/L Pressure Loss to Water Meter z7.8 4 a Total Fitting Length / _ Total Pipe Length `7 (�Gle �G yy a m Subtotal x /z5 (factor) _ `o Total Node Pressure Loss ",7s.40 Proceed to Next Node "arrtL Begin Node O End Node O Flow in GPM 10 Pipe TypelSize ��<< FITTINGS & PIPE Quantities ft/equiv. Total 90 E! = Start Pressure 11.91 T-Bend = Loss to Elev. ft. x.434 = %-7l T-Run = Pressure Loss to Flow Switch Coupling = Pressure Loss to Water Meter Total Fitting Length Total Pipe Length Subtotal X (factor) _ `1•�Z Total Node Pressure Loss s I Ir��' -Uwzv Bulletin 006 Rev. I Model RFC30 (SIN RA0611) C R Model RFC43 (SIN RA0612) Reliable Model RFC49 (SIN RA0616) Residential Flat Concealed Sprinklers A Residential Flat Concealed Sprinkler engineered for a minimum design density of 0.05 gpm/ft2 with low GPM requirements. Features 1. Very low water flow requirements. 2. Cover plate attachment (Plain or Perforated) with '/2" (13mm)Total adjustment. 3. Thread-On/Thread-Off or Push-On/Thread Off cover attachment option. 4. Smooth aesthetic ceiling profile. 5. Available in brass, chrome and black plated or painted finishes. Plain Cover Plate Listings & Approval 1. Listed by Underwriters Laboratories, and certified by UL for Canada (cULus) UL Listing Categories Residential Automatic Sprinklers UL Guide Number - - " =_= = _=_" VKKW ------------ Product Description Model RFC30, RFC43 and RFC49 Concealed Residen- tial Sprinklers are fast response residential fusible solder link automatic sprinklers. Residential sprinklers differ from standard sprinklers primarily in their response time and water distribution patterns. Perforated Cover Plate Model RFC30, RFC43 and RFC49 sprinklers discharge water in a hemispherical pattern below the sprinkler de- and positively attached and blends into the ceiling, con- flector. Residential distribution patterns are higher and cealing the most dependable fire protection available, an generally contain a finer droplet size than standard sprin- automatic sprinkler system. kler patterns. The RFC30, RFC43 and RFC49 are UL Listed Residen- The combination of speed of operation and high dis- tial Sprinklers to be installed in the residential portions charge pattern required for residential sprinklers has of any occupancy in accordance with NFPA 13, 13R, & demonstrated, in fire testing, an ability for controlling 13D. residential fires, and thereby providing significant evacu- The RFC30, RFC43 and RFC49 can reduce the need ation time for occupants. for precise cutting of drop nipples. The threaded cover The RFC30, RFC43 and RFC49 Sprinklers provide the plate assembly can be adjusted without tools to fit ac- best form of fire protection by combining an attractive ap- curately against the ceiling. The fire protection system pearance and 'h" (13mm) of cover adjustment for ease need not be shut down to adjust or remove the cover of installation. The small diameter cover plate is easily plate assembly. The Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523 Application and Installation The RFC30, RFC43 and RFC49, for residential instal- When inserting or removing the wrench from the sprin- lations, use a 165°F (74°C) fusible solder link in a tun- kler/cup assembly, care should be taken to prevent dam- ing fork style sprinkler frame with a drop-down deflector. age to the sprinkler. DO NOT WRENCH ON ANY OTHER This assembly is recessed into the ceiling and concealed PART OF THE SPRINKLER/CUP ASSEMBLY. MODEL by a flat cover plate. The cover plate is attached to the RFC30, RFC43 AND RFC49 CONCEALED SPRINKLERS skirt, using 135°F(57°C)ordinary temperature classifica- MUST BE INSTALLED ONLY WITH 135°F RATED COV- tion solder.When the ceiling temperature rises,the solder ERS. holding the cover plate releases the cover allowing the Note:A leak tight 112" NPT(R1/2)sprinkler joint can be ob- deflector to drop into position and exposing the sprinkler tained with a torque of 8-18 ft-lbs(10,8-24,4 N-m). Do not inside to ceiling temperature. The subsequent operation tighten sprinklers over maximum recommended torque. It of the solder link opens the waterway and causes the de- may cause leakage or impairment of the sprinklers. flector to drop into position to distribute the discharging Cover assemblies provide up to '/2" (13mm) of adjust- water in a hemispherical pattern below the sprinkler de- ment. Turn the cover clockwise until the flange is in con- flector. Any adjustment of thread engagement between tact with the ceiling. For the push-on/thread-off option, the cover plate and cup will assure that the drop-down the cover assembly is pushed onto the cup and final ad- deflector is properly located below the ceiling. The resi- justment is made by turning the cover clockwise until the dential distribution pattern contains a finer droplet size skirt flange makes full contact with the ceiling. Cover re- than a standard sprinkler, and the pattern produces sig- moval requires turning in the counter-clockwise direction. nificantly higher wall wetting. In ceilings that have a plenum space above the sprin- After a 21/8 inch diameter hole is cut in the ceiling, the kler, the plenum space may have neutral or negative sprinkler is to be installed with the Model FC Wrench. pressurization but must not be positively pressurized. When installing a sprinkler, the wrench is first positioned Inspect all sprinklers after installation to ensure that the into the sprinkler/cup assembly and around the hexago- gap between the cover plate and ceiling and the 4 slots nal body of the sprinkler frame. The Wrench must bottom in the cup are all open and free from any air flow impedi- out against the cup in order to ensure proper, safe instal- ment. lation. The sprinkler is then tightened into the pipe fitting. Sprinkler CCP Assembly Max. Model Thread Nominal p y Ambient K Max. (SIN) Size Orifice Temp Rating Temp. Rating Temp. Factor Pressure Inch(mm) Inch(mm) OF °C OF °C OF °C psi(bar) RFC 30 1/2"(15) 2t/64(8,2) 165 74 135 57 100 38 3.0(43.2) 175(12) (RA0611) RFC 43 1/2„(15) 3/6(10) 165 74 135 57 100 38 4.3(62) 175(12) (RA0612) RFC 49 1/2"(15) '/16(11) 165 74 135 57 100 38 4.9(70.6) 175(12) (RA0616) Note: 1 bar= 100 Kpa RFC 30 Ordinary Temp. Rating Max.Coverage To 165°Fl74°Cp of Deflector Minimum area Max.Spacing ( ) to Ceiling Installation Spacing Ft(m) Flow Pressure Inch(mm) Type Ft(m) Ft x Ft(m x m) GPM(Umin) PSI(bar) 12 x 12(3,6 x 3,6) 12(3,6) 9(34,1) 9.0(0,62) Smooth Ceilings 1/2 to 1(13 to 25.4) Beamed Ceilings per NFPA 13D, 13R or Concealed 8(2,4) .0(0,76) 13 installed in beams 1/2 to 1(13 to 25.4) For Ceiling types refer to NFPA 13, 13R or 13D 2. RFC 43 Ordinary Temp. Rating Max.Coverage Top of Deflector Minimum area Max.Spacing (165°F/74°C) to Ceiling Installation Spacing Ft x Ft(m x m) Ft(m) Flow Pressure Inch(mm) Type Ft(m) GPM(Umin) PSI(bar) 12 x 12(3,6 x 3,6) 12(3,6) 12(4,5) 7.8(0,54) 14 x 14(4,3 x 4,3) 14(4,3) 13(49) 9.1 (0,63) Smooth Ceilings 1/2 to 1(13 to 25.4) 16 x 16(4,9 x 4,9) 16(4,9) 13(49) 9.1 (0,63) Beamed Ceilings per NFPA 13D, 13R or Concealed 8(2,4) 13 installed in beams 1/2 to 1(13 to 25.4) 18 x 18(5,5 x 5,5) 18(5,5) 18(68) 17.5(1,21) 20 x 20(6,1 x 6,1) 20(6,1) 21 (79) 23.8(1,64) For Ceiling types refer to NFPA 13, 13R or 13D RFC 49 Ordinary Temp. Rating To of Deflector Minimum Max.Coverage Max.Spacing 165°Fl14°C p Installation area to Ceiling Spacing GPM in PSI Ft x Ft(m x m) Ft(m) Flow Pressure Inch(mm) Type Ft(m) Vm 12 x 12(3,6 x 3,6) 12(3,6) 13(49) 7.0(0,48) 14 x 14(4,3 x 4,3) 14(4,3) 13(49) 7.0(0,48) Smooth Ceilings 1/2 to 1(13 to 25.4) 16 x 16(4,9 x 4,9) 16(4,9) 13(49) 7.0(0,48) Beamed Ceilings per NFPA 13D, 13R or Concealed 8(2,4) 13 installed in beams 1/2 to 1(13 to 25.4) 18 x 18(5,5 x 5,5) 18(5,5) 17(64,3) 12.0(0,83) 20x20(6,1 x6,1) 20(6,1) 20(75,73) 16.7(1,14) For Ceiling types refer to NFPA 13, 13R or 13D Maintenance Model RFC30, RFC43 and RFC49 Concealed Sprin- symmetric lever mechanism, maintaining a Teflon-coated klers should be inspected and the sprinkler system Belleville spring washer and machined brass cap water maintained in accordance with NFPA 25. Do not clean seal assembly containing no plastic parts. Sprinkler sprinklers with soap and water, ammonia or any other K-factor shall be nominal 3.0(44), 4.3(62.4), and 4.91 cleaning fluids. Remove dust by using a soft brush or (70)having a 5/16", 3/g" and '/16" orifice. Temperature rating gentle vacuuming. Remove any sprinkler cover plate as- shall be Ordinary 165°F(74°C); cover plate temperature sembly which has been painted (other than factory ap- rating to be 135°F(570C). Cover plate assembly shall plied) or damaged in any way. A stock of spare sprin- consist of a brass cover plate and copper alloy retainer klers should be maintained to allow quick replacement flange allowing a 112" cover plate adjustment. Any secure of damaged or operated sprinklers. Prior to installation, engagement between the cover plate and the cup will sprinklers should be maintained in the original cartons assure that the drop-down deflector is properly located and packaging until used to minimize the potential for below the ceiling. A plastic protective cap shall be damage to sprinklers that would cause improper opera- provided and factory installed inside the sprinkler cup tion or non-operation. to protect the drop-down sprinkler deflector from dam- age, which could occur during construction before the Model RFC30, RFC43 and RFC49 Residential cover plate is installed. Standard cover finish: [Chrome] Concealed Sprinkler Specification [White] [Specialty-specify]. Residential concealed sprinklers shall be Reliable Model RFC30, SIN RA0611 Sprinklers shall be cULus Listed low flow residential con- (Bulletin 006), Model RFC43, SIN RA0612(Bulletin 006) cealed sprinklers with drop-down deflector and adjust- or Model RFC49, SIN RA0616(Bulletin 006). able flat cover plate engineered for a minimum design density of 0.05 gpm/ft2. Sprinkler frame and deflector shall be of bronze frame construction having a 112" NPT thread. Thermal element shall consist of an approved black-painted beryllium-nickel fusible solder link with 3. Ordering Information Cover Plate Finishes") Specify: Standard Finishes 1. Sprinkler Model Chrome _ 2. Cover Plate Finish White Paint 3. Thread-On or Special Application Push-On Feature Finishes(�) Bright Brass :s �► �' Finished Bronze Black Plating Black Paint Off White Satin Chrome (') Other finishes and colors are available on special order. Consult factory for details. Coverplate custom paint is semi-gloss, unless specified �QO otherwise. M For the perforated style cover- plate,consult factory for avail- ability on these and other cus- tom finishes. I" x 112" REDUCING TEE OR ELBOW n1 In 111 111 L_ _j_ 2j""[66.55mm] 2 - [58.42mm] DIA HOLE IN CEILING _T CUP 2" [50.8mm] MAX. FACE OF FITTING TO FACE OF CEILING DIMENSION CEILING " [12.70mm] MAX. 3� COVER ADJUSTMENT 16 [4.96mmJ FLAT COVER PLATE " [84.21 mm] DIA. ASSEMBLY SPRINKLER 006FG01B COVER PLATE: 1 f2" (12. 7mm-1 ADJUSTMENT The equipment presented in this bulletin is to be installed in accordance with the latest published Standards of the National Fire Protection Association,Factory Mutual Research Corporation,or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable. Products manufactured and distributed by Reliable have been protecting life and property for over 90 years,and are installed and serviced by the most highly qualified and reputable sprinkler contractors located throughout the United States,Canada and foreign countries. Manufactured by M, The Reliable Automatic Sprinkler Co.,Inc. ® Recycled ® (800)431-1588 Sales Offices Paper Rel le lab (800)848-6051 Sales Fax Revision lines indicate updated or new data. (914)829-2042 Corporate Offices www.reliablesprinkler.com Internet Address EG.Printed in U.S.A.05/14 P/N 9999970261 NORTH MASON REGIONAL FIRE AUTHORITY (NMRFA) Sheet 9 Supply Analysis Remote Area #2 TWO HEADS FLOWING 'Node at Static Residual Available Total Required Source Pressure Pressure Flow Pressure Demand Pressure 10 56.00 20.00 200.0 55.49 20.1 51.83 Node Analysis Remote Area #2 Elevation Node Type Pressure Discharge Node (ft) K-Value Source (psi) (gpm) Notes 2 12.50 Orif= 3.00 11.00 10.0 3 12.50 Orif= 3.00 11.00 10.0 5 13.00 10.89 - 6 13.00 11.12 - 7 13.00 13.66 - 8 13.00 16.00 - 9 4.00 29.50 - 10 0.00 Supply 51.83 - NORTH MASON REGIONAL FIRE AUTHORITY (NMRFA) Sheet 10 Pipe Information Remote Area #2 TWO HEADS FLOWING Nodel Elevl Kfactor Qadd Nominal Fittings L (ft) Cfac Total Pt Pipe (ft) Hose ID F (ft) Vel Elev Pe Node2 Elev2 Qtot Actual Length T (ft) Psi/Ft Fric Pf Notes 2 12.50 3.00 10.0 1" 1PE L 0.5 150 Pt 11.00 2 F 5.0 3.4 Pe -0.22 5 13.00 10.0 1.101 5.0 T 5.5 0.0187 Pf 0.10 DR2:K=3.03 -------------------------------------------------------------------------------------------- 3 12.50 3.00 10.0 1" 1PT L 0.5 150 Pt 11.00 3 F 5.0 3.4 Pe -0.22 6 13.00 10.0 1.101 5.0 T 5.5 0.0187 Pf 0.10 DR3:K=3.03 -------------------------------------------------------------------------------------------- 5 13.00 3.03 [10.0] 1" L 12.0 150 Pt 10.89 DR2 5 F 0.0 3.4 Pe 0.00 6 13.00 10.0 1.101 T 12.0 0.0189 Pf 0.23 -------------------------------------------------------------------------------------------- 6 13.00 3.03 [10.1] 1" 2PT L 27.0 150 Pt 11.12 DR3 6 F 10.0 6.8 Pe 0.00 7 13.00 20.1 1. 101 10.0 T 37.0 0.0687 Pf 2.54 BL2:K=5.44 -------------------------------------------------------------------------------------------- 7 13.00 5.44 [20.1] 1" 1PT 2PE L 19.0 150 Pt 13.66 BL2 7 F 15.0 6.8 Pe 0.00 8 13.00 20. 1 1. 101 15.0 T 34.0 0.0687 Pf 2.34 8 13.00 1 1GV 1WFS L 10.0" 16.00 Top of Riser 8 1BKF F 13.4 6.8 Pe 3.90 1BKF = 8.00# 9 4.00 20.1 1.101 13.4 T 23.4 0.0687 Pf 9.61 -------------------------------------------------------------------------------------------- 9 4.00 1" 1MTR 1GV 150 Pt 29.50 9 2PE 1PT F 1 .9 6.8 Pe 1.73 1MTR = 16.00# 10 0.00 20.1 1.101 16.9 T 66.9 0.0687 Pf 20.59 Supply -------------------------------------------------------------------------------------------- Hydraulic Calculations Sheet 1 for ,project Name: NORTH MASON REGIONAL FIRE AUTHORITY (NMRFA) Location: 1801 E TRAILS END DR, BELFAIR WA 98528 Drawing No: 23-230 Date 04/25/23 Job: NMRFA2 Design: Remote Area Number: 2 Remote Area Location: TWO HEADS FLOWING Occupancy classification: 13D RESIDENTIAL Density: 0.05 gpm/sq.ft. Coverage per sprinkler: 196 Square Feet Maximum Type of sprinklers calculated: 3.OK RESIDENTIAL No. of sprinklers calculated: 2 heads Total water required: 51.83 psi @ 20.1 gpm @ Supply Including hose streams 55.49 psi available @ 20.1 gpm Below curve by 3.66 psi for Remote Area 2 Type of System: Wet Water Supply Information: 56.00 psi Static, 20.00 psi Residual @ 200.0 gpm Date: 02/02/23 Location: E. TRAILS END DRIVE Source: TRAILS END WATER DISTRICT Name of Contractor: Fox Fire Prevention Address: P.O. BOX 594 PORT ORCHARD, WA., 98366 Phone Number: (360) 871-1985 Name of designer: ADAM COLE Authority Having Jurisdiction: MASON COUNTY Program: 'HydroCalc' by Micro Space Systems www.MicroSpaceSystems.com WASHINGTON STATE ; CERTIFICATE OF COMPETENCY FIRE PROTECTION SPRINKLER SYSTEMS Adam B. Cole 4871-0305-C Level 3 ; Fox Fire Prevention, Inc. ; FOXFIP1127M8 25MAY23 i Date i � Expires i Signature 12/31/23 ---------------------------� a NORTH MASON REGIONAL FIRE AUTHORITY(NMRFA) Flow Test Summary Sheet N1.85 60 CD I I i i I I I I I I I I I I I I II I I I I I I I I I I I I I I I I I I I I I I I I I I 50 ---- ---- ------------- ' ------'------------------II---------------------------------------- I I 1 I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I 1 I I I I I I I I I I I I I I I I I I I I I I I I I I I 40 - ---1---------------- -__________I_---_________- ______ -_______L--______-_-_----J-____ ------L------------_ I I I I I I I I I I I I 1 1 I I I I I I I I I I I I I I I I I I I I I I I I I I 1 I I I I I I I I I I I I I I I I I I I I I d I I I I I v I I I I I I I I 1 N CL I I I I I I I I I I I I I I I I I I I I 1 I I I I I I I I I I I I I I I I I I I I I I I I 1 I I I I I I I I I 1 I I I I I I I I I I I I I 1 I I I I I I I I I I I I i I I I I I 1 I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I 10 ---- - - -----'- - - -----'-- --- -- '--- -------- --I------ --------- - -- -------- --------- ------- --------- - I I I I I I I I I I 1 I I I I I I I I I I I I I I I I I 1 I 1 I I I I I I I I I I I 20 40 60 80 100 120 140 160 180 201 ■ Static=56 psi. Flow(GPM) ■ Demand at BOR=29.50 psi with 20.1 gpm flowing. ■ Residual=20 psi at a flow of 200 gpm. ■ System demand=51.83 psi with 20.1 gpm flowing. Pressure available=55.49 psi when 20.1 gpm is flowing. Demand is below curve by 3.66 psi (6.60%).for Remote NORTH MASON REGIONAL FIRE AUTHORITY (NMRFA) Sheet 3 Fox Fire Prevention ' Description of Fitting abbreviations Code Description ----------------------------------------------------------------- WFS Waterflow Switch, Vane-type PT Plastic Tee PE Plastic 90 degree Elbow BKF Backflow preventor MTR Meter Loss GV Gate valve Description of Other abbreviations Code Description ----------------------------------------------------------------- DR Drop BL Branch Line CM Cross Main PT Total pressure PE Pressure loss due to elevation changes PF Pressure loss due to friction ^.5 Raised to the power of .5 (Square Root) L Actual pipe length F Fitting equivalent pipe length T Total pipe length ES-A-2000B Job Name Contractor Job Location Approval Engineer Contractor's P.O. No. Approval Representative Series 2000B Double Check Valve Assemblies Sizes: '/2" - 2'r ". 3/4°2000B Series 2000B Double Check Valve Assemblies are designed to (20mm) protect drinking water supplies for dangerous cross-connections " in accordance with national plumbing codes and water authority requirements for non-health-hazard non-potable service applica- tions such as irrigation, fire line, or industrial processing. These valves meet the requirements of ASSE Std. 1015 and AWWA Std. C510 and are approved by the Foundation for — Cross-Connection Control and Hydraulic Research at the � .1 t 9 University of Southern California. .' 2"2000B HC Features (50mm) •Ease of maintenance with only one cover •Top entry Specifications •Replaceable seats and seat discs A Double Check Valve Assembly shall be installed at each not- Modular construction ed location. The assembly shall consist of two positive seating check modules with captured springs and rubber seat discs. The •Compact design check module seats and seat discs shall be replaceable. Service •'/?"-2" Cast bronze body construction of all internal components shall be through a single access cover •Top mounted ball valve test cocks secured with stainless steel bolts. •Low pressure drop The assembly shall also include two resilient seated isolation •No special tools required valves and four top mounted, resilient seated test cocks. The assembly shall meet the requirements of ASSE Std. 1015 •'/2"— 1" have tee handles and AWWA Std. C510. Approved by the Foundation for Cross- Connection Control and Hydraulic Research at the University of Southern California. Assembly shall be an Ames Fire & Waterworks Series 2000B. r The information contained herein is not intended to replace the It is illegal to use this product in any plumbing system providing water for full product installation and safety information available or the human consumption,such as drinking or dishwashing,in the United States. experience of a trained product installer. You are required to Before installing standard material product,consult your local water author- thoroughly read all installation instructions and product safety ity,building and plumbing codes. information before beginning the installation of this product. AiW A M E Ames Fire&Waterworks product specifications in U.S.customary units and metric are approximate and are provided for reference only.For precise measure- F!K E&w 4T E!;uJ O tz KS ments,please contact Ames Fire&Waterworks Technical Service Ames Fire&Waterworks reserves the right to change or modify product design,construction, specifications,or materials without prior notice and without incurring any obligation to make such changes and modifications on Ames Fire&Waterworks products previously or subsequently sold. A WATTS Brand Available Models Standards Suffix: AWWA Std. C510, IAPMO PS31 B- Quarter turn ball valves LBV- less ball valves Approvals s U r ��pSSIFj�o SH 855E stainless steel ball valve handles c Spe C US QD UL)us HC- 2'/2" inlet/outlet fire hydrant fitting(2"valve) 1015 B64.5 3/4"-2-- (LBV Models Only) Pressure — Temperature •Approved by the Foundation for Cross-Connection Control and Temperature Range: 33°F- 140°F(0.5°C-60°C) Hydraulic Research at the University of Southern California. (Excluding all LBV Models) Maximum Working Pressure: 175psi(12.1 bar) . Horizontal and vertical "flow up"approval on all sizes. Dimensions-Weights A 4 I B F Suffix HC - Fire Hydrant Fittings dimension"A"=231h" (594mm) ~H I G SIZE DIMENSIONS WEIGHT A B C F 6 H I in. in. mm in. mm in. mm in. mm in. mm in. mm in. mm Ms. k . 'h 10 254 41A 117 21/6 62 5 127 33/8 85 25/6 59 21/6 52 4.5 2 3/4 111/ 282 4 102 TA 79 63/ie 157 37A6 87 21/8 54 15/c 33 5 2.3 1 13'/4 337 Th 130 4 102 7'h 191 33/8 85 111A6 43 1 VA6 43 12 5.4 11/4 163/8 416 5 127 35/6 84 91h 241 5 127 3 76 2 50 15 6.8 11h 163/4 425 47A 124 3'h 89 93/4 248 513/16 148 3'A 79 2"/16 68 15.86 7.2 2 191h 495 6'/4 159 1 4 102 1 133A 340 6'/a 156 1 3'he 87 1 2"A6 68 1 25.75 11.7 Strainer sold separately Capacities As compiled from documented Foundation for Cross Connection Control and Hydraulic Research at the University of Southern California lab tests. ATypical maximum system kPa psi A 1114" flow rate(7.5 feet/sec., 2.3 meters/sec.) 96 14 83 12 N o 69 10 112n a> 55 8 kPa psi , 41 6 N 83 12 A N 28 4 0 69 10 a) 14 2 -� 55 8 1 N 41 6 28 4 0 0 AP 0 10 20 30 40 50 60 70 80 90 100 110 120 gpm U) 14 2 0 38 76 114 152 190 228 266 304 342 380 418 456 Ipm a` 0 0 5 7.5 10 15 fps 0 2 4 6 8 10 12 gpm 1.5 2.3 3.0 4.6 mps AP 0 7.6 15.2 22.8 30.4 38 45.6 Ipm Flow Rate 5 7.5 10 fps 1.5 2.3 3.0 mps kPa psi 1112" Flow Rate 83 12 kPa psi g�41r m 69 10 y 152 22 0 55 8 41 6 J 124 18 28 4 96 14 N 14 2 In 69 10 d 0 ap0 10 20 30 40 50 60 70 80 90 100 110 120 gpm d 41 6 0 38 76 114 152 190 228 266 304 342 380 418 456 Ipm 14 2 5 7.5 10 15 fps 0 5 10 15 28 25 30 35 40 45 50 gpm 1.5 2.3 3.0 4.6 mps AP 0 19 38 57 76 95 114 133 152 171 190 Ipm Flow Rate 7.5 15 fps 2.3 4.6 mps kPa psi 2" Flow Rate m 83 12 kPa psi 1 u p 69 10 y 110 16 A J 55 8 J 83 12 3 41 6 3 55 18 d 28 4 y 41 6 d 14 2 ` !t 28 4 0 0 d 14 2 0 25 50 75 100 125 150 175 200 gpm AP 0 95 190 285 380 475 570 665 760 Ipm 0 5 10 15 20 25 30 35 40 45 50 55 60 gpm 5 7.5 10 15 fps AP 0 19 38 57 76 95 114 133 152 171 190 209 228lpm 1.5 2.3 3.0 4.6 mps 5 7.5 10 15 fps Flow Rate 1.5 2.3 3.0 4.6 mps Flow Rate A M E FIRE&WATERWC.^.::E: A WATTS Brand USA:Backflow T:(978)689-6066•F:(978)975-8350•ArnesFireWater.com USA:Control Valves T:(713)943-0688•F:(713)944-9445•AmesFireWater.com Canada: T:(905)332-4090•F:(905)332-7068•AmesFireWater.ca Latin America: T:(52)81-1001-8600•AmesFireWater.com ES-A-200013 1735 0 2017 Ames Fire&Waterworks FOX FIRE PREVENTION, INC. PO BOX 594 FOX PORT ORCHARD, WA 98366 360.871.1985 Contractor's Registration FOXFIP1127M8 INFO@FOXFIREPREVENTION.COM North Mason Regional Fire Authority- NMRFA 25APR2023 1801 E Trails End Dr Belfair WA 98528 Information for hydraulic design is included on Fire Sprinkler Plans, provided by Trails End Water District. Adam Cole Design Division Fox Fire Prevention, Inc. PO Box 594, Port Orchard WA 98366 360.871.1985 ph. 360.871.2262 fax www.foxfireprevention.com ------------------------------------------------------------------------------------------------- Bulletin 425 August 2020 lmla�blld Residential Riser cULus Listed 175psi (12 bar) rated Features • Stainless Steel body construction • Factory assembled and tested • Vertical or horizontal installation • Optional mounting bracket Approvals & Listings • Listed by Underwriters Laboratories Inc. and Underwriters Laboratories of Canada(cULus) Product Description The Reliable Residential Riser is UL Listed wet-pipe sprinkler system riser assembly consisting of a stainless steel body, waterflow switch, pressure gage,and drain.Triggering flow for the waterflow switch is 10 gpm(38 LPM).The Residential Riser is intended for use in NFPA 13D and 13R systems,and is offered in 1", 1 1/2",and 2"sizes.The product is available with a variety of end configurations(see table A below),and a choice Shown:2"threaded version with Model TD Test and Drain valve trim, of drain trims including a three position(off/test/drain)valve with optional Model A Pressure Relief valve kit,and optional locking handle several orifice choices.Optional pressure relief valve kits are kit(padlock not provided) also available. The Residential Riser can be wall mounted using the cast-in lugs or stud mounted using the optional support bracket(See Fig. 2). Maintenance Installation The owner is responsible for maintaining the fire protection system in proper operating condition.Any system The Reliable Residential Riser should be installed in maintenance or testing that involves placing a control valve accordance with NFPA 13,NFPA 13D,or NFPA 13R, or detection/control system out of service may eliminate the as well as the requirements of any authorities having fire protection that is provided by the fire protection system. jurisdiction. Failure to follow installation instructions may Notify any required authorities having jurisdiction and void the warranty and listing of the valve.Connect the riser implement appropriate precautions prior to proceeding. manifold to the supply piping and system piping using When required,the Reliable Residential Riser and associated a non-hardening pipe joint compound or joint sealant equipment shall periodically be given a thorough inspection tape for threaded connections. Ensure proper direction and test. NFPA 25, "Inspection,Testing and Maintenance of of flow using the flow arrow cast into the manifold.The Water Based Fire Protection Systems," provides minimum one-inch(1")drain should be piped to a location that will maintenance requirements. Replace any components found avoid damage to property and injury to personnel. to be corroded,damaged,or worn. Increase the frequency of inspections when the valve is exposed to corrosive conditions or chemicals that could impact the valve materials. Nominal Size Available End Connections 1"(25mm) Male or Female NPT 1-1/2" (40mm) Female NPT or Grooved Ends 2"(50mm) Female NPT www.reliablesprinkler.com Residential Riser Assemblies ' Basic Assembly with Ball Valve Drain (Shown with Optional Pressure Relief Kit) Dimensions and Weight F1,61 174 Water B Basic Assembly with Ball Drain Valve Pressure Press.Relief A B C D Weight Gauge Mang Kit(Optional) Manifold Size g Body in in in in Ibs (mm) (mm) (mm) (mm) (kg) System Threaded Female 11 8-1/4 2-3/4 7.3 NPT 1 (25) (279) (210) (70) (3.32) ° Threaded Male NPT 11 8-1/4 2-3/4 7.3 0 1 (25) (279) (210) (70) (3.32) C Threaded Female 11-1/4 11-1/2 8-1/4 3 8.3 A ° (Take Out) NPT 1-1/2(40) (286) (292) (210) (76) (3.77) 0 Threaded Female It-3/4 8-1/4 3-1/4 8.8 °o NPT 2(50) (298) (210) (83) (4.00) Grooved Ends 1-1/2 11-1/2 9-1/2 3 8.3 Supply Drain (40) (292) (241) (76) (3.77) Drain Valve Water Flow D-all Detector Note:Drain tees are plugged when pressure relief kit is not used. 425FG01A Basic Assembly with Test and Drain Valve (Shown with Optional Pressure Relief Kit) B Water Pressure Gauge Press.Relief Manifold Kit(Oplonal)� Dimensions and Weight Body Basic Assembly with Test&Drain Valve System Manifold Size A B C D Weight in in in in Ibs �° ® ® =t (mm) (mm) (mm) (mm) (kg) 0 Threaded Female 14-1/2 8-1/4 3-1/4 9.0 A C NPT 1 (25) (368) (210) (83) (4.09) Drain (Take Out) Threaded Male 14-1/2 8-1/4 3-1/4 9.0 0 NPT 1 (25) (368) (210) (83) (4.09) 10 Threaded Female 11-1/2 15 8-1/4 3-1/2 9.7 NPT 1-1/2(40) (292) (381) (210) (89) (4.41) Supply Test and Drain Threaded Female 15-1/2 8-1/4 3-3/4 10.5 Valve NPT 2(50) (394) (210) (95) (47 Detector 7) Water Fl°W I�D Grooved Ends 15 9-1/2 3-1/2 9.7 D 1-1/2(40) (381) (241) 1 (89) (4.41) Note:Test and Drain valve outlets are plugged when pressure relief kit is not used. Bulletin 425 Page 2 of 4 August 2020 www.reliablesprinkler.com