HomeMy WebLinkAboutFIR2022-00003 Alarm Test - FIR Inspections - 1/31/2024 Mason County Fire Marshal
615 W. Alder St. Shelton WA 98584
Phone: 360-427-9670 x 309
Fire Alarm Certification/Final Test
FIR Location: Z/610
Contractor: �z.%A /114"-"qS Phone #:
Contact: Test Date: 12,31 ?%
CHECKLIST
Verify panel is in "Normal" condition and clear of any signals
✓ Kill Power At Electrical panel &verify dedicated circuit, red breaker & lockout
✓ AC Trouble/ No Power displayed?
✓ Activate device(s), verify it activates the alarm and shows correctly on the panel
Check the Notification Alarm Circuit (NAC) for activation of devices. Walk building while
alarm is activated under battery load. Check for all lights and sounds to be in-sync
✓ Silence Alarm
Activate a few other devices in different areas to verify alarm reactivates after being silenced
Reset Alarm
✓ Does panel still show trouble (due to AC power)?
Disconnect Signal Loop Circuit (SLC) to create/verify a trouble for each device on circuit
vl Reconnect SLC. System should reset& only AC trouble showing
Disconnect the communication line & verify communication trouble
✓ Do batteries AMP/HR match plans?
FACP Sign on Door(s) leading to panel location?
Device Test Log
Notification Device Time Comments
Water flow Inspectors test , L?,�r �.24 '3 7✓
Smoke detector at FACP S ✓
Tamper switch 1 4,;:frA"Sc/-
93� J
Tamper switch 2
Manual pull at �- - y ✓
Manual pull at
Manual pull at
Heat Detector f / (7 .7 ✓
Heat Detector r����o• , �/ �1f
Heat Detector y l cv i?Q„y
Heat Detector
Heat Detector
Smoke Detector
Smoke Detector
Smoke Detector c�
tz :J.� ✓ 64/ /GJ SGtr C✓i� %�/yS C n r/I��
/ i ii QQ N //IPCCU � nn
Punch List/Comments: (�/� �Sl�l✓��� d�ti�✓i�ti�, rz
4nGl lia/QM."Cio/GLt/lf-fOlnl.�//G yIjjfiiaiCib� vtll//n /�</fG+�G�%'LY�/,GnC O�� O<ckis- /
/74w1 -. . /4/2 Ce/�lY /Sffit%G� o��� isles /GcEl/Y
WO# 6002
Viking Automatic Sprinkler Company
3434 First Avenue South
Seattle, WA 98134 NFPA 25 Testing
206 622 4656 of
2 DRY SYSTEMS
SPRINKLER SYSTEM 5 YEAR TEST - DRY P1 WET ❑ DRY STANDPIPE ❑
Occupancy Address: 21 W SANDERSON WAY Occupancy Name: PORT OF SHELTON-NEW BLDG 1
Responsible Person
First& Last Name: NED WILSON Phone Number: 3604906448
Responsible Person
Address, City,State,Zip. SHELTON, WA.98584 Responsible Party
E-M Mail il Address NEDW@PORTOFSHELTON.COM
Technician's Name:TRACY BARGE Certification No. 1962-1208-EG
Date of Test: 11-5-2020 Test Frequency: 5 Year
Riser Valve Make: #1 DRY 6"VIKIVG-D1 1975 Riser Valve Model: #2 DRY VIKING-F1 2004
System Identification No. 2 DRY SYSTEMS System Location: BUILDING#1
DEFICIENCIES FOUND? Yes O No El
List items that were not corrected at the time of the confidence test.
Use the Deficiencies section or attach itemized sheet
REPAIRS: All deficiencies have been corrected 0
Corrected By: Date:
This certifies that this fire and life safety system has been properly tested in accordance with NFPA Standards.
The discrepancies found are noted in the report and have been reported to the building Owner/Manager for
corrective action.
Signature of Technician TRACY BARGE Phone #: (206) 622-4656
Name of Testing Company: Viking Automatic Sprinkler Company— Seattle Washington
Building Representative (signature) Date 11-5-2020
Print Name and Title
Direct Phone # Email:
Building Rep unavailable 7 Building Rep declined to sign report 0
Sprinklers NFPA 25 Page 1 of 3
WO# 6002
SPRINKLER HEADS 2 DRY SYSTEMS
1. The standard sprinkler heads are less than 50 years old or within a prescribed testing period.
If"No"have the heads sample tested or replaced per 2008 NFPA 25 and at the prescribed Yes V( No❑
intervals thereafter.
Due date for sample testing: 2025
2. The Quick Response sprinkler heads are less than 20 years old or within a
prescribed testing period.
If"No"have the heads sample tested or replaced per 2008 NFPA 25 and at N/A Yes ❑ No O
the prescribed intervals thereafter.
Due date for sample testing.
3. The dry type sprinkler heads are less than 10 years old or within a
prescribed testing period.
If"No"have the heads sample tested or replaced per 2008 NFPA 25 and at N/A rV Yes ❑ No❑
the prescribed intervals thereafter.
Due date for sample testing:
GAUGES
The maintenance on the system gauges is up-to-date.
Due date for the next comparison test: 2025
Note:The system gauges are to be compared with a calibrated gauge every five(5)
years. If a gauge is not within+/-3%of the calibrated gauge it must be replaced or Yes Cr No❑
recalibrated.This check should be done for multiple floors at static oressure using
one calibrated gauge and hydraulic calculations.
OBSTRUCTION (INVESTIGATION
1. The 5-year obstruction investigation of Fire Department Connection(FDC)piping is up-to-
date in accordance with 2008 NFPA 25 Chap.14.(off.1012112012) Yes er No❑
Date for next FDC obstruction investigation 2025
2. The 5-year obstruction exam for the FDC(s)included testing and operation of the check Yes P No O
valve.
3. The 5-year Obstruction Examination of the sprinkler piping is up-to-date in accordance
with 2008 NFPA 25 Chap. 14.(eff.1012112012) Yes tW No ❑
Date for next Piping Obstruction Examination 2025
DRY STANDPIPE
1. Standpipe was hydrostatically tested at not less than 200 psi or 50 psi in
access of maximum pressure where maximum pressure Is In excess of 150 N/A or Yes O No❑
psi.
2. The standpipe Fire Department Connection(s)(FDC)is clear of bushes, N/A ❑ Yes t( No❑
guards,or other debris and is visible from the street
3. All FDCs and hose valves have protective plugs or caps. N/A ❑ Yes Q' No❑
4. If a plug or cover was missing from a FDC the piping was inspected N/A ❑ Yes Q' No❑
for debris. (this is required)
5. All caps and plugs have at least 12"clearance for operating wrenches. N/A ❑ Yes Gr No❑
6. All swivels turn freely. N/A ❑ Yes tr No❑
FINAL CHECKS
1. The Fire Alarm was removed from test mode and/or other precautionary
measures were removed to restore fire alarm system to normal N/A 6' Yes ❑ No❑
operation(includes removal of protective coverings).
2. The system was left in service. Yes a No O
If"No",why
3. The confidence test report was given to the owner and a current status tag was posted. Yes gr No❑
4. The confidence test report was sent to the fire marshal's office. Yes 9' No❑
Deficiencies
Sprinklers NFPA 25 Page 2 of 3
This is a Federal Building O
WO#6002
2 DRY SYSTEMS
Deficiencies
Resolved
Location
Deficiency. _
Recommended Resolution:
SFC and/or 2008 NFPA 25 reference:
Resolved
Location:
Deficiency:
Recommended Resolution:
SFC andlor 2008 NFPA 25 reference:
Resolved
Location.
Deficiency
Recommended Resolution
SFC andlor 2008 NFPA 25 reference:
Resolveo —
Location:
Deficiency:
Recommended Resolution:
SFC andlor 2008 NFPA 25 reference:
Resolved
Location:
Deficiency
Recommended Resolution.
SFC andlor 2008 NFPA 25 reference:
Sprinklers—Dry
2012 ver. 1.1 Page 4 of 4