Maintenance and Operation Manual
For
South Shore Enterprises Commercial Buildings
750 E Dalby Road q
Lot 3 of Parcel 32232 43 000103
Union, Mason County, Washington
October 11, 2010
Project#1027
Prepared For:
South Shore Enterprises, LLC
PO Box 249
Union, Washington 98592 tiL CLYDE S
CAP OF WAS�j� Jy?
Prepared By: 4
Envirotech Engineering
74 NE Hurd Road 43045 w�
Belfair, Washington 98528 °��f'FCfS.�gtiOG��t
Phone: 360-275-9374 SIDNALti�
Fax: 360-275-4789
# --
�s
� � .
...�. .. ,
i i
i
d
Introduction
Envirotech Engineering (Envirotech) has completed this maintenance report for a
proposed commercial redevelopment. The property is located at 750 East Dalby Road
(Lot 3 of Parcel 32232 43 00010)in Union, Mason County, Washington(Project).
Manual Purpose
The purpose of this manual is to provide the property owner with a general maintenance
plan in order to ensure the continued proper operation of all stormwater management
facilities associated with this project. Lack of maintenance could lead to local flooding,
water damage, excess pollution, and/ or costly repairs or replacements of property or
drainage systems.
Maintenance Responsibilities
Facility maintenance is ultimately the responsibility of the property owner. Currently,
stormwater maintenance responsibility for this property belongs to:
South Shore Enterprises, LLC
PO Box 249
Union, Washington 98592
360-898-2481
Maintenance Requirements
The following stormwater management facilities include provisions for inspection
procedures and necessary maintenance:
Permanent Vegetation
Permanent vegetation within the drainage swale shall be inspected regularly to insure
establishment and healthy growth. Vegetation shall be re-established, where necessary.
Vegetation may need to be periodically fertilized for continuous growth. Fertilization
shall be applied per manufacturers recommendations.
Envirotech Engineering Operation and Maintenance Manual
Ph. 360-27i-9,74 Paec 1 of 7 7 0 E Dalb- Road, Union. NVashingnon
Fax:360-275-4789 Lot 3 of Parcel 3,2212 4100010
October 11. 2010
r i
Drain Pipes
Drain pipes, including roof gutters should be inspected 3 times per year, and cleaned as
necessary. Overflowing gutters or catch basins are an indication of drain pipe or gutter
clogging. Drain pipes that become separated from the catch basins shall be repaired
immediately.
Energy Dissipation
#7-t'.laintenance ChecUst for Energy Dissipators
atE
Freq'.reney Cra rage 1 Plro:tr Caritior.s to Check For Cor•crtions That Shan c Exist
sys:em
Feat_ire
Ex:ema:
Rcck Pad Nissirg or 'Ay ore eye,w rack exists abare Rock pad rep aced to oe•sgn
i o,.,ed Rock ra&-e rail r area Five s uare feet 5:311.daro5
ar aryer.or arry er:aosve o'na:'+e
soil.
ck rosion .poi eros or n or aojaccrit to mck Rock pad rep aced to 6"gn
aad. s:anoams
spersion Pfae Fl4gec wrn ACcumUlattc seoinertthat P.re ceoned fushec so tat it.
Trench Sedin•ert exceecs 2-%of the cesim depth. ratchet des�;r.
spersion iJ_t Ciccha-gir, isual evvzerce cf water Trench rececigned or rebu t to
Trench View Property oischargirg at corcentrwed;ems starters
a ong;ranch irorrral cor'dition:s a
'sheet 9a•S"'W Water acrg Tenchi
Irtert is:o arevent erosor.carnage.
Ll Cis tNor. Ferfor3t!ons Plu;;ed Over 1:2 of Perforations in wipe are Perforated p pe c Caned or
Trench r uaged kith debris and sedlmert. re;.la ec
sptrsian -Na:er Pow.Odd lop of irahner3rde nersor,observer or Fac:ity rebut t or rases Bred o
Trerctr DisTib roe'Catch Bar-in receives zre3iae report of water s ancaras
foam;out duM any stom•less
tar the desigr scorn or
i:s taus rg
or appearsIiker . ake accl
Cispersien Receiving Area Over- 'hater in recefvrg area is causing No danger of ends ices.
Trench Sa urated or has paternal of eausir.;,la idslice
probe'ra'.
Hemet
b'arho etC Structure rea acea to resign
her^.her ivorr.or Dama^ed?ost Strucse d ssipat rg flaw s anzarzs
5alfles.S ce ay Marnt>er deteriorates to'r of origin s_e or
any corcentraxc worn spot
axceecing one square foot v.•hich
,.wu d make structure urscurc
.arino eti Trash&Debris No:rash or deer s:r the catch
han•ber Tres,ardecre:h the basin:tta: basin
exceecs 3 percent ate snip
depth as measured from the bo:torn
of basr to:Firer.of the oxast pig
rro or out of Ce basin o.r.in no
case leas than a nirimiT of s
inches clearance from the dec-r:3
surface tc the in:art o'the!ones
W. F.`anho e, Tr W&debris Inlet arc out at pipes free a'
harrber Tras,ordetxsr any inlet oroutle: tnshordewis
pipe a ocking n•ore than t:3-fir
d'tla'it.
kf '•anho e- Trash&Debris No dead ariria s or vegetanar
han-ber Dead arena s or vegetation is Present:v thir the catch iascn.
cou d generate odors that could
cause con;,lasts or danbercus
-oses i`. riehaY-i.
k4aMo ev Sedimart Seciment yin^Fie oasinr:fat No ssoirrent in*ie catch basin
harr ber exceecs K percent of tie sum r
ae 35 r'eaLUfed fro'r the bottom
Envirotech Engineering Operation and Maintenance?Manual
Ph. 360-27i-9374 Page 2 of 7 7,;0 E Dolby Road. Union. Washington
Fax: 360-275-4789 Lot 3 of Parcel 32232 43 00010
October 11. 2010
ate
Frequent{ Cra page o:em Condors to Check For Corcitions That Mold Exist
S''y'sIe'll
Feature
of b-cs r o m: o'the lowest pipe
into or out of the basin.Cs in no
case less than a rndrim.rn of E
inches clearance ttom the sedirrert
surface to the irvert of the loAles:
.air ho e+C Structure Cartage to Top slat:has hoes a—,er than 2 Top s ab is free or he es arc
han,ber Frame andlorTw Saab square inches or crack-lit,cer than cracks.
tt4 inch drtent is to make sure ro
material is rmring rto basin:.
ar io e C Strucr i-e Camage to Frame nut sitting rush or top cab.
h 3rrber Frame anoFor-oo S ab i.e.separation of more than 514 Frame is sittitg'4.sh-•r the
inch of the`-ame from the top s ab riser rin;s or top sla:an
Frame net secure,y attached firm Ir W.acted.
.ar o e,'- Fractures or Cracks in M3itterance persor judges:hat Basin rep aced or reps red to
h3mber Basin'Aa1WBottom sTucture snsound. design standards.
Vat o e Fractures or Cracks In ::rout 8 bt has separated or P pe is re;routec and secure
harrber Basin'1.'a9 r Bottom cracker xider than 1�_inch and at basin
longer than 1 foot at tee joist of ant
ini tloutlet pipe or any evidence of
soi`part cles enterrg catch basin
thrott^h cracks.
.ar o e SettiemenC If fai ure of basin his created a Basin rep aced or reps re c t_
han-ber Wisal-gnment We y,fur ction.or design V,ott*M design standards.
Warhoe?C Contamination Aryevidence efol,yaso ine, o cor Iran s er zo r.3r
ts
hamber and Po l.r on coh:ani nants or other pot L ants present.
itoordirate removarceanuo wth
oc a 'A-a:er qua ky response
avercv:.
Catch Cover Not in Place Corer is miss r4 or only pa tia.ly h !sty'open catc-i::3s r re;ui-e;
basin place. mairterance. -_a'c-Lcsn
Cc;er ccver is c ose
C3teh Locking Mechanism htsctwrism cannot re ape> a ci Necharism opens vitn prooer
Basin Not Work rig one rnainterance person wraith too s
Cover proper too s.Bolt irto fr3hre ha•re
ess than VZ inch of thread.
C 3tt1 Cover CirNeut One mairrenance persor carnet Cover car.be removed by ore-
Basin to I2ernove remove lid a'.er a--o!ying normal maintenance person.
Cove- i'tino:/essure. +Intent is keep
cover'ram sealing off access to
rraintar3rce.:�
If you are unsure whether a problem exists, please contact a Professional Engineer.
XG
(M) Monthly from November through April.
(A) Once in late summer(preferable September)
(S) After any major storm(use 1-inch in 24 hours as a guideline).
EnA irotech Engineering Operation and Maintenance Manual
Ph. 360-2 7;-9374 Page 3 of 7 750 E Dalb}-Road. Union.Washington
Fax: 360-27 -4789 Lot 3 of Parcel 32232 43 000 10
October 11.2010
Dispersion Trenches
Date of Inspection-
Inspector:
Maintenance Checklist for
Dispersion Trenches
Dlspemian Trenches are rock filled devices used to spread water from a collection source over a wide
area to encourage gradual infiltration over a large area. Larger trenches may contain catch basins and
boards to assist in spreading the water.
Frequency Drairtage Conditions requiring Results Expected After
Systems Maintenance (leaning) Maintenance Performed
Feature
Twice per Distribution Sediment"exceeds 10%of Sediment,trash and debris
Year Catch Basin storage depth or it any at any cleaned out
location the depth exceeds
15%of the storage depth
Twice per Distribution Evidence that water fknm•s oul Clean system and contact
year Catch Sasin of catch basin instead of design engineer to debermtne
prpetlrench whether reCe5igr1 or rebm"d 15
necessary
Twice per Pipe Over 7,of perforallo•is are Pope cleaned o-replacer]
Year Perforalions
Twice per Erosion Evidence of channe'ized Trench Redesignec or rehui,l is
Year I discharge ruts at outlet,etc.l I produce srmet flow
See a?sa Catch Basin Checklist if Trench design contains catch basir
Emvirotech Engineering Operation and Maintenance Manual
Ph. 360-275-9374 Pagc 4 of 7 70 E Dalb,,-Road.Union. Washington
Fax: 360-27S-4799 Lot 3 of Parcel 32232 43 0ti010
October 11. 2010
Catch Basins
*5-Pala r:ena:nce CheA istfor Caten Easins
i ra
C .-ons t_C-RA F'x „ondk-c s That Should
c ysr;.-)-, Exist
ene-a 'C. r.•-c p3 _:an-; ' Sc cr swnp should be 'A3 -ig s-'rs:e.g..
nJf v si;,ie and easilg read 'C.:ntp Uo Was -C=-s x
_ St am'r shall:_paint
or-nbos-sed cn or
adjac-n--o all sprn da.-
inlets.
ene a -ras s -rasr or I--Ys whi:h is 13:a:e: No'ash or debts located
_ m^,edia-ey in rrmt of the ca=h m•^ec:a*y in rout of
casm opening or is blocking :ate^tasin or on graze
n e:bng capactr cf a bas r by opening
^urethan tc%.
'ras^or c=,-s:n t^e basin; Vo-rash or debrs in the
-,,at exceeds 5'j percent of the cater tasm.
sump depth as measure:4�^.
:he c•c•:L n•I casin:o -wen of
s :Wes:pipe into or cu:c`:ne
:.3sin,but in nc case less than
a mnim im of six inches_
:Iealan:e from:he detrs
surfa cE:J:he --den of t-e
c%-es-.pipe
I 'jenera. 7ras-b 7ras-Or Ccr 5 any Inlet or i^.'iel and c0et pipes free
JEb^.s ou:';et o*e blcckmg"ere than o*:rasr or-*vs.
S- :s heiaht.
V 'oenera. 7ras^S -,sa_animals o :epeta:ian:hat No read arir4s cr
JEG'.s ::)j)t genera:E odors-.hat couid vepeta:!3'
'-se ccmD'.a'ts cr danper3us the cater tas'.
ses ie._..r .hanei
t3sl^':^.at Vo sedinen:in the ta:ch
seeds dC percent c':hc sump casin
cep:-as measured from:ne
s:.tern&t:asin.o -•een of t-e
coves:pipe irtc Dr cut c`:he
z3v%but in nc case less than
a rr nmun of 5 inches
ciea•a :e from:he sed,men-
ssf3ce'o:he -vertoft-a
Cwes-.c ce
-era Damage to -op slab-=s _s arger than lop slab s wee c=-_=s
Fray-e and cr-x sc are inches cr:racks w:_ a d c-acks.
Slab -tan':4 -:h'nt s m-take
sure no na'e,i s running ir•tc
Lasi^:i.
cnc._�a slur-re-';F-3ge tc 'rara nol sa flu ng sh.en top
Frame and cr sab•i.e,separa-o^c`rnore =rare is sang Push on
q-ab Yar 2.4 nc'-_=:he�Ta^'e from - e-set rings or top s_'at
-"is: p slab.F-ane -oc frrny=:hed
sECurely 3-t3Cr E
-_ •Cracks in btai-tenancepersD-;udges-hat 'as-rep ace:cr
l a cm stmature s u^sound standares.
Envirotech Engineering Operation and Maintenance Manual
Ph. 360-27 -937-t Page of 7 750 E Dalby Road. Union"Washington
Fax: 360-27i-4789 Lot 3 of Parcel 32232 43 00010
October 11" 2010
=repuency = --__e =%NZ,111 Unc-ions t:C-*.k F e Con*c,-s That Should
is.e1. Exist
enera rraaires or Graz ks m 3-au:filiet nas separa:ed or -ipe is reprauted a-_
335m Y,alls:Belem cracked w._t-w 1 Z inar and secure at b3s-wa!!
cnger than 1 root at the iD-t of
any inle:•cu:let pipe or a ,
eviden:e of soil part 6es
an:enn2 catch t3SIn thMU2r
CM—Is.
genera =:c=lent f fa'ure of basin has area.ed a 'asir,rep 3cec cr repai e:
Sfs3;gnmrvni safe-y `unction,ordesk2n m casign standards.
czt em.
csenera vegeatcn ',.ege:atcn?raring a:ross a-: Vo vegetation blocking
Necking mere than 1 Y' c`:ne cpen:ng tc basin
=3sir c enin
genera •.-ge:atcn ',;egeatcn groeoing - Na-.wgetaJor.cr root
nle.^cutiet pipe jams iha: s Growth pre=_en:.
-11ore titan six inches:al'.anc
ess than six inches 3 a't
Any vooen:e of oil,2asc one, .a r_";am:nan cr
?e^era PSI.I Cr. contarri er other oc ,Ian-7 Failu:ass preeer..
;coordinate remcva'cgs-_;
with W:a'eoaw auaiit2
R nse
-vc, over Mc:in Piace Cover is missing or cn'y .any open ca»h basin
=35 carialty in place. eauires maintenance.
;ale!'t3sin cover's
aiased
at•: c c4 rg t.tecran sm ` c:han:sm cannc:be opened `Ae:h3n sin opens mt-
=as- :'hen g cy cne m3 merance person *,cper tools.
•rrth Proper:oois Bohs ima
game nave less than t:_in&c`
ate :aver GficuB to Cne r-an 9ran:e oer=_cn Cover can be removec c•y
_as ?eneve cannat remcvel,c af:r app pry one m3in:enante person
tier ^•crma'liftng pressu•e. nten:
s keep:over from ss aiin2 c'f
a::ess to ra men ante'I
_acce; w cce-?.rgs_"sa-e -adcer,s ursa`e due to ntssing -adaer r-ee.5 oes gn
-ungs,not sec-,ely ata:hed to standards and aiio.n
casir wall,m-sal 2r^ent.nst mairtenance person safe
a:ks crs-arp edges a:oess
_:es ate open rg Craz=-what_-;�tiderthan Craze open ng n•ees
—a.= '4 nc^. :es,o,slanaares.
ras-and:2:"a.hat is -r3:e'' c-:'ash a
:+cek,ng mere than o c' acrs.
7e sJ^face In•-.e:fn :3 acd:'.
:'.30ec Y .-raze missing cr otoken :raze s In p';a:e an:me—:,
M°s.'..7. -1?^tlera,C-:ne'"3:E. :es: -Vindaras.
got-are un&t.re• lhethe-a problen• e'�ists p ease con:3c*a =r:fessiona Engineer
;M1 Mwthly from Noveinberthrouah Aprl.
iA. Once in late summer;preferable Septerniw'i
fS; After any ma-or storm fuse 1-rch in 24 hours as u guidelile:.
Envirotech Engincerino Operation and Maintenance Manual
Ph. ',60-27i 9 374 Pagc 0 of 7 750 E Daltiv Road. Union.Washington
Fax: 60-27i-4789 Lot of Parcel 32232.13 00010
October 11.2010
oil/Water Separators
Date of Inspection:
Inspector.
Maintenance Checidist for
01I/Water Separators
Definition: Separators are designed to remove oil and sediment from water before the
water is discharge to the storm drainage or sewer system. It is an underground
structure with above ground access for maintenance. It may have baffles (vertical
plates)or absorbent pads to retain floating oil. You need to identify which type of oil
water separator you have and if it discharges to stormwater or sanitary sewer.
Frequency Drainage Conditions requiring Results Expected After
Systems Maintenance(cleaning) Maintenance Performed
Feature
Quarterly Any o(w Structure is not separating oil Separator repaired or replaced
and after separator from water or is ejecting oil so that oil is being removed
each oils ill back into stormwater system from stormwater
Quarterly Spill control After each spill Ali oil removed
and after ofw
each oils ill separator
Quarterly Spill control When oil accumulation All oil removea
and after o!w exceeds'/� inch in the first
each oil spill separator chamber or any visible oil in
the second or third chamber.
Quarterly AN olw When oil accumulation All oil removed
and after separator exceeds%inch in the first
each oil spill chamber or any visible oil in
the second or third chamber.
Quarterly API o!w When the sediment level All sediment remove
and after separator reaches 6 inches it should be
each oil spill removed.
Quarterly Coalescing When oil accumulation All oil removed
and after plate exceeds %inch in the first
each oil spill separator chamber or any visible oil in
the second or third chamber
Quarterly Coalescing When the sediment level All sediment removed
and after plate reaches 6 inches it should be
each oils ill I separator removed.
Emvirotech Engineering Operation and Maintenance Manual
Ph. 360-275-9374 Page 7 of 7 7i0 E Dalbv Road.Union. Washington
Fax: 360-27 --47R9 Lot 3 of Parcel 32232-43 000 10