HomeMy WebLinkAboutBLD2013-00426 Calculation Submittal - BLD Engineering / Geo-tech Reports - 6/10/2013 i James W. Ashley-Cole, P. E. CONSULTING ENGINEER CALCULATION SUBMITTAL For Wells Modular Building Foundation Design MH No. 11625 & 11626 5961 E State Rt. 3 Shelton WA Prepared for: Bill Wells 5961 E State Rt. 3 Shelton WA June 10,2013 Project No.2013.62 Extent of Analysis: The detail sheet, general notes, and sealed engineering calculations included with this submittal have been prepared per the structural requirements of the 2009 IBC. This submittal is limited to the design of the foundation. No aspect of the superstructure above the level of the foundation has been addressed by this submittal. Non-structural building systems, including: thermal or moisture protection, furnishings, doors, equipment, mechanical electrical, finishes, siding, paneling veneers, paints and coatings are not the responsibility of the Engineer of Record. Design Criteria: Roof: 25 PSF N_ Floor: 40 PSF Wind: 85 MPH Exp. B. Seismic: Sds=0.8334, R= 6.5. 525 Columbia Street NW,Suite 201 Olympia WA 985 t. 3 !" STRUCTURAL NOTES These structural notes apply to all structural components of the primary structural systems. Any discrepancies found among the drawings, these notes and the site conditions shall be reported to the Engineer of Record, who shall correct such discrepancy in writing. Any work done by the Contractor after discovery of such discrepancy, but prior to correction of such discrepancy, shall be done at the Contractor's risk. • The Contractor shall field locate and identify all site utilities prior to performing any site excavation or demolition. The Contractor shall be responsible for all safety precautions and methods, techniques, sequences or procedures required to perform the Contractor's work. The Consulting Engineer has no overall supervisory authority or actual and/or direct responsibility for the specific working conditions at the site and/or for any hazards resulting from the actions of any trade contractor. The Consulting Engineer has no duty to inspect, supervise, note, correct, or report any health or safety deficiencies to the Owner, Contractor,or other entities or persons at the project site. • All structural systems which are to 'be composed of components to be field erected shall be supervised by the supplier during manufacturing, delivery, handling, storage and erection in accordance with the written instructions prepared by the supplier. • It is the Contractor's responsibility to verify all field measurements and site conditions prior to fabrication of any structural elements. No allowance will be made for any items incorrectly fabricated or installed due to failure to perform such verification prior to commencing work. Contractor initiated changes shall be submitted to the Consulting Engineer in writing for approval prior to fabrication, construction or field modification. Changes shown on shop drawings only will not satisfy this requirement. • Non-structural building systems, including: paints and coatings are not the responsibility of the Consulting Engineer. CONSTRUCTION STABILITY The design, adequacy and safety of erection bracing, shoring and all temporary supports is the sole responsibility of the Contractor, and has not been considered by the Engineer of Record. The Contractor shall provide the bracing necessary to provide stability to the structure prior to the completed application of the lateral system.During construction the Contractor shall keep loads within the design roof and floor loads limits shown on the drawings. CODES AND DESIGN All methods, materials and workmanship shall conform to the 2009 edition of the International Building Code (IBC) as amended and adopted by the local Building Department. All reference to other codes and standards, such as ACI,ASTM,AISC, etc. shall be for the latest or most current edition available. DESIGN LIVE LOADS Roof: 25 PSF Floor: 40 PSF Wind: 85 MPH,Exposure B Seismic: Sds(Seismic Design Category D)=0.8334,R=6.5 SOIL BEARING The foundation has been designed for 1500 PSF bearing per the Bradley-Nobel Engineering Geologist Report (David Strong, L.E.G., 357-7883). Perform all special gradings, excavations and fills per the requirements of this report. GENERAL FRAMING NOTES • Nails: Nails designated for roof and floor diaphragms, and in the shear wall schedule, shall have the following minimum diameters; 16d common nail : Shank diameter=0.162 inches minimum,Length=3.5 inches. 16d galvanized box nail : Shank diameter=0.135 inches minimum Length=3.5 inches. 1 Od common nail : Shank diameter=0.148 inches minimum,Length=3.0 inches. 1 Od galvanized box nail : Shank diameter=0.128 inches minimum,Length=3.0 inches. 8d common nail : Shank diameter=0.131 inches minimum,Length=2.5 inches. 8d galvanized box nail : Shank diameter=0.113 inches minimum,Length=2.5 inches. • All fasteners in preservative treated material shall be either hot dipped galvanized,tumbled or stainless steel of American or Canadian manufactured only. • Minimum nail penetration in backing framing= 1 1/2 inches. • Dimensions; Contractor shall field verify and coordinate all dimensions shown with the existing conditions. STRUCTURAL CONCRETE Special Inspection not Required GENERAL All concrete shall meet the requirements of ACI-301, "Specifications For Structural Concrete For Buildings." Proportioning of ingredients for each concrete mix shall be by Method 2 or the alternate procedure given in ACI-301, Chapter Seven. Place concrete per ACI-304 and conform to ACI-306R for cold weather placement and ACI-305R for hot weather placement. All concrete thicker or deeper than 4 inches shall be vibrated during-placement. Use internal mechanical vibrators. Do not over-vibrate. Inserts,bolts,boxes,pipes, conduits, and other accessories shall be securely installed and inspected prior to placing concrete. Remove water, debris, wood, and loose concrete from space where concrete is to be placed. Protect all concrete from premature drying, excessive hot or cold temperature. Curing should start immediately after the concrete has been finished and be continued for at least seven(7) days. PROPERTIES Footings, foundation walls and slab-on-grade: • f c :3000 PSI minimum at 28 days,5 %z sack minimum mix Slump : 5 inches maximum 4 inches maximum at interior slab-on-grade water/cement : 0.45 maximum by weight air entrainment : 5%+/- 1% 3%+/- 1%at interior slab-on-grade 3/ inch maximum size aggregate MATERIALS Cement: ASTM C150,normal—Type I or I-H Coarse and fine aggregate: ASTM C33 Water shall be clean and not detrimental to concrete. ADMIXTURES Water reducing admixture: ASTM C494, Type A. Admixtures shall be used in exact accordance with manufacturer's instructions. Air entrainment:ASTM C260 and ASTM C494,except those containing chlorides may not be used. No other admixture permitted unless approved by the Consulting Engineer. Do not use calcium chloride, or fly ash and related materials. PLACEMENT A. General: Comply with requirements of ACI 304 and as follows: 1. Schedule continuous placement and consolidation to prevent formation of cold joints. 2. Deposit concrete as close as possible to its final location,to avoid segregation. 3. Thoroughly consolidate without displacing reinforcing using internal vibrators. 4. Strike off and level concrete slab surfaces,using bull floats before bleed water can collect on surface. Do not work concrete further until finishing operations are commenced. REINFORCING STEEL Reinforcing steel shall conform to ASTM A615 Grade 60 new billet stock, deformed steel free of rust, scale or other bond-reducing coatings. Tie bars securely with #16 double annealed wire. Fabricate in accordance with ACI 315. Provide support as indicated or recommended by ACI STD 315. Reinforcing shall be placed in accordance with"CRSI Recommended Practice For Placing Reinforcing Bars." CONCRETE. COVER The following concrete cover shall be provided for reinforcement: • Concrete cast against and permanently exposed to earth: 3 inches for footings 2 inches for interior slab-on-grade • Concrete exposed to earth or weather: 1%Z inches for#5 bars and smaller and WWF CONCRETE DOWELING ADHESIVE(CDA) INTO CONCRETE AND SOLID MASONRY Adhesive anchors shall consist of a threaded anchor rod, nut, and washer and an injectable adhesive material. Manufacturer's instructions shall be followed for all installation steps including: material handling and storing, substrate drilling and cleaning,and adhesive installation. The injectable adhesive material shall be HIT HY 150, as manufactured by Hilti, Inc or SET-PACK EZ, as manufactured by Simpson 1. Only injection tools and static mixing nozzles recommended by the manufacturer shall be used. 2. Anchor rods shall be ASTM A36 furnished with two chamfered end so that either end will accept a nut and washer. WOOD FRAMING AND LUMBER GRADING Allowable stress required shall be in accordance with standard grading rules of West Coast Lumber No. 16. Moisture content shall be maximum 19%. All studs, plates and blocking at shear walls, load bearing and exterior studs and plates shall be of grade Douglas-fir#2 or better,unless noted otherwise. Structural Panel Sheathing including Plywood and Oriented Strand Board (OSB) sheathing shall be APA grade trademark sheathing with nominal thickness as indicated on the contract drawings. All glue-lam beams shall be 24F-V4 UNO as 24F-V8 at cantilever conditions. Glue laminated beams specified to be treated shall be treated to refusal with ACQ to a"SPLASH"level exposure. Wood framing details, not shown otherwise, shall be constructed to the minimum standards of the 2009 IBC and shall conform to the Fastening Schedule 2304.9.1. Unless noted otherwise, all nailing callouts refer to common type nails. Notations on drawings relating to framing clips, joist hangers and other connectors refer to catalog numbers manufactured by the Simpson Strong Tie Company, San Leandro, CA, Catalog C-2012. All hangers in contact with preservative treated lumber shall be "Z-MAX" galvanized with approved fasteners as noted. PRESERVATIVE-TREATED WOOD • All fasteners in preservative treated material shall be either hot dipped galvanized, tumbled or stainless steel including anchor bolts and washers. Preservative treatment: All lumber required to be preservative treated shall conform to the requirements of the applicable AWPA Standards, per the 2009 IBC Section 2302.1.8. Preservatives shall conform to AWPA P1/P13, P2, P5, P8, and P9. Preservative-treated wood shall bear the quality mark of an inspection agency per the 2009 IBC Section 2302.1.8.1. Each piece of treated lumber shall bear an approved quality mark or that of an approved inspection agency which maintains continuing supervision, testing and inspection over the quality of the product, as described in the IBC standards, and shall be identified as required by these standards. Where FDN lumber is cut or drilled after treatment, the cut surface shall be field treated with approved preservatives by repeated brushing,dipping or soaking until the wood absorbs no more preservative. Fasteners: Fasteners for preservative-treated wood shall be of hot-dipped zinc-coated galvanized steel, stainless steel, silicone bronze or copper. Fastenings for wood foundations shall be as required in AF & PA Technical Report No. 7. SECTIONS AND DETAILS Sections and details showing reinforcing, bolts, framing members, and connections are intended to illustrate specific detail. No attempt has been made to show all elements passing through a specific section or detail. Exposed bolted beam connections may have to be furred by the Contractor to conceal connector. Construction details not specifically shown on the drawings shall follow similar details or sections of this project as approved by the Engineer. PROJECT NUMBER:2©/� James W. Ashley Cole, P.E. CONSULTING ENGINEER DATE: SHEET OF i Z4 !Z /2 ,l Nl 1p I �6)' . r i L 13� r b g� L , o� - - 1 i - i Sffi`�s � , H � • ��a L��1fL � sue" PROJECT NUMBER:2D l - f� James W. Ashley-Cole, P.E. CONSULTING ENGINEER DATE: -- SHEET OF ---------�-- --.: - --- ---- �o_ter - I �� ENGINEER APPROVAL SAC INDUSTRIES 1.0 TIE DOWNS ��'� 1 NEF `psi `f •:''�'ti���.• a// ENGINEERED TIE DOWN SYSTEM GENEFZA.I, NOTES HEM DESIGN LOADS: j * WIND ---------------- 15psf (70 MPH EXPOSURE"C") * WIND ---------------- 25psf (85 MPH EXPOSURE"C") ` * WIND ---------------- 35psf (100 MPH EXPOSURE"C") * SEISMIC ZONE ---------- 4 `''`• �'" * SOIL BEARING ---------- 1000 psf NOTE: MAXIMUM SOIL PRESSURE v <' IS 1000 psf WITHOUT A SOIL REPORT, * EARTH AUGERS --------- 4750# MIN. TOTAL LOAD CAPACITY 3150# WORKING LOAD CAPACITY * STABIL-X DRIVE ANCHORS-- 4750# MIN. TOTAL LOAD CAPACITY �,;':'.. -"-` =:•�i: 3150# WORKING LOAD CAPACITY ��;_.::; i• ' 1` * CONCRETE SLAB ANCHORS-- 4750# MIN. TOTAL LOAD. CAPACITY ` 3150# WORKING LOAD CAPACITY * TIE DOWN STRAPS ----- 4750# MIN. TOTAL LOAD CAPACITY r �- 3150# WORKING LOAD CAPACITY r TIE DOWN STRAPS MEETS FEDERAL SPECIFICATION QQ-S-781 H FOR TYPE 1, CLASS B, GRADE 1 STRAPPING AND BE AT LEAST 1 1/4" x .035 ZINC PLATED. ID 1. THE CHARTS SHOW THE REQUIRED NUMBER OF TIE DOWNS ON THE SIDES AND r ENDS OF THE MANUFACTURED HOME. 2. COMBINATIONS OF THE DIFFERENT TYPES OF TIE DOWNS CAN BE USED. 3. FOR ALL TIE DOWN INSTALLATIONS, THE MANUFACTURED HOME CHASSIS MEMBERSp r•. ARE SHOWN AS"I" BEAMS. (FOR ILLUSTRATION PURPOSE ONLY) CHASSIS BEAMS CAN ALSO BE "C" SHAPED OR "RFC" SHAPED. 4. SIDE TIE DOWNS ARE REQUIRED ALONG THE OUTSIDE CHASSIS BEAMS. END TIE DOWNS ARE REQUIRED AT EACH END OF EACH TRANSPORTABLE SECTION OF THE �jk � MANUFACTURED HOME. / END TIE DOWNS CAN BE LOCATED WITHIN 18" OF EITHER SIDE OF CHASSIS BEAM UT ,��� r4z;;r t•7 AXIS, AND BOLT-ON TOP CAN BE ATTACHED WITHIN 18" TO 60" FROM END OF CHASSIS BEAM. �1 6, THE SIZES, TYPES, LENGTHS, ECT. OF MATERIALS SHOWN HEREON ARE MINIMUM. LARGER, LONGER, HEAVIER MATERIALS SUPPLIED BY SAC INDUSTRIES, INC. MAY \ •3yU! ' BE USED AT THE SAME SPACING AND LOCATIONS SHOWN. 7. ALL PARTS ARE COATED WITH RUST RESISTANT INDUSTRIAL SHOP PRIMER. 8. THIS TIE DOWN SYSTEM MEETS THE REQUIREMENTS OF SECTION 1336.3 SUB- SECTION (o). STATE APPROVAL sac INDUSTRIES, INC. 1324-A EAST BEAMER ST. WOODLAND, CA. 9 7 c`v%`' G "� PH: (800) 7 ` ' ENGINEERED TIEDDWN SYSTEM A f 1= APPROVED A' S0JECT TO CORRECTIONS NOTED .' y o� Approvct flees r,ct authorize or approve any omission or n!!d Oeviatic� from reGe:rements cf applicable any laws and wzi D State of Ca!ifornia ' �L �partmEot cf Hou -a :G C mmcrity Development SIC+ ODES DSTANDARDSBy (Signature ate /610.q CA svaao f Ts _ ,� `��� : N This Plan Approval Expires �'/ Z(1-y�t� PACIFIC CONSULTING ENGINEERS ":�':• 2150 BELL AVE. SUITE 145 � . SACRAMENTO, CA. 95838 D}� PH: (916) 564-6028 I,�t� SAC IND. EARTH AUGER TIE DOWN ANCHORS p�0 A rI � #6005 = �' #6006 #7000 #7001 #7002 #4002 p�p CHASSIS� I i #4002 PIER BOLT-ON TOP / If7002 7 STEEL _ ' /J7000 7' STEEL ' STRAP STRAP W/BUCKLE W/HOLE moo. #6005 SPLIT BOLT & NUT 110 60. cq NOTE +2 . #6006 STABILIZER PLATE NOTE 3 #6001 #6000 //6000 SERIES EARTH AUGER (TYPICAL) NOTE 4 0 ID VERTICAL OR ANGULAR INSTALLATION IS OPTIONAL AUGER TIE-DOWN INSTALLATION INSTRUCTIONS 1. CONTRACTORS WARNING: CHECK FIRST FOR UNDERGROUND UTILITIES. 2. INSTALL GROUND ANCHOR INTO GROUND LEAVING 12"-14" OF SHAFT EXPOSED. 3. PLACE STABILIZER PLATE NEXT TO SHAFT BETWEEN THE ANCHOR AND CHASSIS BEAM, AND DRIVE INTO GROUND. 4. FINISH TURNING ANCHOR INTO THE GROUND APPLYING CONSTANT DOWNWARD PRESSURE TO MINIMIZE SOIL DISTURBANCE, UNTIL ANCHOR HEAD IS FLUSH WITH STABILIZER PLATE. 5. ATTACH STRAPS TO CHASSIS BEAM IN MANNER SHOWN. 6. IF ANGLE OF SIDE STRAP IS GREATER THAN 60', STRAP CONNECTION CAN BE MADE FROM ANCHOR TO OPPOSITE CHASSIS BEAM. 7. INSERT STRAP THROUGH SPLIT BOLT. CUT OFF EXCESS STRAP AND TIGHTEN BOLT UNTIL STRAP IS S END TIE DOWN END TIE DOWN END TIE DOWN SEE CHART SEE CHART SEE CHART L If � r i r r Q U U-cl U 2 N H 30 W V W W W W W V7 v > v > l J l J l 1 l 1 l J l 1 I , � i i `j V� V V v vi SINGLE WIDE DOUBLE WIDE TRIPLE WIDE SAC IND. STABIL-X DRIVE •TIE DOWN ANCHORS 4- m #6013 #6005 #7000 #7001 #7002 #4002 CHASSIS— #7000 or #7002 � #4002 PIER 7' STEEL STRAP BOLT—ON TOP #6005 SPLIT �7002 #7000 7' STEEL BOLT & NUT 7 STEEL 7. STRAP W/BUCKLE #6013 STABILE' STRAP \ W/HOLE 0. DRIVE ANCHOR . BOLOS SPLIT sOq BOLT & NUT GROUND LINE ii OJT 6� 4HfM ca��t 0-10. 0'-I O DETACH" 0-10 SEE DETAIL"A' VERTICAL OR ANGULAR INSTALLATION IS OPTIONAL r` STABIL-X DRIVE TIE DOWN SEE DETAIL"A" INSTALLATfON' INSTRUCTIONS 1. CONTRACTORS WARNING: CHECf -'FIRST FOR UNDERGROUND UTILITIES. 2. DRIVE STABILIZER PLATE INTQ`GROUND. 3. DRIVE CROSS RODS THROUGH HEAD TUBES INTO SOIL: AS SHOWN. ++'+ 4, ATTACH STRAPS TO CHASSIS BEAM IN MANNER SHOWN`., i 5. IF ANGLE OF SIDE STRAP IS GREATER THEN 60', STRAP 'CONNECTION CAN BE MADE FROM ANCHOR/0 OPPOSITE CHASSIS BEAM. /#6002 6. INSERT STRAP THRO/OGH SPLIT BOLT. CUT OFF EXCESS STRAP AND TIGHTEN BOLT UNTIL STRAP AS SNUG. SEE NOTE #7 7. #6002 ANCHOR Cr4N BE USED WHERE HARD OR ROCKY SOIL OCCURS. IF THE AND NOTE #8 GROUND SURFA¢E IS OTHER THAN ROCKY SOIL OR MINIMUM 2" `ASPHALT, USE STABIL—X ANCHOR OR ENCASE ANCHOR WITH 12"xl2"xl2" CUBE OF CONCRETE. 8. WHEN #6007V/ANCHOR IS USED FOR ANY REQUIRED ANCHOR -- (2).,ANCHORS MUST BE USED AT THAT LOCATION. WI 70 MPH — 85 MPH — 100 MPH EXP."C" — SEISMIC ZONE 4 REQUIRED NUMBER OF COMBINED ANCHORS FOR EACH 2H AND END OF MANUFACTURED HOME L GTH WIND SPEED SEISMIC No. OF SIDE No. OF END TOTAL No. OF WIDTH TIE DOWNS TIE DOWNS ITIE DOWNS SINGLE 70 MPH EXP. C =15PSF ZONE 4 4 2 12 WIDE 0'-78' 85 MPH EXP. C =25PSF ZONE 4 8 1 2 20 �-- TO 16' 100 MPH EXP. C =3 5 P S F I ZONE 4 1 12 1 2 28 rUB 70 MPH EXP. 'C =15PSF ZONE 4 4 4 16 ID 0'-78' 85 MPH EXP. C =25PSF ZONE 4 8 4 24 8' 100 MPH EXP.' C '=35PSF ZONE 4 12 4 37ti, TRIPLE 70 MPH EXP. C =15PSF ZONE 4 4 1 6 1 20 WIDE 0'-78' 85 MPH EXP. C' =25PSF ZONE 4 8 1 6 1 28 TO 42' 100 MPH EXP. C"=35PSF ZONE 4 12 1 6 1 36 SAC IND. CONCRETE *TIE DOWN ANCHORS a e #4002 PIER CHASSIS BOLT—ON TOP a #7 v ' 7 STEEL STRAP " � � #7000 7' STEEL #6005 SPLIT STRAP W/BUCKLE 6005 #7000 #7001 #7002 BOLT & NUT #6004 d,o {®J ® 6U "QA. OR A � ' \OR 0 #6003 #4002 #6003 #6004 ° CONCRETE TIE—DOWN a INSTALLATION INSTRUCTIONS NEW CONCRETE — #6004 1. PLACE CONCRETE ANCHOR INTO WET CONCRETE, AND ALLOW TO PROPERLY CURE. 2. ALTERNATE CONNECTION REQUIRES #5 REBAR PROPERLY EMBEDDED IN CONCRETE. - _------3+ EXISTING CONCRETE — #6003 1. CONCRETE MUST BE A MINIMUM 3 1/2" THICK AND IN GOOD CONDITION. E OF EACH ANCHOR IS 28 SQUARE FEET.SLAB �2. MINIMUM SLA Q ALTERNATE -��3. DRILL PROPER SIZE HOLE IN SLAB, A MINIMUM OF 12" FROM ANY SIDE. CONNECTION -� 4. EXPANSION BOLT IS 5/8" x 3 1/2" WITH MINIMUM 2 3/4" EMBEDMENT AND 6,180 POUND PULL OUT, 7,160 POUND SHEAR. CHASSIS CONNECTION 1. ATTACH STRAPS TO CHASSIS BEAM IN MANNER SHOWN. 2. IF ANGLE OF SIDE STRAP IS GREATER THAN 60', STRAP CONNECTION CAN BE MADE FROM ANCHOR TO OPPOSITE CHASSIS BEAM. 3. INSERT STRAP THROUGH SPLIT BOLT. CUT OFF EXCESS STRAP AND TIGHTEN BOLT UNTIL STRAP IS SNUG. NOTE:SIDE TIE DOWNS ARE REQUIRED ALONG THE OUTSIDE CHASSIS BEAMS. _—, -END TIE DOWNS ARE REQUIRED AT EACH END OF EACH TRANSPORTABLE SECTION OF THE MANUFACTURED HOME. NOTE: A COMBINATION OF DIFFERENT TYPES OF TIE DOWNS CAN BE USED. DRILL 9/16" HOLE AT MID HEIGHT/ OF BEAM AND INSTALL 1/2" A307 BOLT ! (TYPICAL) /- ,, SIDE VIEW END VIEW END TIE DOWN DE VIEW SIDE VIEW EAM CHASSIS "RFC" BEAM CHASSIS NOTE:END TIE DOWNS CAN BE LOCATED WITHIN 18" OF EITHER SEE GENERAL NOTE #3 SEE GENERAL NOTE #3 SIDE OF CHASSIS BEAM AXIS. CONTRACTORS CERTIFICATION I CERTIFY THAT I HAVE INSTALLED THE SAC IND., INC. ANCHORING SYSTEM AS PER THE INSTALLATION INSTRUCTIONS. I HAVE MADE NO MODIFICATIONS TO THE ANCHORING SYSTEM OR TO THE BUILDING STRUCTURE. COMPANY NAME: CONTRACTORS LIC.# PROJECT NUMBER: -5 4;'Y/ James W. Ashley-Cole, P.E. Gem// CONSULTING ENGINEER DATE: SHEET OF Z Z K 44� /Z i1 /" - h o I I I S I�j ��iJLfv r 4,sb Z/� Z- 6 o �M, -z-C7 -4. ' z 1 rz w � r � p � PROJECT NUMBER: c/ 5. James W. Ashley Cole, P.E. ,! CONSULTING ENGINEER DATE: SHEET'/ OF ila2 44� td PROJECT NUMBER: James W. Ashley Cole, P.E. D141� � CONSULTING ENGINEER ATE: Co SHEET OF 3 9 � 7�1 C-fOeIJ - r S2 t• 2 0 RCVD ,� 06-10-13P02 :5 " '3 'A STATE OF OREGON BUILDING CODES DIVISION PLUMBING PLAN REVIEW `\ IN ` ����� ► FEB 1 9 2003 �`.tom `\ I �0 °Ixoltal�E�`�tnm�nNn'gtimBlr�P`°,"1�n"" _• ` '10 / `\'4 IS to crynnIM1Y nary bccl�] IY � R-AN RENEWED BY:_ 'Lt--t4 1 � WATER PIPING: Fl%IURE UNITS................100 1 -DEVELOPED LENOM..........70' ELEVATION DIFFERENCE........0' uv Y 1 -STREET PRESSURE............48 1°BO t uv -METER SIZE..................1 1/2' JIV n v I Y'vnI 1 `\ uV -BUILDINO SUPPLY SIZE........2' M JIV tY•`i i`\\ uv GENERAL NOTE5: POTABLE WATER MATERIAL-COPPER OR AOUAPEx 1 `1\ 'x• Y v,R -HOT WATER LINES YSULATED VAIN 1'. I F 9RF 1 i I ��\ Jly r v R ANGLE STOP MA AN SUPPLY ON ACCESSIBLE JIV nXIURES- LLOBE INSULATED. HAMMER ARRESTOR$INSTALLED TO UPC 600.10. CONTINUATION OF WA TEN MAIN DONE ON SITE BY OTHER& -z " " AS PER UPC SDB.3,A IM"IN A PLUG WILL BE &3 I Nrtl I I I PROVIDED FOR A THERMAL EXPANSION DEVICE TO 2. "•/ JIV BE NSTALLED ON SITE BY OTHERS IF NEEDED. 171NE1.IEF LINE EXTENDED TO DAYUGHT ON SITE BY r F WIo•EtI i\'E R,o�al r �\ \ -WATER HEATERS SHALL BE AN04ORED OR STRAPPED 2 2 I I I i \\ �. PER CODE UPC 510.5 PLUMBING FDCTURE 5Ch1EDULE r DRAINAGE AND VENT PIPING: �1 ,\ 1 � uR`l Q LIR FlxTE DESDESCRIPTIONII SO I N' ° 5 I 3 WATER CLOSETS-Onh GERBER 25-SM -SIZE OF BUILDING DRAIN......4' / I 7. s 3 FLUSH VALVES SLOAN tt1-1-xL -AOCREGME AREA.............13.51 r uv r C.O. r 3 URINALS OERBER 27-750 t 7 RUSH VALVE SLOAN IN-1-XL GENERAL NOTES: uV 4 LAVATORY SIN(-Er9P In CRANE 1-315V -O.W.V.MATERIAL-P.V.C. uV 2 MOP SIN(-24.24 MT OS1924%24 ' -P-TRAPS ON ACCESSIBLE FlYlURE9 7 SHOVER STALL W/tV FIBERFAID 3BNB INSULATED. =' -CONTINUATIONHE LINE GONE 1 FAUCET-H-LWv A 23115,404 ON 911E BYBY OTHERS. 2 FAUCET-rtwP A/$8344.11Z004 0 2 WATER HEATER 206/3 Phi B/W M-9-5024RW m 7 SHOWER VALVE P.B. A/!1495,Jd) g 1 MOOR DRAINS 2-4 SN%Ux CHIEF 841-3PNR PLUMBING SCHEMATICS DATA z TRAP PRIMER ,DR MWAII Z-� PPP SWA Job: 11625-26 12rarn 64 pain COPYRIGHT AL THEERLUSIV PROIES,INC. MOBII.r= RESTROOM BUILDING for: PILE: Pllnn N:b. T F BLAZER MATENAL IB THE.INC.AND FROPERIY I»ue Drta I-16A3 p OF BERE INDUSTRIES.INC.HO9ULL no ' N 24%44 impregllo Healy 39 NOT BE OTHERS EXCEPT 10E0,USED. Rf ED BYTE n, DRAWN BY: AIB ut TO OTHERS E%DEFT A9 AUT1gRIZED BY IIIE "''� 'y'""" DATE: I-14-03 DATE REVISION BY WRITTEN PERMISSION OF BLAZER INDUSTRIES. F.O.WX 4B9 R AUNSVILLE,m 97325-0489 OR.BLUE G.E.ModUlaF SPace Portland,OI'CgOn JOB NO: I J15 C� �180 cf.EXHAUST FAN W/BACKDRAFT& 2 X 4 FLUORESCENT DAMPER,TIP.OF 3 TROFFER o . e . e . 0 0• o 0 0 0 0 EL 2 x 2 SUPPLY AIR FIRE SPRINKLER 2 x 4 SUSPENDED GRILLE HEAD T-GRID CEILING REFLECTED CEILING PLAN plan ® B•YWA SUPPLY Apt O • O • e • O KV%AI >_I 3 TON WALL HUNG BMO UMT•/IS t• • , I.DUCT MATERIAL IS 26 GA.GALV.AND FLEX DUCT.DUCTWORK SHALL BE CDMWRT"O,I"1L ROOM R� SUPPORTED PER UMC CHAPTER 6. tERTILATOR-S*XLE PHASE WT 12 10 2,MATERIAL IN DUCTS SHALL HAVE A FLAME SPREAD INDEX OF LESS THAN 25. 12 c 10 c SMOKE DEVELOPMENT OF 50 PER UMC CHAPTER 6. d 3. SEAL TRANSVERSE JOINTS IN ACCORDANCE WITH UMC CHAPTER 6. 4.USE ISOLATION SLEEVES AT LINE CONNECTIONS TO PLENUMS PER UMC CHAPTER 6. 5. 6"DIFFUSERS W/MANUAL DAMPERS, TYPICAL. FIRE SPRINKLER Pe 8.MINIMUM 200 CFM OUTSIDE AIR REWIRED PER UBC CHAPTER 12. HEAD F e TPA, $ QTY. SIZE DESCRIPTION F�9 e HN.A.C. I 3 TON IS I,W WALL HUNG UNIT W/COMM.ROOM VENTILATOR .8 THERMOSTAT 1 BARD /8403-043 STANDARD MECHANICAL PLAN I-02.o3 PRPOMINA Y REVIEW A,B COPYRIGHT 2003,BLAZER NDUSTRIES,W. � MOBILE RESTROOM BUILDING for: TITLE: K.B C. MedI.P. 2-10-03 5PRINKLER HEAD5 ADDED AIB TMS AZER 11 AL IS THE TRIES,INC.AIVEND PROPERTY .. M1^e D Date: 2-AJI3 M 1 OOT BE ER IRODUCED, SEE AND DISCLOSE ., 24 x 44 Impregflo Healy DRAWN BY: -0 - NOT BE RS XCIX:EO,USED,ORLXSOLO®ED DATE: I-4-03 TO OTHERS EXCEPT AB AUTHORIZED BY THE OR.BLUE G.E.Modular 5 ace Portland,Ore On a DATE REV1510 BY WRITTEN PERMISSION OF BLAZER INDUSTRIES. P.O.o0x hB7■nUNtiVRLL,aN 9/32S-OI�B9 P 9 JOB NO: I 6 5- W. Sprinkler Main SEE CALCULATIONS FOR ADDITIONAL Y PIPE AND FITTINGS ADDED. ' NOTES: 0 1. Harvey and Price to "rough—in" piping O Blazer plant. 2. This is a addition to an existing dry sprinkler system. 3. All mains are to be Allied "dyna—flow; with grooved ends. 4. Branch—lines ore to be Allied dyna—thread;" with threaded fittings. Branch outlets are mechanical tees. 5. All pendents are to be dry" semi—recessed. 6. All hangers, pipe, sway bracing, valves, sprinklers, spacing, LU and installation to conform with NFPA 13 standards. 7. Hydraulic calculations were based off of 80 psi static, 66 residual, with 750 GPM flowing. 8. Total sprinklered area = 1056 sq. ft. A CROSS SECTION: SCALE: 1/8" = 1' 9. Provide extra sway bracing for shipping. FP.1 N N =1 —NFPA 13 —LIGHT M DRY ""^;F 1056 w,Pe n..1a "u.iv a ..".s IDD Ili I44 - r . 49.6-223.6-•,BASE OF RISER -.. ... ❑- 3 12 ,�� Apr -- B1 4 _ �/� -- 'CENTRAL' �..__._.._.. ... .._ —. GB QR 1/2" RECESSED/FLUSH 1 0l 1 1 l DRY PENDENT CD C 144 0 2 1 9-4h 1 .0 - r 1 - 0 4 14 8-3144.0 1 C o dh PROVIDE DRUM DRIPS - A 2 hr 12 7h iv I 161- h Al _1j"I 1. ._ 2 ��_ _1 1h 1h 1 1 �'44 0 2 -6 0 6-2 2-10 . 1 4. 144.0 ...._1- .._... .._ .._1 4.0 .. 1- h. . .l- ... aunty A TYP. 'DRUM DRIP' ASSMB. DRY SYSTEM AUXILIARY DRAIN klr ctrn.A M1w� SprinWer Plan FIRE SPRINKLER PLAN NORTH 1,/r.r-V BLAZER TUNNELL_—EFE j PANEL SCHEDULE u v e r (MOTOR.COMPRESSOR.HEATER STZESI NOTE: ALL CONDUCTORS COPPER. 200 AMP PANEL THREE PHASE OPERATION VOLTAGE 1 197 MIN. 253 MAX. ['7 INDOOR BLO 15.7 RLA 96 LRA INDOOR BLOWER FAN 2.2 FLA 1 3 H.P. TART MART Iw 2 l009 NN 2 1. WA1[111[ART 2WTDOOR BLOWER FAN 1.5 FLA 1 5 H.P. 4 HEAT STRIP 15 KVA 651U1 11x0o 23w A M WAC MIMMVM LiRWIT AMPS AMPS wn[R 20 12 200 - 200 / / / 10 MAXIMUM OVERCURRENT PROTECTION Y0 AMPS _Ts m 12 HS. 14 OVERCURRENT PROTECTION OR SCR Q Tit REAKERY NSE IB 8 19 20 21 22 23 24 25 26 27 _ 230 8 \o/ x \A \off \o/ U ujuj 39 32 33 34 35 36 3T 38 39 40 2aaa 41 12 oP O O ® I n (r ® 0 STATE OF UREGON I I BUILDING CODES DIVISION ELECTRICAL PLAN REVIEW ELECTRICAL PLAN REVIEW LOAD CALCULATIONS kW /' a FEB 1 9 2003 VOLTAGE: 120 2oB PHASE: 3�_ #,, r 2 Am,"10 dAna.a.aPm.m a1W2gn a 4[W2m kan W2IgWw,eX[d m dm a CONNECTED LOAD CALL,LOAD __._ gT21W.R AmM.ap RK1/2}a-a�m��b{2d a6wX[. LIGHTINGL_l_i_i_l_i_1_i_1_1_' ' 1_l_ RAB PfVIEYWO By EXTERIOR 2D V.A.vA % 1zs Y. _ 25 V.A.v.A. )IT R_o-e INTETNDR 71l V,A. 125 X 9J0 V.A. EXIT V,A. X 125 X - V.A. 7 EMERGENCY V,A. X 125 Y. V.A. TIME CLOCK V.A. X 125 X - V.A. O O O O EXHAUST FANS • • 220 V.A.vN % 125 X 900 V.A. RECEPTACLES THRU 10.000 1800 V.A. X 100 X 1800 V.A. o11 OVER 10000 V.A, X 50% V.A. RAV-T'T'T'T-T-T-T-T-T-T-T' -T-T- -T-T-T-T-T-T' 'T-T-T-T-T-T' TRAY, /13 I 1 I I I I I T I I I MOTORS,COMPR. TOTAL 528 V.A. % 100% 528 V.A. S LARGEST (528) VA. x 25X 132 V.A HEATING 15000 V.A. X 100% 150DO V.A. WATER HEATER 48000 V.A. X 100% 48000 V,A. FIRE SPRINKLER SON CIRCUIT 1200 V.A. X 125 X 15M V.A. HEAD D.C. V.A, x 100 X - VAVA A �7 V.A. % %vA X % ELECTRICAL H1 SYMBOLSy.A. % X SYMBOL DESCRIPTION TOETOP REMARKS TOTAL KVA 6&0 TOTAL KVA" ELECTRICAL PLAN O ,%JfR SINGLE POLE SWITCH 48" 1440 V.A. TCONNECTED AMA" IB8.8 LO'DLATID AMPS I/4"=1' D• '4- THREE WAY SWITCH 48" 1440 V.A. ' DUPLEX RECEPT. 20" 100 V.A.EACH ONE—LINE—DIAGRAM NOTES: op,GROUND FAULT RECEPT. NOTED 100 V.A.EACH CITY. SIZE I DESCRIPTION 200 AMP FEEDER PANEL WEATHER PROOF RECEPT. 20" 180 V.A.EACH MAIN BREAKER 1. WHEN STRANDED WIRE IS USED, ALL TERMINATIONS T THERMOSTAT 48" TO TOP OF J-BOX H.V.A.C. 1 3 TON 15 kW WALL HUNG BARD UNIT, 120/208V/SINGLE PHASE 120/208/30 ARE MADE BY A PRESSURE TERMINAL,BY TAIUNG W/ SIGN CIRCUIT 20' 1200 V.A.EACH COMMERCIAL ROOM VENTILATOR OFF WITH SOLID CONDUCTORS OF OTHER APPROVED 2O0 AMP MEANS OF TERMINATION. 1 HVAC DISCONNECT THERMOSTAT I BARD/8403-043 STANDARD a PORCH LIGHT 84" 10 V.A.EACH 2. ALL CONDUCTORS ARE COPPER; TYPE THHN. PHOTOCELL 84" ELECTRICAL PANEL 1 200 AMP THREE PHASE- STUB THRU- ROMEX tATER p Z"P.V.C. 3.RATING OF STANDARD PANEL IS 22,D00 A.I.C. EXHAUST FAN 180 cim CEIUNG 110 V.A.EACH LIGHTING 8 2 A 4 TROFFER 3- 7-8 TUBES W/ELECTRONIC BALLAST 2-1 4 CV STUB THRU BY BLAZER ORD.ROD 2_3/D Cu/HHN 4.WRING METHOD N.M.B. (W) 50 GAL WATER HEATER FLOOR 25000 V.A.EACH 2 10 WATT VANDAL RES157ANT LEXAN PORCH LIGHT ON PHOTOCELL 1-1/0 C�THNN " 1 !e 5. SERVICE ENTRANCE SLEEVE TO BE SCHEDULE 80 24•a y TRpTER COLINO T/BE3 TUBE MC BALLAST EXHAUST FAN 4 ISO 01 P.V.C.IF REWIRED 93 V.A.EACH FlBALLA XTURE WATER HEATER Z 50 GAL. ELECTRIC 1� POWER PANEL 72' 1-02.03 rREUMINATO'REVIEW AJB COPYRIGHT 2003.MAZER INDUSTRIES,INC. RESTROOM BUILDING for: TITLE` EkccncAl mm z-I o-03 nNAL Ev1Ew aD Tres AMTER Q Is THE T9 eLu81VE vROPERTr MOBILE »ue Date: 2-I O-03 Eml INCNO SHALL ., IM^ .,2-;PN. 24x44Impregllo Healy DRAWN By,TO NOT BE REPRODUCED -03 ,USED,OR g8CL09ED TE VI ION Y VWTIOT N PERMISSION OF BLAZER THERS EXCEPT, DNDUSTRIES. OR.BLUE G.E,Modular5 ace Portland,Ofe On DATE: I.1 5-2 ,0.BOX A89■nUtivRl[,w 92326-0A89 F 9 JOB NO: I 1$'MICROLLAM 1 1/2"MICRO LAM TH E%TEND ONE STUD UP ALONG EXTEND ONE STUD UP ALONG 4i2��WI " RIOGEBEAM AND FASTEN WITH FIT AND FASTEN WITH NAILS EACH END 6- 10d x 3"BOX NAILS OR EQUAL 6- 10d x 3"BOX NAILS OR EQUAL GABLE END RAFTER SIIMMP ON ST2215 OR EWAL. SIMPPSSON ST2215 OR EQUAL USE 7- IOd x 11S"NAILS USE 7- 10d x 1 1/2'NAILS— o EACH END OF STRAP. EACH END OF STRAP. Xt"DIA. BOLT WITH 1Y2"DIA. WASHER — END O MN INTERIOR GGLLBAN -1'2 SPACER USE DOUBLE 2 x 4 D.F.'STANDARD." USE SIX 2 x 4 D.F.'STANDARD." FASTEN STUDS TOGETHER WITH FASTEN STUDS TOGETHER WITH DOUBLE ROW OF 10d x 3"BOX A DOUBLE ROW OF 10d x Y BOX NAILS OR EWAL AT B"— NAILS OR EOUAL AT B'DD. NAILS TO BE ANGLED SUGHTLY TO NAILS TO BE ANGLED SLIGHTLY TO PREVENT NAIL PENETRATION THRU PREVENT NAIL PENETRATION THRU NEXT COLUMN STUD. NEXT COLUMN STUD. CHORD SPLICE DETAIL + 1 1/2"=1'-0" [SIMILAR AT FLOOR] ADD TIGHT FIT 2 x 4 BLOCKING TO NEXT STUD AT WALL THIRD POINTS. STIR Q-+SI$IMPSSON ST2215 OR EQUAL SIMPSON ST2215 OR EQUAL USE 7-10d x 1)r NAILS USE 7- IOd.U¢'NAILS EACH END OF STRAP. VENT SCREEN 18 CA. 1 3/4'STAPLES O 4'!a EACH END OF STRAP. 0�j�eW EXCEPT AT 4VFENNT NOTCHES. 2x4 TOP ROOF RIM"INRIM JOIST 4'xY NOTCH AT EACH BAY. 1k!'MICROLLAM FLOOR JDI51 1XS-MIICROLLAM FLOOR JOIST RAFTER 3/B'�x 3'x 22'/SHEATHING A�J"mINTO EACH RMAPLES ADD TIGHT FIT BLOCKING UNDER ADD TIGHT FIT BLOCKING UNDER COLUMN FOR R11L BEARING. COLUMN FOR FULL BEARING. 2 x 4 x 20"SPACER BLOCKS BOTTOM ROOF RIM I x 6 FASCIA VAPOR BARRIER 1 EC224- END COLUMN DETAIL-DBL 2 x 4 2 IC624: INTERIOR COLUMN DETAIL-6 STUD SIDING NAILS Y 4"99 1 _ 1' 0 1" 1'-0" RM/.LEDGE .$'IIS FASTW!!r(A SIDING 1QQ--13 GAL x 2 1/2",STAPLES $o1IbONIE SAIEETA"2 (B'PANELS CUT TO FIT) MICROLLAM RIOGEBEAM� LB DRIVEN EA04 WAY) \ FASTEN SHEATHING TO VENT FASTEN 2 x 2 x 20"VENT ..� BLOCKS WITH 16 GA. x 1N" BLOCKS 24'oc.TO RIOGEBEAM STAPLES AT 4'ec. WITH 10d x 3"BOX NAILS LSTA24 STRAP BENT AT 5"oc.MAX. OVER BRAG€WIT„4 EAVE DETAIL 8d x 1 1/2 NAILS - - 1 1/2"- 1'-0" TO RACE AND 4-Bd x 1 tp2"NAILS TO BEAM RAFTER RAFTER I�Ot 2 x 4 D.F."STANDARD' `�pINB FL OF EXTRA BOLTS + _ JO' AS SHOWNBRACES BELOW.O"m IN COLUMN AREA. :M Liza r4k. 4-15GA SrifIVS,2 E4,w4-Y DA 1.8d r IWA14 *ADD BRACES AT B'-0'99 . `RCA 3c INsvLAnDN g td.sfp a� PC K.V2 NMOA.T,UNOCUTTRURESEH'S OPTON. s �q"1 TO BRACES REIYD BRACES RI IRIITIOK DA k. e'-0'IM 8'-0" 12'-0't 6'-0' 6'-0"11 ONE DRY CUP PERM y2"SPACER VAPOR BARRIER X2'SPACER,CONT. 2C ASTWAV4 r i/N�JHFE'T A"2kZ_ . • ° `'Y FLASHING t/2'90LiS o 2'AND D' . SITE WORK: $'X 8'BELT RAIL EnDI sIx nr CO. R � 2 INSTALL-IRIDGEVENTNSULATION WITH P MGALV.ARRIAGE SCREWS AT 12"oc. EACH SIDE. FASTENED VATH 20'-0" 2'-Cr 2.INSTALL INSULATION AT MARRIAGE LINE, Bd CALV.NAILS. 3. INSTALL VAPOR BARRIER ACROSS MARRIAGE LINE, 2 MIL.MIN. INSULATION REQUIRED COL.A COL B COL.C COL O (CLOSE-UP PLASTIC SUPPLIED WITH BUILDING MAY BE USED). INSTALLED ON SITE 0 5 RIDGEBEAM BRACING DETAIL- 16" 6 RIDGE DETAIL 7 FLOOR DETAIL 1 1/2"= 1'-D' 1 i/2"=1'-D" 1 1/2"- V-0. z 10-03 ENGINEEUNG W NBY COPYRIOHT2003. AZERINDUSTRIES,INC D MOBILE RESTROOM BUILDING for: TITLE' D""I 2-1003 FINAL REVIEW TM8 MATERIAL 19 THE EXCLUSIVE PROPERTY 1»ue DAte: 2-10-03 C� NO LAZER BE REPRXU ODUCED. USED NA BWLLL ., Icy"IA'.IM 2A}X A}4 Impregilo Healy DRAWN BY: NB A=46s NOT BE OTHERS EXCEPT A USED. RI ED By THE TO OTHERS EXCEPT A9 AUTHORIZED BY THE DATE, I-14-03 DATE REVISION VM2IITEN PERMI6810N OF BLAZER INDUSTRIES. I.9.IIOx 1.89 B At111111,DI19/525-01,89 OR.BLUE G.E.Modular 5pac Portland,Oregon JOB NO: 5- Q Q 2 FLOOR LINE _________ ______________________ _ __ _ _________ __ _________________ ____ ______ ___ ___ •T•FLASHING WALL 'A' ELEVATION ��III'I'41'�;b411101 I}II 'I'll I11 411' r I '"�$t,. y I " 13 1 MJ-4k141444 m 14 D--- ------- -- - ----- ------------------ BorroM of ---------------------------------------------------------------------------------------- FtooR aasrs WALL 'C' ELEVATION B B B ttttt ELECTRIC ENDWALLS PANEL STUB THRU -INSTALL ST2215 STRAPS WHERE SHOWN w/7- 10A x 1 1/2'NAILS N - TO EACH END OF EACH STRAP g __ ___ ____________ _____ _ ________________________________________________ `NOINEE1 10 Uj TAD LOCAnDN TAc LDCAnDNJ WALL T ELEVATION WALL '2' ELEVATION 12-31-02 MINARY REVIEWNB COPYRIGHT 2003,8LAZERINDIISTRIE8.RJC. ■ M.,.�• w MOBILE MA=3 RESTROOM for: IZED 01 i-16-03 [NGINEERING NB TW9 MATERIAL 19 THE EXCLUSIVE PROPERTY OF HLAZER,NDUHTED,USED, ANDBWLLL 24.44Impregllo Healy 2-10-03 FINAL REVIEW NB NOT BE REPRODUCED,UBED,OA dSCLOBED DATE REVISION BY WRITTEN PERMISSION OFF TO OTH RS EXCEPT AS BLAZER INDUSTRIES. ■■ P 9 DAT r.9.eox 6S9■nlMsvRtE,OR 9/320-O4S9 OR.BLUE G.E.Modular 5 ace Portland,Ore on FASTENING SCHEDULE MATERIAL LIST w•� am: PLATE-70-STUD MIN,OF 2-10d A 3"BOX NAILS(SENCO KC27 OR EQUAL) 2 It B FLOOR JOIST-TO-RIM MM.OF 4-10d x 3'BOX NAILS(SENCO KC27 OR EQUAL) ROOFING.............PASCO 25 YEAR ARCHITECTURAL SHINGLE VW SHEETROCK SENCO P15 STAPLES 3 BLUE CLASS"A'BOTTOM COVER-TO-JOIST 16 GA.x 3/5"WIDE CROWN O 12"oc MAX.EDGES ONLY OVER TWO LAYERS 15F FELT APPLIED SHINGLE FASHION.-HIGH WAND APPLICATION- BOTTOM PLATE-TO-FLOOR 10d.3'BOX NAILS O 16"—(SENCO KC27 OR EQUAL) FLOOR DECKING-TO-2.JOIST QQ113'x 2 3 B'RING SHANK O 6".EDGE,12'FIELD. (SENCO OL-4). USE CONSTRUCTION ADHESIVE(AFOOT)ON JOISTS SHEATHING...........7/16"OSS(24/16) DURATEMP SIDING-TO-STUD O SIDEWALL .099 x 2 1/4'OALV BOX NABS O 6".EDGE.12'FIELD FRAMING.............2 x 6 DF/2 RAFTERS O 24'oc AND ENDWALL (EXCEPT USE 4"a:O TOP h BOTTOM) BM RIDOEBEAM..........1 1/2'x 16"MICROLLAM LVL 2,0 E THREE STUD CORNER CONNECTION 10d x 3"BOX NAILS O 12'.(SENCO KC27 OR EQUAL RM-TO-RAFTERS MIN.OF S-tOd v J"BOX NAILS(-MICNCORO KC27 TO EQUAL) (2-TOP RIM TO RAFTER, -MICRO RIM TO RAF7E T LEDGERS.............2 x 4 TAPER CUT ROOF RIM-TO-TOP PLATE 10d x 3"BOX NAILS O B'm. (SENOD KC27 OR EQUAL) RIMS.................2 x 6 MICROLLAM LEDGER-TO-RM 10d x 3"BOX NAILS O 3"oc k 3 O BUTT JOINTS (SENCO KC27 OR EQUAL) W/NOTCHED 2 x 4 ON TOP LEDGER-TO-RIDGESEAM 10a x 3"BOX NAILS O 3"oc k 3 O BUTT JOINTS (SENCO KC27 OR EQUAL) INSULATION......... .R-19 CELLULOSE BLOW-IN RAFTER-TO-RIDGEBEAM 4-10d x 3'BOX NAILS(SENCO KC27 OR EQUAL) CEILING..............SUSPENDED T-BAR(PER LOG STD,25-21 SHEATHING-TO-ROOF MEMBERS 16 GA,x 1 3/4'STAPLES O S"oc EDGE,12"FIELD(SENCO N19) VENTING.............CONT.EAVE AND RIDGE NOTE: SHEATHING TO BE INSTALLED PERPENDICULAR TO THE RAFTERS. OFFSET SHEATHING 4 H1. SOCK EDGES OF ANY PIECES LESS THAN 24" Rua MAq AAF 06 CONWCTIM- NOTE: ALL MARRIAGE LINES(DEFINED AS THE SPACE BETWEEN ADJOINING MODULES) SIDING...............5/8"DURATEMP T1-11 W/GROOVES O B"Pc MUST BE INSULATED AT THE ROOF,FLOOR AM WALLS CIE. FASCIA..............1 w 6 PRIME TRIM RIDGEBEAMS 1/2"BOLTS W/1 1/2'OIA WASHERS O 4'-O"x AND 6"MOM EACH END TRIM.................1 v 4 PRIME TRIM O CORNERS/MODLNE (MINIMUM 2"EDGE DISTANCE) RIM JOISTS 1/2 BOLTS W/1 1/2"NA.WASHERS O 2'-B'-AND W FROM EACH ENO FRAMING........EXT:2 x 4 D.F.'STANDARD"a"STUD' (MINIMUM 2"EDGE DISTANCE) a BETTER STUDS O 16"ec, OR 2 x 6 D.F."STANDARD'a'STUD' a BETTER STUDS O 16"- .. ^ INTT2 If 4 D.F.O IS'-,EXCEPT PLUMBING WALLS TOP PLATE..........2 x 4 CONTINUOUS MICROLLAM �,I/ { • BOTTOM PLATE. x 4 O.F. INSULATION......EXT R-13. �I `\ 72 3 INTERIOR FINISH......5/e"WNYLWRAP SHEETROCK AND 2 _ PL WAINSCOT PER CODE,AND TO T I48".AFF BEHIND MOP SINIfS so Ic i BELT RAIL...........1 x 6 PRIME TRIM P4'_ \ 3`SEE,AM BI CHIC FLOM SEE DETAIL �. I I COVERING....... ..CONGOLEUM'DIAMOND 49045 SHEET VINYL -- W/METAL TRANSTION STRIP AT MODLINE _ CAUU(AT FLAME SPREAD LOP PA DECKING......... 2Pd:1%-ULTRAPLY�STURO-I-FLOOR 15 25 OR LESS FRAMING..............x 6S GF OMIT LS5a-RAocL RIMS.................2 x B CONTINUOUS MICROLLAM w H' ONF I1RV CUP PERM VAPOR I t n BARRIER QU TREZ9ARA�-SIGF, INSULATION..........fl-25 CELLULOSE BLOW-IN Z c+ BOTTOM COVER......CLASS"A' 0 p7 U I 0 I TYPE................TRANSVERSE fi WAINSCOT MAIN RAIL...........10"JR.I-BEAM WITH FULL WIDTH 7 1 7 C-CHANNEL CROSSMEMBERS 0 FRONT A REAR AXLES ...............3 BRAKE k00 v 14.5 14 PLY TKRES HFFCN...............DETACHABLE A FASTEMNC REd11REMEN75: I ) FLOOR JOIST TO I-BEAM.....5/16"x 3"LAOS O 32". \ \ / �K AT (ALTERNATE SIDE TO SIDE OF EACH I-BEAM) 90 PLATE END CROSSMEMSER CONNECTION TO END RIM JOIST... ` (7)5/16'•3"LAGS O I-BEAM, 99)" PCE _ 99(" 4 10I s SA Tra"*q TV-10" s — -- �+es E OB SECTION - A A W To 11 ❑04 DATE: 02-03 PRLUMINA VIEW AB COPYRIGHT 2003,THE ERIRDUVF PRONG. NI MOBILE RE5TROOM BUILDING for: TITLE` saMPP .16-03 ENGINEERING AJB THIS MATERIAL 19 THE tXCIL8IVE PROPERTY Ie Date: 2-I O-03 OF HKAREIROUBT E.. INC.AND Imp�egilo Healy A=212-10.03 rINAL KEVIEw ae 24 x 44 DRAWN BY: AJe NOT BE REPRODUCED,USED,T AS AUTHORIZED BY T1F-0 D TE REVI 1 BY VWRITTENRPERMI380N OF BLAZER INDUSTRIES A M.O.B6%469 WnUNtivILlF.tll 9/S26ALB9 OP.BLUE G.E.Modular Space Portland,Oregon OBENO: I-14-03 20--1 SHOWER UD FINISH TO FINISH TYPICAL P.L.WAJNSCOT TO 040-A�FF S _O,-0' 3-- 3. _ EQ. EQ. EQ. lb ........ ........ ........ ........ ........ ........ ........ SHOWERS P.V.C.CURTAIN V-6- 3'-Or 3'-OP 3'-4- 3'-6" TYPICAL 5'-Ior 3'-I1r SHOWERS, TOILETS & URINALS FAUCET W/BRACE TO WALL pcvWw 44'-0" 1�.WAINSCOT 4'-O'AFF WASTE TER STUBS SCOT OR SINK WA �T 4*-0"AFF & — 24' 24".1 W.H, W.H. x 2.8 AU. u u u lim F/ x i L MOP SINKS & WATER HEATERS 318"=1'-0" 6 Pon, IC624 10'-6" A A-4 0 , IC 21 4 1 1E 11 AI 4 �11 411 1 1 14 LOCKERS (OPTIONAL) (OPTIONAL) 1 2 LOCKERS A, t4 "'T N 0 0 0 DIAGONAL LOCKERS RACES 12" (OPT 12" MIN rl IN 4 T-T-T-T-T T-T-T-T-T T-T-T�-T-T-T-= -T-7-T-T-T- T-1 -.1 T-I i I I i 1 11 j I I I I I I I i T-T-T T-1 3 LAV. COUNTER ELEVATION OTY. SIZE DESCRIPTION LOCK REMARKS LT DOORS INSULATED GALV, SITE, PUSH/PULL 8 R'C NRP HINGES L PAINT FINISH 2 6 STEEL JAMS AND B662 LCN 146 LOSER I S FLOOR PLAN P C WEATHERSTRIPPING OBLD KEY KICKPLATE DEA BOLT m0 2-03 rFtr MINAWREVIrW- AJ15 COPYRIGHT 2003.BIKER INDUSTRIES,INC m MOBILE RE!5TROOM BUILDING for: TrrLe: m—pw 6-03 CU5TOMEPC"ANGE5 AJB THIS MATERIAL IS THE EXCLUSIIFFFITY O.�t 2-10-03 2-10-03 IINAL REVIEW AM 04�BLAZER INDUSTRIES,INC. 24.44 Impregilo Healy DRAWN BY: AJB 65 NO BE REPRODUCED,USED.0 TO DATE: 1-14-03 "Y T OTHERS EXCEPT AS AUTHORIZED BY THE G.E.Modular Sra� Portland.Orejon AmIl 6� —07—F REVISION "ITTEN PERMISSION OF BLAZER INDUSTRIES 1,89 W—VILLE,at 97325-0489 OR.BLUE L►�C�MI C1�1 OOI M1 o ] 0 g O n ffo Cr aTA reTE Cf OREGLNJ BVBDBxi C00®pyLGICN Im p gRn o Healy Thetl mrN vn eppaWd Nrmemclbntlnvind M A*T•P'EM44ri�.••nrodf a�Bm n nN ion b NN npPwntl FEB 25 JW-A003 x d r+W W mural se nwmned N and Pw�eaw BN au•eti'�ac°°•enr.�na Weetlim PmrUand5l o 1ragon �Me�v PIn RnMwdaY 0 o c o ey�i,2ts�2s�3 Code CDMP� ING ftPCc �n�OTMgool Ndu W DTIM g Applicable Codes: 1998 Oregon Structural Spools"Code Site Address: I:.Ipregllo Healy T-1 Title Sheet. 2002 Oregon Mechanical Specialty Code 2400 Front AV 2000 Oregon Plumbing Specialty Cade Portland,OR 97209 A-1 Floor Plan,Door&Window Schedule. 2002 Oregon Electrical Specialty Code nlulnomah County A-2 Section,Fastening Schedule&Material List. A-3 Elevations. Dealer: G.E.Capital Modular Space Type of Construction: V-N 0975 N Rivergate BV A-4 Details. Portland,OR 97203-6572 Description: Restroom Building M-1 Reflected Ceiling Plan,Mechanical Plan,Interior Elevations. Occupancy: B Builder: Blazer Industries,Inc. PO Box 489 P-1 Plumbing Schematics Floor Area: 1043 square feet Aumavllle,OR 97325 Ccntact: John Roth E-1 Electrical Information. ho (503) 749-19M Job Number: 11825-28 Pne: i�ex: (503) 740-3969 FP-1 Fire Sprinkler Hervey&Price Energy Zone: 2 mail:iohnnMblazednd.com ueneW HOW Des�'U- n Loads KL.E.A.% The Structural Design Details Herein are Specific to the Building Size and Roof..............:.....30 P.S.F. 1. Electrical Connection to Service Module Configuration Shown on the Floor Plan of These Drawings. Wlnd....................90 M.P.H.Exposure"B" 2. Plumbing Connection to Service No Authorization is Given or Implied for use of the Modules In the Initial or Subsequent Installation Which Results in a Building Size or Installed Module Floor...................50 P.S.F.or 20001b. 3. Rldgeventing,Insulation(i.e.Marriage Line y")Vapor Configuration Different Than Shown on These Drawings. Barriers,Dreflatope and Fire Blocking Installed on Site Selamlc...............Zone 3 -This Building will be sited a minimum of 20 feet from all Properly lines and 4. Water Hester Pressure Relief Terminating at the 201eet from any assumed Property Linea between existing structures on this site. Building Exterior-------� -Sit rac n�&pwfllblli ro yasllA�ly�a411� S �TIPa SaRINK[fk JYS?EAr LnMOLET,dv�F fANNELIIMV e eonf nee code c[[[[ !d ON-Tin .".7ci SEE bee �/ 6, E fq s�y�If�3 ....... F P1^l3�N Plm a �5a56PE 8 � RWNW �W.TORNO�' P1/•A0""eh FEB ) 1 2003 1 BUILaNB COOPS eCfMCY 2,10,03 IINAL KIV1111',C.W,T, l_,8411j COPYRIGHT 1113,BLAZER INDUaTRIE9,INC. MOBILE T1TLl: Title Sheet THIS MATERIALIS THE E%CLU"PROPERTY RE5TROOM BUILDING for: ,,,p,0ate z-loos OP xA1E PRp aTED.U NC.OR 019CLL ••ErY THEN V•y 24 x as Impregllo Healy DRAWN BY, Are T. NOT 9E REPRODUCED,USED,OR SFAL09ED A 2 DA1E REVI51(TJ BY WRITTEN PERMISSION OF BUiER�NDU9TR1E9. ■. P.O.Box LBD/nU1AYGLE.OR"311-0. OR.BLUE G.E.Modular Space Portland,01C90n DpgtNO I 14 03 (124)MagicMail Webmail :: Drawings for Blazer Building Page 1 of 1 File view Help � - - �9 __ - - Fllhr. Search: ! ClearJ HoodCanalJ = C a -4 _4 0 & 0' r'i "• °Y` Check Mail Cortgoae Reply Reply AN Forward Forward as Do" Mark As Mon._ Address Calendar acmMn_ _ Book.-- billwells@h=.net Foldao Subject Drawings tor Blain Building Inbox(124) I Sender Jeffrey Swanborough Y Dn is Recipient billweils@th c.net•* Sent Cate Today 18:04 Spam Trash T-tpdf A-1.pdf A-2.pdf A-3.pdt AJ.pdf E-tpdf FP-t pol M-1 pol P-1 pdf Bill, Attached are the drawings we have for building#11625-26. Please let me know if you have any questions. I � - Thank you, Jeffrey Swanborough E-Mail Settings I Warranty/QC Manager I Blazer Industries,Inc.I PO Box 489,945 Olney St I Aumsville,OR 97325 I p:503-749-19001 f:503-7493969 Iwww blazernd coin I. Address Email Book options f spW 'CM. Spam Status:Jun 03rr_'? You have been protected from 1 j spam message today. III I I I i I I I I I t htlps://mail.hcc.neVtuxedo/? task=mail& action=show& uid=4105& mbox=INBOX 6/3/2013