HomeMy WebLinkAboutConfidence Testing Diesel Fire Pumps - FIR Inspections - 7/19/2018 fapitol
5891 Mullen Road SE • Lacey, WA 98503
(360) 493-1830
Fax: (360)923-1841
Email:hcaulfield@capitolpump.com
1111 pill
CONFIDENCE TESTING
DIESEL
FIRE PU117PS
Address: 780 West Highway 108 Shelton, WA
Occupied as: Alta Forest Products
Inspected by: Kyle Nunley Certificate#'N-08336
Date of Inspection: July 191h,2018 Type of Test: Quarterly❑ Annual
Fire Dept. Official Contacted:
Pump Model: 6AEF14G Impeller: 13.36 Serial No.: 166027
Pump Design Conditions: 1500 GPM @ 75 PSI
Controller Model: FTA1100-JL12N Serial No: 793415-01RE
Engine Model: PDFP-L6YT 2504 Serial No.: U646032C
Block Heater Operational: Yes No❑ Engine Hours: 1137
Controller Voltage: 12 volts Batteries: 13.3/13.2
Fire Pump:
Cut-in Pressure: 80 psi Cut-out Pressure: Alan.psi
Timer set at: 0 min.
Jockey Pump:
Cut-in Pressure: n/a psi Cut-out Pressure: n/a psi
Timer set at: n/a min.
Pump starts on eater from roof? Yes❑ No ® AT/A❑
Pump starts on pressure drop? Yes® No ❑ N/A ❑
Pump Motor: Diesel ® Electric❑ Other
Routine maintenance is performed and records are kept? Yes ® No ❑
CPR •Care• Pride •Response• Pumps •Valves • Controls •Sales• Service •Rental •Repair •Testing
i
Static city water pressure 13 psi
Churn suction pressure 13 psi Churn discharge pressure 102 psi
Was 300 GPM flow conducted? Yes ® No❑
Hose size: N/A inch Tip size: N/A inch Hose length: N/A fl
Pitot reading: Flowmeter GPM: 1500
Was pump run for 10 minutes flowing? Yes® No ❑ �)
Were all fire pumps tested? Yes ® No ❑
Flow Chart j
NO.&SIZE PUMP PRESSURE PITOT FLOW R AI VOLTS AMPS COMMENTS
OF NOZZELS PRESSURE
DISCUG. SUCT. NET
CHURN 102 13 89 - - 1825
Flowmeter 82 10 72 1500 1820
Flowmeter 61 6 55 2250 1821
Problems found: Jockey pump running constantly-not holding pressure.
Corrections made:
Date corrections made: By:
THIS IS TO CERTIFY THAT THE FIRE PUMP SYSTEM HAS BEEN PROPERLY
TESTED AND INSPECTED FOR RELIABILITY TO COVER THE ITEMS LISTED
IN THIS REPORT; IS CONSISTANT WITH MANUFACTURER'S REQUIREMENTS;
AND ALL CORRECTIONS ARE TO BE MADE BY OWNER.
Signature of Tester:
Agency: Capitol Pump R sources Phone: (3 -1830
Capitol Pump Resources Invoice
Fax (360) 923-1841 DATE INVOICE#
5891 Mullen Road SE 7/23/2018 01-7763
Lacey, WA 98503
i
BILL TO SHIP TO
Alta Forest Products
780 West Highway 108
Shelton, WA 98584
P.O. NO. TERMS REP SHIP DATE SHIP VIA FOB Job#
Net 30 KN 1876659
DESCRIPTION QUANTITY PRICE EACH AMOUNT
One Diesel Fire Pump Confidence Test on 7/19/2018 1 600.00 600,007
Sales Tax-Mason 8.50% 51.00
Thank you for your business.
Total
$651.00
Payments/Credits $0.00
Job Total Balance S651.00
fapl'tol -
5891 Mullen Road SE • Lacey,WA 98503
(.360) 493-1830
''eta Fax: (360)923-1841
Email:hcaulfield@capitolputup.coin
CONFIDENCE TESTING
DIESEL
FIRE PUMPS =
Address: 780 West Highway 108 Shelton, WA
Occupied as: Alta Forest Products
Inspected by: Kyle Nunley Certificate#N-08336
Date of Inspection: May 5111,2017 Type of Test: Quarterly❑ Annual
Fire Dept. Official Contacted:
Pump Model: 6AEF14G Impeller: 13.36 Serial No.: 166027
Pump Design Conditions: 1500 GP)11 a 75 PSI
Controller Model: FTA1100-JL12N Serial No: 798415-01RE
Engine Model: PDFP-L6YT 2504 Serial No.: U646032C
Block Heater Operational: Yes ® No ❑ Engine Hours: 1095
Controller Voltage: 12 volts Batteries: 13.3/13.3
Fire Pump:
Cut-in Pressure: 16 psi Cut-out Pressure: Man.psi
Timer set at: 0 min.
Jockey Pump:
Cut-in Pressure: n/a psi Cut-out Pressure: n/a psi
Timer set at: n/a min.
Pump starts on water from roof? Yes ❑ No® N/A ❑
Pump starts on pressure drop? Yes ® No❑ NIA❑
Pump Motor: Diesel ® Electric[] Other
Routine maintenance is performed and records are kept? Yes No ❑
CPR • Care• Pride • Response•Pumps •Valves • Controls • Sales• Semite •Rental •Repair•Testing
Static city water pressure 13 psi
Churn suction pressure 13 psi Churn discharge pressure 94 psi
Was 300 GPM flow conducted? Yes ® No ❑
Hose size: NIA inch Tip size; N/A inch Hose length: N/A ft
Pitot reading: Flowmeter GPM: 1500
Was pump run for 10 minutes flowing? Yes® No ❑
Were all fire pumps tested? Yes ® No❑
Flow Chart
NO.&SIZE PUMP PRESSURE PITOT FLOW RPDI VOLTS AMPS cO,tiiliuN-rS
OF NOZZELS PRESSURE
DtSCFIG. SUCT. NET
CHURN 94 113 81 - - 11795
Flo►vmeter 82 10 62 1500 1 1792
Flownieter 62 4 58 2250 1781
Problems found; RPM was Iow during flows
Corrections made: Increased RPM
Date corrections made: 5/25/17 By: KN
THIS IS TO CERTIFY THAT THE FIRE PUMP SYSTEM HAS BEEN PROPERLY
TESTED AND INSPECTED FOR RELIABILITY TO COVER THE ITEMS LISTED
IN THIS REPORT; IS CONSISTANT WITH MANUFACTURER'S REQUIREMENTS;
AND ALL CORRECTIONS ARE TO BE MADE BY OWNER.
Signature of Tester: .---
3
Agency: Capitol Pump Resources Phone: (360) 493-1830