HomeMy WebLinkAboutConfidence Testing Diesel Fire Pumps - FIR Inspections - 7/19/2018 fapitol 5891 Mullen Road SE • Lacey, WA 98503 (360) 493-1830 Fax: (360)923-1841 Email:hcaulfield@capitolpump.com 1111 pill CONFIDENCE TESTING DIESEL FIRE PU117PS Address: 780 West Highway 108 Shelton, WA Occupied as: Alta Forest Products Inspected by: Kyle Nunley Certificate#'N-08336 Date of Inspection: July 191h,2018 Type of Test: Quarterly❑ Annual Fire Dept. Official Contacted: Pump Model: 6AEF14G Impeller: 13.36 Serial No.: 166027 Pump Design Conditions: 1500 GPM @ 75 PSI Controller Model: FTA1100-JL12N Serial No: 793415-01RE Engine Model: PDFP-L6YT 2504 Serial No.: U646032C Block Heater Operational: Yes No❑ Engine Hours: 1137 Controller Voltage: 12 volts Batteries: 13.3/13.2 Fire Pump: Cut-in Pressure: 80 psi Cut-out Pressure: Alan.psi Timer set at: 0 min. Jockey Pump: Cut-in Pressure: n/a psi Cut-out Pressure: n/a psi Timer set at: n/a min. Pump starts on eater from roof? Yes❑ No ® AT/A❑ Pump starts on pressure drop? Yes® No ❑ N/A ❑ Pump Motor: Diesel ® Electric❑ Other Routine maintenance is performed and records are kept? Yes ® No ❑ CPR •Care• Pride •Response• Pumps •Valves • Controls •Sales• Service •Rental •Repair •Testing i Static city water pressure 13 psi Churn suction pressure 13 psi Churn discharge pressure 102 psi Was 300 GPM flow conducted? Yes ® No❑ Hose size: N/A inch Tip size: N/A inch Hose length: N/A fl Pitot reading: Flowmeter GPM: 1500 Was pump run for 10 minutes flowing? Yes® No ❑ �) Were all fire pumps tested? Yes ® No ❑ Flow Chart j NO.&SIZE PUMP PRESSURE PITOT FLOW R AI VOLTS AMPS COMMENTS OF NOZZELS PRESSURE DISCUG. SUCT. NET CHURN 102 13 89 - - 1825 Flowmeter 82 10 72 1500 1820 Flowmeter 61 6 55 2250 1821 Problems found: Jockey pump running constantly-not holding pressure. Corrections made: Date corrections made: By: THIS IS TO CERTIFY THAT THE FIRE PUMP SYSTEM HAS BEEN PROPERLY TESTED AND INSPECTED FOR RELIABILITY TO COVER THE ITEMS LISTED IN THIS REPORT; IS CONSISTANT WITH MANUFACTURER'S REQUIREMENTS; AND ALL CORRECTIONS ARE TO BE MADE BY OWNER. Signature of Tester: Agency: Capitol Pump R sources Phone: (3 -1830 Capitol Pump Resources Invoice Fax (360) 923-1841 DATE INVOICE# 5891 Mullen Road SE 7/23/2018 01-7763 Lacey, WA 98503 i BILL TO SHIP TO Alta Forest Products 780 West Highway 108 Shelton, WA 98584 P.O. NO. TERMS REP SHIP DATE SHIP VIA FOB Job# Net 30 KN 1876659 DESCRIPTION QUANTITY PRICE EACH AMOUNT One Diesel Fire Pump Confidence Test on 7/19/2018 1 600.00 600,007 Sales Tax-Mason 8.50% 51.00 Thank you for your business. Total $651.00 Payments/Credits $0.00 Job Total Balance S651.00 fapl'tol - 5891 Mullen Road SE • Lacey,WA 98503 (.360) 493-1830 ''eta Fax: (360)923-1841 Email:hcaulfield@capitolputup.coin CONFIDENCE TESTING DIESEL FIRE PUMPS = Address: 780 West Highway 108 Shelton, WA Occupied as: Alta Forest Products Inspected by: Kyle Nunley Certificate#N-08336 Date of Inspection: May 5111,2017 Type of Test: Quarterly❑ Annual Fire Dept. Official Contacted: Pump Model: 6AEF14G Impeller: 13.36 Serial No.: 166027 Pump Design Conditions: 1500 GP)11 a 75 PSI Controller Model: FTA1100-JL12N Serial No: 798415-01RE Engine Model: PDFP-L6YT 2504 Serial No.: U646032C Block Heater Operational: Yes ® No ❑ Engine Hours: 1095 Controller Voltage: 12 volts Batteries: 13.3/13.3 Fire Pump: Cut-in Pressure: 16 psi Cut-out Pressure: Man.psi Timer set at: 0 min. Jockey Pump: Cut-in Pressure: n/a psi Cut-out Pressure: n/a psi Timer set at: n/a min. Pump starts on water from roof? Yes ❑ No® N/A ❑ Pump starts on pressure drop? Yes ® No❑ NIA❑ Pump Motor: Diesel ® Electric[] Other Routine maintenance is performed and records are kept? Yes No ❑ CPR • Care• Pride • Response•Pumps •Valves • Controls • Sales• Semite •Rental •Repair•Testing Static city water pressure 13 psi Churn suction pressure 13 psi Churn discharge pressure 94 psi Was 300 GPM flow conducted? Yes ® No ❑ Hose size: NIA inch Tip size; N/A inch Hose length: N/A ft Pitot reading: Flowmeter GPM: 1500 Was pump run for 10 minutes flowing? Yes® No ❑ Were all fire pumps tested? Yes ® No❑ Flow Chart NO.&SIZE PUMP PRESSURE PITOT FLOW RPDI VOLTS AMPS cO,tiiliuN-rS OF NOZZELS PRESSURE DtSCFIG. SUCT. NET CHURN 94 113 81 - - 11795 Flo►vmeter 82 10 62 1500 1 1792 Flownieter 62 4 58 2250 1781 Problems found; RPM was Iow during flows Corrections made: Increased RPM Date corrections made: 5/25/17 By: KN THIS IS TO CERTIFY THAT THE FIRE PUMP SYSTEM HAS BEEN PROPERLY TESTED AND INSPECTED FOR RELIABILITY TO COVER THE ITEMS LISTED IN THIS REPORT; IS CONSISTANT WITH MANUFACTURER'S REQUIREMENTS; AND ALL CORRECTIONS ARE TO BE MADE BY OWNER. Signature of Tester: .--- 3 Agency: Capitol Pump Resources Phone: (360) 493-1830