HomeMy WebLinkAboutBLD2023-00717 Cancelled Deck - BLD Inspections - 12/13/2024 4 �
Mason County
Mason County - Division of Community Development
615 W. Alder St.
Building 8
She lton, WA 98584
360-427-9670 ext 352
www.masoncountywa.gov
\ V
B DD2023-00717 CARPORT/DECK/ COVERED
PROJECT DESCRIPTION: DECK REPLACEMENT(NO FOOTPRINT ISSUED: 06/27/2023
CHANGE)
SITE ADDRESS: 20 E MARINE VIEW DR ALLYN EXPIRES: 12/24/2023
PARCEL: 122205100017
APPLICANT: PAUL RICHARD D&SHARON R OWNER: PAUL RICHARD D&SHARON R
P O BOX 1739 P O BOX 1739
ALLYN,WA 98524 ALLYN,WA98524
1.360.275.4488
VALUATIONS: FEES: Paid Due
Uncovered Deck 141.00 $2,115.00 Technology Surcharge $4.72 $0.00
State Fee-Residential $6.50 $0.00
Plan Check Fee $80.00 $0.00
Building Permit Fee $156.00 $0.00
Total: $2,115.00 Totals : $247.22 $0.00
REQUIRED INSPECTIONS
Setback Inspection Framing Inspection
Footing Inspection BLD-Final Inspection
CONDITIONS
' All construction must meet or exceed all local and state ordinances in addition to the International Codes requirements as
adopted and amended by Mason County and the State of Washington. Occupancy is limited to the approved and permitted
classification. Any non-approved change of use or occupancy would result in permit revocation.
CONSTRUCTION PROCESS TO BE FIELD CORRECTED AS REQUIRED PER MASON COUNTY BUILDING
DEPARTMENT AND THE ADOPTED BUILDING CODE.
The construction of the permitted project is subject to inspections by the Mason County Building Department. All
construction must be in conformance with the international codes as amended and adopted by Mason County. Any
corrections, changes or alterations required by a Mason County Building Inspector shall be made prior to requesting
additional inspections.
Printed by:Annie Wilson on:06/27/2023 08:39 AM
Page 1 of 2
Mason County
Mason County - Division of Community Development
615 W.Alder St.
Building 8
Shelton,WA 98584
360-427-9670 ext 352
www.masoncountywa.gov
CARPORT/DECK/ COVERED BLD2023-00717
* Provisions for surface/subsurface drainage control must be implemented with new construction or development on site and
MUST NOT adversely impact adjacent parcels. Under the requirements of Mason County Stormwater Ordinance, either
private ditches and drains will meet requirements of the stormwater ordinance or prior approval will be granted to use an
existing utility and drainage easement dedicated for that specific purpose. For further information regarding this ordinance
contact the Mason County Public Works Department prior to construction at Ext 450
* All RED stamped approved plans are required to be on-site for inspection purposes. If an inspection is called for and
plans are not available on site,then approval will not be granted. In addition, a re-inspection fee (refer to current fee
schedule, minimum 1 hour)will be charged and must be collected by the Building Department prior to any further inspections
being performed or approvals granted.
* REQUIREMENTS FOR ROOF COVERINGS. Roof coverings shall be applied in accordance with the applicable
provisions of the current code and the manufacturer's installation instructions.
A drip edge shall be provided at eaves and gables of shingle roofs.
* Proposed structure(s)must maintain a minimum of a 5'setback from all property lines, easements and 25'from all County
and State Road right of ways. Setbacks are measured from the furthest projection of the structure.
X
* The foundation/footing must be placed on undisturbed, firm-native soil. Proper frost depth shall be observed below grade
in undisturbed soils.
* OWNER/BUILDER acknowledges submission of inaccurate information may result in a stop work order or permit
revocation.Acknowledgement of such is by signature below. I declare that I am the owner, owners legal representative, or
contractor. I further declare that I am entitled to receive this permit and to do the work as proposed. I have obtained
permission from all the necessary parties, including any easement holder or parties of interest regarding this project. The
owner or authorized agent represents that the information provided is accurate and grants employees of Mason County
access to the above described property and structure(s)for review and inspection. This permit/application becomes null &
void if work or authorized construction is not commenced within 180 days or if construction work is suspended for a period of
180 days. PROOF OF CONTINUATION OF WORK IS BY MEANS OF INSPECTION. INACTIVITY OF THIS PERMIT
APPLICATION OF 180 DAYS WILL INVALIDATE THE APPLICATION.
* All building permits shall have a final inspection performed and approved by Mason County Building Department prior to
permit expiration. The failure to request a final inspection or to obtain approval will be documented in the legal property
records on file with Mason County as being non-compliant with Mason County ordinances and building regulations.
* PROOF OF CONTINUATION OF WORK IS BY MEANS OF INSPECTION. INACTIVITY OF THIS PERMIT APPLICATION
OF 180 DAYS WILL INVALIDATE THE APPLICATION.
I hereby certify that I have read and examined this application and know the same to be true and correct.
All provisions of Laws and Ordinances governing this type of work will be complied with whether
specified herein or not. The granting of a permit does not presume to give authority to violate or cancel
the provisions of any other state/local law regulating construction or the performance of construction.
Issued By: � 3'1
�L 7
Contractor or Authorized Agent: � Date: � � � L C
Printed by:Annie Wilson on:06/27/2023 08:39 AM
Page 2 of 2
MASON COUNTY 615 W.Alder St.Bldg 8,SHELTON,WA 98584
SHELTON:360 427-9670,EXT 352
COMMUNITY SERVICES
BELFAIR:360-275-4467,EXT 352
Building Planning,Cnvironmentul Health,Community Health ELMA:360-482-5269,EXT 352
www.co.mason.wa.us
INSPECTION CARD AND CERTIFICATE OF OCCUPANCY`"
To schedule an inspection call or visit http://www.co.mason.wa.us/community-services/bid-inspection.php
Permit Number BLD2023-00717 Date Issued 06/27/2023 Issued By krl f e
Project DECK REPLACEMENT(NO FOOTPRINT CHANGE)
Site Address 20 E MARINE VIEW DR
Applicant PAUL RICHARD D&SHARON R
Contractor
Contractor Phone
Primary Code UPC IBC,IRC,IFC,IEC,IMC,& Type
Permit Type CARPORT/DECK/COVERED Occupancy
-APPROVED PLANS MUST BE ONSITE FOR ALL INSPECTIONS.
-DO NOT PROCEED BEYOND EACH STAGE OR COVER WORK UNTIL APPROVAL IS GRANTED.
-THIS CARD MUST BE POSTED IN A CONSPICUOUS LOCATION,FRONT OF THE PREMISES IS BEST FOR MAKING ENTRY.
-ALL PERMITS EXPIRE 180 DAYS AFTER THE PERMIT IS ISSUED OR 180 DAYS AFTER DATE OF LAST INSPECTION.
-OWNER/AGENT IS RESPONSIBLE FOR REQUESTING ALL INSPECTIONS THROUGH FINAL INSPECTION.
"THIS STRUCTURE MAY NOT BE USED OR OCCUPIED UNTIL ALL APPROVALS ARE GRANTED."
PRIOR TO CALLING FOR FINAL INSPECTION,ALL CONDITIONS OF THE PERMIT MUST BE MET
Public Works Access/Driveway Other
Health Septic Well
Deptartment
Planning Site Inspection
Department
Fire Marshall Fire Apparatus Access Fire Sprinkler
Auto Fire Alarm Hood and Duct
Other Final
Building
Department Building Official: Community Services Designee
Concrete Setbacks Slab
Footing Perimeter Point load Footing
Footing Interior Footing Decks/Porches
Foundation Stem Walls Other
Rough-in Groundwork Plumbing Framing
Groundwork Mechanical Plumbing
Groundwork Gas Pipe Mechanical
Gas Piping Shear Wall Nailing
Underfloor
Other
Insulation Slab Ceiling
Floor Vaulted Ceiling
Walls Vapor Barrier
Other
Wallboard Interior Wall Brace Panels Fire Walls
Nailing
Other
Final Building
Manufactured Setbacks Setup
Home
Concrete Foot/Runners Final
Other
MASON COUNTY COMMUNITY SERVICES Permit No: ql-"
PERMIT ASSISTANCE CENTER:
•BUILDING•PLANNING•PUBLIC HEALTH•FIRE MARSHAL
615 W.Alder Street,Shelton,WA 98584
Phone Shelton:(360)427-9670 ext.352•Fax:(360)427-7798 Phone131 N 2 6 ��23
Belfair.(360)2754467•Phone Elma:(360)482-5269
BUILDING PERMIT APPLICATION 615 W. Alder Street
PROPERTY OWNER INFORMATION: CONTRACTOR INFORMATION:
NAME: NAME:
MAILING ADDRESS: ?0 E,MO rwm ILING ADDRESS:
CITY: 001fum STATE: WA ZIP: CITY: STATE: ZIP:
PHONE#1: Z5 PHONE: CELL:
PHONE#2: EMAIL:
EMAIL: t"IC•5 z a l�!'GL &I REG# EXP.
PRIMARY CONTACT: OWNER® CONTRACTOR❑ OTHER❑
NAME 2YYCp EMAIL
MAILING ADDRESS CITY STATE ZIP
PHONE CELL
PARCEL INFORMATION:
PARCEL NUMBER(12 Digit Number) P Aga0'5!'D0a 1 J ZONING
LEGAL DESCRIPTION(Ahhreviatedl I_f 4 d V i ((A qC_ :T FIRE DISTRICT
SITE ADDRESS ,2-0 F _f Y I(,4_JC iKs— view D r• CITY_A((y Y1
DIRECTIONS TO SITE ADDRESS
IS THE PROJECT WITHIN 300 FT OF SLOPE(S)GREATER THAN 14%: YES[] NO❑ SNOW LOAD:_psf
IS PROPERTY WITHIN 200 FT OF THE FOLLOWING: (Checkall that apply):
SALTWATER❑ LAKE❑ RIVER/CREEK❑ POND❑ WETLAND❑ SEASONAL RUNOFF❑ STREAM❑
TYPE OF WORK: NEWg ADDITION❑ ALTERATION❑ REPAIR❑ OTHER ❑
USE OF STRUCTURE(Residence,(enrage,Commercial Bldg,
IS USE: PRIMARY❑ SEASONAL❑ NUMBER OF BEDROOMS NUMBER OF BATHROOMS
HEATED STRUCTURE? YES(Whole ❑ YES(Parr[s)ofBldg) NO❑
DESCRIBE WORK
SQUARE FOOTAGE:(proposed)
1 00 sq.ft. 2ND FLOOR sq.ft. 3RD FLOOR sq.ft. BASEMENT sq.ft.
EC � COVERED DECK sq.ft. STORAGE sq.ft. OTHER sq.ft.
sq.ft. Attached❑ Detached❑ CARPORT sq.ft. Attached❑ Detached❑
MANUFACTUR *4 COPIES OF THE FLOOR PLAN REQUIRED*
MAKE MODEL EAR LENGTH
W TH BEDROOMS BATHS SERI MBER
------------
ENVIRONMENTAL HEALTH:
SEWAGE/SEWE SEPTIC❑ SEWER❑ / W❑ EXISTING❑
PL G IN STRUCTURE? YES❑ NO❑ [fyes,attach comp ater Adequacy Form
re_
RIMETER/FOUNDATION DRAINS PROPOSED? YES❑ NO[] EXIS'
EXISTING BEDROOMS PROPOSED BEDROOMS TOTAL BEDROOMS
OWNER acknowledges that submission of inaccurate information may result in a stop work order or permit revocation.Acknowledgement of such is by
signature below.I declare that I am the owner and I further declare that I am entitled to receive this permit and to do the work as proposed.1 have
obtained permission from all the necessary parties,including any easement holder or parties of interest regarding this project. The owner or legal
representative,represents that the information provided is accurate and grants employees of Mason County access to the above described property
and structure(s)for review and inspection. This permit/application becomes null&void if work or authorized construction is not commenced within 180
days or if construction work is suspended for a period of 180 days.
PROOF OF CONTINUATION OF WORK ON THIS PERMIT IS BY MEANS OF INSPECTION. INACTIVITY OF THIS
PER PP ICATIOPTOF0 DA7 OF MORE WILL CAUSE THE APPLICATION TO BE EXPIRED.(MASON
COUNTY CODE 14.08.42)
X 6 LZI,Z&7,
Ignature of OWNER(Must be signed by the OWNER) D to
DEPARTMENTAL REVIEW APPROVED DATE DENIED DATE TAGS/NOTES/CONDITIONS
BUILDING DEPARTMENT
PLANNING DEPARTMENT
FIRE MARSHAL
PUBLIC HEALTH
oo
f44
flit
f'
F
All
w
JJY.�tt '. �!`-
>,
t
DECK PLAN SPECIFICTIONS
Owners Name IchaAd-, L- Permit Number. 21)23--00� I
Site address: 21) C V I L-'t,(Vbe. Parcel Number: I�,aa•�— 5 I— OCR I�-
Submittal Requirements:
1. Building Permit Application
2. Site Plan must show all structures,septic,slopes,driveway,and shoreline.
1. Complete all items in form below. incomplete submittal will be returned.2018 IRC Section 507 Deck.
DESCRIPTION EXAMPLE YOUR DECK
1. Overall Deck Size 10' wide x 12' tong 8'6" x 20 1.
2. Decking Surface Cedar or Trex Timbertech 2.
3. Height Above Grade 48" at highest point Ledger Board at 60"- HP at 75' 3.
A.Joist Length&Size 72' and 2"x70" ��6"a�-� J'k►o" A.
B. Ledger Size 2"x70" 2"x I0" B.
C. Lateral Tension Device R507.9.2(1) & R507.2(2) C.
2 locations x 1500 LBS or 4 2 Locations
locations x 750 LBS
D.Spacing of Joist 76" O.C. or 24" O.C. 16" O.C. D.
E.Joist Overhang/Cantilever E.
(Max allowed 25%of Joist See Table 507.6 8" - approx. 9%
Span)
F. Beam Size 6"x10 6" x 10" F.
G. Beam Overhang G.
(Max allowed 25%of beam See Table R507.5(2) 9" Approx. 10%
Span)
H. Post Size 6"x 6" - 70' tall 4' x 4" - 75�� H.
I. Post Spacing 48" Center- Center 60" Center- Center I.
J. Footing Size Square 18"x 78" - 72"thick. J.
See table 507.3.7
K. Ledger %"lag Screws @ 73" 1/2" [age Screws at 13" K.
SEE PAGE TWO FOR DETAIL LOCATION
The Mason County Deck,stair and landinG detail provides Guidance.
https://www.co.mason.wa.us/forms/Community Dev/deck.pdf
• Lumber used for construction,including ledgers,shall be of naturally durable or preservative treated
wood.
• Hardware and fasteners must be hot-dipped galvanized or stainless steel.
• The included design criteria will not support a hot tub,jacuzzi or P? VIEWS
• Decks using this design will be limited to a single joist span an 1n a eamr��.s, an pe a ncTyj'!tables. C:OM AE
• The deck cannot be supported by a mobile or manufactured homfVIAS®N COUNTY
BUILDING DEPARTMENT
���� Date -a2pl-p?3
E
l
F J
D
� B
K
REVIEWED FOR
u,,-)DE COMPLIANCE
MASON COUNTY
BUILDING DEPARTMENT
`VM1
REVIEWED FOR
CODE COMPLIANCE
MAS N COUNTY
B IT DIN DEPARTMENT
CD Date 6-.24-�3
I � i
t
� �
-LZFO �oskS =3 �. p
QGC 5 e
,� p-A-0�
Deck Footing Size Requirements
Table R507.3.1
Soil bearing Capacity
Live or
Ground Tributary
Snow Load Area 1500 psf
(psf) (sq. ft.) Side of a square Diameter of a round Thickness
footing footing (Inches)
riches inches
5 7 8 6
20 12 14 6
60 Live or 70 40 19 ,,.L._
Ground Snow 60 21 24 8
Load 80 25 28 9
100 28 31 11
120 30 34 12
140 33 37 13
160 35 40 15
a Interpolation permitted,extrapolation not permitted
b Reserved
c Footing dimensions shall allow complete bearing of the post
d. If the support is a brr*or CMU pier,the footing shall have a minimum 2-inch projection on all sides.
e Area.in square feet of deck surface supported by post and footings.
f Minimum thickness shall only apply to plain concrete footings
12'MIN MANUFACTURED POST CONNECTOR
IN ALLOWABLE SOILS TYRCAI PT POST
'1 12
j GRADE
■
T f
DIAMETER
DEPTH PER TABLE THROUGH BOLTS
PER TAB&E N BOTH D,RECTUNS
MINIMUM 17
NOTE NOT SCREWS
OF EEMBEDMENTBEDBEDMENT
REVIEWED FOc .
,,"'.)DE COMPLIANCE
MASON COUNTY
'!GILDING DEPARTMENT
s
MASON COUNTY
COMMUNITY SERVICES
Building,Planning,Environmental Health,Community Health
2018 International Residential Code for single-story decks.
The 2018 International Residential Code Section R507 contains additional
information and details specific to deck construction.
New or existing Open guards on decks more than 30 inches above grade or floor below shall
Light required have members spaced so that a 4 inch diameter sphere cannot pass through.
Guard Openings for required Stairway Notes:
guards on the sides 1. Stairways shall be not less than 36'in width.
of stair treads shall 2. Stairway risers shall be no greater than 7 314".
not allow a 4 318' 3. Stairway treads shall have a minimum run of 10'.
I 4. The length of Run and the height of Riser shall not
( diameter sphere to vary more than 318'in the run of the stair.
pass through. 6. Stairs are required to be illuminated.
36'min. 6. Open risers are permitted if the opening is less
height t than 4".
7. Tread nosing shall be not less than 314"but not
more than 1-114"on stairways with solid risers.
Except when treads are 11'or more.
8. Composite materials may require additional
stringers.
Deck
34-38"above
Less than nosing's
6"dia. Handrail(See Details)
1
Guard required if 10'min.ru
more than 30' from nosing
to nosing
Landing same
Open risers 36'Min. width of stairs
Less than 4'Ll }
7 314'max.rise Finished grade
Deck Footing Size Requirements
Table R507.3.1
Soil bearing Capacity
Live or
Ground Tributary
Snow Load Area 1500 psf
(Psf) (sq. ft.) Side of a square Diameter of a round Thickness
footing footing (Inches)
Inches inches
5 7 8 6
20 12 14 6
60 Live or 70 40 18 20 6
Ground Snow 60 21 24 8
Load 80 25 28 9
100 28 31 11
120 30 34 12
140 33 37 13
160 1 35 40 15
a, Interpolation permitted,extrapolation not permitted.
b. Reserved.
c. Footing dimensions shall allow complete bearing of the post.
d. If the support is a brick or Ch4U pier,the footing shall have a minimum 2-inch projection on all sides.
e. Area,in square feet,of deck surface supported by post and footings.
f. Minimum thickness shall only apply to plain concrete footings,
17 MIN MANUFACTURED POST GONNECTOR
IN ALLOWABLE SOILS
TYP".CAL PT POST
12
GRADE ,j
} -7
DIAMETER
DEPTH y .- PER TABLE THROUGH BOLTS
PER TABLE IN BOTH DIRECTIONS MINIMUM 12"
NOTE.NOT SCREWS OF EMBEDMENT
Code Re uirement Code Reference
All wood must be pressure treated or of natural resistance to decay. IRC R317.1
Fasteners, hangers, nails, etc„ must be stainless steel, hot-dipped galvanized, or as IRC R317.3.1
specifically required for the specified wood preservative used.
Lateral connection is required to resist overturning IRC R507.5.1
Ledger boards must be attached with structural wood screws to the building and all IRC R507.2
connections between the deck and dwelling must be flashed with metal flashing. Hold- IRC R507.2A
down tension ties shall be installed in not less than 2 locations_
Joists are of appropriate size to support imposed loads. The span of a joist is measured
from the centerline of bearing at one end of the joist to the centerline of bearing at the IRC R507.5
other end of the joist and does not include length of the overhangs. Use Table 1 to
determine joists an based on lumber size and joistspacing.
All decks,. balconies or porches, open sides of landings and stairs which are more than
30"above grade or a floor below must be protected by a guardrail not less than 36"high
(42"for commercial or common areas of multi-family dwellings). Open guardrails and IRC R312
stair railings require intermediate rails or an ornamental pattern such that a ball 4" in
diameter cannot pass through.
Footings are of appropriate size to support imposed loads and extend a minimum of 12"
below grade. See Table 1 for footingsizes. IRC 403.1.4
Columns and posts exposed to the weather or to water splash must be supported by
and connected to concrete piers or metal pedestals projecting above grade. Columns IRC R317.1.2
and posts in contact with the ground or embedded in concrete or masonry must be of IRC R317.1.4
special pressure treated wood approved for ground contact.
Positive connections required to secure posts to beams. IRC R507.7.1
Decks should not overhang beams by more than '/.the actual adjacent span, nor should IRC R507.5
beams overhang posts by more than '/.the actual beam span at the ends unless a IRC R507.6
specific design is calculated_ Floor joist spacing at 24"on center requires 2x decking, IRC R507.4
and floor joistspacing at 16"on center requires 1 Y.actual thickness.
Deck stairs(exterior stairways)shall be provided with a source of illumination at the top IRC R303.8
landing, controlled from within the dwelling or by automatic means.
Typical Handrail Elevation- IRC Section 311.7.8
Handrails are continuous for
the full length of the flight.
Handrails may be interrupted
by a newel post at a turn, Wal
Handrails are
required on not `
less than one -.
side of each Handrail ends returned
co°+tnuous run of to the wall or terminated
trews or flightin newel posts or safety
wath four or more terminals
users.
The height of the
handrail is measured
vertically from the
Sloped plane adjoining
the tread nosing.
TABLE R507.4 DECK POST HEIGHT
Maximum Deck Post Heighta
(feet-inches)
L((Psf)b Post Species` Sized Tributary Areag,'
(sq.ft.)
20 40 60 80 100 120 140 160
4 x 4 14-0 10-10 8-7 7-0 5-8 4-1 NP NP
Douglas Fire, 4 x 6 14-0 13-10 11-1 9-5 8-2 7-3 6-4 5-4
Hem-fire, 6 x 6 14-0 14-0 14-0 14-0 14-0 13-3 10-9 6-11
60 Live SPFe
Load, 8 x 8 14-0 14-0 14-0 14-0 14-0 14-0 14-0 14-0
:560 Redwoodr 4 x 4 14-0 10-3 7-0 NP NP NP NP NP
Ground
Snow Western 4 x 6 14-0 13-6 10-6 8-4 5-10 NP NP NP
Load Cedarsf, 6 x 6 14-0 14-0 14-0 14-0 11-11 NP NP NP
Ponderosa 8 x 8 14-0 14-0 14-0 14-0 14-0 14-0 14-0 14-0
Pinef,
Red Pinef
For SI:1 inch=25.4 mm,1 square foot=0.0929 m2,1 pound per square foot=0.0479 kPa,NP=Not permitted.
a. Measured from the underside of the beam to top of footing or pier.
b. 10 psf dead load.Snow load not assumed to be concurrent with live load.
C. No.2 grade,wet service factor included.
d. Notched deck posts shall be sized to accommodate beam size per in accordance with Section R507.5.2.
e. Includes incising factor.
f. Incising factor not included.
g. Area,in square feet,of deck surface supported by post and footing.
h. Interpolation permitted.Extrapolation not permitted.
Deck Ledger Attachment Details & Specifications
❑Lag screws and bolts shall be staggered per diagram below.
❑Lag screw tips shall extend beyond the inside face of the band/rim joist.
❑Maximum gap between band/rim joist and ledger shall be 1/2"with spacer(s)
❑Flashing shall be installed to prevent water intrusion at structural attachment.
❑Deck Ledger shall be minimum 2"x 8" pressure preservative treated, No. 2 grade lumber.
(IRC Section R507.9.1.1)
❑Deck ledger shall not be supported on stone or masonry veneer.
TABLE R507.9.1.3(1) II
DECK LEDGER CONNECTION TO BAND JOIST
On-Center Spacing of Fasteners'(inches)
Loads Joist
1/24nch diameter lag 1/2-inch diameter bolt
Span' 1/2-inch diameter bolt with
(psf) feet screw with 1/2-inch with 1/2-inch maximum f
(feet)
maximum sheathing°,' sheathings 1-inch maximum sheathing
6 22 36 35
60 Live 8 16 31 26
Load or 10 13 25 21
70 Ground 12 11 20 17
Snow
Load 14 9 17 15
16 8 15 13
18 7 13 11
For SI: 1 inch=25.4 mm, 1 foot=304.8 mm, 1 pound per square foot=0.0479 kPa.
a. Interpolation permitted. Extrapolation is not permitted.
b. Ledgers shall be flashed in accordance with Section R703.4 to prevent water from contacting the house
band joist.
c. Dead load= 10 psf.Snow load shall not be assumed to act concurrently with live load.
d. The tip of the lag screw shall fully extend beyond the inside face of the band joist.
e. Sheathing shall be wood structural panel or solid sawn lumber.
f. Sheathing shall be permitted to be wood structural panel,gypsum board,fiberboard, lumber or foam
sheathing. Up to 1/2-inch thickness of stacked washers shall be permitted to substitute for up to 1/2 inch of
allowable sheathing thickness where combined with wood structural panel or lumber sheathing.
TABLE R507.9.1.3(2)
PLACEMENT OF LAG SCREWS AND BOLTS IN DECK LEDGERS AND BAND
JOISTS
Minimum End and Edge Distances and Spacing Between Rows
Top Edge Bottom Edge Ends Row Spacing
Ledgera 2 inchesd 3/4 inch 2 inchesb 1 5/8 inchesb
Band Joist° 3/4 inch 2 incheSe 2 inchesb 1 5/8 inchesb
For SI: 1 inch=25.4 mm
a. Lag screws or bolts shall be staggered from the top to the bottom along the horizontal run of the deck
ledger in accordance with Figure R507.9.1.3(1).
b. Maximum 5 inches.
c. For engineered rim joists,the manufacturer's recommendations shall govern.
d. The minimum distance from bottom row of lag screws to the top edge of the ledger shall be in accordance
with Figure R507.9.1.3(1).
e. The 2 inches may be reduced to 3/<inch when the band joist is directly supported by a mudsill,a header or
by double top wall plates.
STAGGER FASTENERS
!v IN 2 ROWS
T 5_5'M1N_ 2 X Ir *DISTANCE SHALL HE PERMITTED TO
5"F=1 aX 8,5'M[N.FOR 2 x 1q BE REDUCED Tt34.5'IF LAD SCREWS
T.5'M1W FOR 2 x 12 ARE USED OR 900 SPACING 19
REDUCED TO THAT OF LAG SCREWS
TOATTACH 2 X 8 LEDGERS TO 2 X 8
2`! 1h3. BAND JOISTS.
LE ER- LAG SCREW OR SMT 3d#"WN.
FIGURE R507.9.1.3(1')PLACEMENT OF LAG SCREWS AND BOLTS IN LEDGERS
EXTERIOR SHEATHING
EXISTING STUD WALL ►
EXISTING 2x BAND JOIST
OR ENGINEERED RIM BOARD
2"MIN. DECK JOIST
1 s/a"MIN.
5"MAX. LAG SCREWS OR BOLTS
2"MIN.
O 0 0
FLOOR FRAMING O o
.c�jo.a ..o
JOIST HANGER
O 'P .
EXISTING o 0
FOUNDATION WALL �'
Deck Attachment for Lateral Loads
FIGURE R507.9.2(1) and FIGURE R507.9.2(2)
HOLD-DOWN OR SIMILAR
TENSION DEVICE Hold down tension devices
FLOOR SHEATHING NAILING AT shall be installed in not less
6'MAXIMUM ON CENTER TO
JOIST WITH MOLD-DOWN than two locations per
deck,within 24 inches of
end of the deck.Each
+ + + I + + + device shall have an
+ + + + allowable stress design
I capacity of not less than
fIITI 1,500 pounds.
FLOOR JOIST J DECK JOIST
SHEATHING
MOTE: SIDING
THIS DETAIL IS APPLICABLE FLASHING FOR
WHERE FLOOR JOISTS ARE WATER TIGHTNESS
PARALLEL TO DECK JOISTS.
DECKING
APPROVED JOIST HANGERS
2'MIN. 2x LEDGER WITH FASTENERS
04 ACCORDANCE WITH TABLE R507.9.1.30)
HOLD-DOWN DEVICE MIN 750 LB.CAPACITY
FLOOR JOISTS AT 4 LOCATIONS,EVENLY DISTRIBUTED
ALONG DECK AND ONE WITHIN 24'OF EACH
END OF THE LEDGER,HOLD-DOWN DEVICES
SHALL FULLY ENGAGE DECK JOIST PER
HOLD-DOWN MANUFACTURER_
A FULLY THREADED 31*'DIAMETER LAG
SCREW PREDRILLED Wt MIN.3"PENETRATION
TO CENTER OF TOP PLATE.STUDS,OR HEADER.
R507.9.2 Deck lateral load connections. Lateral loads shall be transferred to the ground or
to a structure capable of transmitting them to the ground.Where the lateral load connection is
provided in accordance with Figure R507.9.2(1),hold-down tension devices shall be installed in not
less than two locations per deck,within 24 inches of each end of the deck.Each device shall have an
allowable stress design capacity of not less than 1500 pounds(6672 N). Where the lateral load
connections are provided in accordance with Figure R507.9.2(2),the hold-down tension devices shall
be installed in not less than four locations per deck,and each device shall have an allowable stress
design capacity of not less than 750 pounds(3336 N).
Exception:Decks not more than 30 inches above grade at any point may be unattached.
TABLE R507.5(2)
MAXIMUM DE%-*14 BEAM SPAN
60 PSF LIVE LOAD c
Deck Joist Spana,i(feet)
Beam 6 8 10 12 14 16 18
Beam Species° size Maximum Beam Spana,b,f(feet-
inches)
— - 1-2x6 3-8 3-1 2-8 _2-4 2-2 2-0 1-10
1-2x8 5-0 4-1 3-6 3-1 2-10 2-7 2-5
1-2x10 6-1 5-2 4-6 4-0 3-7 3-4 3-2
1-2x12 7-1 6-1 5-5 4-10 4-5 4-1 3-10
2-2x6 1 5-6 4-9 4-3 3-10 3-5 3-1 2-10
2-2x8 7-5 6-5 5-9 5-0 4-6 4-1 3-9
Douglas fir-larch9, 2-2x10 9-0 7-10 7-0 6-4 5-9 5-2 4-10
Spruce-pine-firs 2-2x12 10-6 9-1 8-1 7-5 6-10 6-4 5-10
3-2x6 6-11 6-0 5-4 4-11 4-6 4-2 3-10
3-2x8 9-3 8-0 7-2 6-6 6-1 5-6 5-0
3-2x10 11-4 9-10 8-9 8-0 7-5 6-11 6-5
3-2x12 13-2 11-5 10-2 9-4 8-7 1 8-1 7-7
1-2x6 6-9 3-2 2-9 2-5 2-2 2-0 1-11
1-2x8 4-10 4-2 3-7 3-2 2-11 2-8 2-6
1-2x10 5-10 5-1 4-6 4-1 3-8 3-5 3-3
1-2x12 6-10 5-11 5-3 4-10 4-5 4-2 3-11
2-2x6 5-7 4-10 4-4 3-11 3-6 3-2 2-11
Redwood'', Western 2-2x8 7-1 6-2 5-6 5-0 4-7 4-2 3-10
Cedars', Ponderosa 2-2x10 8-8 7-0 6-9 6-2 5-8 5-4 4-11
Pine', Red Pine' 2-2x12 10-1 8-9 7-10 7-2 6-7 6-2 5-10
3-2x6 6-8 6-1 5-5 5-0 4-7 4-3 3-11
3-2x8 8-9 7-9 6-11 6-4 5-10 5-5 5-2
3-2x 10 10-11 9-5 8-5 7-8 7-2 6-8 6-3
3-2x12 12-8 10-11 9-9 8-11 8-3 7-9 7-3
For SI:1 inch=25.4 mm,1 foot=304.8 mm,1 pound per square foot=0.0479 kPa,1 pound=0.454 kg.
a. Interpolation permitted.Extrapolation not permitted.
b. Beams supporting a single span of joists with or without cantilever.
C. Dead load=10 psf,UA=360 at main span,UA=180 at cantilever.Snow bad not assumed to be concurrent with live
bad.
d. No.2 grade,wet service factor included.
e. Beam depth shall be equal to or greater than the depth intersecting joist for a flush beamconnection.
f. Beam cantilevers are limited to the adjacent beam's span divided by4.
9. Includes incising factor.
h. Incising factor not included.
i. Deck joist span as shown in Figure R507.5.
RIM PRii�VMTY PfU64A#tY
STRUCTURE S T PUC's URE
FOR CAi�TILEVEREO
JOISTS
BLOCKING OR
OTHER LATERAL. LEDGER LEDGER
RESTRAINT
REOLHREO OVER BOARD JOIST
BOARD
BEAM
JOIST Y JOISTS
.kOiSTSEIR REAM N,At3END
GER
tiAN sER > EACH END
SEANt �>
POST(£EYONO) )/f POST(BEYOND) /
+ JOIST SPAN a,T SPAN MEASURQ__
CENTERLB+EE TO CENTERLINE
COP EVER OFj STHANGERS
CANTILEVERED JOISTS WITH DROPPED BEAM JOISTS WITH FLUSH BEAM
RIM
FOR CANTILEVERED JOISTS
BLOCKING OR OTHER
LATERAL RESTRAINT
REWRELI OVER SEAM r—.SST
J'1
op
14
t
SST INGER
SEAM 'A'+ JE?R
° BEAM EACH END
POST(BEYOND) POST(BEYOND)
---► .—W-- JOIST SPAN JOIST S'AIN MEA.r"URED3
OPTIONALOPTiOftAt CENTERUNE TO CENTERLI E
CANTILELLtER CANTILEVER OF ILNSTx !HERS
JOISTS ON FREE-STANDING DECK JOISTS ON FREE-STANDING DECK
NTH DROPPED BEAM WITH FLUSH SEAPA
DECKING MATERIAL TYPE AND MAXIMUM ON-CENTER SPACING
NOMINAL SIZE Decking perpendicular to Decking diagonal to
joist joist(a)
1 '/4- inch-thick wood 16 inches 12 inches
2-inch-thick wood 24 inches 16 inches
Plastic composite In accordance with Section In accordance with
R507.2 Section R507.2
(a) Maximum angle of 45 degrees from perpendicular for wood deck boards.
TABLE R507.6
MAXIMUM DECK JOIST SPANS
Allowable Joist Spanb,° Maximum Cantileverf,9(feet-inches)
Loada Joist Joist (feet-inches)
(psf) Species' Size
Joist Spacing(inches) Adjacent Joist Back Span9(feet)
12 16 24 4 6 8 10 12 14 16 18
60 Live Douglas fir- 2x6 7-11 7-1 5-9 1-0 1-6 NP NP NP NP NP NP
Load or larche,
70 Hem-fire, 2x8 10-5 9-5 7-8 1-0 1-6 2-0 2-1 NP NP NP NP
Ground Spruce- 2x10 13-3 11-6 9-5 1-0 1-6 2-0 2-6 2-8 NP NP NP
Snow pine-fire
Load 2x12 15-5 13-4 10-11 1-0 1-6 2-0 2-6 3-0 3-3 NP NP
Redwood', 2x6 7-4 6-8 5-10 1-0 1-4 NP NP NP NP NP NP
Western
Cedars', 2x8 9-8 8-10 74 1-0 1-6 1-11 NP NP NP NP NP
Ponderosa 2x10 12-4 11-0 9-0 1-0 1-6 2-0 2-6 2-6 NP NP NP
Pine',
Red Pine' 2x12 14-9 12-9 10-5 1-0 1-6 2-0 2-0 3-0 3-0 NP NP
For SI: 1 inch=25.4 mm, 1 foot=304.8 mm,1 pound per square foot=0.0479 kPa, 1 pound=0.454 kg,NP=Not permitted.
a. Dead load=10 psf dead load.Snow load not assumed to be concurrent with live load.
b. No.2 grade,wet service factor included.
C. L/A=360 at main span.
d. L/A=180 at cantilever with 220-pound point load applied to end.
e. Includes incising factor.
f. Incising factr not included.
g. Interpolation permitted.Extrapolation not permitted.
SAFETY GLAZING:
Glazing where the bottom GLAZING NOT REGULATED
exposed edge of the glazing BY SECTION R308.4.6
is less than 36 inches
above the plane of the
adjacent walking surface of
stairways, landingsEl
between flights of stairs / ,', SAFETY
and ramps shall be ,%,- GLAZING
SAFETY !
considered a hazardous S LAZING f 'X
location. [IRC R308.4.6] <36 INCHES ',',
Glazing adjacent to the +�'� ,1' <36 INCHES
landing at the bottom of a
stairway where the glazing
is less than 36 inches LANDING
above the landing and
within a 60 inch arc measured
from the bottom tread shall
be considered a hazardous location.
[IRC R308.4.7]