HomeMy WebLinkAboutFIR2023-00027 - FIR Permit / Conditions - 9/26/2023 STAND-ALONE 13-D SPRINKLER SYSTEM INSPECTION REPORT FIR Z,�2� v00 7 ADDRESS FIRM ROUGH-IN/HYDRO INSPECTION Inspector Date /211/212 1 . Piping Installed per approved plans? Yes ✓ No 2. If "No" did the plans deviate enough to require "As Builts"? Yes No 3. Hydro test (At normal operating pressure for 2 hours) 11.2.1.1 Start date i Z2 End date i Z,51_ 4. Are hangers sufficient to secure pipe? 7.4 Yes ✓ No 5. Is attic piping tented with insulation (min R-15)? 7.7 Yes ✓ No 6. If required, did Bucket Test deliver GPM needed? fps Heads 1) (2)/I NA 7. Hydro/Rough-In Inspection Passed Yes ✓ No Date Corrected Comments /Vra- � :f��;r FINAL INSPECTION Date /i Inspector 1,.,Q1 r 1 . Spare Heads & Wrench with BOX (2 of each when 2 or more are used) Yes ✓ NO 2. Main drain (min '/2") valve present? 7.2.1 Yes ✓ No 3. Concealed head covers removed (only req. if ceiling is painted)? Yes No ✓ NA 4. Shut-off valve controls domestic 7.1.1(Only if interconnected)? Yes NO N/A ✓ 5. Does shut-off valve have required sign? 6.3.4 Yes ✓ No (Permanent metal"Sprinkler System Shut-off Valve") 6. Is shut-off valve "locked" in open position w/zip-tie? Yes ✓ No 7. Heads unobstructed by lights, ceiling fans, beams, etc. Yes ✓ No 8. "Calc" plate present with required pressures/K-factor? Yes ✓ No 9. Pass Final Inspection Yes ✓ No If no, pass date Comments ry Page of CALCULATION WORKSHEET Contractor Phone Job Location 'Z4iSZz.? W N4x2'1, Begin Node (D. End Node V Flow in GPM % Pipe Type/Size ! ���►'°UG FITTINGS & PIPE Quantities ft/equiv. Total 90 El = Start Pressure..................I........... T-Bend — Loss to Elev. ft.x,434 = T-Run a Pressure Loss to Flow Switch Coupling ,�, >t Pressure Loss to Water Meter Total Fitting Length Total Pipe Length 48 r,— Subtotal 16— x ���`' (factor) — Z 32- Total Node Pressure Loss Proceed to Next Node Begin Node O End Node 0 Flow in GPM Pipe Type/Size 4XV-4G FITTINGS & PIPE Quantities ftlequiv. Total 90 El = Start Pressure 2,� Z T-Bend Jr = Loss to Elev, ft. x.434 3 T-Run / — Pressure Loss to Flow Switch 2 Coupling = Z Pressure Loss to Water Meter _ 'J Total Fitting Length Zo Total Pipe Length Subtotal x 'aa!"41) (factor) = Z � Total Node Pressure Loss !l/- 2 3 Page of CALCULATION WORKSHEET Contractor Phone Job Location Begin Node / End Node D Flow in GPM Pipe TypelSize FITTINGS & PIPE Quantities ftlequiv. Total 90 El = Start Pressure..............................AlIZ2 T-Bend — Loss to Elev. ft.x.434 Z T-Run � = 7 Pressure Loss to Flow Switch 3 6) r 7✓ Coupling — Pressure Loss to Water Meter v�tje, �o Total Fitting Length Z 5,/ Total Pipe Length D Subtotal x y (factor) Total Node Pressure Loss Z� Z Proceed to Next Node Begin Node End Node Flow in GPM Pipe Type/Size FITTINGS & PIPE Quantities ft/equiv. Total 90 El = Start Pressure 26=Z T-Bend = Loss to Elev. ft. x.434 T-Run — Pressure Loss to Flow Switch Coupling = Pressure Loss to Water Meter Total Fitting Length Total Pipe Length Subtotal 2S7i k / 4+ (factor) — Zl2•��Z Total Node Pressure Loss a'A Hydraulic Overview Job Number:CASCA23-1180 Report Description:Residential Joh Design Engineer CASCA23-1180 Michael Agner Job Nary: Plane FA% — Benson Residence 206-953-4843 Ad—t Stae Cetdllna60nAJ anew Nanber _- 24520 N Hwy 101 CASCAFP8331-2 AM-2 - ANJ Hoodsport,WA 98548 Mason County Aaaress 3 Job SMIB.ildmg ---—— — — Kitchen/Living System Density Area of Application 0.059pm/tt2 173ft2(Actual 173ft2) Moat Demanding SpnnkW Date Nwe Sbeams 3 K-Factor 10.00 at 11.111 0.00 Coverage Per SpdnkW Number Of Sp&M—CaW.W 256ft2 2 Ssatem P .Wnund syatam Flow DameiM 48.443 20.08 Total Demand Pressure Resua 20.08 @ 48.443 +9.769(16.8%) Supplies Check Point Gauges Node Name Flow(apm) Hose Flow(gpm) Static(psi) Residual(psi) Identifier Pressure(psil K-Factor(K) Flow(gpm) 100 Water Supply 35.00 60.000 55.000 WASHINGTON STATE � CERTIFICATE OF COMPETENCY FIRE PROTECTION SPRINKLER SYSTEMS i Michael Paul Agner II N 4344-0218-C Level 1 Cascadia Fire Protection,LLC N e i CASCAFP833L2 00 i ce.Elae�i��icer Expires Signature oecass ; 231180-COTTAGE-FP.cad Water Supply at Node 100(35.00,0.00,60.000,55.000) 100 90 80 70 60 Static Pressure 60.000 n 5.00 55.000 50nf'0.08 @ 48. d 40 o_ 30 fiLletm demand curve 20 10 0, .... 0714 21 28 35 42 49 56 63 70 Water flow,gpm 1Lyt,©M.E.P.CAD,Inc. ��AutoSPRINK 2018 v14.3.10.0 8/22/2023 11:57:33AM Page 1 a'1 Hydraulic Summary Job Number..CASCA23-1180 Report Description:Residential , Job Jab Number Design Engineer CASCA23-1180 Michael Agner Job Name: Stile CerEfiglvulioanMNumieer Benson Residence CASCAFP8331-2 Add—t AHJ 24520 N Hwy 101 Mason County Acld—2 Job SibaSutdrp Hoodsport,WA 98548 Kitchen/Living Address 3 Drawing Name — ---- 231180-COTTAG E-F P.cad System Remote Area(s) Most Demanding Sprinkler Data Occupancy Job SURIv 3 K-Factor 10.00 at 11.111 Residential Hose All—nos At 5— _. --� _ Density _ AreadAppitcadw 0.00 0.05gpm/ft' 173ft'(Actual 173ft') Addibonal Hose Supplies Number Of SpMWtva Cekadated Coverage Per Sprnkler Node Flow m 2 256ft' MttoPeak Results:Pressure For Re—Areas)Adjacent To Most Remote Area Right:68.065 Total Hose Screams 0.00 Syatam F Demand Tote)Water Required(Including Hues Albwance) 20.08 20.08 Madmum Pressure Unba—In Loops 0.000 Ma,k,m Velocity Above Ground 6.77 between nodes 99 and 103 Maximum Velocity Under Ground 8.28 between nodes 100 and 99 Volume capacity,of Wet Pipes Volume capacity of Dry Pipes 14.33gal Supplies Hose Flow Static Residual Flow Available Total Demand Required Safety Margin Node Name m) (psi) (psi) (gpm) (psi) oe m (psi) (psi 100 Water Su I 60.000 55.000 35.00 58.212 20.08 48.443 9.769 Contractor Canlracior Number ConmG Name Contact Tide CASCAFP8331-2 Michael Agner Name of Contractor: Ph— Eu 1. Cascadia Fire Protection 206-953-4U3 Address t FAX PO BOX 206 Add—2 E al Puyallup,WA 98371 michaelgcascadiafirepro.com Add—3 vueasbe k,0 M.E.P.CAD,Inc. E AutoSPRINK 2018 v14.3.10.0 8/22/2023 11:57:37AM Page 2 Jill Summary Of Outflowing Devices Job Number:CASCA23-1180 Report Description:Residential Actual Flow Minimum Flow K-Factor Pressure Device m m K (psi Sprinkler 101 10.00_ _ ___ 10.00 3 11.111 Sprinkler 102 10.08 _ 10.00 3 11.280 b Most Demanding Sprinkler Data ( ,0 M.E.P.CAD,Inc. 111 AutoSPRINK 2018 04.3.10.0 8/22/2023 11:57:46AM Page 3 �+ Node Analysis Job Number:CASCA23-1180 �J Report Description:Residential Node Elevation Foot Fittings Pressure(psi) Dischar e m 100 -3'-6 S 48.443 20.08 101 _ _ _ 9'-0 S r-11.111 11.111 10.00 102 9'-0 S r-11.280 11.280 10.08 99 2'-6 BaIV 16.601 103 — 9'-6 T 5'-0,T 1'-0 11.168 �j,©M.E.P.CAD,Inc. +;Vy AutoSPRINK 2018 v14.3.10.0 8/22/2023 11:57:49AM Page 4 AN Hydraulic Analysis Job Number:CASCA23-1180 Report Description:Residential Pipe Type Diameter Flow Velocity HWC_ _ Friction Loss Length Pressure Downstream Elevation Discharge K-Factor Pt Pn Fittings Eq.Length Summary Upstream Total Length ea•••••Route 1•••• DR 1.1010 10.00 3.37 150 _ 0.018874 8'-6 Pf 0.274 101 91-0 10.00 3 11.111 Sprinkler, 6'-0 Pe -0.217 103 9'-6 11.168 T(5'-0),Tr(1'-0) 14'-6 Pv BL 1.1010 20.08 6.77 _ _ 150 0.068517 27'-0 Pf 2.398 103 9'-6 10.08 11.168 Flow(q)from Route 2 8'-0 Pe 3.035 99 2'-6 16.601 3Tr(1'-0),T(V-0),BaIV 35'-0 Pv UG 0.9950 20.08 8.28 150 0.112177 256'-0 Pf 29.241 99 2'-6 16.601 4'-8 Pe 2.601 100 -3'-6 48.443 2E(2'-4),S 260'-8 Pv 0.00 Hose Allowance At Source 100 20.08 ea•••••Route 2••••• DR 1.1010 10.08 3.40 150 0.019139 0'-6 Pf 0.105 102 9'-0 10.08 3 11.280 Sprinkler, 5'-0 Pe -0.217 103 9'-6 11.168 T(5'-0) 5'-6 Pv Equivalent Pipe Lengths of Valves and Fittings(C=120 only) C Value Multiplier Actual Inside Diameter 4.87 Value Of C 100 130 140 150 ( Schedule 40 Steel Pipe Inside Diameter ) =Factor Multiplying Factor 0.713 1.16 1.33 1.51 �{ ©M.E.P.CAD,Inc. iYy AutoSPRINK 2018 04.3.10.0 8/22/2023 11:57:52AM Page 5 �M1 Hydraulic Analysis Job Number:CASCA23-1180 Report Description:Residential Pipe Type Diameter _ Flow Velocity HWC Friction Loss Length Pressure Downstream Elevation Discharge K-Factor Pt Pn Fittings Eq.Length Summary Upstream Total Length Pipe Type Legend Units Legend Fittings Legend AO Arm-Over Diameter Inch ALV Alarm Valve BL Branch Line Elevation Foot AngV Angle Valve CM Cross Main Flow gpm b Bushing DN Drain BaIV Ball Valve DR Drop Discharge gpm DY Dynamic Velocity fps BFP Bacflow Preventer Y BV Butterfly Valve FM Feed Main Pressure psi C Cross Flow Turn 90° FR Feed Riser Length Foot cplg Coupling MS Miscellaneous Friction Loss psi/Foot Cr Cross Run OR Outrigger HWC Hazen-Williams Constant CV Check Valve RN Riser Nipple Pt Total pressure at a point in a pipe DeIV Deluge Valve SP Sprig DPV Dry Pipe Valve ST Stand Pipe Pn Normal pressure at a point in a pipe E 90°Elbow UG Underground Pf Pressure loss due to friction between points EE 45`Elbow Pe Pressure due to elevation difference between indicated Eel 11'/.°Elbow points Ee2 22Y:°Elbow Pv Velocity pressure at a point in a pipe f Flow Device fd Flex Drop FDC Fire Department Connection fE 90°FireLock(TM)Elbow fEE 45'FireLock(TM)Elbow flg Flange FN Floating Node fT FireLock(TM)Tee g Gauge GloV Globe Valve GV Gate Valve Ho Hose Hose Hose HV Hose Valve Hyd Hydrant LtE Long Turn Elbow mecT Mechanical Tee Noz Nozzle P1 Pump In P2 Pump Out PIV Post Indicating Valve PO Pipe Outlet PrV Pressure Relief Valve PRV Pressure Reducing Valve red Reducer/Adapter S Supply sCV Swing Check Valve SFx Seismic Flex Spr Sprinkler St Strainer T Tee Flow Turn 90' Tr Tee Run U Union WirF Wirsbo WMV Water Meter Valve Z Cap �{ ©M.E.P.CAD,Inc. 41'11 AutoSPRINK 2018 04.3.10.0 8/22/2023 11:57:52AM Page 6 Bulletin 006 January 2020 Rel ® Model RFC Series Residential Sprinklers Flat Concealed Pendent cULus Listed Features Alm • cULus Listed as Residential Sprinklers • Push-On cover plate installation i • Low water flow requirements Product Description Model RFC Series residential sprinklers are flat cover plate, concealed pendent sprinklers intended for installation in Model RFC30&RFC30LL Model RFC43&RFC43LL accordance with NFPA 13, NFPA 13R, or NFPA 13D. The sprinklers are cULus Listed as Residential Sprinklers in ac- cordance with UL 1626. In addition, Model RFCLL Series sprinklers are cULus Certified for Health Effects to NSF/ANSI , + . standard 61 Annex G(LL)and Australian WaterMark Certified (WMCS). Model RFC30 sprinklers have a 165°F (74°C) temperature rated fusible-link operating element. Model RFC43, RFC49, RFC58,and RFC76 sprinklers are offered with either a 1650F (74°C) or 212OF (100°C) temperature rated fusible-link oper- ating element. Sprinklers with a 1650F (74°C) temperature Model RFC49&RFC49LL Model RFC58 rating are ordinary temperature classification and are listed for use with a 1350F (57°C) temperature rated cover plate. Sprinklers with a 212OF (100°C) temperature rating are inter- mediate temperature classification and are listed for use with a 1650F(74°C)temperature rated cover plate. Model RFC Series sprinklers are installed with a Model RFC or Model G5 Cover Plate. Model G5 Cover Plates may be installed by either pushing or threading the cover plate into the sprinkler cup.Model RFC30,RFC30LL,RFC43,RFC43LL, RFC49 and RFC49LL sprinklers allow 1/2" (13 mm) of cover plate adjustment. Model RFC58 and RFC76 sprinklers allow 3/4" (19 mm) of cover plate adjustment. Model RFC and G5 Model RFC76 Model RFC&G5 Cover Plate Cover Plates are available in a variety of finishes as listed in Table H. 10611 Nominal K-Factor Max.Coverage Area Listings& Sprinkler Identification ' Sprinkler Model gpm/psi'/2(1/min/bar'g ft x ft(m x m) Approvals Number(SIN) RFC30 3.0(43) 14 x 14 (4.3 x 4.3) cULus RA0611 RFC30LL 3.0(43) 14 x 14(4.3 x 4.3) cULus, LL,WMCS RA3211 RFC43 4.3(62) 20 x 20(6.1 x 6.1) cULus RA0612 RFC43LL 4.3(62) 20 x 20(6.1 x 6.1) cULus, LL,WMCS RA3212 RFC49 4.9(71) 20 x 20(6.1 x 6.1) cULus RA0616 RFC49LL 4.9(71) 20 x 20(6.1 x 6.1) cULus, LL,WMCS RA3216 RFC58 5.8(84) 20 x 20(6.1 x 6.1) cULus RA0613 RFC76 7.6(109) 20 x 20(6.1 x 6.1) cULus RA0618 cULus:cULus Listed to UL1626,Residential Sprinklers for Fire Protection Service. LL:cULus Certified for Health Effects to NSF/ANSI Standard 61 Annex G(Less than 0.25%Lead content). WMCS:Australian WaterMark Certified. www.reliablesprinkler.com ModelRFC3 1 & RFC30LL •- • 1 16 11 Technical Specifications Sensitivity Style:Flat Concealed Pendent Fast-response Threads:1/2"NPT or ISO 7-1 R1/2 Nominal K-Factor:3.0(43 metric) Temperature Rating ti....... Max.Working Pressure:175 psi(12 bar) 165'F(74'C)sprinkler tr Min.Spacing:8 ft.(2.4 m) 1350F(57°C)cover plate Material Specifications Cover Plate , Thermal Sensor:Nickel Alloy Solder Link Model RFC Cover Plate Sprinkler Body:Brass Alloy Model G5 Cover Plate Levers:Bronze Alloy Yoke:Brass Alloy Sprinkler Wrench Sealing Assembly:Nickel Alloy with PTFE Model FC(without wrench-able cap) Load Screw-Bronze Alloy Model W3(with wrench-able cap) Towers:Copper Alloy Pins:Stainless Steel Listings and Approvals cULus Listed to UL 1626 Deflector:Bronze Alloy Bottom View Cup:Steel cULus Certified for Health Effects to NSF/ANSI Standard 61 Annex G(RFC30LL only) Cover Plate Finishes Watermark Certified(RFC30LL only) , (See Table H) Model RFC30&RFC30LL Sprinkler Components and Dimensions 2-5/16"(58 mm) Threads Dia. Body Cup�\ Tower 1-3/4"(44 mm)+/-1/4"(6 mm) Fusible Link Nominal face of fitting to ceiling Deflector(retracted) 3/16'(5 mm) ....... ....... Pin(extended) i Deflector(extended)� } Model G4/G5 Cover Plate 3-5/16"(84 mm)Dia. Ceiling Model RFC30 and RFC30LL Sprinkler Hydraulic Design Criteria •• Minimum Flow and Residual Pressure t't Max.Coverage Area(2) Flow Pressure ft.x ft. gpm psi (m x m) (1/min) (bar) 12 x 12 9 (3.6 x 3.6) (34) (0.62) 14 x 14 10 11.0 (4.3 x 4.3) (38) (0.76) Notes: 1. For NFPA 13 installations the flow per sprinkler must be the greater of:(1)the flow listed in Table B above and(2)the flow required to achieve a minimum design density of 0.1 gpm/sq ft over the design area of the sprinkler. 2. For coverage area dimensions less than those listed above,use the minimum required flow for the next larger max.coverage area listed. Bulletin 006 el�abl Page 2 of 8 January 2020 www.reliablesprinkler.com ,► Cover Plate FinishesM Standard Finishes Special Application Finishes White Polyester Off White Paint Black Paint Raw Brass Chrome Plated Bright Brass Finished Bronze Black Plated Satin Chrome Stainless Steel Clad(3) Custom Color Paint(2) Notes: 1. Paint or any other coating applied over the factory finish will void all approvals and warranties. 2. Custom color paint is semi-gloss,unless specified otherwise. 3. Stainless steel clad cover plates are Type 316 Stainless Steel on the finished side and C102 Copper Allow on the backside.Cover plates are not listed or approved as corrosion resistant. Installation Dimensions - Recommended Min.to Min.to Max. Sprinkler Cover Cover Plate Hole Diameter Cover Plate Max. Face Dropped Deflector Cover Plate Plate Diameter Adjustment of Fitting to Distance below Temperature Model Model inch(mm) in Ceiling inch(mm) Ceiling0l, Ceiling Rating inch(mm) inch(mm) inch(mm) RFC30, RFC or 3-5/16 2-5/8 1/2 1-1/2 to 2 1/2 to 1 1350F RFC30LL G5 (84) (67) (13) (38 to 51) (13 to 25) (57°C) RFC43, 1350F(2) RFC43LL, RFC or 3-5/16 2-5/8 1/2 1-1/2 to 2 1/2 to 1 (57°C) RFC49, G5 (84) (67) (13) (38 to 51) (13 to 25) or 1650F(3) RFC49LL (74-C) 1350F(2) RFC58, RFC or 3-5/16 2-5/8 3/4 1-1/2 to 2-1/4 1/4 to 1 (57°C) RFC76 G5 (84) (67) (19) (38 to 57) (6 to 25) or 1650F(3) (74°C) Notes: 1. Face of fitting to ceiling dimensions are based on a nominal thread make up.Verify dimensions based on fitting and thread sealing method prior to installation.A 1/2"x 1/2"brass nipple extension(Reliable P/N 6999991900)is available where necessary for replacement of existing sprinklers. 2. For use with 165°F(74°C)temperature rated sprinklers where the Maximum Ceiling Temperature does not exceed 100°F(3800). 3. For use with 212OF(100°C)temperature rated sprinklers where the Maximum Ceiling Temperature does not exceed 150°F(660C). Installation Model RFC series sprinklers are intended to be installed in Do not exceed the maximum recommended torque. Exceeding accordance with NFPA 13,NFPA 13R,or NFPA 13D,as well as the maximum recommended torque may cause leakage or the requirements of applicable authorities having jurisdiction. impairment of the sprinkler.Use care when inserting or removing Model RFC series sprinklers must not be installed in ceilings with the wrench from the sprinkler to avoid damage to the sprinkler. positive pressure in the space above.Ensure that the 4 slots in the cup are open and unobstructed following installation. Model Install the cover plate by hand by pushing the cover plate into the RFC series sprinklers are shipped with a wrench-able protective cup and turning the cover in the clockwise direction until it is tight cap that should remain on the sprinkler until the sprinkler system against the ceiling. is placed in service following construction. Model RFC series sprinklers can be installed without removing Application the wrench-able protective cap using the Model W3 wrench. Model RFC series sprinklers are intended for installation where Alternatively,Model RFC series sprinklers can be installed using residential sprinklers are permitted or required by NFPA 13, the Model FC wrench by temporarily removing the protective cap NFPA 13R, and NFPA 13D.The sprinklers are concealed during installation of the sprinkler.The use of any other wrench to pendent residential sprinklers, installed Model RFC series sprinklers is not permitted and may damage the sprinkler. Fully insert the Model W3 wrench over Model RFC 30 and RFC30LL sprinklers are available in the cap until it reaches the bottom of the cup,or the Model FC ordinary temperature classification for installation where wrench over the sprinkler until the wrench engages the body. the Maximum Ceiling Temperature does not exceed 100OF Do not wrench any other part of the sprinkler/cup assembly.The (38°C). Model RFC43, RFC43LL, RFC49, RFC49LL, RF058, Model W3 and FC wrenches are designed to be turned with a and RFC76 sprinklers are available in either ordinary or standard 1/2"square drive.Tighten the sprinkler into the fitting intermediate temperature classification for installation where after applying a PTFE based thread sealant to the sprinkler's the Maximum Ceiling Temperature does not exceed 100OF threads. Recommended installation torque is 8 to 18 ft-Ibs(11 (38°C)or 150°F(66°C), respectively. to 24 N-m)for 1/2"thread sprinklers and 14 to 20 ft-Ibs(19 to 27 N-m)for 3/4"thread sprinklers. Bulletin 006 Reliabl Page 7 of 8 January 2020 www.reliablesprinkler.com AMF Model FC Model W3 For use with Model RFC Series sprinklers For use with Model RFC Series sprinklers without wrench-able cap installed with wrench-able cap installed Maintenance Guarantee Model RFC series sprinklers should be inspected and the For the Reliable Automatic Sprinkler Co., Inc.guarantee,terms, sprinkler system maintained in accordance with NFPA 25. Do and conditions,visit www.reliablesprinkler.com. not clean sprinklers with soap and water,ammonia or any other cleaning fluids. Remove dust by gentle vacuuming. Replace Patents any sprinkler cover plate assembly which has been painted (other than factory applied)or damaged in any way. A stock of Model RFC30, RFC30LL, RFC43, RFC43LL, RFC49, RFC49LL, spare sprinklers should be maintained to allow quick replace- RFC58,and RFC76 sprinklers are covered by U.S. Patent No. ment of damaged or operated sprinklers. Prior to installation, 9,248,327 and U.S. Patent No. 7,275,603. sprinklers should be maintained in the original cartons and packaging until used to minimize the potential for damage to Model RFC30, RFC30LL, RFC43 and RFC43LL sprinklers are sprinklers that would cause improper operation or non-oper- additionally covered by U.S. Patent No. 8,776,903. ation. Listings and Approvals Ordering Information Listed by Underwriters Laboratories, Inc. and UL Certified for Specify the following when ordering. Canada to UL1626, Residential Sprinklers for Fire-protection Service(cULus). Sprinkler • Model (RFC30, RFC30LL, RFC43, RFC43LL, Certified by Underwriters Laboratories, Inc. and Underwrit- RFC49, RFC49LL, RFC58, RFC76) ers Laboratories of Canada for Health Effects to NSF/ANSI • Temperature Rating Standard 61 Annex G (LL)(RFC30LL, RFC43LL, and RFC49LL Cover Plate only). • Model RFC or G5 • Temperature Rating Australian WaterMark Certified (RFC30LL, RFC43LL, and • Finish (See Table H) RFC49LL only). Sprinkler Wrench • Model FC • Model W3 v z co 0 N m Bulletin 006 eliabl Page 8 of 8 January 2020 www.reliablesprinkler.com Pipe • • Fig. 24 - Hanger for CPVC Plastic Pipe & IPS Steel Pipe** ®TOLCO Double Fastener Strap Side Mounted (cooper B-Line 83183) c@us Size Range: 3/4" (20mm)thru 2" (5omm)CPVC pipe LISTED Material: Pre-Galvanized Steel Function: Intended to perform as a hanger to support CPVC piping used in automatic fire sprinkler systems. Can be installed on the top or on the bottom c -of a beam. ` Approvals: Underwriters Laboratories Listed in the USA(UL) and ' Canada(cUL)to support fire sprinkler piping. May be installed in wood using fasteners supplied with product, or into minimum 20 gauge(0.912mm)steel using (2) 1/4" x 1"tek type screws. Meets and exceeds the requirements of NFPA 13, 13R and 13D. Features: Fig. 24 incorporates features which protect the pipe and ease installation.The flared edge design protects the CPVC pipe from -� any rough surface. Easily attaches to the building structure using the 1 two UL Listed hex head self threading screws*furnished with the product. It is recommended that rechargeable electric drills fitted with a hex socket attachment be used as installation tools. No impact tools(such as a hammer)are allowed. Damage has been known to result from installations using impact type tools. No pre-drilling of a pilot hole in wood is required. B Finish: Pre-Galvanized B Order By: Figure number and pipe size A Hardened hex head self threading screw is furnished with the product and is the minimum fastener size acceptable. "With reduced spacing, consult factory. CPVC Max.Hanger Fastener Hex Approx. ,• 0i 24-3/4 3/4" (20) 25/16" (58.7) 15/32" (27.8) 13/16" (30.2) 51/2 (1.67) 5/16" (7.9) 9 (4.1) 24-1 1" (25) 25/8" (66.7) 15/16" (33.3) 13/16" (30.2) 6 (1.83) 5/16" (7.9) 9 (4.1) 24-11/4 11/4" (32) 3" (76.2) 11/2" (38.1) 13/16" (30.2) 61/2 (1.98) 5/16" (7.9) 11 (5.0) 24-11/2 11/2" (40) 31/4" (82.5) 15/8" (42.3) 13/16" (30.2) 7 (2.13) 5/16" (7.9) 12 (5.4) 24-2 1 2" 1 (50) 311/16" 1 (93.7) 127/32" (43.6) 13/16" (30.2) 8 (2.44) 5/16" (7.9) 1 15 (6.8) Fig. 25 - Surge Restrainer c&us n Size Range: — One size fits 3/4" (20mm)thru 2" (40mm)pipe. f LISTED m Ba Material: — Pre-Galvanized Steel N Function: — Designed to be used in conjunction with Fig. 200 band f hangers to restrict the upward movement of piping as it occurs during sprinkler head activation or earthquake type activity.The surge restrainer is easily and efficiently installed by snapping into a locking position on the band hanger. This product is intended to satisfy the requirements as indicated in the National Fire Protection Association NFPA 13, 2010 1 edition, 9.2.3.4.4.1 and 9.2.3.4.4.4 Can be used to restrain either steel ., pipe or CPVC plastic Pipe. " Approvals: — Underwriters Laboratories Listed only when used with band hanger Fig. 200, in the USA(UL)and Canada(cUL). Finish: Pre-Galvanized Order By: Figure number and band hanger, size from 3/4" (20mm)thru 2" (40mm). Patent#5,344,108 All dimensions in charts and on drawings are in inches.Dimensions shown in parentheses are in millimeters unless otherwise specified. 01 COOPS B-Line