Loading...
HomeMy WebLinkAboutFIR2024-00006 - FIR Permit / Conditions - 11/12/2024 Mason County Fire Marshal 615 W. Alder St. Shelton WA 98584 Phone: 360-427-9670 x 309 ilk Fire Alarm Certification/Final Test FIR Location: Z30"/ 0, Contractor: /' .;moo Phone #: ze ?z,, Contact: Test Date: CHECKLIST Verify panel is in "Normal" condition and clear of any signals Kill Power At Electrical Panel ✓ AC Trouble/ No Power i panel & verify dedicated circuit, red breaker& lockout Activate device(s), verify it activates the alarm and shows correctly on the panel ✓ Check the Notification Alarm Circuit (NAC) for activation of devices. Walk building while alarm is activated under battery load. Check for all lights and sounds to be in-sync Silence Alarm Activate a few other devices in different areas to verify alarm reactivates after being silenced ✓ Reset Alarm ✓ Does panel still show trouble (due to AC power)? ✓ Disconnect Signal Loop Circuit(SLC) to create/verify a trouble for each device on circuit Reconnect SLC. System should reset & only AC trouble showing �n �L Disconnect the communication line & verify communication trouble �3,;� �r Do batteries AMP/HR match plans? (Z - 55 AMPAIR) FACP Sign on Door(s) leading to panel location? Notification Device Device Test Log Time Comments Smoke detector at FACP 917 N"c%- Waterflow Inspector's Test l� Tamper Switch N/q Manual pull at Manual pull at Manual pull at kl 'Q�t�L`1Qx ✓/%a, .. Z Heat Detector ZZ, u , , q Z Heat Detector Heat Detector 5?32- Heat Detector Smoke Detector Smoke Detector Smoke Detector pa.,,/ Punch List/Comments: Sys sw a���i1�/S �w� l � i��cxrs�`or� arc zkfa� �rn� 4 Passed Final Test? Yes No cosco Fire Protection WCC Transformer& Switch Project Flame Detector Compliance COSCO Fire Protection has tested and inspected the new installation of the FSL100 flame detectors at the "WCC Transformer& Switch"project as according to the commissioning document provided by Honeywell. There are two exceptions that have been taken on the commissioning document. 99—Check the cable screening is correctly bonded to the controller. #10—Check that armored conduit is earthed(grounded)but isolated from the cable screen. Per the FSL100 Technical Handbook page 15 section 5.2 titled"Cabling Recommendations", armored field cable is recommended but not required. COSCO Fire Protection did not install armored conduits in this installation. Please see the attached manual section indicating that armored field cable is a recommendation and not a requirement. Digitally signed by Dustin Squires Q DN:C=US,E=dsquires@coscofire.com, Dustin S g U i IYY G S o=cosco Fire Protection,oU=Alarm& Detection Manager,CN=Dustin Squires Date:2024.11.08 07:34:22-08'00' 2501 SE Columbia Way,STE 100 Vancouver,WA 98661 call(360)883-6383 fax(360)883-6390 www.coscofire.com FIRE PROTECTION AND LIFE SAFETY SPECIALISTS INSTALLATION 5 Electrical Installation 5.1 Power Supply Typical Cable Data Maximum Cable Length(L) Cable size Cable resistance Metres Feet (cross sectional area) S2/km(f2/mile) 0.5 mmZ-20 AWG 36.8(59.2) 245 808 1.0 mmZ-17 AWG 19.5(31.4) 462 1516 1.5 mmZ=16 AWG 12.7(20.4) 709 2326 Table 1. FSL100 Cable Data Note: Safety margins should include an allowance for resistance changes due to changes in T ambient over time. I.e. Higher temperature=higher resistance,while resistance may increase due to oxidation or loss of ductility over time. 5.2 Cabling Recommendations The FSL100 Flame Detector is supplied fitted with a suitable gland. For example,three core copper cable,with screen(90%coverage)and suitable mechanical protection(i.e.insulated steel wire armour)to suit M20 gland entry. The maximum conductor size for the terminals is 1.5 mmZ(16 AWG). Ensure the cable gland is installed correctly and fully tightened.All unused cable/conduit entries must be sealed with a suitable certified sealing plug. 5.3 Earth (Ground) Regimes Please note: • Controllers should be connected to protective earth(ground)via an isolator switch that cannot disconnect the earth line. • Field cable screens should be connected to instrument earth(ground)in the controller only.The other end of the field cable screen shall be cut and isolated. • Field cable armour/conduit shall be insulated from the cable screening and earthed(grounded). • Avoid earth(ground)loops at all times. MAN0987_Iss 2 09/16 15 FSL100 Series Flame Detectors Technical Handbook Testing FSL100 Flame Detectors Commissioning: Carry out the following steps before the flame detector is activated for the first time and in conjunction with the associated Controller or PLC's Technical Manual: 1.Satisfy yourself that the chosen FSL100 is the correct choice for this situation, location and controller. 2. Clean the FSL100 window using a microfiber glass cloth or optical wipe. 3. Check the terminals, seals and cable gland, and then close and secure the FSL100 housing. 4. Check position and alignment. 5. Check if there are potential false alarm sources in the field of view and shield if necessary. 6.Thoroughly tighten the cable gland and all fasteners. 7. Check the cabling in between the FSL100 and the controller. 8. Check the controller is electrically safe(isolator, protective earth(ground)etc.) 11.Test the manual self-test by shorting FSL100 terminals 1 &14 for approximately 5 seconds. 12. Perform a functional test with the FSL100-TL or FSL100-TLX test lamp even if the manual test was ok. 13. If satisfied,and when all detectors are commissioned and tested, set the Controller or PLC to normal operation. dV, UWI R, IR3 Flame Detectors uV/TR Tl,)J The FSL100 Series of flame detectors from Honeywell delivers robust,fast,and 0"'k, .al' His reliable detection of flaming fires in a wide range of applications. The range consists of UV, UV/IR and IR3 flame detectors. With a large field of view it can All utilize sophisticated sensing and signal analysis to detect a range of different types detect fires quickly while also rejecting false alarms. of fire including hydrocarbon The FSL100 may be small and lightweight for and non-hydrocarbon sources. easy installation but it is designed to work in Available in UV, UWIR and 31R we tough indoor/outdoor environments, as well have your application covered. as potentially explosive atmospheres. Suitable for Many Applications •UV,UV/IR and IR3 available •Hydrocarbon and non-hydrocarbon sources oe�F�r� •Use in potentially explosive atmospheres •Indoor and outdoor operation •High visibility red or discrete white models available Great Performance F S �4'�oGi- •Approved to EN54-10 and FM3260 flame i '94 R detector standards •Comprehensive automatic self test ` • i` •Remote manual self test option Fast& Reliable •High speed sensors and microprocessor •Sophisticated analysis algorithms •Continuous health monitoring •False alarm rejection Reduced Life Cost s*1 •Long life elements K �`�► •Pressure compensation to avoid contamination ,. + a� ♦�+ •2yearwarranty •Buywith confidence Ease of Installation and Use •Relay and mA outputs as standard •Lightweight GRP housing •Pre-formed knockouts •Optional swivel mounting bracket •Long range test lamp available FSL100-UV • Suitable for indoor applications; for Flame Detector example fume hoods and hydrogen storage areas • Effective solution for materials burning with low temperatures, e.g. Sulphur FSL100-UV • Alarms to fires from heavy hydrocarbons (wood, paper, petroleum, etc.), light hydrocarbons Honeywell (methanol, methane, etc.), and hydrogen • Good resistance against the influences of: - Direct and reflected sunlight -Artificial light, such as fluorescent tubes and glass covered halogen lamps •y j k dLr�` e i F µ h .s FSL100-UWIR • Analysis of the flame flicker-frequency Flame Detector for improved false alarm rejection • Dual sensing methodology enables a wide range of hydrocarbon and non-hydrocarbon fires to be effectively detected • Good resistance against the influences of: FSt-70o-uwR - Direct and reflected sunlight -Artificial light, such as fluorescent tubes HoneyHoneywell and glass covered halogen lamps well -Arcs and electric discharges (static or from e.g. electric motors) -The radiation from electric welding provided that the electric welding takes place at a distance more than 10 feet from the flame detector(a welding rod contains organic compounds which may produce a small flame) t �II � as FSL100-IR3 • Analysis of the flame flicker frequency Flame Detector for improved false alarm rejection • Particularly suited to liquid • hydrocarbon and dirty fires • • Affected less by window contamination or smoky fires FSLI00-IR3 • Good resistance against the influences of: Honeywell - Direct and reflected sunlight -Artificial light, such as fluorescent tubes and glass covered halogen Lamps -Arcs and electric discharges (static or from e.g. electric motors) -The radiation from electric welding provided that the electric welding takes place at a distance more than 10 feet from the flame detector(a welding rod contains organic compounds which may produce a small flame) • Especially suitable fires that emit Large amounts of smoke 14 APPLICATIONS APPLICATION* UV UV/1R IR3 Aircraft hangars ✓ ✓✓ Atriums ✓ ✓✓ Battery storage rooms/data communication ✓ ✓✓ Biogas __ ✓ ✓✓ Car,bus,tram and train parking ✓ ✓✓ Clean rooms semi-conductor,pharmaceutical,&hospital operating rooms ✓ ✓✓ CNG filling/refilling for buses(public transportation) ✓✓ ✓✓ Cold storage ✓✓ Electric power transformers ✓✓ ✓ Engine test celLs/rooms ✓ ✓✓ ✓✓ Fume hoods ✓✓ ✓ Gas cabinets ✓ ✓✓ ✓ Gas/Gasoline engine rooms ✓ ✓✓ ✓✓ Heating rooms for chemicals Of✓ ✓ Indoor chemical,fuel,and solvent storage ✓ ✓✓ ✓ Indoor hydrocarbon storage and processing ✓ ✓ ✓✓ Indoor hydrogen storage and processing ✓✓ Of✓ Laboratories ✓ ✓✓ ✓ Loading and unloading terminals:truck,rail,&marine ✓✓ ✓✓ Monitoring of machinery ✓ ✓✓ ✓✓ Oil and Gas pipe line and pumping stations ✓ ✓✓ Outdoor chemical,fuel,paint,and solvent storage ✓ ✓✓ Outdoor hydrogen storage and processing ✓✓ Paint spray booths ✓✓ Radio amplifier rooms/Isolators for antennas ✓✓ Recycling and waste processing plants ✓ ✓✓ Suitable ✓ Recommended ✓✓ *Please contact your regional sales representative to discuss your application r. M GENERAL SPECIFICATION 00 SERIES FLAME DETECTORS FSL100 Flame Detector types FSL100-UV,FSL100-UVIR and FSL100-IR3;Choice of red orwhite housings Range i 110 ft/35 m(IR3),25 m/80 ft(UV,UV/IR)alarming within 10 secondsto a 1 ft2(0.1 mz)n-heptane fire Cone of vision 90`minimum horizontal and vertical Power 10-28 VDC(12-24 VDC nominaU • Continuous green:normal operation Local LEDs • Continuous yellow:fault • Flashing yellow:Fault and guide to repeat self-test after a self-test failure • Continuous red:alarm Standard available 4-20 mA(stepped,sinking,non-isolated) 0 mA power fault/microprocessor fault Current output 2 mA optical fault 4 mA normal operation >20 mA alarm Relay output De-energized during normal operation,no alarm,SPDT,30 VDC-2 A,60 W max.Energised during normal operation,no fault, Alarm relay SPDT,30 VDC-2 A,60 W max -Fault relay Cable gland&terminals Cable entry M 20 clearance.Supplied with gland suitable for cable diameter from 0.2'(5.5mm)to 0.5'(13mm).Terminals suitable for 0.5mm (20AWG)to 1.5mm (15AWG)wire Start up times <10 sec Alarm response time 8 to 30 sec Alarm output settings Selectable LEDs and relays latching/non-latching;factory setting:latching Automatic 6 manual Self-Test Automatic Sensor Test(built in Self-Test)and manual Self-Test Operating current normal Current in alarm,at 24 VDC ±75 mA at 24 VDC • Fire control panels using end of line(EOL)and alarm resistors(current increase) Connections to: Devices that operate via relay switched outputs PLCs with 4-20 mA inputs To be adjusted to the fire control panel;free terminals are dedicated to the resistors End of line and alarm resistor Note:the alarm and EOL resistor must be rated 2 W min.each and the total power dissipation of both alarm and EOL resistor should not exceed 2 W Housing Glass Reinforced Polyester(GRP),Non-incendive.UV resistant,Self-Extinguishing V-0(UL-94) Swivel Mount PA66,UV resistant;Stainless Steel fixings;280 g(0.62 lb) Pressure compensating element PCE(Pressure Compensating Element)avoids moisture build-up in the detector housing due to changes in ambient air-pressure Dimensions 4.9 x 3.15 x 2.25 in(125 x 80 x 57 mm) Weight 1.05 lb(465 g) Ingress protection IP65 Temperature,operating -40°F to+158'F(-40°C to+70'C) Temperature,ambient ATEX and FM class 3611 -13'F to+158'F(-25'C to+70'C) �1 Honeywell INDUSTRIAL FIXED FSL100 Flame Detectors FSL100 Flame Detectors Overview Fhma Ua{a<tn FA 100-WM� Honeywell Honeywell's FSL100 range of Light Industrial/Commercial Flame Detectors enables simple coverage of fire hazard areas across many fire hazard applications.Installation,set-up and operation are simple.Wide solid area coverage and fast speed of response omtimize safety. With inbuilt automatic test and test lamps available to cover all models,reliability is ensured. Product Overview: The newest Optoelectronic flame detector for a wide range of Light Industrial fire detection from Honeywell Analytics. A range of middle market Optical Flame Detectors joining the HA FSX High End products.Addresses a wide range of fire protection applications both indoors and outdoors.With 3 versions to cover a wide range of flaming fires:Ultraviolet(UV),Ultraviolet/Infrared(UV/IR) and Triple Infrared(IR3). Detects wide range of Hydrocarbon&Non-Hydrocarbon firesDetecting a wide range of Hydrocarbon and Non-Hydrocarbon flaming fires means that many application areas can be addressed. Wide viewing angleOptical detection of radiant energy in a solid angle Field of View enables coverage of a large risk area.Simple optional mounting bracket allows the FSL100 to be installed and aligned covering the hazard. Fast responseFar faster than other technologies,by responding to flaming fires in seconds enabling a more rapid response to danger before the fire can escalate. FM Classl,2&3 Div2Can be installed indoors or outdoors and in Hazardous areas typically looking into a Div 1 area from a distance. FM 3260 performance certCertified to FM 3260 for flame Detector performance. Relay and current output(Fault and Alarm)Analog stepped output and Alarm/Fault relays for simple connectivit . Inbuilt Automatic Test and Simple to use Test LampsFSL100 maintains continuous internal health monitoring. operational and Field of View testing. Features&Benefits: • UV,UWIR and IR3 Flame Detectors to cover a wide range of applications • Robust,simple to install&set-up:Wide angle and fast speed of response • Automatic test and test lamps for simple check and maintenance. Quick Speer: FCI 1 nn GI omo ncrcr+nre_1 I\/I IWID a 4 IDQ fnr linhl inrli wtriol annlirohinne 1/3 • 12-14Vdc,25mA nominal operation w, • 4 to 20mA and Relay outputs. ` Fire and Gas Consultancy Services 1,,k Even the best products deserve expert maintenance! Elevate your gas detectors'potential with Honeywell's expert maintenance services!Maximize uptime,eliminate costs,and ensure on-time,on-budget project completion. Explore our fixed,_portable,and high-tech support services now! Specifications BRAND Brand • Honeywell • Notifier CATEGORY Sub-Category • Flame Detectors Product Number FSL100-IR3 Triple IR flame detector.Suitable for ATEX zone 2/22:FM 3611 Class 1:20 Div2EN54-10(HIGH sensitivity)certificateFM3260 approval.Red Housing. FSL100-IR3-W Triple IR flame detector.Suitable for ATEX zone 2/22:FM 3611 Class 1:20 Div2EN54-10(HIGH sensitivity)certificateFM3260 approval.White Housing. FSL100-SM21 FSL100 Optional swivel mount FS1_100-TL FSL100 test lamp:incl universal charger and carrying case:non EX FSL100-TLBT 12V DC Battery for FSL-TL Test Lamp FSL100-TLBU H3 light bulb for FSL-TL test lamp FSL100-TLX FSL100 test lamp:incl.carrying case:intrinsically safe(Pending') FSL100-UV UV flame detector.Suitable for ATEX zone 2/22:FM 3611 Class 1:2&3 Div2EN54- 10(HIGH sensitivity)certificateFM3260 approval.Red Housing 2/3 FSL100-UV-W UV flame detector.Suitable for ATEX zone 2/22:FM 3611 Class 1:2&3 Div2EN54- 10(HIGH sensitivity)certificateFM3260 approval.White Housing. I FSL100-UVIR UV/IR flame detector.Suitable for ATEX zone 2/22:FM 3611 Class 1:2&3 Div2EN54-10(HIGH sensitivity)certificateFM3260 approval.Red Housing. Alternative Products FS20X Flame Detector FS20X Flame Detector FS24X Flame Detector FS24X Flame Detector Honeywell FSL100 Flame Detectors Safety and Productivity ©2024 Honeywell International Inc. Honeywell Solutions All rights reserved. 855 S Mint St Charlotte,NC 28202 800-582-4263 This document was generated on 2024-04-30 11:35:52 AM(YYYY-MM-DD,HH:mm:ss).Subject to change without notice. 3/3 �J NOTIFIER by Honeywell FST-951 Series Intelligent Addressable Heat Detectors The NOTIFIER® FST-951 Series intelligent thermal detectors are designed for both performance and aesthetics, and are direct replacements for the FST-851 Series. A new modern, sleek, con- temporary design and advanced thermal technologies make the FST-951 Series ideal for both system operation and building design. The point ID address, set using rotary decimal switches, provide specific detector locations. The series includes a 135°F/57°C fixed-temperature, rate-of-rise, and a 190°F/88°C fixed high-temperature detectors.These thermal detectors provide effective, intelligent property protection in a variety of applications. Detectors are available for both FlashScan® and I! CLIP applications as designated. Features 1 SLC LOOP: • Two-wire SLC loop connection • Unit uses base for wiring ADDRESSING: Installation • Addressable by device FST-951 Series plug-in intelligent thermal detectors use a detach- Rotary,decimal addressing able base to simplify installation, service and maintenance. Installa- (Refer to the NOTIFIER panel manuals for device capacity.) tion instructions are shipped with each detector. ARCHITECTURE: Mount detector base(all base types)on an electrical backbox which • Designed to meet UL 268 7th Edition is at least 1.5" (3.81 cm) deep. For a chart of compatible junction boxes,see DN-60054. • Sleek, low-profile,stylish design NOTE: Because of the inherent supervision provided by the SLC loop, • State-of-the-art thermistor technology for fast response end-of-line resistors are not required. Wiring 7-taps"or branches are • Integral communications and built-in device-type identification permitted for Style 4(Class`B)wiring only. • Built-in tamper resistant feature When using relay or sounder bases, consult the ISO-X(A) installation sheet 156-1380 for device limitations between isolator modules and iso- • Built-in functional test switch activated by external magnet lator bases. OPERATION: • Fixed temperature model (FST-951) factory preset to 135°F Applications (57°C) Use thermal detectors for protection of property. For further informa- • Rate-of-rise model(FST-951 R),I YF(8.3°C)per minute tion, refer to 156-6522, Applications Manual for System Smoke • High-temperature model FST-951 H) factory preset to 190°F Detectors, which provides detailed information on detector spacing, (88-C) placement,zoning,wiring,and special applications. • 360°-field viewing angle of the two visual alarm indicators, LEDs Construction blink red in Normal condition and turn on steady red in Alarm • LEDs blink every time the unit is polled These detectors are constructed of fire-resistant plastic. The FST- 951 Series plug-in intelligent thermal detectors are designed to com- MECHANICALS: mercial standards and offer an attractive appearance. • Sealed against back pressure • SEMS screws for wiring of the separate base Operation • Designed for direct-surface or electrical-box mounting Each FST-951 Series detector uses one of the panel's addresses • Plugs into separate base for ease of installation and maintenance (total limit is panel dependent)on the NOTIFIER Signaling Line Cir- • Separate base allows interchange of photoelectric,ionization and cuit (SLC). It responds to regular polls from the control panel and thermal sensors reports its type and the status. If it receives a test command from the panel (or a local magnet test), it stimulates its electronics and OTHER SYSTEM FEATURES: reports an alarm. It blinks its LEDs when polled and turns the LEDs • Remote test feature from the panel on when commanded by the panel. The FST-951 Series offers fea- tures and performance that represent the latest in thermal detector • Walk test with address display technology. • Low standby current OPTIONS: • Remote LED output connection to optional RA10OZ remote LED annunciator DN-60975:B•6/26/2019—Page 1 of 3 Product Line Information B200SCOA-WH: White, Intelligent, programmable sounder base in i English/French (required in Canada for ULC applications with CO NOTE:"-IV"suffix indicates CLIP and FlashScandevice. Series detector applications FST-951: White, low-profile intelligent 135°F fixed thermal sensor, B200SCOA-IV: Ivory Intelligent, programmable sounder base in FlashScan only English/French (required in Canada for ULC applications with CO FST-951A: Same as FST-951 but with ULC listing Series detector applications, ULC listing FST-951-IV: Ivory, low-profile intelligent 135°F fixed thermal sensor, B20OS-LF-WH: White, Low Frequency Intelligent, programmable FlashScan and CLIP sounder base. Produces a fundamental frequency of 520 Hz +/- FST-951A-IV: Same as FST-951-IV but with ULC listing 10% with a square wave or its equivalent; designed to meet the NFPA 72 sleeping space requirement. (CSFM: 7300-1653:0238) FST-951R: White, low-profile intelligent rate-of-rise thermal sensor, FlashScan only B200S-LF-IV: Ivory, Low Frequency Intelligent, programmable sounder base. Produces a fundamental frequency of 520 Hz +/- FST-951RA: Same as FST-951 but with ULC listing 10% with a square wave or its equivalent; designed to meet the FST-951 R-IV: Ivory, low-profile intelligent rate-of-rise fixed thermal NFPA 72 sleeping space requirement. (CSFM: 7300-1653:0238) sensor, FlashScan and CLIP B200SR-WH: White, Intelligent sounder base capable of producing FST-951 RA-IV: Same as FST-951 R-IV but with ULC listing sound output with ANSI Temporal 3 or continuous tone. Intended for FST-951 H: White, low-profile intelligent 190°F fixed thermal sensor, retrofit applications. (CSFM: 7300-1653:0213) FlashScan only B200SR-IV: Ivory, Intelligent sounder base capable of producing sound output with ANSI Temporal 3 or continuous tone. Intended for FST-951 HA: Same as FST-951 H but with ULC listing retrofit applications. (CSFM: 7300-1653:0213) FST-951H-IV: Ivory, low-profile intelligent 190°F thermal sensor, B200SRA-WH:Same as B200SR-WH with,ULC listing FlashScan and CLIP FST-951HA-IV Same as FST-951 but with ULC listing B200SRA-IV:Same as B200SR-IV in Ivory color, ULC listing B200SR-LF-WH: White, Low Frequency Intelligent, programmable INTELLIGENT BASES sounder base. Produces a fundamental frequency of 520 Hz +/- NOTE:For details on intelligent bases,see DN-60981. 10% with a square wave or its equivalent; designed to meet the B300-6:White,6"base,standard flanged low-profile mounting base NFPA 72 sleeping space requirement. Intended for retrofit applica- (CSFM: 7300-1653:0109) tions. (CSFM: 7300-1653:0238) B300-6-IV: Ivory,6" base, standard flanged low-profile mounting B200SR-LF-IV: Ivory, Low Frequency Intelligent, programmable sounder base. Produces a fundamental frequency of 520 Hz +/- base(CSFM: 7300-1653:0109) 10% with a square wave or its equivalent; designed to meet the B300A-6: Same as B300-6, ULC listed NFPA 72 sleeping space requirement. Intended for retrofit applica- B300A-6-IV: Ivory, 6" standard flanged low-profile mounting base, tions. (CSFM: 7300-1653:0238) ULC listed MOUNTING KITS AND ACCESSORIES B300-6-BP: Bulk pack of B300-6, package contains 10 TR300:White,replacement flange for B210LP(A)base B501-WHITE: White, 4" standard European flangeless mounting TR300-IV: Ivory, replacement flange for B210LP(A)base base. UL/ULC listed (CSFM: 7300-1653:0109) RA100Z(A): Remote LED annunciator. 3-32 VDC. Mounts to a U.S. B501-BL: Black, 4" standard European flangeless mounting base. single-gang electrical box. For use with B501(A)and B300-6(A). UL/ULC listed (CSFM: 7300-1653:0109) M02-04-00:Test magnet B501-IV: Ivory color, 4" standard European flangeless mounting M02-09-00:Test magnet with telescoping handle base. UL/ULC listed (CSFM: 7300-1653:0109) B501-WHITE-BP: Bulk pack of B501-WHITE contains 10 CK300:Color Kit(includes cover and trim ring),white, 10-pack B224RB-WH:White, relay base(CSFM: 7300-1653:0216) CK300-IV:Color Kit(includes cover and trim ring), ivory, 10-pack B224RB-IV: Ivory, relay base(CSFM:7300-1653:0216) CK300-BL:Color Kit(includes cover and trim ring), black, 10-pack B224RBA-WH:White, relay base, ULC listing B224RBA-IV: Ivory, relay base, ULC listing B224BI-WH:White, isolator detector base(CSFM:7300-1653:0216) B224BI-IV: Ivory isolator detector base(CSFM:7300-1653:0216) B224BIA-WH:White, isolator detector base, ULC listing B224BIA-IV: Ivory isolator detector base, ULC listing B20OS-WH:White, Intelligent addressable sounder base capable of producing sound output in high or low volume with ANSI Temporal 3, ANSI Temporal 4,continuous tone, marching tone,and custom tone. Uses FlashScan protocol. (CSFM: 7300-1653:0213) B20OS-IV: Ivory, Intelligent addressable sounder base capable of producing sound output in high or low volume with ANSI Temporal 3, ANSI Temporal 4,continuous tone,marching tone,and custom tone. Uses FlashScan protocol. (CSFM: 7300-1653:0213) B200SA-WH: Same as B200S-WH, ULC listing B200SA-IV: Same as B200S-IV, ULC listing Page 2 of 3—DN-60975:B-6/26/2019 r SPECIFICATIONS � o 0 Sensitivity: UL Applications: 0.5/n to 4. /o 0 per foot obscuration. ULC is 0.5%to 3.5% Size: 2.0"(5.3 cm)high; base determines diameter —B300-6:6.1"(15.6 cm)diameter —B501:4"(10.2 cm)diameter For a complete list of detector bases see DN-60981 Shipping weight:3.4 oz. (95 g) Operating temperature range: • FST-951, FST_95 ries:—4°F to 100°FA 20°C to 38'C) I • F to 150°F(-20°C to f�b -7, O. D ector spacing: UL approved for 50 ft. (15.24 m) center-to-cen- ter, FM approved for 25 x 25 ft.(7.62 x 7.62 m)spacing / Relative humidity: 10%—93% non-condensing Thermal ratings:fixed-temperature set point 135°F(57°C), rate-of- rise detection 15°F(8.3°C)per minute, high temperature heat 190°F (88°C) Mounting: B300-6(A)Flanged base, included See "Product Line Information: Intelligent Bases," if using a dif- ferent base. ELECTRICAL SPECIFICATIONS Voltage range: 15-32 volts DC peak Standby current(max. avg.):200Nf.@ 24 VDC (one communica- tion every 5 seconds with LED enabled) Max current:4.5 mA @ 24 VDC("ON") Listings and Approvals Listings and approvals below apply to the FST-951 Series detectors. In some cases, certain modules may not be listed by certain approval agencies, or listing may be in process. Consult factory for latest listing status. • UL/ULC Listing:S747 • FM Approved • CSFM:7270-0028:0502 I® e®e�rl�ra�s IIIIITT I/ITEM This document is not intended to be used for installation purposes. We try to keep our product information up-to-date and accurate. We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice. NOTIFIER FlashScant and NOTIFIER:�are registered trademarks of Honeywell 12 Clintonville Road International,Inc. C) Northford,CT 06472 M19 by Honeywell International Inc.All rights reserved.Unauthorized �J NOT 1 F 1 E R 203.484.7161 use of this document is strictly prohibited. www.notifier.com Country of Origin:Mexico by Honeywell �` ,� Sean Hallstrom <seanh@nellc.net> FW: 18-318 1(3-1) WCC MV PH2: New RFI 81 (FIRE ALARM PLANS) Mark Merritt<Mark.Merritt@hargis.biz> Wed, May 22, 2024 at 4:34 PM To: Sean Hallstrom <seanh@nellc.net> Cc: Ron Eliason <Ron.Eliason@hargis.biz> Sean, Per our phone conversation, and my discussion with our mechanical engineer Ron Eliason, the ambient air temperature in the generator room while the generators are running should not be more than the _'. ou"lairternperaft e+ 1(Y degrees. This is because there is so much air being brought through the air intake louvers that open when the generators are running. t s like e t pi # ,� 'n should no be more hoes# 114 degrees can th e.morst ey. Thank You, Mark Merritt Associate, Electrical H A R G I S d . 1.5342 c 425.68 .9965 v v-card J ` Honeywell FarenhytT" Series THE POWER OF CONNECTED L-Series Indoor Horns, Strobes, and Horn Strobes The L-Series audible visible notification products offers the most versatile and easy-to-use line of horns,strobes,and horn strobes in the industry with lower current draws and modern aesthetics. F F With white and red plastic housings,standard and compact I i devices,and plain,FIRE,and FUEGO-printed devices,System R R Sensor L-Series can meet virtually any application requirement. E ' E The L-Series line of wall-mount horns,strobes,and horn strobes include a variety of features that increase their application versatility while simplifying installation.All devices feature plug-in designs with minimal intrusion into the back box,making installations fast and foolproof while virtually eliminating costly and time-consuming ground faults. tW i C'S To further simplify installation and protect devices from _ t construction damage,the L-Series utilizes a universal mounting plate for all models with an onboard shorting spring,so installers can test wiring continuity before the device is installed. INDOOR SELECTABLE-OUTPUT HORNS, STROBES,AND HORN STROBES FOR WALL Installers can also easily adapt devices to a suit a wide range APPLICATIONS of application requirements using field-selectable candela settings,automatic selection of 12-or 24-volt operation,and a rotary switch for horn tones with two volume selections. FEATURES & BENEFITS • Updated Modern • Meets DOD • Automatic selection of Mounting plate • Compatible with Aesthetics specification 12-or 24-volt shorting spring checks System Sensor • Offers small profile requirements operation at 15 and 30 wiring continuity synchronization devices for horns and • Features a plug-in candela before device protocol horn strobes design with minimal • Uses field-selectable installation . Listed for wall • Color lens intrusion into the back candela settings on Supports electrically mounting only attachments for use box wall units:15,30,75, compatible with with clear lens wall or • Horn rated at 88+dBA 95,110,135,185 existing SpectrAlert ceiling strobe at 16 volts Mounting plate for at[ and SpectAlert • Designed with • Supports rotary switch standard and at[ Advance devices tamper-resistant for horn tone and two compact watt units construction volume selections N, L-SERIES SPECIFICATIONS ARCHITECT/ENGINEER SPECIFICATIONS GENERAL L-Series standard horns,strobes,and horn strobes shall mount to a standard 2 x 4 x 1 7/8-inch back box,4 x 4 x 11/2-inch back box, 4-inch octagon back box,or double-gang back box.L-Series compact products shall mount to a single-gang 2 x 4 x 1 7/8-inch back box.A universal mounting plate shall be used for mounting ceiling and wall products for all standard models and a separate universal mounting plate shall be used for mounting wall compact models.The notification appliance circuit wiring shall terminate at the universal mounting plate.Also,L-Series products,when used with the Sync•Circuit'"Module accessory,shall be powered from a non- coded notification appliance circuit output and shall operate on a nominal 12 or 24volts.When used with the Sync-Circuit Module, 12-volt-rated notification appliance circuit outputs shall operate between 8.5 and 17.5 volts;24-volt-rated notification appliance circuit outputs shall operate between 16.5 and 33 volts.Indoor L-Series products shall operate between 32 and 120 degrees Fahrenheit from a regulated DC or full-wave rectified unfiltered power supply.Strobes and horn strobes shall have field-selectable candela settings including 15,30,75,95,110,135,and 185. STROBE The strobe shall be a System Sensor L-Series Model_______listed to UL 1971 and shall be approved for fire protective service.The strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible signaling appliances,flashing at 1 Hz over the strobe's entire operating voltage range.The strobe light shall consist of a xenon flash tube and associated lens/reflector system. HORN STROBE COMBINATION The horn strobe shall be a System Sensor L-Series Model_______listed to UL 1971 and UL 464 and shall be approved for fire protective service.The horn strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements forvisible signaling appliances,flashing at 1 Hz overthe strobe's entire operating voltage range.The strobe light shall consist of a xenon flash tube and associated lens/reflector system.The horn shall have two audibility options and an option to switch between a temporal three pattern and a non-temporal(continuous)pattern.These options are set by a multiple position switch.The horn on horn strobe models shall operate on a coded or non-coded power supply. SYNCHRONIZATION MODULE The module shall be a System Sensor Sync-Circuit model MD L3 listed to UL 464 and shall be approved for fire protective service. The module shall synchronize L-Series strobes at 1 Hz and horns at temporal three.Also,while operating the strobes,the module shall silence the horns on horn strobe models over a single pair of wires.The module shall mount to a 4 11/16 x 411/16 x 2 1/8-inch back box.The module shall also control two Style Y(class B)circuits or one Style Z(class A)circuit.The module shall synchronize multiple zones.Daisy chaining two or more synchronization modules together will synchronize all the zones they control.The module shall not operate on a coded power supply. PHYSICAL AGENCY LISTINGS AND APPROVALS Wall-Mount Dimensions(including tens):5.6" L x 4.7-W x 1.25"D UL:Listed (143 mm L x 119 mm W x 32 mm D) FM:Approved Compact Wall-Mount Dimensions(including tens):5.26"L x 3.46"W CSFM•Listed x 1.93"D(133 mm L x 88 mm Wx 49 mm D) Horn Dimensions:5.6"L x 4.7-W x 1.25" D(143 mm L x 119 mm W x 32 mm D) Compact Horn Dimensions:5.25"L x 3.45"W x 1.25"D(133mm L x 88mm W x 32mm D) ELECTRICAL SPECIFICATIONS Strobe Flash Rate:1 flash per second Nominal Voltage Regulated:12VDC or regulated 24DC/FWR1 Operating Voltage Rangez:8 to 17.5 V(12 V nominal)or 16 to 33 V(24 V nominal) Operating Voltage Range(MDL3)Sync Module:8.5 to 17.5V(12 V nominal)or 16.5 to 33 V(24V nominal) Input Terminal Wire Gauge:12 to 18 AWG ENVIRONMENTAL Standard Operating Temperature:32°F to 120°F(0°C to 49°C) Humidity Range:10 to 93%non-condensing Notes: 1.Full Wave Rectifi ed(FWR)voltage is a non-regulated,time-varying power source that is used on some power supply and panel outputs. 2.P,S,PC,and SC products will operate at 12 V nominal only for 15 and 30 cd. .y UL MAX HORN CURRENT DRAW(mA RMS) UL MAX STROBE CURRENT DRAW(mA RMS) SOUND PATTERN DB 8-17.5V 16-33V CANDELA 8-17.5V 16-33V DC DC FWR DC DC FWR Temporal High 39 44 54 CANDELA 15 88 43 60 Temporal Low 28 32 54 RANGE 30 143 63 83 Non-Temporal High 43 47 54 75 N/A 107 136 Non-Temporal Low 29 32 54 95 N/A 121 155 Non-Temporal Low 29 32 54 110 N/A 148 179 3.1 KHz Temporal High 39 41 54 135 N/A 172 209 3.1 KHz Temporal Low 29 32 54 185 N/A 222 1 257 3.1 KHz Non-Temporal High 42 43 54 3.1 KHz Non-Temporal Low 28 29 54 Coded High 43 47 54 3.1 KHz Coded High 42 43 54 UL MAX CURRENT DRAW(mA RMS),2-WIRE HORN STROBE,CANDELA RANGE(15-115 CD) 8-17.5V 16-33V DCINPUT 15CD 30CD 15CD 30CD 75CD 95CD 110CD 135CD 185CD EM Temp Hi 98 158 54 74 121 142 162 196 245 EM Temp Low 93 154 44 65 111 133 157 184 235 EM Cont Hi 106 166 73 94 160 182 211 262 EM Cont Low 93 156 51 71 119 139 162 190 239 3.1K Temp Hi 93 156 53 73 119 140 164 190 242 3.1K Temp Low 91 154 45 66 112 133 160 185 235 3.lK Cont Hi 99 162 69 90 135 157 175 208 261 3.lK Cont Low 93 156 52 72 119 138 162 192 242 16VFWR SWITCH POSITION 15CD 30CD 75CD 95CD 110CD 135CD 185CD EM Temp Hi 83 107 156 177 198 234 287 EM Temp Low 68 91 145 165 185 223 271 EM Cont Hi 111 135 185 207 230 264 316 EM Cont Low 79 104 157 175 197 235 283 3.1KTemp Hi 81 105 155 177 196 234 284 3.1KTemp Low 68 90 145 166 186 222 276 3.1K Cont Hi 104 131 177 204 230 264 326 3.1K Cont Low 77 102 156 177 199 234 291 HORN AND HORN STROBE OUTPUT(DBA) 8-17.5V 16-33V FWR SWITCH POSITION SOUND PATTERN DB DC DC 1 Temporal High 84 89 89 2 Temporal Low 75 83 83 3 Non-Temporal High 85 90 90 4 Non-Temporal Low 76 84 84 5 3.1 KHz Temporal High 83 88 88 6 3.1 KHzTemporal Low 76 82 82 7 3.1 KHz Non-Temporal High 84 89 89 8 3.1 KHz Non-Temporal Low 77 83 83 9 Coded High 85 90 90 10 3.1 KHz Coded High 84 89 89 L-SERIES DIMENSIONS rt 3.46 1.91 —3.45 For a complete listing of all y compliance approvals and 1.25 1.25 certifications,ptease visit www.farenhyt.com..com. 4 A44 A°A° Microsoft,Windows,and ° 0°000°°°°°A the Windows Logo are 5.27 5.27 ooi°°0000000° registered trademarks or trademarks of A.A.AQA.A�I A�A�A�AeA�o� Microsoft Corporation. A'A'A'A'A'Ah - o Honeywell°and ° System Sensor®are registered trademark Compact Strobe i Horn Strobe compact Horn of and Farenhyt-is a trademark of Honeywell International,Inc. This document is not intended to be used for 4.70 installation purposes.We try to keep our product 1.91 4.70 information up-to 1.25 date and accurate.We 1.25 cannot cover alt specific applications or anticipate alt requirements.All ,54ti46ti specifications are subject 5.67 5.67 to change without notice. For Tec h n i ca l ' Support,Please call i 800-446-6444. Strobe;Horn Strobe Horn L-SERIES ORDERING INFORMATION WALL HORN STROBES HORNS P2RL:2-Wire,Horn Strobe,Red HRL:Horn,Red P2WL:2-Wire,Horn Strobe,White HWL:Horn,White P2GRL:2-Wire,Compact Horn Strobe,Red HGRL:Compact Horn,Red P2GWL:2-Wire,Compact Horn Strobe,White HGWL:Compact Horn,White P2RL-P:2-Wire,Horn Strobe,Red,Plain P2WL-P:2-Wire,Horn Strobe,White,Plain ACCESSORIES P2RL-SP:2-Wire,Horn Strobe,Red,FUEGO TR-2:Universal Wall Trim Ring Red P2WL-SP:2-Wire,Horn Strobe,White,FUEGO TR-2W:Universal Wall Trim Ring,wht SBBRL:Wall Surface Mount Back Box,Red WALL STROBES SBBWL:Wall Surface Mount Back Box,White SRL:Strobe,Red SBBGRL:Compact Wall Surface Mount Back Box, SWL:Strobe,White Red SGRL:Compact Strobe,Red SBBGWL:Compact Watt Surface Mount Back Box, SGWL:Compact Strobe,White White SRL-P:Strobe,Red,Plain Note: SWL-P:Strobe,White,Plain All-P models having a plain housing(no"FIRE SRL-SP:Strobe,Red,FUEGO marking on cover. SWL-CLR-ALERT:Strobe,White,ALERT All-SP models have"FUEGO"marking on cover All-ALERT models have"ALERT"marking on cover For more information Learn more about Honeywell's Farenhyt Series and other products available by visiting www.farenhyt.com Honeywell Security&Fire 12 Clintonville Road Northford,CT 06472 Doc 3515741 Rev B 1 02/18 Honeywell 800-328-0103 ©2018 Honeywell International Inc.