STAND-ALONE 13-D SPRINKLER SYSTEM
INSPECTION REPORT
FIR Zazl�- ADDRESS /J��/�i��l % FIRM
ROUGH-IN/HYDRO INSPECTION Inspector get,�Z __ Date ly z
1 . Piping Installed per approved plans? ���SPdr���//s y�4 V10 Yes y/ No
2. If "No" did the plans deviate enough to require "As Builts"? Yes No
3. Hydro test (At normal operating pressure for 2 hours) 11.2.1.1 Start date1-11LEnd date 1
4. Are hangers sufficient to secure pipe? 7.4 Yes / No
5. Is attic piping tented with insulation (min R-15)? 7.7 Yes �No
6. If required, did Bucket Test deliver GPM needed? Heads 1 T2) NA
7. Hydro/Rough-In Inspection Passed Yes ✓"No Date Corrected
Comments Al Aliv► Flirdwj � 20 X&11l
FINAL INSPECTION Date q 11 2 Inspector rfj(��
1, Spare Heads & Wrench with BOX (2 of each when 2 or more are used) Yes No
2. Main drain (min 1/z") valve present? 7.2..1 Yes No
3. Concealed head covers removed (only req.if ceiling is painted)? Yes No NA V_
4. Shut-off valve controls domestic 7.1.1(Only if interconnected? Yes No N/A
5. Does shut-off valve have required sign? 6.3.4 Yes No
(Permanent metal"Sprinkler System Shut-off Valve")
6. Is shut-off valve "locked" in open position w/zip-tie? Yes � No
7. Heads unobstructed by lights, ceiling fans, beams, etc. Yes y1 No
8. "Calc" plate present with required pressures/K-factor? Yes )/ No
9, Pass Final Inspection Yes �No If no, pass date
Comments
KNIGHT FIRE PROTECTION, INC. Job Name:Central Mason FD Temp Bldg.
9702 LATHROP INDUSTRIAL DRIVE SW KFP Job No. 24-048
OLYMPIA, WA 98512-9188
(360) 786-8606 MATERIAL & TEST
FAX 786-8722 REPORT FOR
ABOVEGROUND PIPING
"ON GUARD LICENSE NO. KNIGHFP044LK
24 HOURS A DAY'
Procedure upon completion of work: Inspection and tests shall be made by the contractor's representative and witnessed by the AHJ.
All defects shall be corrected and system left in service before contractors personnel finally leave the job.
A certificate shall be filled out and ,signed by both representatives. Copies shall be prepared for approving authorities, owners, and
contractor. It is understood the owner's representative's signature in no way prejudices any claim against contractor for faulty
material, poor workmanship, or failure to comply with approving authoritys requirements or local ordinances.
PROPERTY NAME Central Mason F.D. Temp. Building DATE
PROPERTY ADDRESS 1741 E Pickering Rd., Shelton, WA 98584
SYSTEM LOCATION OR ID 1 Wet System (Residential Pump Package)
REVIEWED AND ACCEPTED BY Mason County
PLANS ADDRESS 411 N 5th St., Shelton, WA 98584
INSTALLATION CONFORMS TO ACCEPTED PLANS N YES ❑NO
EQUIPMENT USED IS APPROVED N YES ❑NO
IF NO, EXPLAIN
HAS PERSON IN CHARGE OF FIRE EQUIPMENT BEEN INSTRUCTED AS TO 14 YES ❑NO
INSTRUCTIONS CARE AND MAINTENANCE OF THE NEW EQUIPMENT AND THE LOCATION OF ALL CONTROL VALVES?
HAVE COPIES OF THE FOLLOWING BEEN LEFT ON THE PREMISES:
1. SYSTEM COMPONENT CARE, AND MAINTENANCE INSTRUCTIONS ❑ YES M NO
2. MAINTENANCE AGREEMENT ❑ YES M NO
MAKE MODEL S.I.N. YEAR THREAD K—FACT QTY. TEMP.
RELIABLE RESIDENTIAL PENDENT — CONCEALED RA0616 2024 % ' 4.9K 29 165'
SPRINKLERS
PIPE AND TYPE OF PIPE BLACK STEEL SCHEDULE 40 AND CPVC
FITTINGS TYPE OF FITTINGS THREADED, AND GLUED
WATER FLOW INDICATOR INFORMATION MAXIMUM TIME TO OPERATE
THROUGH TEST CONNECTION
4AFtM LOCATION TYPE c MAKE 'MODEL`,, >. '• MIN. SEC.
DEVICES`, Riser Room Va,e:; iz4 n# .4 Potter
DRY VALVE Q.O.D.
MAKE MODEL SERIAL NO. MAKE I MODEL SERIAL N0.
TIME TO TRIP * TIME WATER ALARM
THROUGH TEST WATER AIR TRIP POINT REACHED OPERATED
DRY PIPE N A CONNECTION PRESSURE PRESSURE AIR PRESSURE TEST OUTLET PROPERLY
OPERATING MIN. SEC. PSI PSI PSI MIN. SEC. YES NO
TEST WITHOUT
Q.O.D.
WITH
Q.O.D.
IF NO, EXPLAIN
* MEASURED FROM THE TIME THE INSPECTORS TEST CONNECTION IS OPENED (OVER)
HYDROSTATIC: HYDROSTATIC TEST SHALL BE MADE AT NOT LESS THAN 200 PSI FOR TWO HOURS OR
50 PSI ABOVE STATIC PRESSURE IN EXCESS OF 150 PSI FOR TWO HOURS. DIFFERENTIAL DRY-PIPE
VALVE CLAPPERS SHALL BE LEFT OPEN DURING TEST TO PREVENT DAMAGE. ALL ABOVEGROUND PIPE
TEST LEAKAGE SHALL BE STOPPED.
DESCRIPTION PNEUMATIC: ESTABLISH 40 PSI AIR PRESSURE AND MEASURE DROP WHICH SHALL NOT EXCEED 1-1/2
PSI IN 24 HOURS. TEST PRESSURE TANKS AT NORMAL WATER LEVEL AND MEASURE AIR PRESSURE
DROP WHICH SHALL NOT EXCEED 1-1/2 PSI IN 24 HOURS.
ALL PIPING HYDROSTATICALLY TESTED AT 200 PSI FOR 2 HRS. IF NO, STATE REASON
TESTS DRY PIPING PNEUMATICALLY TESTED ❑YES ❑NO X N/A
EQUIPMENT OPERATES PROPERLY 0 YES _ ❑NO ❑N/A
KNIGHT FIRE PROTECTION, INC. CERTIFIES THAT ADDITIVES AND CORROSIVE CHEMICALS, SUCH AS
SODIUM SILICATE OR DERIVATIVES OF SODIUM SILICATE, BRINE, OR OTHER CORROSIVE CHEMICALS
WERE NOT USED FOR STOPPING LEAKS.
DRAIN I READING OF GAGE LOCATED NEAR THE RESIDUAL PRESSURE WITH MAIN DRAIN VALVE
TEST MAIN DRAIN: PSI OPEN WIDE PSI
UNDERGROUND MAINS AND LEAD INS TO THE SYSTEM RISERS WERE FLUSHED BEFORE CONNECTION
WAS MADE TO THE ABOVEGROUND SPRINKLER PI
VERIFIED BY UNDERGROUND TEST CERTIFICATE ❑YES JII NO El OTHER EXPLAIN
FLUSHED BY KNIGHT FIRE PROTECTION ❑YES ONO
APPROVING AUTHORITY TITLE DATE
TEST CAPS NUMBER USED LOCATIONS NUMBER REMOVED
WELDED PIPING ❑YES ONO
WELDING IF YES......
KNIGHT FIRE PROTECTION CERTIFIES THAT WELDING PROCEDURES COMPLY
WITH THE REQUIREMENTS OF AT LEAST AWS B2.1 AND D10.9, LEVEL AR-3 18(YES ❑NO
KNIGHT FIRE PROTECTION CERTIFIES THAT THE WELDING WAS PERFORMED BY
WELDERS QUALIFIED IN COMPLIANCE WITH THE REQUIREMENTS OF AT LEAST X YES ❑NO
AWS B2.1 AND D10.9, LEVEL AR-3
KNIGHT FIRE PROTECTION CERTIFIES WELDING WAS CARRIED OUT IN COMPLIANCE WITH A
DOCUMENTED QUALITY CONTROL PROCEDURE TO INSURE THAT ALL DISCS ARE RETRIEVED,
THAT OPENINGS IN PIPING ARE SMOOTH, THAT SLAG AND OTHER WELDING RESIDUE ARE
REMOVED, AND THAT THE INTERNAL DIAMETERS OF PIPING ARE NOT PENETRATED X YES LJ NO
CUTOUTS KNIGHT FIRE PROTECTION CERTIFIES THAT THEY HAVE A CONTROL FEATURE TO ENSURE THAT ALL
(DISCS) CUTOUTS (DISCS) ARE RETRIEVED. YES ❑NO
HYDRAULIC DATAPLATE PROVIDED IF NO, EXPLAIN
DATAPLATE M YES ❑NO
REMARKS DATE LEFT IN SERVICE WITH ALL CONTROL VALVES OPEN:
DOCUMENTS DOES THE OWNER HAVE A COPY OF NFPA #25 FOR THEIR REFERENCE. ❑YES ONO
KNIGHT FIRE PROTECTION, INC. LICENSE# KNIGHFP044LK
ACCEPTANCE PROPERTY REP. TITLE DATE
Aglx •te r' 17 1 t 4 C/
KNIGHT FIRE P OTECT TI�TrLEws� ( fir DA n
Yy a�,.. j/
APP R� ING AUTHORITY `�I�l� TITLE DA E
I CERTIFY THAT THE INFORMATION HEREIN IS TRUE AND THAT THIS SPRINKLER SYSTEM WAS
CERTIFICATION INSTALLED IN ACCORDANCE WITH THE RULES ADOPTED BY THE WASHINGTON ADMINISTRATIVE CODE
AS ADMINISTERED BY THE STATE FIRE MARSHAL.
Frrrr.r�rrrrrrrrrrrrrrrrrrrrrr7
t Expirne WASHINGTON STATE
DEC 91,24 CERTIFICATE OF COMPETENCY I
FIRE SPRINKLER SYSTEMS MARK CANMLL
i Mark A. Cantrell NAME OF CERTIFICATE OF COMPETENCY HOLDER
6657-0415-B-H Level
Knight Fire Protection, Inc. —� <
� KNIGHFP044LK �
9/ 19124 1 SIGNATURE OF CERTIFICATE OF COMPETENCY HOLDER
signatara Data —j 6657-0415-B—H
Urrrr rrrrrr rrrrrrrrw rrrrrrrrwa CERTIFICATE REGISTRATION #
CERTIFICATION STAMP
Page ) of
CALCULATION WORKSHEET
Contractor Phone 3r;0-7fJ�-v`' Job Location -'?y/ 2� --=J:---
Begin Node End Node 0 Flow in GPM Pipe Type/Size
FITTINGS & PIPE
Quantities ft/equiv. Total
90 El = Start Pressure.............................. 70
T-Bend — .6 Loss to Elev. ft.x.434 =
T-Run = / Pressure Loss to Flow Switch
Coupling — Pressure Loss to Water Meter
a
Total Fitting Length (�
Total Pipe Length JL
Subtotal ZZ x °d 1` p (factor)
Total Node Pressure Loss Z 4751'
Proceed to Next Node
i/
Begin Node 0 End Node O Flow in GPM Pipe Type/Size GhYG
FITTINGS & PIPE
Quantities ft/equiv. Total
90 E1 = Start Pressure 7.67,E
T-Bend = Loss to Elev. ft. x.434 =
T-Run — Pressure Loss to Flow Switch
Coupling = Pressure Loss to Water Meter
Total Fitting Length
Total Pipe Length Ili
Subtotal Z x '��` (factor) = Z•��
Total Node Pressure Loss /D'y3
Page of
CALCULATION WORKSHEET
Contractor Phone Job Location
f �
Begin Node End Node Flow in GPM Pipe Type/Size / GPVG
FITTINGS & PIPE
Quantities ftlequiv. Total
90 El = Start Pressure..............................
T-Bend = Loss to Elev. ft.x.434 =
T-Run = Pressure Loss to Flow Switch
Coupling — Pressure Loss to Water Meter
Total Fitting Length
Total Pipe Length
Subtotal Z x 3o 7 (factor) —
Total Node Pressure Loss
Proceed to Next Node
J/
Begin Node 0 End Node 0 Flow in GPM Pipe Type/Size
FITTINGS & PIPE
Quantities ft/equiv. Total
90 El = Start Pressure
T-Bend = Loss to Elev. ft. x.434 =
T-Run = Pressure Loss to Flow Switch _
Coupling = Pressure Loss to Water Meter
Total Fitting Length
Total Pipe Length
Subtotal x 1 (factor)
Total Node Pressure Loss %L).212
Page of
CALCULATION WORKSHEET
Contractor ���=�r �L Phone Job Location /7?1 E ��u��5
i
Begin Node End Node 0 Flow in GPM Pipe Type/Size /— c l�✓G
FITTINGS & PIPE
Quantities ft/equiv. Total
90 El = Start Pressure................... .....
T-Bend - Loss to Elev. ft.x.434 =
li T-Run = Z- Pressure Loss to Flow Switch —
Coupling = Pressure Loss to Water Meter
Total Fitting Length Z
Total Pipe Length LL
Subtotal0 x (factor)
Total Node Pressure Loss
Proceed to Next Node
Begin Node O End Node 0 Flow in GPM Pipe Type/Size �r CMG
FITTINGS & PIPE
Quantities ft/equiv. Total
90 El = Start Pressure
T-Bend = Loss to Elev. ft. x.434 =
T-Run - Pressure Loss to Flow Switch
Coupling = Pressure Loss to Water Meter
Total Fitting Length
Total Pipe Length 2
Subtotal vU x ' (factor) - 383,781)
Total Node Pressure Loss �S � �
Page of
CALCULATION WORKSHEET
Contractor Phone Job Location
v2 � C�l/G
Begin Node End Node Flow in GPM Pipe Type/Size
FITTINGS & PIPE
Quantities ft/equiv. Total
90 El = Start Pressure.............................. �s
T-Bend — Loss to Elev. ft.x.434 77)
�1 T-Run = 1 Pressure Loss to Flow Switch f3•D
/ Coupling / — Pressure Loss to Water Meter
Total Fitting Length
Total Pipe Length
97 Subtotal x �� ' (factor) — \
Total Node Pressure Loss ZO (Z3 f n.gbrr l��S
Proceed to Next Node /
Begin Node O End Node O Flow in GPM Pipe Type/Size
FITTINGS & PIPE
Quantities ft/equiv. Total
90 El = Start Pressure
T-Bend = Loss to Elev. ft.x.434 =
T-Run = Pressure Loss to Flow Switch
Coupling = Pressure Loss to Water Meter
Total Fitting Length
Total Pipe Length
Subtotal x (factor) _
Total Node Pressure Loss
n
II' �11
1
KNI
i
........................ �s7
E>< W. WASHINGTON STATE
QEC 31,24 CERTIFICATE OF COMPETENCY
FIRE SPRINKLER SYSTEMS
Mark A.Cantrell
6657-0415-B-H Level 2
Knight Fire Protection, Inc.
KNIGHFP044LK
6/25/24 i
j Signatara Data j
Knight Fire Protection
9702 Lathrop Industrial Dr. SW
Tumwater,WA 98512
360-786-8606
Job Name : Central Mason Fire&EMS-Portable Bldg.
Drawing : 1 of 1
Location 1741 E Pickering Rd,Shelton,WA 98584
Remote Area 111
Contract 24-048
Data File 24-048 Central Mason Fire& EMS Hyd Calc 111-1.WXF
Knight Fire Protection Page 1
Central Mason Fire & EMS- Portable Bldg. Date 6-25-24 '
HYDRAULIC CALCULATIONS
for
JOB NAME Central Mason Fire & EMS- Portable Bldg.
Location 1741 E Pickering Rd, Shelton, WA 98584
Drawing# 1 of 1
Contract# 24-048
Date 6-25-24
DESIGN
Remote area# ill
Remote area location Common Area
Occupancy classification Residential
Density .05- Gpm/SgFt
Area of application 1024-SgFt
Coverage/sprinkler 256-SgFt
Type of sprinkler calculated 4.9K Res. Pendent
#Sprinklers calculated 4
In-rack demand N/A-GPM
Hose streams N/A-GPM
Total water required(including hose streams) 53.51 -GPM @ 44.50- Psi
Type of system Wet
Volume of system(dry or pre-action) N/A- Gal
WATER SUPPLY INFORMATION
Test date N/A
Location Pump/Storage Tank(By Others)
Source of info Keith Reitz(Central Mason Fire Marshal)
CONTRACTOR INFO Knight Fire Protection
Address 9702 Lathrop Industrial Dr. SW/Tumwater, WA 98512
Phone# 360-786-8606
Name of designer Mark Cantrell
Authority having jurisdiction Mason County
NOTES:
A water storage tank with a minimum capacity of 1,606 gallons
(53.51 GPM x 30 Minutes)shall be provided by the owner. Owner to provide a UL
listed fire pump to provide a minimum of 53.51 GPM @ 44.5 PSI to the remote
sprinklers.
Computer Programs by Hydratec Inc. Revision: 50.5520.727
Water Supply Curve
Knight Fire Protection Page 2
Central Mason Fire & EMS- Portable Bldg. Date 6-25-24
Demand:
D1 - Elevation 3.032
D2 - System Flow : 53.505
D2 - System Pressure 44.502
Hose ( Demand )
D3 - System Demand : 53.505
Safety Margin
150
140
130
P 120
R 110
E 100
S 90
S 80
U 70
R 60
E 50
40
30
20
10
10 20 30 40 50 60 70 80 90
FLOW ( N ^ 1.85 )
Computer Programs by Hydratec Inc. Revision: 50.5520.727
Fittings Used Summary
Knight Fire Protection Page 3
Central Mason Fire & EMS- Portable Bldg. Date 6-25-24
Fitting Legend
Abbrev. Name '/2 '/, 1 1'/< 1'/2 2 2'/2 3 3'/2 4 5 6 8 10 12 14 16 18 20 24
Ball B Ball Milw BB-SC100 2.25 2 2.5 2.25 10
Fsp Flow Switch Potter VSR Fitting generates a Fixed Loss Based on Flow
N* CPVC 90'EII 0 4 5 6 7 9 12 13 0 0 0 0 0 0 0 0 0 0 0 0
O* CPVC Branch Tee 0 3 5 6 8 10 12 15 0 0 0 0 0 0 0 0 0 0 0 0
S NFPA 13 Swing Check 0 0 5 7 9 11 14 16 19 22 27 32 45 55 65
Units Summary
Diameter Units Inches
Length Units Feet
Flow Units US Gallons per Minute
Pressure Units Pounds per Square Inch
Note: Fitting Legend provides equivalent pipe lengths for fittings types of various diameters.
Equivalent lengths shown are standard for actual diameters of Sched 40 pipe and CFactors
of 120 except as noted with *. The fittings marked with a * show equivalent lengths values
supplied by manufacturers based on specific pipe diameters and CFactors and they require no
adjustment. All values for fittings not marked with a*will be adjusted in the calculation
for CFactors of other than 120 and diameters other than Sched 40 per NFPA.
Computer Programs by Hydratec Inc. Revision: 50.5520.727
Flow-Summary - NFPA
Knight Fire Protection Page 4
Central Mason Fire & EMS- Portable Bldg. Date 6-25-24
SUPPLY ANALYSIS
Node at Static Residual Available
Source Pressure Pressure Flow Pressure Total Demand Required Pressure
SRC 0.0 0 0.0 0.0 53.51 44.502
NODE ANALYSIS
Pressure Discharge
Node Tag Elevation Node Type at Node at Node Notes
111 H 8.0 4.9 7.0 12.96 0.05 256
112H 8.0 4.9 7.48 13.4 0.05 256
121 H 8.0 4.9 7.42 13.35 0.05 256
122H 8.0 4.9 7.92 13.79 0.05 256
ill 8.5 6.95
112 8.5 7.44
121 8.5 7.38
122 8.5 7.9
11 8.5 9.58
12 8.5 10.15
TOR 8.5 13.76
BOR 4.5 19.02
FLG 0.5 23.19
SRC 1.0 44.5
Computer Programs by Hydratec Inc. Revision: 50.5520.727
Final Calculations : Hazen-Williams
Knight Fire Protection Page 5
Central Mason Fire & EMS- Portable Bldg. Date 6-25-24
Node1 Elev1 K Qa Nom Fitting Pipe CFact Pt
to or Ftngs Pe ******* Notes ******
Node2 Elev2 Fact Qt Act Eqiv Len Total Pf/Ft Pf
111 H 8 4.90 12.96 1 O 5.0 0.500 150 7.000
to 5.000 -0.217
111 8.500 12.96 1.101 5.500 0.0305 0.168 Vel = 4.37
0.0
111 12.96 6.951 K Factor= 4.92
112H 8 4.90 13.40 1 O 5.0 0.500 150 7.478
to 5.000 -0.217
112 8.500 13.4 1.101 5.500 0.0324 0.178 Vel = 4.52
0.0
112 13.40 7.439 K Factor= 4.91
121 H 8 4.90 13.35 1 O 5.0 0.500 150 7.421
to 5.000 -0.217
121 8.500 13.35 1.101 5.500 0.0322 0.177 Vel = 4.50
0.0
121 13.35 7.381 K Factor= 4.91
122H 8 4.90 13.79 1 O 5.0 0.500 150 7.925
to 5.000 -0.217
122 8.500 13.79 1.101 5.500 0.0342 0.188 Vel = 4.65
0.0
122 13.79 7.896 K Factor= 4.91
111 8.500 12.96 1 16.000 150 6.951
to 0.0
112 8.500 12.96 1.101 16.000 0.0305 0.488 Vel = 4.37
112 8.500 13.40 1 O 5.0 13.830 150 7.439
to 5.000 0.0
11 8.500 26.36 1.101 18.830 0.1134 2.136 Vel = 8.88
0.0
11 26.36 9.575 K Factor= 8.52
121 8.500 13.35 1 16.000 150 7.381
to 0.0
122 8.500 13.35 1.101 16.000 0.0322 0.515 Vel = 4.50
122 8.500 13.79 1 O 5.0 13.830 150 7.896
to 5.000 0.0
12 8.500 27.14 1.101 18.830 0.1197 2.254 Vel = 9.15
0.0
12 27.14 10.150 K Factor= 8.52
11 8.500 26.36 1.25 16.000 150 9.575
to 0.0
12 8.500 26.36 1.394 16.000 0.0359 0.575 Vel = 5.54
12 8.500 27.14 1.25 N 6.0 21.080 150 10.150
to 6.000 0.0
TOR 8.500 53.5 1.394 27.080 0.1332 3.606 Vel = 11.25
0.0
TOR 53.50 13.756 K Factor= 14.42
TOR 8.500 53.51 1.25 Fsp 0.0 4.000 150 13.756
to 4.732 * * Fixed Loss= 3
BOR 4.500 53.51 1.394 4.000 0.1332 0.533 Vel = 11.25
Computer Programs by Hydratec Inc. Revision: 50.5520.727
Final Calculations : Hazen-Williams
Knight Fire Protection Page 6
Central Mason Fire & EMS- Portable Bldg. Date 6-25-24
Node1 Elev1 K Qa Nom Fitting Pipe CFact Pt
to or Ftngs Pe ******* Notes ******
Node2 Elev2 Fact Qt Act Eqiv Len Total Pf/Ft Pf
BOR 4.500 -0.01 1.25 Ball 3.174 4.000 150 19.021
to S 11.11 14.284 1.732
FLG .500 53.5 1.394 18.284 0.1332 2.435 Vel = 11.25
FLG .500 0.0 1.5 100.000 150 23.188
to -0.217
SRC 1 53.5 1.263 100.000 0.2153 21.531 Vel = 13.70
0.0
SRC 53.50 44.502 K Factor= 8.02
Computer Programs by Hydratec Inc. Revision: 50.5520.727
KNIGHT FIRE PROTECTION, INC.
9702 LATHROP INDUSTRIAL DR. SW
OLYMPIA, WA 98512-9188
ISM (360) 786-8606
FAX 786-8722
LICENSE NO. KNIGHFP044LK
Fire Sprinkler System
Equipment Submittal
Central Mason Fire & EMS
Portable Building
1741 E Pickering Rd.
Shelton, WA 98584
KFP Job #24-048
Bulletin 006 December 2021
RL
blmlabld
Model RFC Series Residential Sprinklers
Flat Concealed Pendent
cULus Listed
Features
• cULus Listed as Residential Sprinklers
• Push-On cover plate installation
• Low water flow requirements
Product Description
Model RFC30&RFC30LL Model RFC43&RFC43LL
Model RFC Series residential sprinklers are flat cover plate,
concealed pendent sprinklers intended for installation in
accordance with NFPA 13, NFPA 13R,or NFPA 13D.The
sprinklers are cULus Listed as Residential Sprinklers in
accordance with UL 199. In addition, Model RFCLL Series
sprinklers are cULus certified for Health Effects to NSF/ANSI/
CAN 600,cULus certified less than 0.25%Lead Content to
NSF/ANSI 372 Annex G,and Australian WaterMark certified.
Model RFC Series sprinklers are offered with either a 165°F Model RFC49&RFC49LL Model RFC58
(74°C)or 212°F(100°C)temperature rated fusible-link
operating element.Sprinklers with a 165°F(74°C)temperature
rating are ordinary temperature classification and are listed
for use with a 135°F(57°C)temperature rated cover plate.
Sprinklers with a 212°F(100°C)temperature rating are
intermediate temperature classification and are listed for use
with a 165°F(74°C)temperature rated cover plate.
Model RFC Series sprinklers are installed with a Model G5
cover plate. Model G5 cover plates are installed by pushing the
cover plate into the cup and turning in the clockwise direction
until it is tight against the ceiling. Model RFC30, RFC30LL,
RFC43, RFC43LL, RFC49 and RFC49LL sprinklers allow 1/2" Model RFC76 Model G5 Cover Plate
(13 mm)of cover plate adjustment. Model RFC58 and RFC76
sprinklers allow 3/4"(19 mm)of cover plate adjustment. Model
G5 cover plates are available in a variety of finishes as listed in
Table H.
Nominal K-Factor Max.Coverage Area Listings& Sprinkler Identification
Sprinkler Model gpm/psi12(1/min/bar72) ft x ft(m x m) Approvals Number(SIN)
RFC30 3.0(43) 14 x 14 (4.3 x 4.3) cULus RA0611
RFC30LL 3.0(43) 14 x 14 (4.3 x 4.3) cULus, LL,WMCS RA3211
RFC43 4.3(62) 20 x 20(6.1 x 6.1) cULus RA0612
RFC43LL 4.3(62) 20 x 20 6.1 x 6.1 cULus LL WMCS RA3212
RFC 4.9(71) 20 x 20 6.1 x 6.1 cULus RA0616
RFC49LL 4.9(71) 20 x 20(6.1 x 6.1) cULus, LL,WMCS RA3216
RFC58 5.8(84) 20 x 20(6.1 x 6.1) cULus RA0613
RFC76 7.6(109) 20 x 20(6.1 x 6.1) cULus RA0618
cULus: cULus listed for Safety to ANSI/UL199
LL: cULus certified for Health Effects to NSF/ANSI/CAN 600
cULus certified less than 0.25%Lead Content to NSF/ANSI 372 Annex G.
WMCS:Australian WaterMark certified,certificate number 23347.
www.reliablesprinkler.com
Model • Sprinklers
RFC49LL: SINRA3216
• • Technical Specifications Sensitivity
Style:Flat Concealed Pendent Fast-response
Threads: 1/2"NPT or ISO 7-1 R1/2
Nominal K-Factor:4.9(71 metric) Temperature Rating 3
Max.Working Pressure: 175 psi(12 bar) Ordinary:
Min.Spacing:8 ft.(2.4 m) 165'F(74'C)sprinkler
135'F(57°C)cover plate
Material Specifications Intermediate:
Thermal Sensor:Nickel Alloy Solder Link 212°F(100°C)sprinkler
Sprinkler Body:Brass Alloy 165°F(74'C)cover plate
Levers:Bronze Alloy
Yoke:Brass Alloy Cover Plate
Sealing Assembly:Nickel Alloy with PTFE Model G5 Cover Plate
Load Screw:Bronze Alloy
Towers:Copper Alloy Sprinkler Wrench ,
Pins:Stainless Steel Model FC(without wrench-able cap)
Deflector:Bronze Alloy Model W3(with wrench-able cap) Bottom View
Cup:Steel
Listings and Approvals*
Cover Plate Finishes cULus Listed to UL 199
(See Table H)
'Note:RFC49LL is also cULus certified for Health Effects to NSF/ANSI/CAN 600,cULus certified less than 0.25%Lead Content to NSF/ANSI 372 Annex G,
and Australian WaterMark certified(certificate number 23347).
Model RFC49&RFC49LL Sprinkler Components and Dimensions
2-5/16"
(58 mm)
Threads Cup Dia.
Body
Cup
Tower 2-5/8"(67 mm)
1-3/4"(44 mm)+/-1/4"(6 mm) Hole in Ceiling
Fusible Link Nominal face of fitting to ceiling
PF 3/16"
Deflector(retracted) — (5 mm)
s3 r',;. .
ODMG
Pin(extended) I0'ozM
—~H ti
Deflector(extended) 3-5/16"
Model G5 Cover Plate (84 mm) Ceiling
Dia.
Model RFC49&RFC49LL Sprinkler Hydraulic Design Criteria
Minimum Flow and Residual PressureM
Ordinary Temperature Intermediate Temperature
Max.Coverage Area(')
ft.x ft. Flow Pressure Flow Pressure
(m x m) gpm psi gpm psi
Ilmin bar Ilmin bar
16 x 16 13 7.0 13 7.0
(4.9 x 4.9) (49.0) (0.48) (49.0) (0.48)
18 x 18 17 12.0 17 12.0
(5.5 x 5.5) (64.3) (0.83) (64.3) (0.83)
20 x 20 20 16.7 21 18.4
(6.1 x6.1) (75.7) (1.15) (79.5) (1.27)
Notes:
1. For NFPA 13 installations the flow per sprinkler must be the greater of:(1)the flow listed in Table D above and(2)the flow required to achieve a mini-
mum design density of 0.1 gpm/sq ft over the design area of the sprinkler.
2. For coverage area dimensions less than those listed above,use the minimum required flow for the next larger max.coverage area listed.
Bulletin 006 Reliable Page 4 of 8
December 2021 www.reliablesprinkler.com
Cover Plate Finishes') -
Standard Finishes Special Application Finishes
White Polyester Off White Paint Black Paint Raw Brass
Chrome Plated Bright Brass Finished Bronze Custom Color Paint(2)
Satin Chrome Stainless Steel Cla&)
Notes:
1. Paint or any other coating applied over the factory finish will void all approvals and warranties.
2. Custom color paint is semi-gloss,unless specified otherwise.
3. Stainless steel clad cover plates are Type 316 Stainless Steel on the finished side and C102 Copper Allow on the back side.Cover plates
are not listed or approved as corrosion resistant.
Installation Dimensions
Recommended Min.to Min.to Max.
Sprinkler
Cover Cover Plate Hole Diameter Cover Plate Max.Face Dropped Deflector Cover Plate
Plate Diameter Adjustment of Fitting to Distance below Temperature
Model Model inch(mm) in Ceiling inch(mm) Ceiling0) Ceiling Rating
inch(mm) inch(mm) inch(mm)
RFC30,
RFC30LL, 135°F(2)
RFC43, 3-5/16 2-5/8 1/2 1-1/2 to 2 1/2 to 1 (57°C)
RFC43LL, G5 (84) (67) (13) (38 to 51) (13 to 25) or 165°F(3
RFC49, (74°C)
RFC49LL
RFC58, 3-5/16 2-5/8 3/4 1-1/2 to 2-1/4 1/4 to 1 135 (57°C)
RFC76 G5 (84) (67) (19) (38 to 57) (6 to 25) orr 165°F�3
(74°C)
Notes:
1. Face of fitting to ceiling dimensions are based on a nominal thread make up.Verify dimensions based on fitting and thread sealing method prior to
installation.A 112"x 1/2"brass nipple extension(Reliable P/N 6999991900)is available where necessary for replacement of existing sprinklers.
2. For use with 165°F(74°C)temperature rated sprinklers where the maximum ceiling temperature does not exceed 100°F(38°C).
3. For use with 212°F(100°C)temperature rated sprinklers where the maximum ceiling temperature does not exceed 150°F(66°C).
Installation
Model RFC series sprinklers are intended to be installed in Note:When used with gasketed fittings,follow fitting
accordance with NFPA 13, NFPA 13R,or NFPA 13D, as well as manufacturer's installation instructions regarding tightening to
the requirements of applicable authorities having jurisdiction. achieve a leak-free connection.
Model RFC series sprinklers must not be installed in ceilings with
positive pressure in the space above. Ensure that the 4 slots in Do not exceed the maximum recommended torque. Exceeding
the cup are open and unobstructed following installation. Model the maximum recommended torque may cause leakage or
RFC series sprinklers are shipped with a wrench-able protective impairment of the sprinkler. Use care when inserting or removing
cap that should remain on the sprinkler until the sprinkler system the wrench from the sprinkler to avoid damage to the sprinkler.
is placed in service following construction.
Install the cover plate by hand by pushing the cover plate into the
Model RFC series sprinklers can be installed without removing cup and turning the cover in the clockwise direction until it is tight
the wrench-able protective cap using the Model W3 wrench. against the ceiling.
Alternatively, Model RFC series sprinklers can be installed using
the Model FC wrench by temporarily removing the protective cap
during installation of the sprinkler.The use of any other wrench
to installed Model RFC series sprinklers is not permitted and may
damage the sprinkler. Fully insert the Model W3 wrench over
the cap until it reaches the bottom of the cup, or the Model FC
wrench over the sprinkler until the wrench engages the body.
Do not wrench any other part of the sprinkler/cup assembly.The
Model W3 and FC wrenches are designed to be turned with a
standard 112"square drive.Tighten the sprinkler into the fitting
after applying a PTFE based thread sealant to the sprinkler's
threads. Recommended installation torque for iron pipe fittings is
8 to 18 ft-Ibs(11 to 24 N-m)for 1/2"thread sprinklers and 14 to
20 ft-Ibs(19 to 27 N-m)for 3/4"thread sprinklers.
Bulletin 006 Reliably Page 7 of 8
December 2021 www.reliablesprinkler.com