HomeMy WebLinkAboutCOM2023-00058 Mechanical - COM Inspections - 11/14/2024 Mason County
�.� Mason County - Division of Community Development
615 W. Alder St.
Building 8
Shelton, WA 98584
360-427-9670 ext 352
www.masoncountywa.gov
COM2023-00058 MECH/PLUMB - COMMERCIAL
PROJECT DESCRIPTION: INSTALL (1) 16-TON AND (1) 14-TON NEW ISSUED: 06/22/2023
OUTDOOR HEAT PUMP CONDENSING UNITS. INSTALL (2) BRANCH
SELECTORS, (8) DUCTED FAN COIL UNITS, (4)4-WAY CEILING EXPIRES: 12/19/2023
CASSETTES, (1)WALL MOUNTED UNIT, (12) ERV'S. MODIFYING
DUCTWORK AND GRILLES AS NEEDED"
SITE ADDRESS: 161 SE COLLIER RD SHELTON
PARCEL: 320281160010
APPLICANT: SOUTHSIDE SCHOOL DIST#42 OWNER: SOUTHSIDE SCHOOL DIST#42
161 SE COLLIER RD 161 SE COLLIER RD
SHELTON,WA 98584 SHELTON, WA98584
1.360.426.8437
GENERAL CONTRACTOR'S LICENSE: HERMANSON COMPANY LLP License: HERMACLO05BJ
1221 2ND AVE N Expires: 08/25/2024
KENT, WA98032-2945
1.206.775.6414
FEES: Paid Due
Final Inspection $80.00 $0.00
Technology Flat Convenience $5.00 $0.00
Fee
State Fee-Commercial $25.00 $0.00
Mechanical Fees $462.00 $0.00
Technology Surcharge $11.44 $0.00
Mechanical Base Fee $30.00 $0.00
Totals : $613.44 $0.00
FIXTURES
(sty Mechanical Fixtures
2.0000 Heat Pump(s)
2.0000 For each air-handling unit over 10,000 cfm
(4719L/s)
27.0000 Other
Printed by:Annie Wilson on:06/22/2023 09:30 AM
Page 1 of 3
Mason County
Mason County - Division of Community Development
615 W. Alder St.
Building 8
Shelton, WA 98584
360-427-9670 ext 352
www.masoncountywa.gov
MECH/PLUMB - COMMERCIAL COM2023-00058
REQUIRED INSPECTIONS
Mechanical Inspection Mechanical/Plumbing Final Inspection
CONDITIONS
* All building permits shall have a final inspection performed and approved by Mason County Building Department prior to
permit expiration.The failure to request a final inspection or to obtain approval will be documented in the legal property
records on file with Mason County as being non-compliant with Mason County ordinances and building regulations.
* The demolition and disposal of debris must meet the regulations of Mason County and Olympic Region Clean Air Agency
(ORCAA).
It is unlawful for any person to cause or allow the demolition (or major renovation)of any structure unless all asbestos
containing materials have been identified and removed from the area to be demolished. Work shall not commence on an
asbestos project or demolition project unless the owner or operator has obtained written approval from ORCCA.2490 B
Limited Lane NW, Olympia WA98502, 360.586.1044/800.422.5623 www.orcaa.org
* OWNER/BUILDER acknowledges submission of inaccurate information may result in a stop work order or permit
revocation.Acknowledgement of such is by signature below. I declare that I am the owner, owners legal representative, or
contractor. I further declare that I am entitled to receive this permit and to do the work as proposed. I have obtained
permission from all the necessary parties, including any easement holder or parties of interest regarding this project. The
owner or authorized agent represents that the information provided is accurate and grants employees of Mason County
access to the above described property and structure(s)for review and inspection. This permit/application becomes null &
void if work or authorized construction is not commenced within 180 days or if construction work is suspended for a period of
180 days. PROOF OF CONTINUATION OF WORK IS BY MEANS OF INSPECTION. INACTIVITY OF THIS PERMIT
APPLICATION OF 180 DAYS WILL INVALIDATE THE APPLICATION.
* All furnace installations shall meet the minimum efficiencies set forth in the current edition of the Washington state energy
code (WSEC). any portion of the mechanical system that is altered or replaced shall meet the minimum standards set forth
in the WSEC and international mechanical code.
* CONSTRUCTION PROCESS TO BE FIELD CORRECTED AS REQUIRED PER MASON COUNTY BUILDING
DEPARTMENT AND THE ADOPTED BUILDING CODE.
The construction of the permitted project is subject to inspections by the Mason County Building Department. All
construction must be in conformance with the international codes as amended and adopted by Mason County. Any
corrections, changes or alterations required by a Mason County Building Inspector shall be made prior to requesting
additional inspections.
* All construction must meet or exceed all local and state ordinances in addition to the International Codes requirements as
adopted and amended by Mason County and the State of Washington. Occupancy is limited to the approved and permitted
classification. Any non-approved change of use or occupancy would result in permit revocation.
* All permits expire 180 days after permit issuance, or 180 days after the last inspection activity is performed. The Building
Official may grant a one time extention of 180 days, upon the receipt of a written extension request prior to permit expiration.
Letter must indicating that circumstances beyond the control of the permit holder preventing action from being taken. No
more than one extension may be granted.
* Owner/Agent is responsible to post the assigned address and/or purchase and post private road signs in accordance
with Mason County Title 14.28 and 14.17.
Printed by:Annie Wilson on:06/22/2023 09:30 AM
Page 2 of 3
Mason County
Mason County - Division of Community Development
615 W. Alder St.
Building 8
Shelton, WA 98584
360-427-9670 ext 352
www.masoncountywa.gov
MECH/PLUMB - COMMERCIAL COM2023-00058
Contractor registration laws are governed under RCW 18.27 and enforced by the WA State Dept of Labor and Industries,
Contractor Compliance Division. There are potential risks and monetary liabilities to the homeowner for using an
unregistered contractor. Further information can be obtained at 1-800-647-0982. The person signing this condition is either
the homeowner, agent for the owner or a registered contractor according to WA state law.
Smoke detectors are required for all HVAC systems with a CFM of greater than 2000. Ref Plans for specific code info. Ref
NFPA and IMC for exceptions as listed.
I hereby certify that I have read and examined this application and know the same to be true and correct.
All provisions of Laws and Ordinances governing this type of work will be complied with whether
specified herein or not. The granting of a permit does not presume to give authority to violate or cancel
the provisions
AE
ofany other s'ta1te1/local law regulating construction or the performance of construction.
Issued By: �/1 11P, �N 1 ISOI�I
Contractor or Authorized Agent: Date: -11'
Printed by:Annie Wilson on:06/22/2023 09:30 AM
Page 3 of 3
MASON COUNTY 615 W.Alder St.Bldg 8,SHELTON,WA 98584
SHELTON:360 427-9670,EXT 352
COMMUNITY SERVICES
BELFAIR:360-275-4467,EXT 352
Buildinry Plnnninq,Cnvironmental I leelth.Community Heald E LMA:360-482-5269,EXT 352
www.co.mason.wa.us
INSPECTION CARD AND CERTIFICATE OF OCCUPANCY"
To schedule an inspection call or visit http://www.co.mason.wa.us/community-services/bid-inspection.php
Permit Number COM2023-00058 Date Issued 06/22/2023 Issued By A hli f e
install(1) 16-ton and(1)14-ton new outdoor heat pump condensing units.Install(2)branch selectors,(8)
Project ducted fan coil units,(4)4-way ceiling cassettes,(1)wall mounted unit,(12)ERV's.Modifying ductwork and
grilles as needed."
Site Address 161 SE COLLIER RD
Applicant SOUTHSIDE SCHOOL DIST#42
Contractor HERMANSON COMPANY LLP
Contractor Phone 1.206.775.6414
Primary Code UPC IBC,IRC,IFC,IEC,IMC,& Type
Permit Type MECH/PLUMB-COMMERCIAL Occupancy
-APPROVED PLANS MUST BE ONSITE FOR ALL INSPECTIONS.
-DO NOT PROCEED BEYOND EACH STAGE OR COVER WORK UNTIL APPROVAL IS GRANTED.
-THIS CARD MUST BE POSTED IN A CONSPICUOUS LOCATION,FRONT OF THE PREMISES IS BEST FOR MAKING ENTRY.
-ALL PERMITS EXPIRE 180 DAYS AFTER THE PERMIT IS ISSUED OR 180 DAYS AFTER DATE OF LAST INSPECTION.
-OWNER/AGENT IS RESPONSIBLE FOR REQUESTING ALL INSPECTIONS THROUGH FINAL INSPECTION.
**THIS STRUCTURE MAY NOT BE USED OR OCCUPIED UNTIL ALL APPROVALS ARE GRANTED.—
PRIOR TO CALLING FOR FINAL INSPECTION,ALL CONDITIONS OF THE PERMIT MUST BE MET
Public Works Access/Driveway Other
Health Septic Well
Deptartment
Planning Site Inspection
Department
Fire Marshall Fire Apparatus Access Fire Sprinkler
Auto Fire Alarm Hood and Duct
Other Final
Building
Department Building Official: Community Services Designee
Concrete Setbacks Slab
Footing Perimeter Point load Footing
Footing Interior Footing Decks/Porches
Foundation Stem Walls Other
Rough-In Groundwork Plumbing Framing
Groundwork Mechanical Plumbing
Groundwork Gas Pipe Mechanical
Gas Piping Shear Wall Nailing
Underfloor
Other
Insulation Slab Ceiling
Floor Vaulted Ceiling
Walls Vapor Barrier
Other
Wallboard Interior Wall Brace Panels Fire Walls
Nailing
Other
Final Building 11-19241D&C
Manufactured Setbacks Setup
Home
Concrete Foot/Runners Final
Otth7er 1 / /
SERVICESI eloa0t
BUI!LDING TECHNICAL
& BALANCE TEST
CERTIFIED REPORT
Southside Elementary School
Shelton, WA
Report Version: 1.0
00
I
r
' � T � � I I � •• a
REPORT SUMMARY
ti:ry
•`") �y;,� /��F -� _ VIA
l J y
Project Name: Southside Elementary School
Address: 161 SE Collier Road, Shelton, WA 98584
Velocity Number: 802039691
This is to certify that Velocity Building Technical Services, LLC has Tested,Adjusted, and Balanced the
systems described herein to their best possible performance capabilities. Data presented is a record of
measurements and adjustments at the time the work was performed.This test and the associated
balancing was performed in accordance with the current edition of the TABB Procedural Guide and
other industry standards.This work is warrantied for and expires ninety days from the report date
unless otherwise stated in contract documents specific to this project.
Submitted and certified by:Angela Roper,TABB Technician
Date:August 23, 2023
XGertifi
cal'o
a �
Aigefe M Roper
11
p8B1182813T
E-9—OWW2025 TESTING,ADJUSTING AND BALANCING BUREAU
Ce�frfiedTech��G\a THE PROFESSIONAL'S CHOICE—
.910dtV
REPORT SUMMARY
1) General Information
a) This report is based on actual field readings taken during operation unless otherwise noted.
Work was completed on:August 21, 2023
b) Equipment is inspected for proper and safe operation unless noted in this summary or the
associated data contain herein
c) Work requiring adjustments will be performed to +/-10%of the design value unless other
specifications require increased/decreased tolerances and approval by the Engineer of
Record (EOR) or Authority Having Jurisdiction (AHJ). Flow rates were measured with
calibrated instruments and are listed on the tool summary
d) All suggestions to further improve performance or function need to be fully vetted and
verified by all interested parties (i.e. Engineer, Owner,Tenant, Contractor)
e) Deficiencies noted throughout this report are the responsibility of the parties having an
interest in them and are not to be corrected by the TAB team unless instructed in the
contract documents. Notes are added for clarification as applicable
f) Design information is drawn from various sources to include, but not limited to: Drawings,
specifications, user manuals, shop drawings, submittals, service history, legacy documents,
and oral & photographic information. Additionally, unspecified values may be field
determined as required in the absence of engineered values, based on current best
practices
2) Scope of the Project(Overview)
a) Testing and balancing of twelve (12) Energy Recovery Ventilators (ERV) and twelve (12) Fan
Coil Units (FCU)
b) Correct any deficiencies if possible
c) Provide a certified TAB report demonstrating the actual airflow
3) System Description
a) Twelve (12) Energy Recovery Ventilators serving classrooms, library, and assorted office
spaces
b) Twelve (12) Fan Coil Units serving classrooms, library, and assorted office spaces
4) Findings
a) FCU-401 &402 are ducted together with their associated ERV. Outside air values are listed
under the Fan Coil Unit. ERV-402 exhaust serves the boys and girls restrooms.The inlets
were initially read at 100%open,then proportioned after.The actuator at the unit appeared
to be fully open.
b) FCU-403 through 407 and their associated ERV are ducted together for the return & exhaust
airflow. Design CFM is listed under the FCU.
c) FCU-411 & ERV-411 are ducted together.Traverses were taken at the return duct to the
FCU, exhaust duct to the ERV, and the ERV supply duct.There was no suitable duct run to
take a total duct traverse on the FCU supply duct.The FCU has six supply ducts branching
out to serve the assorted spaces indicated on the prints.The outlets were proportioned to
keep the 65 CFM offices near or at design given their lower airflow requirement.The spaces
with higher CFM designs were proportioned as best as possible to maximize airflow.The
'Vel• 21440 •• 98032 • " ' - • • •
REPORT SUMMARY
staff lounge is kept open 80-90%of the time during the school year when students are
present. It is open 100% of the time when no students are present. With the number of
supply branches coming off the unit, additional proportioning would likely result in overall
reduction of airflow.
d) See attached data and prints for reference.
10
'ot
BUILDING TECHNICAL SERVICES
Cover Page
PROJECT: Southside Elementary School DATE: 8/23/2023
LOCATION: Shelton,WA
PROJECT#: 802039691
FIRM: Velocity PHONE: 206-575-9700
21440 68th Ave. South FAX: 206-575-9800
Suite 220
Kent, WA 98032
PROJECT: Southside Elementary School
161 SE Collier Road DATE: 8/23/2023
PROJECT#: 802039691
Shelton, WA 98584
0
locit
i UILDING TECHNICAL SERVICES
Velocity Report Version: 1.0
10 Ot
e ci
V
DING TECHNICAL SERVICES
Table Of Contents
PROJECT: Southside Elementary School DATE: 8/23/2023
LOCATION: Shelton, WA
PROJECT#: 802039691
Table Of Contents
1 Fan Coil.................................................................................................................................................................... 3
1.1 FCU-401............................................................................................................................................................. 3
1.2 FCU-402............................................................................................................................................................. 4
1.3 FCU-403............................................................................................................................................................. 5
1.4 FCU-404............................................................................................................................................................. 6
1.5 FCU-405............................................................................................................................................................. 7
1.6 FCU-406 ............................................................................................................................................................ 8
1.7 FCU-407............................................................................................................................................................. 9
1.8 FCU-408............................................................................................................................................................. 9
1.9 FCU-409.............................................................................................................................................I............... 10
1.10 FCU-411........................................................................................................................................................... 10
1.11 FCU-411/Inlet-01............................................................................................................................................... 11
1.12 FCU-41 1/Return Duct....................................................................................................................................... 12
1.13 FCU-412........................................................................................................................................................... 13
1.14 FCU-413......................................................................................................................................................... .
14
2 Energy Recovery Unit.............................................................................................................................................. 15
2.1 ERV-401............................................................................................................................................................. 15
.........................................................................
2.2 ERV-402.................................. ............................... 16
2.3 ERV-403............................................................................................................................................................. 17
2.4 ERV-404.............................................................................................................................................................
I
2.5 ERV-405............................................................................................................................................................. 20
2.6 ERV-406.............................................................................................................................................................
2.7 ERV-407............................................................................................................................................................. 21
2.8 ERV-408............................................................................................................................................................. 22
.................................................
2.9 ERV-409.......................................................... ........................... 23
2.10 ERV-410........................................................................................................................................................... 24
2.11 ERV-411............................................................................................................................................................ 25
2.12 ERV-41 1/Exhaust Duct..................................................................................................................................... 26
2.13 ERV-411/Supply Duct....................................................................................................................................... 27
........................................................................................................
2.14 ERV-412.......................................... ......... 28
Velocity Report Version: 1.0
ot
i0c,
V
DING TECHNICAL SERVICES
Fan Coil
PROJECT: Southside Elementary School DATE: 8/23/2023
LOCATION: Shelton,WA
PROJECT#: 802039691
SYSTEM/UNIT: FCU-401 Tested By: Angela Roper
AREA: Hallway/Library Date: 8/21/2023
Manufacturer Daikin Motor HP 1 HP
Model Number FXTQ54TAVJUAAB Motor Rated Volts 208-230 Volts
Serial Number 2001027141 Motor Phase 1 Ph
Unit Condition New Motor Hertz 60 Hz
FCU-401/SF Filter Motor FL Amp 6.9 Amps
Filter Manufacturer Columbia Drive Type Direct Drive
MERV Rating 13
Filter Type Pleated
Filter Qty-S1 1 Design Actual
Filter Size-S1 18x22x2 Total Air 1985 CFM 2040 CFM
Return Air 1985 CFM 1820 CFM
External SP 0.60 in.we 0.59 in.we
Volts 209 Volts
Amps 5.3 Amps
Fan Speed Medium
Log: FCU-401 8/21/2023 Angela Roper FCU&ERV return/exhaust on the same duct. Design
CFM listed is for both units.
FCU-401 Supply Outlet Summary
Outlet-01 Hallway 290 410 141 300 103 CD 10 RD Flowhood 1.00
Outlet-02 Audio/Video 100 70 70 90 90 CD 6 RD Flowhood 1.00
Outlet-03 Library 395 390 99 410 104 LSD 10 RD Flowhood 1.00
Outlet-04 Library 600 565 94 610 102 SWG 18x12 Flowhood 1.00
Outlet-05 Library 600 575 96 630 105 SWG 18x12 Flowhood 1.00
FCU-401 Return Inlet Summary
"InletM-011Library 1 990 1 625 1 63 1 625 1 63 1 EG 1 12 RD I Flowhood I 1.00
Inlet-02' Library 990 1 1195 1 121 1195 1 121 EG 20 3/4 x Velocity 1 2.69
20 3/4 1 Grid
Log: FC7401/Inlet-02 8/23/2023 Angela Roper No volume damper.
Velocity Report Version: 1.0 Page 3 of 28
to Ot
V
DING TECHNICAL SERVICES
Fan Coil
PROJECT: Southside Elementary School DATE: 8/23/2023
LOCATION: Shelton,WA
PROJECT#: 802039691
SYSTEM/UNIT: FCU-402 Tested By: Angela Roper
AREA: Assorted Staff Areas Date: 8/21/2023
Manufacturer Daikin Motor HP 1/2 HP
Model Number FXTQ24TAVJUAAD Motor Rated Volts 208-230 Volts
Serial Number 2301293310 Motor Phase 1 Ph
Unit Condition New Motor Hertz 60 Hz
FCU-402/SF Filter Motor FL Amp 3.9 Amps
Filter Manufacturer Columbia Drive Type Direct Drive
MERV Rating 13
Filter Type Pleated
Filter Qty-S1 1 Desian Actual
Filter Size-S1 16x20x2 Total Air 1345 CFM 1335 CFM
Return Air 745 CFM 735 CFM
External SP 0.60 in.we 0.57 in.we
Volts 208 Volts
Amps 2.5 Amps
Fan Speed High
FCU-402 Supply Outlet Summary
—SysteinfUhIt Ar6a3erved03 gn to o t 13ffistrunw1w
ow DIM Airflowv e LxW 1 D Factor
Outlet-01 Office 150 150 100 150 100 LSD 10 RD Flowhood 1.00
Outlet-02 Office 190 210 111 200 105 LSD 10 RD Flowhood 1.00
Outlet-03 Office 100 85 85 105 105 LSD 10 RD Flowhood 1.00
Outlet-04 Office 1275 1 260 1 95 265 1 96 LSD 10 RD Flowhood 1.00
Outlet-05 Hallway 1 530 485 92 505 95 Cu 12 RD Flowhood 1.00
Outlet-06 Girls RR 1 50 80 160 55 110 CD 8 RD Flowhood 1.00
Outlet-07 Boys RR 50 75 150 55 110 Cu 8 RD Flowhood 1.00
FCU-402 Return Inlet Summary
"In1 Hallway 320 225 1 70 225 70 RG 8 RD Flowhood 1.00
Inlet-02` Library 425 510 1 120 510 120 RG 18 RD I Flowhood 1.00
Log:
FCU-402/Inlet-02 8/23/2023 Angela Roper No volume damper.
Velocity Report Version: 1.0 Page 4 of 28
loat
Fan Coil BUILDING TECHNICAL SERVICES
PROJECT: Southside Elementary School DATE: 8/23/2023
LOCATION: Shelton,WA
PROJECT#: 802039691
SYSTEM/UNIT: FCU-403 Tested By: Dylan Reese
AREA: Classroom Date: 8/18/2023
Manufacturer Daikin Motor HP 1/2 HP
Model Number FXTQ30TAVJUAAD Motor Rated Volts 208-230 Volts
Serial Number 2305199486 Motor Phase 1 Ph
Unit Condition New Motor Hertz 60 Hz
FCU-403/SF Filter Motor FL Amp 3.9 Amps
Filter Manufacturer Columbia Drive Type Direct Drive
MERV Rating 13
Filter Type Pleated
Filter Qty-S1 1 Desian Actual
Filter Size-S1 16x20x2 Total Air 810 CFM 820 CFM
Return Air 1280 CFM 935 CFM
External SP 0.60 in.we 0.50 in.we
Volts 210 Volts
Amps 1.8 Amps
Fan Speed Low
Log: FCU-403 8/17/2023 Angela Roper OSA provided by ERV-403,ducted separately.
FCU-403 8/17/2023 Angela Roper FCU&ERV return/exhaust on the same duct. Design
CFM listed is for both units.
FCU-403 Supply Outlet Summary
"OutleMt-01IClassroom 270 1 330 1 122 1 295 1 109 1 LSD 10 RD Flowhood 1.00
Outlet-02 Classroom 1 270 1 305 1 113 265 98 1 LSD 10 RD Flowhood 1.00
Outlet-03 I Classroom 1 270 1 305 1 113 260 96 LSD 10 RD Flowhood 1.00
Velocity Report Version: 1.0 Page 5 of 28
10 Ot
V
DING TECHNICAL SERVICES
Fan Coil
PROJECT: Southside Elementary School DATE: 8/23/2023
LOCATION: Shelton,WA
PROJECT#: 802039691
SYSTEM/UNIT: FCU-404 Tested By: Dylan Reese
AREA: Classroom Date: 8/18/2023
Motor HP 1/2 HP
Daikin
Manufacturer Model Number FXTQ24TAVJUAAD Motor Rated Volts 208-230 Volts
1 Motor Phase 1 Ph
230223223
Serial Number 60 Hz
Unit Condition New Motor Hertz
FCU-404/SF Filter Motor FL Amp 3.9 Amps
Filter Manufacturer Columbia Drive Type Direct Drive
MERV Rating 13
Filter Type Pleated
Filter Qty-S1 1 Desicin Actual
Filter Size-S1 16x20x2 Total Air 735 CFM 750 CFM
Return Air 1205 CFM 1070 CFM
External SP 0.60 in.we 0.50 in.we
Volts 210 Volts
Amps 2.6 Amps
Fan Speed Medium
Log: FCU-404 8/17/2023 Angela Roper OSA provided by ERV-404,ducted separ:duct.
y.
FCU-404 8/17/2023 Angela Roper FCU&ERV return/exhaust on the same Design
CFM listed is for both units.
FCU-404 Supply Outlet Summary
Outlet 01 Classroom 245 215 88 230 94 LSD 10 RD Flowhood 1.00
Outlet-02 Classroom 245 230 94 250 102 LSD 10 R D Flowhood 1.00
Outlet-03 Classroom 245 240 98 270 110 LSD 10 RD 1 Flowhood 1.00
Velocity Report Version: 1.0 Page 6 of
loat
Fan Coil BUILDING TECHNICAL SERVICES
PROJECT: Southside Elementary School DATE: 8/23/2023
LOCATION: Shelton, WA
PROJECT#: 802039691
SYSTEM/UNIT: FCU-405 Tested By: Dylan Reese
AREA: Classroom Date: 8/18/2023
Manufacturer Daikin Motor HP 1/2 HP
Model Number FXTQ30TAVJUAAD Motor Rated Volts 208-230 Volts
Serial Number 2305199489 Motor Phase 1 Ph
Unit Condition New Motor Hertz 60 Hz
FCU-405/SF Filter Motor FL Amp 3.9 Amps
Filter Manufacturer Columbia Drive Type Direct Drive
MERV Rating 13
Filter Type Pleated
Filter Qty-S1 1 Desian Actual
Filter Size-S1 16x20x2 Total Air 810 CFM 850 CFM
Return Air 1280 CFM 1040 CFM
External SP 0.60 in.we 0.64 in.we
Volts 210 Volts
Amps 1.8 Amps
Fan Speed Low
Log: FCU-405 8/17/2023 Angela Roper FCU&ERV return/exhaust on the same duct.Design
CFM listed is for both units.
FCU-405 8/17/2023 Angela Roper OSA provided by ERV-405,ducted separately.
FCU-405 Supply Outlet Summary
PnOu=tlet-01 Classroom 1 270 1 370 137 1 280 1 104 1 LSD 10 RD Flowhood 1 1.00
Outlet-02 Classroom 270 270 100 290 1 107 1 LSD 10 RD Flowhood 1 1.00
Outlet-03 Classroom 1 270 1 225 83 280 1 104 1 LSD 10 RD Flowhood 1 1.00
Velocity Report Version: 1.0 Page 7 of 28
10 ot
V
DING TECHNICAL SERVICES
Fan Coil
PROJECT: Southside Elementary School DATE: 8/23/2023
LOCATION: Shelton,WA
PROJECT#: 802039691
SYSTEM/UNIT: FCU-406 Tested By: Angela Roper
AREA: Hallway/Classroom Date: 8/18/2023
Manufacturer Daikin Motor HP 1/2 HP
Model Number FXTQ30TAVJUAAD Motor Rated Volts 208-230 Volts
Motor Phase 1 Ph
2305199487
Serial Number 60 Hz
Unit Condition New Motor Hertz
FCU-406/SF Filter Motor FL Amp 3.9 Amps
Filter Manufacturer Columbia Drive Type Direct Drive
MERV Rating 13
Filter Type Pleated
Filter Qty-S1 1 Design Actual
Filter Size-S1 16x20x2 Total Air 900 CFM 945 CFM
Return Air 1370 CFM 1220 CFM
External SP 0.60 in.we 0.83 in.we
Volts 209 Volts
Amps 2.6 Amps
Fan Speed Medium
FCU-406 8/17/2023 Angela Roper FCU&ERV return/exhaust on the same duct.Design
Log: CFM listed is for both units.
FCU-406 8/16/2023 Angela Roper OSA provided by ERV-406,ducted separately.
FCU-406 Supply Outlet Summary
merit AK
Outlet-01 Hallway 210 265 126 225 107 CD 12 RD Flowhood 1.00
Outlet-02 Classroom 230 235 102 235 102 LSD 12 RD Flowhood 1.00
Outlet-03 Classroom 230 270 117 250 109 LSD 12 RD Flowhood 1.00
Outlet-04 Classroom 230 330 143 235 102 LSD 12 RD Flowhood 1.00
Velocity Report Version: 1.0 Page 8 of zu
et
loci
BUILDING TECHNICAL SERVICES
Fan Coil
PROJECT: Southside Elementary School DATE: 8/23/2023
LOCATION: Shelton,WA
PROJECT#: 802039691
SYSTEM/UNIT: FCU-407 Tested By: Angela Roper
AREA: Classroom Date: 8/18/2023
Manufacturer Daikin Motor HP 1/2 HP
Model Number FXTQ30TAVJUAAD Motor Rated Volts 208-230 Volts
Serial Number 2305199487 Motor Phase 1 Ph
Unit Condition New Motor Hertz 60 Hz
FCU-407/SF Filter Motor FL Amp 3.9 Amps
Filter Manufacturer Columbia Drive Type Direct Drive
MERV Rating 13
Filter Type Pleated
Filter Qty-S1 1 Desian Actual
Filter Size-S1 16x20x2 Total Air 810 CFM 915 CFM
Return Air 1280 CFM 1155 CFM
External SP 0.60 in.we 0.70 in.we
Volts 210 Volts
Amps 1.8 Amps
Fan Speed Low
Lag: FCU-407 8/17/2023 Angela Roper FCU&ERV return/exhaust on the same duct. Design
CFM listed is for both units.
FCU-407 8/16/2023 Angela Roper OSA provided by ERV-407,ducted separately.
FCU-407 Supply Outlet Summary
"OutletE-01 Classroom 1 270 1 335 1 124 1 295 1 109 1 LSD 1 12 RD I Flowhood 1.00
Outlet-02 Classroom 270 360 133 320 119 LSD 12 RD Flowhood 1.00
Outlet-03 Classroom 270 1 330 1 122 1 300 111 LSD 12 RD Flowhood 1.00
SYSTEM/UNIT: FCU-408 Tested By: Angela Roper
AREA: Classroom Date: 8/16/2023
Manufacturer Daikin Motor HP 0.14 HP
Model Number FXUQ36PAVJU Motor Rated Volts 208-230 Volts
Serial Number C000603 Motor Phase 1 Ph
Unit Condition New Motor Hertz 60 Hz
FCU-408/SF Filter Motor FL Amp 1.1 Amps
Filter Type Washable Drive Type Direct Drive
Filter Qty-S1 1
Filter Size-S1 2lx2lxl
Desicin Actual
Total Air 985 CFM 1030 CFM
Volts 209 Volts
Amps 0.6 Amps
Fan Speed High
Velocity Report Version: 1.0 Page 9 of 28
10 Ot
e a
V
DING TECHNICAL SERVICES
Fan Coil
PROJECT: Southside Elementary School DATE: 8/23/2023
LOCATION: Shelton,WA
PROJECT#: 802039691
SYSTEM/UNIT: FCU-409 Tested By: Angela Roper
AREA: Classroom Date: 8/16/2023
Manufacturer Daikin Motor HP 0.14 HP
Model Number FXUQ36PAVJU Motor Rated Volts 208-230 Volts
Serial Number C000602 Motor Phase 1 Ph
Unit Condition New Motor Hertz 60 Hz
FCU-409/SF Filter Motor FL Amp 1.1 Amps
Filter Type Washable I Drive Type Direct Drive
Filter Qty-S1 1
Filter Size-S1 21x21x1
Design Actual
Total Air 870 CFM 880 CFM
Volts 210 Volts
Amps 0.6 Amps
Fan Speed Medium
SYSTEM/UNIT: FCU-411 Tested By: Angela Roper
AREA: Assorted Staff Areas Date: 8/21/2023
Manufacturer Daikin Motor HP 1/2 HP
Model Number FXMQ48TBVJU Motor Rated Volts 208-230 Volts
Serial Number E000768 Motor Phase 1 Ph
Unit Condition New Motor Hertz 60 Hz
FCU-411/SF Filter Motor FL Amp 2.9 Amps
Filter Manufacturer Columbia Drive Type Direct Drive
MERV Rating 13
Filter Type Pleated
Filter Qty-S1 1 Design Actual
Filter Size-S1 18x24x2 Total Air 1710 CFM 1535 CFM
Return Air 1695 CFM 1130 CFM
External SP 0.60 in.we 0.95 in.we
Volts 210 Volts
Amps 2.4 Amps
Fan Speed High
Log: FCU-411 8/21/2023 Angela Roper Staff lounge left with both dampers 100%open to
reduce effects of proportioning and potential total
CFM loss.The door to the room stays open 80-90%
of the school year,open 100%when no students
resent.
Velocity Report Version: 1.0 Page 10 of zts
loat
BUILDING TECHNICAL SERVICES
Fan Coil
PROJECT: Southside Elementary School DATE: 8/23/2023
LOCATION: Shelton,WA
PROJECT#: 802039691
SYSTEM/UNIT: FCU-411/Inlet-01 Tested By: Angela Roper
Date: 8/21/2023
Type of Traverse Round Sum of Readings 5182
Diameter 12.00 in. Average Reading 324 FPM
Air Flow Area 0.79 sq.ft. Reading Std.Dev. 114 FPM
Number Of Rows 2 Design Total Flow 470 CFM
Readings Per Row 8 Actual Total Flow 256 CFM
Total Readings 16 Duct Static Press. -0.02 in.we
Location of Holes 1 Left
Location of Holes 2 Bottom
Traverse Data Points
72
419
Hole 1 76 261 ® 377 d37 ® ® 412 r
317
312
�G7
IV
N
O
O
2
Velocity Report Version: 1.0 Page 11 of 28
10 Ot
V
DING TECHNICAL SERVICES
Fan Coil
PROJECT: Southside Elementary School DATE: 8/23/2023
LOCATION: Shelton,WA
PROJECT M 802039691
SYSTEM/UNIT: FCU-411/Return Duct Tested By: Angela Roper
Date: 8/21/2023
Type of Traverse Round Sum of Readings 20161
12.00 in. Average Reading 1260 FPM
Diameter Air Flow Area 0.79 sq.ft. Reading Std.Dev. 327 FPM
Number Of Rows
2 Design Total Flow 1290 CFM
995 CFM
Readings Per Row 8 Actual Total Flow
Total Readings
16 Duct Static Press. -0.33 in.we
Location of Holes 1 Left
Location of Holes 2 Bottom
Traverse Data Points
I 12 'I
1495
1547
1488
1375
Hole 1 F91F7 778 1134 1102 1463 1356 1214 ® TN
1492
1688
1448
1177
N
O
S
Velocity Report Version: 1.0 Page 12 of eo
10aet
V
DING TECHNICAL SERVICES
Fan Coil
PROJECT: Southside Elementary School DATE: 8/23/2023
LOCATION: Shelton,WA
PROJECT#: 802039691
FCU-411 Supply Outlet Summary
Outlet-01 Office 65 80 123 60 92 CD 8 RD Flowhood 1.00
Outlet-02 Office 65 80 123 65 100 CD 8 RD Flowhood 1.00
Outlet-03 Counselor 50 50 100 45 90 CD 8 RD Flowhood 1.00
Outlet-04 Office 65 75 115 60 92 CD 8 RD Flowhood 1.00
Outlet-05 Office 65 60 92 65 100 CD 8 RD Flowhood 1.00
Outlet-06 Staff Lounge 250 1 145 58 160 1 64 CD 8 RD Flowhood 1.00
Outlet-07 Staff Lounge 250 190 76 200 80 CD 8 RD Flowhood 1.00
Outlet-08 Hallway 415 385 93 405 98 CD 8 RD Flowhood 1.00
Outlet-09 Nurse 210 200 95 205 98 CD 8 RD Flowhood 1.00
Outlet-10 Health Room 165 165 100 170 103 CD 8 RD Flowhood 1.00
Outlet-11 Hallway 1 110 95 1 86 1 100 91 1 CD 8 RD Flowhood 1.00
FCU-411 Return Inlet Summary
Inlet-01` Hallway 470 265 56 260 55 RG 8 RD Flowhood 1.00
Inlet-02 Office 65 80 123 65 100 RG 8 RD Flowhood 1.00
Inlet-03 Office 65 75 115 65 100 RG 8 RD Flowhood 1.00
Inlet-04 Counselor 50 105 210 50 100 RG 8 RD Flowhood 1.00
Inlet-05 Office 65 60 92 60 92 RG 8 RD Flowhood 1.00
Inlet-06 Office 1 65 1 60 1 92 1 60 1 92 1 RG 8 RD Flowhood 1.00
Inlet-07 Staff Lounge 1 540 1 315 1 58 1 320 1 59 RG 12 RD Flowhood 1.00
Inlet-08 Nurse 210 130 62 125 60 RG 10 RD Flowhood 1.00
Inlet-09 Health Room 165 130 79 1 125 1 76 RG 10 RD Flowhood 1.00
Log: FCU-411/Inlet-01 8/21/2023 Angela Roper No damper,open path.
SYSTEM/UNIT: FCU-412 Tested By: Angela Roper
AREA: Classroom Date: 8/16/2023
Manufacturer Daikin Motor HP 0.14 HP
Model Number FXUQ36PAVJU Motor Rated Volts 208-230 Volts
Serial Number C000608 Motor Phase 1 Ph
Unit Condition New Motor Hertz 60 Hz
FCU-412/SF Filter Motor FL Amp 1.1 Amps
Filter Type Washable Drive Type Direct Drive
Filter Qty-S1 1
Filter Size-S1 21x21x1
Design Actual
Total Air 820 CFM 865 CFM
Volts 210 Volts
Amps 0.6 Amps
Fan Speed Medium
Velocity Report Version: 1.0 Page 13 of 28
10
ot
VDING TECHNICAL SERVICES
Fan Coil
PROJECT: Southside Elementary School DATE: 8/23/2023
LOCATION: Shelton,WA
PROJECT#: 802039691
SYSTEM/UNIT: FCU-413 Tested By: Angela Roper
AREA: Classroom Date: 8/16/2023
Manufacturer Daikin Motor HP 0.14 HP
Model Number FXUQ36PAVJU Motor Rated Volts 208-230 Volts
Serial Number C000611 Motor Phase 1 Ph
Unit Condition New Motor Hertz 60 Hz
FCU-413/SF Filter Motor FL Amp 1.1 Amps
Filter Type Washable Drive Type Direct Drive
Filter Qty-S1 1
Filter Size-S1 2lx2lx1
Design Actual
Total Air 890 CFM 890 CFM
Volts 211 Volts
Amps 0.6 Amps
Fan Speed Medium
Velocity Report Version: 1.0 Page 14 of 28
loat
BUILDING TECHNICAL SERVICES
Energy Recovery Unit
PROJECT: Southside Elementary School DATE: 8/23/2023
LOCATION: Shelton,WA
PROJECT#: 802039691
SYSTEM/UNIT: ERV-401 Tested By: Angela Roper
AREA: Library Date: 8/21/2023
Unit Manufacturer Daikin ERV-401/EF
Unit Model Number VAM600GVJU Motor HP 3/8 HP
Unit Serial Number F002425 Motor Rated Volts 208-230 Volts
Unit Type Plate Exchanger Motor Phase 1 Ph
Unit Condition New Motor Hertz 60 Hz
ERV-401/EF Filter Motor FL Amps 3.7 Amps
Filter Type Washable Drive Type Direct Drive
Filter Qty-S1 1 ERV-401/SF
Filter Size-S1 29 3/4 x 9 x 3/8 Motor HP 3/8 HP
ERV-401/SF Filter Motor Rated Volts 208-230 Volts
Filter Type Washable Motor Phase 1 Ph
Filter Qty-S1 1 Motor Hertz 60 Hz
Filter Size-S1 29 3/4 x 9 x 3/8 Motor FL Amps 3.7 Amps
Drive Type Direct Drive
S/Fan Design Airflow 600 CFM
S/Fan Actual Airflow 550 CFM
E/Fan Design Airflow 600 CFM
E/Fan Actual Airflow 545 CFM
ERV-401/EF
Motor Volts T1-T2 208 Volts
Motor Amps T1 1.50 Amps
Speed High
ERV-401/SF
Motor Volts T1-T2 208 Volts
Motor Amps T1 1.10 Amps
Speed High
Log: ERV-401 8/23/2023 Angela Roper ERV-401 is ducted directly into FCU-401. No inlets or
outlets.
Velocity Report Version: 1.0 Page 15 of 28
10
et
VDING TECHNICAL SERVICES
Energy Recovery Unit
PROJECT: Southside Elementary School DATE: 8/23/2023
LOCATION: Shelton,WA
PROJECT#: 802039691
SYSTEM/UNIT: ERV-402 Tested By: Angela Roper
AREA: Assorted Staff Areas Date: 8/21/2023
Unit Manufacturer Daikin ERV-402/EF
Motor HP 3/8 HP
VAM600GVJU
Unit Model Number Unit Serial Number F002436 Motor Rated Volts 208-230 Volts
Unit Type Plate Exchanger Motor Phase 1 Ph
Unit Condition New Motor Hertz 60 Hz
ERV-402/EF Filter Motor FL Amps 3.7 Amps
Filter Type Washable Drive Type Direct Drive
Filter Qty-S1 1 ERV-402/SF 3/8 HP
Filter Size-S1 29 3/4 x 9 x 3/8 Motor HP
ERV-402/SF Filter Motor Rated Volts 208-230 Volts
Filter Type Washable Motor Phase 1 Ph
Filter Qty-S1 1 Motor Hertz 60 Hz
Filter Size-S1 29 3/4 x 9 x 3/8 Motor FL Amps 3.7 Amps
Drive Type Direct Drive
S/Fan Design Airflow 600 CFM
S/Fan Actual Airflow 550 CFM
E/Fan Design Airflow 600 CFM
E/Fan Actual Airflow 460 CFM
ERV-402/EF
Motor Volts T1-T2 208 Volts
Motor Amps T1 1.50 Amps
Speed High
ERV-402/SF
Motor Volts 71-T2 208 Volts
Motor Amps T1 1.10 Amps
Speed High
ERV-402 Exhaust Inlet Summary
%o Final Inlet Type ize I n3 rument AK
Factor
Inlet-0=1 Girls RR 300 1 205 68 220 73 EG t 12x12 Flowhood
Inlet-02 Boys RR MU265 1 88 240 80 EG 12x12 Flowhooc'
Velocity Report Version: 1.0 Page 16 of 28
loat
BUILDING TECHNICAL SERVICES
Energy Recovery Unit
PROJECT: Southside Elementary School DATE: 8/23/2023
LOCATION: Shelton,WA
PROJECT#: 802039691
SYSTEM/UNIT: ERV-403 Tested By: Angela Roper
AREA: Classroom Date: 8/18/2023
Unit Manufacturer Daikin ERV-403/EF
Unit Model Number VAM470GVJU Motor HP 3/8 HP
Unit Serial Number F002439 Motor Rated Volts 208-230 Volts
Unit Type Plate Exchanger Motor Phase 1 Ph
Unit Condition New Motor Hertz 60 Hz
ERV-403/EF Filter Motor FL Amps 3.5 Amps
Filter Type Washable Drive Type Direct Drive
Filter Qty-S1 1 ERV-403/SF
Filter Size-S1 29 3/4 x 9 x 3/8 Motor HP 3/8 HP
ERV-403/SF Filter Motor Rated Volts 208-230 Volts
Filter Type Washable Motor Phase 1 Ph
Filter Qty-S1 1 Motor Hertz 60 Hz
Filter Size-S1 29 3/4 x 9 x 3/8 Motor FL Amps 3.5 Amps
Drive Type Direct Drive
S/Fan Design Airflow 470 CFM
S/Fan Actual Airflow 475 CFM
ERV-403/EF
Motor Volts T1-T2 210 Volts
Motor Amps T1 1.20 Amps
Speed High
ERV-403/SF
Motor Volts T1-T2 210 Volts
Motor Amps T1 1.40 Amps
Speed High
Log: ERV-403 8/18/2023 Angela Roper Exhaust air is tied into its associated FCU return and
listed under that unit.
ERV-403 Supply Outlet Summary
etve o o Ana u i3 ie nstrument AK
Airflow Airflow Diff. Airflow Diff. Tye LxW/D Factor
Outlet-01 Classroom v :7:; i L 1 Z n ., ;;4 ,,
470 475 101 475 1
Velocity Report Version: 1.0 Page 17 of 28
ot
VDING TECHNICAL SERVICES
Energy Recovery Unit
PROJECT: Southside Elementary School DATE: 8/23/2023
LOCATION: Shelton,WA
PROJECT#: 802039691
SYSTEM/UNIT: ERV-404 Tested By: Angela Roper
AREA: Classroom Date: 8/18/2023
Unit Manufacturer Daikin ERV-404/EF
Vikin VJU Motor HP 3/8 HP
Unit Model Number 208-230 Volts
Unit Serial Number F002434 Motor Rated Volts
Plate Exchanger Motor Phase 1 Ph
Unit Type Unit Condition New Motor Hertz 60 Hz
ERV-404/EF Filter
Motor FL Amps 3.5 Amps Filter Type Washable Drive Type Direct Drive
Filter Qty-S1 1 ERV-404/SF
29 3/4 x 9 x 3/8 3/8 HP
Filter Size Motor HP S1 208-230 Volts
ERV-404/SF Filter Motor Rated Volts
Filter Type Washable Motor Phase 1 Ph
Filter Qty-S1 1 Motor Hertz 60 Hz
Filter Size-S1 29 3/4 x 9 x 3/8 Motor FL Amps 3.5 Amps
Drive Type Direct Drive
S/Fan Design Airflow 470 CFM
S/Fan Actual Airflow 470 CFM
ERV-404/EF
Motor Volts T1-T2 209 Volts
Motor Amps T1 1.40 Amps
Speed High
ERV-404/SF
Motor Volts T1-T2 209 Volts
Motor Amps T1 1.40 Amps
Speed High
Log: ERV-404 8/18/2023 Angela Roper Exhaust air is tied into its associated FCU return and
listed under that unit.
ERV-404 Supply Outlet Summary
System rift rea erved es gn Te o
lirfJow Di Airflow DifF.
Outlet 01 Classroom F 470 1 470 100 100 1 CD 12 RD I Flowhood I1.00
470
Page 18 of�u
Velocity Report Version: 1.0
ot
10CI
BUILDING TECHNICAL SERVICES
Energy Recovery Unit
PROJECT: Southside Elementary School DATE: 8/23/2023
LOCATION: Shelton,WA
PROJECT#: 802039691
SYSTEM/UNIT: ERV-405 Tested By: Angela Roper
AREA: Classroom Date: 8/18/2023
Unit Manufacturer Daikin ERV-405/EF
Unit Model Number VAM470GVJU Motor HP 3/8 HP
Unit Serial Number F002471 Motor Rated Volts 208-230 Volts
Unit Type Plate Exchanger Motor Phase 1 Ph
Unit Condition New Motor Hertz 60 Hz
ERV-405/EF Filter Motor FL Amps 3.5 Amps
Filter Type Washable Drive Type Direct Drive
Filter Qty-S1 1 ERV-405/SF
Filter Size-S1 29 3/4 x 9 x 3/8 Motor HP 3/8 HP
ERV-405/SF Filter Motor Rated Volts 208-230 Volts
Filter Type Washable Motor Phase 1 Ph
Filter Qty-S1 1 Motor Hertz 60 Hz
Filter Size-S1 29 3/4 x 9 x 3/8 Motor FL Amps 3.5 Amps
Drive Type Direct Drive
S/Fan Design Airflow 470 CFM
S/Fan Actual Airflow 450 CFM
ERV-405/EF
Motor Volts T1-T2 208 Volts
Motor Amps T1 1.40 Amps
Speed High
ERV-405/SF
Motor Volts T1-T2 209 Volts
Motor Amps T1 1.40 Amps
Speed High
Log: ERV-405 8/18/2023 Angela Roper Exhaust air is tied into its associated FCU return and
listed under that unit.
ERV-405 Supply Outlet Summary
"tem, n rea etve e m o m Final %Final Outlet z Instrument AW
Diff. Xyga LxW I jX. _ for
Outlet-01 Classroom 470 450 1 96 450 c, CD 12 RD Flowhood 1.00
Velocity Report Version: 1.0 Page 19 of 28
10 Ot
V
DING TECHNICAL SERVICES
Energy Recovery Unit
PROJECT: Southside Elementary School DATE: 8/23/2023
LOCATION: Shelton,WA
PROJECT#: 802039691
SYSTEM/UNIT: ERV-406 Tested By: Angela Roper
AREA: Classroom Date: 8/18/2023
Unit Manufacturer Daikin ERV-406/EF
Unit Model Number VAM470GVJU Motor HP 3/8 HP
Unit Serial Number F002430 Motor Rated Volts 208-230 Volts
Unit Type Plate Exchanger Motor Phase 1 Ph
Unit Condition New Motor Hertz 60 Hz
ERV-406/EF Filter Motor FL Amps 3.5 Amps
Filter Type Washable Drive Type Direct Drive
Filter Qty-S1 1 ERV-406/SF
Filter Size-S1 29 3/4 x 9 x 3/8 Motor HP 3/8 HP
ERV-406/SF Filter Motor Rated Volts 208-230 Volts
Filter Type Washable Motor Phase 1 Ph
Filter Qty-S1 1 Motor Hertz 60 Hz
Filter Size-S1 29 3/4 x 9 x 3/8 Motor FL Amps 3.5 Amps
Drive Type Direct Drive
S/Fan Design Airflow 470 CFM
S/Fan Actual Airflow 480 CFM
ERV-406/EF
Motor Volts T1-T2 209 Volts
Motor Amps T1 1.30 Amps
ERV-406/SF
Motor Volts T1-T2 209 Volts
Motor Amps T1 1.40 Amps
Log: ERV-406 8/18/2023 Angela Roper Exhaust air is tied into its associated FCU return and
listed under that unit.
ERV-406 Supply Outlet Summary
Outlet-01 Classroom 1 470 485 480 CD 0
Velocity Report Version: 1.0 Page 20 of 28
loat
V
DING TECHNICAL SERVICES
Energy Recovery Unit
PROJECT: Southside Elementary School DATE: 8/23/2023
LOCATION: Shelton,WA
PROJECT#: 802039691
SYSTEM/UNIT: ERV-407 Tested By: Angela Roper
AREA: Classroom Date: 8/18/2023
Unit Manufacturer Daikin ERV-407/EF
Unit Model Number VAM470GVJU Motor HP 3/8 HP
Unit Serial Number F002432 Motor Rated Volts 208-230 Volts
Unit Type Plate Exchanger Motor Phase 1 Ph
Unit Condition New Motor Hertz 60 Hz
ERV-407/EF Filter Motor FL Amps 3.5 Amps
Filter Type Washable Drive Type Direct Drive
Filter Qty-S1 1 ERV-407/SF
Filter Size-S1 29 3/4 x 9 x 3/8 Motor HP 3/8 HP
ERV-407/SF Filter Motor Rated Volts 208-230 Volts
Filter Type Washable Motor Phase 1 Ph
Filter Qty-S1 1 Motor Hertz 60 Hz
Filter Size-S1 29 3/4 x 9 x 3/8 Motor FL Amps 3.5 Amps
Drive Type Direct Drive
S/Fan Design Airflow 470 CFM
S/Fan Actual Airflow 445 CFM
ERV-407/EF
Motor Volts T1-T2 208 Volts
Motor Amps T1 1.40 Amps
Speed High
ERV-407/SF
Motor Volts T1-T2 208 Volts
Motor Amps T1 1.50 Amps
Speed High
Log: ERV-407 8/18/2023 Angela Roper Exhaust air is tied into its associated FCU return and
listed under that unit.
ERV-407 Supply Outlet Summary
ystem/Un f' rea erved Desi o rem Final o final Outlet Size nstrument AK
Airflow Airflow Diff. Airflow Diff. Type LxW/D Factor
%0 ;5 RDF. ..
Totals: 470 445 95 445 95 -
Velocity Report Version: 1.0 Page 21 of 28
10 Ot
V
DING TECHNICAL SERVICES
Energy Recovery Unit
PROJECT: Southside Elementary School DATE: 8/23/2023
LOCATION: Shelton,WA
PROJECT#: 802039691
SYSTEM/UNIT: ERV-408 Tested By: Angela Roper
AREA: Classroom Date: 8/21/2023
Unit Manufacturer Daikin ERV-408/EF
Unit Model Number VAM470GVJU Motor HP 3/8 HP
Unit Serial Number F002455 Motor Rated Volts 208 Volts
Unit Type Plate Exchanger Motor Phase 1 Ph
yp
Unit Condition New Motor Hertz 60 Hz
ERV-408/EF Filter Motor FL Amps 3.5 Amps
Filter Type
Washable Drive Type Direct Drive
Filter Qty-S1 1 ERV-408/SF
Filter Size-S1 29 3/4 x 9 x 3/8 Motor HP 3/8 HP
ERV-408/SF Filter Motor Rated Volts 208 Volts
Filter Type Washable Motor Phase 1 Ph
Filter Qty-S1 1 Motor Hertz 60 Hz
Filter Size-S1 29 3/4 x 9 x 3/8 Motor FL Amps 3.5 Amps
Drive Type Direct Drive
S/Fan Design Airflow 470 CFM
S/Fan Actual Airflow 525 CFM
E/Fan Design Airflow 425 CFM
E/Fan Actual Airflow 445 CFM
ERV-4081EF
Motor Volts T1-T2 211 Volts
Motor Amps T1 1.70 Amps
Speed High
ERV-408/SF
Motor Volts T1-T2 211 Volts
Motor Amps T1 1.70 Amps
Speed High
ERV-408 8/17/2023 Angela Roper Speed options are low&high.Low speed setting
Log: resulted in exhaust inlet dropping below 90%of
design.Left on high speed.
ERV-408 Supply Outlet Summary
E.
A
Fa_.
Outlet-01 Classroom 115 100 87 130 113 CD 10 RD Flowhood 1.00
Outlet-02 Classroom 115 110 96 130 113 CD 10 RD Flowhood 1.00
Outlet-03 Classroom 120 -1 96 130 108 CD 10 RD Flowhood 1.00
Outlet-04 Classroom 120 110 92 135 113 CD 10 RD Flowhood 1.00
ERV-408 Exhaust Inlet Summary
$y nlem01n t Areassroom Airflow Airfi _370 Diff. Airflow Di
5 EG 30x26 Flowhood 1.00
Velocity Report Version: 1.0 Page 22 of 28
locit
V
DING TECHNICAL SERVICES
Energy Recovery Unit
PROJECT: Southside Elementary School DATE: 8/23/2023
LOCATION: Shelton, WA
PROJECT#: 802039691
SYSTEM/UNIT: ERV-409 Tested By: Angela Roper
AREA: Classroom Date: 8/21/2023
Unit Manufacturer Daikin ERV-409/EF
Unit Model Number VAM470GVJU Motor HP 3/8 HP
Unit Serial Number F002474 Motor Rated Volts 208 Volts
Unit Type Plate Exchanger Motor Phase 1 Ph
Unit Condition New Motor Hertz 60 Hz
ERV-409/EF Filter Motor FL Amps 3.5 Amps
Filter Type Washable Drive Type Direct Drive
Filter Qty-S1 1 ERV-409/SF
Filter Size-S1 29 3/4 x 9 x 3/8 Motor HP 3/8 HP
ERV-409/SF Filter Motor Rated Volts 208 Volts
Filter Type Washable Motor Phase 1 Ph
Filter Qty-S1 1 Motor Hertz 60 Hz
Filter Size-S1 29 3/4 x 9 x 3/8 Motor FL Amps 3.5 Amps
Drive Type Direct Drive
S/Fan Design Airflow 450 CFM
S/Fan Actual Airflow 420 CFM
E/Fan Design Airflow 400 CFM
E/Fan Actual Airflow 360 CFM
ERV-409/EF
Motor Volts T1-T2 210 Volts
Motor Amps T1 1.10 Amps
Speed Low
ERV-409/SF
Motor Volts T1-T2 210 Volts
Motor Amps T1 1.20 Amps
Speed Low
ERV-409 Supply Outlet Summary
"O.tleMt-011Classroom 110 130 1 118 1 105 95 1 CD 10 RD Flowhood 1.00
Outlet-02 Classroom 115 130 1 113 1 105 1 91 1 CD 10 RD Flowhood 1.00
Outlet-03 Classroom 115 130 113 10 1 91 CD 10 RD Flowhood 1.00
Outlet 04 1 Classroom 1 110 130 118 1 105 95 CD 10 RD Flowhood 1.00
ERV-409 Exhaust Inlet Summary
t Type
iff. LxYV! Factor
Inlet-01 Classroom 400 470 118 360 90 E 30x26 Flowhood 1.00
Velocity Report Version: 1.0 Page 23 of 28
10 Ot
e a
V
DING TECHNICAL SERVICES
Energy Recovery Unit
PROJECT: Southside Elementary School DATE: 8/23/2023
LOCATION: Shelton,WA
PROJECT#: 802039691
SYSTEM/UNIT: ERV-410 Tested By: Angela Roper
AREA: Classroom Date: 8/21/2023
Unit Manufacturer Daikin ERV-410/EF
Unit Model Number VAM470GVJU Motor HP 3/8 HP
Unit Serial Number F002456 Motor Rated Volts 208 Volts
Unit Type Plate Exchanger Motor Phase 1 Ph
Unit Condition New Motor Hertz 60 Hz
ERV-410/EF Filter Motor FL Amps 3.5 Amps
Filter Type Washable Drive Type Direct Drive
Filter Qty-S1 1 ERV-410/SF
Filter Size-S1 29 3/4 x 9 x 3/8 Motor HP 3/8 HP
ERV-410/SF Filter Motor Rated Volts 208 Volts
Filter Type Washable Motor Phase 1 Ph
Filter Qty-S1 1 Motor Hertz 60 Hz
Filter Size-S1 29 3/4 x 9 x 3/8 Motor FL Amps 3.5 Amps
Drive Type Direct Drive
S/Fan Design Airflow 480 CFM
S/Fan Actual Airflow 475 CFM
E/Fan Design Airflow 405 CFM
E/Fan Actual Airflow 395 CFM
ERV-410/EF
Motor Volts T1-T2 211 Volts
Motor Amps T1 1.40 Amps
Speed High
ERV-410/SF
Motor Volts T1-T2 211 Volts
Motor Amps T1 1.40 Amps
Speed High
ERV-410 Supply Outlet Summary
4m Final %Final tC
t
SizeIn riitne AK
F ctor
Outlet-01 Classroom 120 120 100 120 100 Flowhood 1.00
Outlet-02 Classroom 120 115 96 115 96 Flowhood 1.00
Outlet-03 Classroom 120 120 100 120 100 Flowhood 1.00
Outlet-04 Classroom 120 120 100 120 100 CD Flowhood 1.00
ERV-410 Exhaust Inlet Summary
Inlet-01 Classroom 405 305 75 395 98 EG 30x26 Flowhood 1.00
Velocity Report Version: 1.0 Page 24 of 26
ot
10CI
BUILDING TECHNICAL SERVICES
Energy Recovery Unit
PROJECT: Southside Elementary School DATE: 8/23/2023
LOCATION: Shelton,WA
PROJECT#: 802039691
SYSTEM/UNIT: ERV-411 Tested By: Angela Roper
AREA: Classroom Date: 8/21/2023
Unit Manufacturer Daikin ERV-411/EF
Unit Model Number VAM470GVJU Motor HP 3/8 HP
Unit Serial Number F002473 Motor Rated Volts 208-230 Volts
Unit Type Plate Exchanger Motor Phase 1 Ph
Unit Condition New Motor Hertz 60 Hz
ERV-411/EF Filter Motor FL Amps 3.5 Amps
Filter Type Washable Drive Type Direct Drive
Filter Qty-S1 1 ERV-411/SF
Filter Size-S1 29 3/4 x 9 x 3/8 Motor HP 3/8 HP
ERV-411/SF Filter Motor Rated Volts 208-230 Volts
Filter Type Washable Motor Phase 1 Ph
Filter Qty-S1 1 Motor Hertz 60 Hz
Filter Size-S1 29 3/4 x 9 x 3/8 Motor FL Amps 3.5 Amps
Drive Type Direct Drive
S/Fan Design Airflow 420 CFM
S/Fan Actual Airflow 476 CFM
E/Fan Design Airflow 375 CFM
E/Fan Actual Airflow 441 CFM
ERV-411/EF
Motor Volts T1-T2 211 Volts
Motor Amps T1 1.50 Amps
Speed High
ERV-411/SF
Motor Volts T1-T2 211 Volts
Motor Amps T1 1.40 Amps
Speed High
Log: ERV-411 8/21/2023 Angela Roper Supply duct ties into outlets on FCU-411.
Velocity Report Version: 1.0 Page 25 of 28
10 et
BUILDING TECHNICAL SERVICES
Energy Recovery Unit
PROJECT: Southside Elementary School DATE: 8/23/2023
LOCATION: Shelton,WA
PROJECT#: 802039691
SYSTEM/UNIT: ERV-411/Exhaust Duct Tested By: Angela Roper
AREA: ERV-411 Date: 8/21/2023
Type of Traverse Round Sum of Readings 8920
Diameter 12.00 in. Average Reading 558 FPM
Air Flow Area 0.79 sq.ft. Reading Std.Dev. 151 FPM
Number Of Rows 2 Design Total Flow 375 CFM
Readings Per Row 8 Actual Total Flow 441 CFM
Total Readings 16 Duct Static Press. -0.06 in.we
Location of Holes 1 Left
Location of Holes 2 Bottom
Traverse Data Points
12 •I
561
Hole 1 150 39�7 ® ® 619 ® ® 705 �
6fi1
M
O
AL
Velocity Report Version: 1.0 Page 26 of 28
loat
VDING TECHNICAL SERVICES
Energy Recovery Unit
PROJECT: Southside Elementary School DATE: 8/23/2023
LOCATION: Shelton, WA
PROJECT M 802039691
SYSTEM/UNIT: ERV-411/Supply Duct Tested By: Angela Roper
AREA: ERV-411 Date: 8/21/2023
Type of Traverse Round Sum of Readings 9625
Diameter 12.00 in. Average Reading 602 FPM
Air Flow Area 0.79 sq.ft. Reading Std.Dev. 158 FPM
Number Of Rows 2 Design Total Flow 420 CFM
Readings Per Row 8 Actual Total Flow 476 CFM
Total Readings 16 Duct Static Press. 0.42 in.we
Location of Holes 1 Bottom
Location of Holes 2 Right
Traverse Data Points
12
s�4
579
t ® 1 ® ® ® ® Fn7s ® Hale 2
491
766
9HQ
ai
O
Velocity Report Version: 1.0 Page 27 of 28
10 Ot
V
DING TECHNICAL SERVICES
Energy Recovery Unit
PROJECT: Southside Elementary School DATE: 8/23/2023
LOCATION: Shelton,WA
PROJECT#: 802039691
SYSTEM/UNIT: ERV-412 Tested By: Angela Roper
AREA: Classroom Date: 8/21/2023
Unit Manufacturer Daikin ERV-4121EF
VAM470GVJU Motor HP 3/8 HP
Unit Model Number Motor Rated Volts 208 Volts
Unit Serial Number F002472 1 Ph
Unit Type Plate Exchanger Motor Phase
New Motor Hertz 60 Hz
Unit Condition Motor FL Amps 3.5 Amps
ERV-412/EF Filter Direct Drive
Filter Type Washable Drive Type
Filter Qty-S1 1 ERV-412/SF 3/8 HP
29 3/4 x 9 x
Filter Size 3/8 Motor HP S1 Motor Rated Volts 208 Volts
ERV-412/SF Filter Motor Phase 1 Ph
Filter Type Washable 60 Hz
Filter Qty-S1 1 Motor Hertz
29 3/4 x 9 x 3/8 Motor FL Amps 3.5 Amps
Filter Size S1 Drive Type Direct Drive
S/Fan Design Airflow 450 CFM
S/Fan Actual Airflow 435 CFM
E/Fan Design Airflow 375 CFM
E/Fan Actual Airflow 340 CFM
ERV-412/EF
Motor Volts T1-T2 211 Volts
Motor Amps T1 1.40 Amps
Speed High
ERV-412/SF
Motor Volts T1-T2 211 Volts
Motor Amps T1 1.50 Amps
Speed High
Lag: ER 8/17/2023 Angela Roper FSD on exhaust duct does not open.No power
coming in,verified power at the junction box where
the supply FSD wiring comes in. Manually opened to
allow airflow.
ERV-412 Supply Outlet Summary
Area Served esign Pt¢t m o rem o
Ai w i Airflo, Di— T
Outlet-01 Classroom 105 105 100 105 100 CD 10 RD Flowhood 1.00
O'tlet-02 Classroom 105 110 105 110 105 CD 10 RD Flowhood 1.00
Outlet-03 Classroom 105 115 110 115 110 CD 10 RD Flowhood 1.00
Outlet-04 Classroom 105 105 100 105 100 CD 10 RD Flowhood 1.00
ERV-412 Exhaust Inlet Summary
Inlet-01 Classroom 375 0 0 340 91 EG 38x16 Flowhood 1.00
Velocity Report Version: 1.0 Page 28 of zu
ot
eloa
BUILDING TECHNICAL SERVICES
AC or ACU Air Conditioning Unit EAT Entering Air Temperature AP Pressure Drop.
AHU Air Handling Unit EF Exhaust Fan PH Phase
Ak The area of an opening in sq./ft. EG/ED Exhaust Grille/Diffuser PSI Pounds per Square Inch
ATM Atmosphere EMS Energy Management System RA Return Air
AVG Average ERU Energy Recovery Unit RAT Return Air Temperature
BHP Brake Horsepower FHT Fume Hood Test RF Return Fan
CAV Constant Air Volume FPB Fan Powered Box RH Relative Humidity
CBV Cal. Balance Valve FPM Feet per Minute RHC Reheat Coil
CC Cooling Coil FT Foot, Feet RPM Revolutions per Minute
CD Ceiling Diffuser GPM Gallons per Minute RTU Roof Top Unit
CFM Cubic Feet per Minute HC Heating Coil SA Supply Air
CH Chiller TDH—Total Dynamic Head- Pump SAT Supply Air Temperature
CHWS Chilled Water Supply HEPA High Efficiency Particulate S.F. Service Factor
Arrestance
CHWR Chilled Water Return HP Horsepower SF Smoke/Fire Damper
CP Circulating Pump HVAC Heating Ventilation and AC SWG Sidewall Grille
CD/CR Ceiling Diffuser/Register HWS Heating Water Supply TAB Test,Adjust& Balance
CRAC Computer Room AC HWR Heating Water Return TEMP Temperature
CRU Computer Room Unit HX Heat Exchanger TON 12,000 BTUH (Cooling
CT Cooling Tower HZ Hertz, cycle/second of current TSTAT Thermostat(T)
CU Condenser Unit in.w.g. inches of water gauge TSP Total Static Pressure
CUH Cabinet Unit Heater K-factor Correction factor to the UH Unit Heater
free area needed to calculate CFM
CWS Condenser Water Supply KW Kilowatts V Volt—Either AC or DC
CWR Condenser Water Return LAT Leaving Air Temperature VAV Variable Air Volume box
D Discharge LWT Leaving Water Temperature VD Volume Damper
DAT Discharge Air Temperature MAU Make-up Air Handling Unit VEL Velocity(usually in FPM)
DB Dry Bulb MBH 1,000 BTUH VFD Variable Frequency Drive
DDC Direct Digital Controls NT Not Tested VVT Variable Volume Terminal
DP Differential Pressure OSA Outside Air W.G. Water Gauge
DNA Data not available or given OBD Opposed Blade Damper WB We Bulb
DNV Data Not Visible OD Outside Diameter
1) TAB—Test the quantitative performance of a system then regulate it to a specific rate and to the proportion the flow
according to the design
2) Flowhood—Instrument used by a Balancer to capture air and measures and reports in CFM
3) Total Static Pressure-Difference in pressure from the inlet to the discharge of a fan added together
4) Economizer—Components and controls that allow an air handler to effectively use outside air instead of mechanical
cooling to save energy and provide building pressurization
5) Total Dynamic Head-The difference between the pressure of a fluid entering a pump vs exiting added together
6) Design Tolerance—Specified by the designer or+/-10%
7) Ratio of Tolerance-Used to verify that terminals and/or the system are within Design Tolerance; Example 90%-110%
of design if design was 250 then.90/1.10=1.22 and flow between 275CFM-225CFM would be acceptable
tesntes,ADAIST cs AND eu.aMcsw DUMU
TM veo"881am"Is CHMB-
eloa
BUILDING TECHNICAL SERVICES Y
Balancing Equipment List
Calibration
Equipment Manufacturer Model/Serial Number Date
Thermo-Hygrometer Testo 605i/49309620 10/25/2021
Hot-Wire Anemometer Testo 405i/48907852 10/25/2021
IR Thermometer Testo 805i/49611867 10/25/2021
Vane Anemometer Testo 410i/49008393 10/25/2021
DP Manometer Testo 510i/49101891 10/25/2021
Volt Meter Fluke 323/43541454WS ---
Wrist Recorder Evergreen Telemetry 9201516 N/A
DP Sensor Evergreen Telemetry 1900286 11/11/2021
DP Sensor Evergreen Telemetry 1700326 11/11/2021
Flow Hood Evergreen Telemetry 18in base/1900135 N/A
TESTUNk ADJUSMO AM MALANOMMi MUrAW
TM ROFUSMUAL,eMO!eM-