Loading...
HomeMy WebLinkAboutSpecial Inspection Report for COM2010-00042 - COM Engineering / Geo-Tech Reports - 12/14/2010 GQ,M �o -6Gby Z �w,v%rotech �vt,g%l�.eer�wg (�-,eotechvUwL° evwlroKvKevLtal°Draioage ° _oadwnt 11!!CE t DEC r r�� 1 December 14, 2010 426 h! 6 2019 r-• Martig Engineering TO g E KEPT IN T' ' E�qR ST PO Box 11850 /� Olympia, Washington 98508-1850 Ply R`1 E L F I I Z%gol_�o - 600g3 RE: Special Inspection Report for the Harstine Island Estates Association Emergency Replacement of Water Storage Tanks, Mason County, Washington Dear Mr. Martig, Envirotech Engineering (Envirotech) has been authorized by Mason County to perform special inspection duties for the referenced project. Inspection services included observing and/or testing of the high strength bolting installation, anchor bolt operations, and construction of the water storage tank's reinforced concrete foundation. Special inspections were completed by Michael Staten, P.E. with Envirotech on several occasions from September 30, 2010 to December 11, 2010. Concrete cylinders were tested by Krazan & Associates upon 7 days and 28 days after placement of the concrete. Water storage tank information was provided by Martig Engineering which included plans and specifications from both Martig Engineering and Tank Connection, the tank manufacturer. Foundations were observed to bear on very dense glacial till, suitable for this type of structure. Reinforcement steel for the foundation was observed to conform to plans and specifications. Poured concrete was tested and observed to be acceptable for the placement of the ring foundation. Concrete testing revealed a slump of approximately 3 inches, and temperature of 64 degrees. Test results for the 28-day concrete breaks exceeded the required 4000 psi design strength. See attached. Tank bolting was observed to meet or exceed specification requirements. Panel bolts supplied by the tank manufacturer were torqued to an average of 90 ft-lb, which exceeded tank requirements. Anchor bolts, 7/8" in diameter embedded 8 inches deep, were epoxied (Hilte RE 500) into pre-drilled holes within the foundation. Anchor bolt installation appeared to meet or exceed specifications. Envirotech Engineering Special Inspection Report Ph. 360-275-9374 Page 1 of 2 Harstine Island Estates Association Fax 360-2754789 Water Storage Tank December 14,2010 Please contact Michael Staten at 360-275-9374 if you have any questions, comments, or require additional information. Best Regards, Envirotech Engineering y CLYDE ��G��aF WAS}jl cTq� rP 43045 <v4 01, R�°cIs �SSI�NALE��` Michael Staten, P.E. Project Director cc: Mason County Department of Community Development Envirotech Engineering Special Inspection Report Ph 360-275-9374 Page 2 of 2 Harstine Island Estates Association Fax 360-275-4789 Water Storage Tank December 14,2010 r ATTACHMENTS KRAZAN CONCRETE BREAKS Krazan&Associates,Inc. 1230 FINN HILL RD. POULSBO WA 98370,(360) 598 2126 Project No. 106-10 Cyl.Code P 18517 Pour Date 9/30/2010 Report No. 48674 Weather Jurisdiction Permit No. Project HARSTINE ISLAND ESTATES ASSOC. Engineer Location Architect Client ENVIROTECH ENGINEERING Contractor ENVIROTECH ENGINEERING Field Data CYLINDER REPORT Reported Batch Data Concrete X Other Design Actual Weights Weights Supplier BAYSIDE REDI Plant No. Site Mix Mix No. Cem.lbs. Mix Air Unit F.Ash lbs. Slump Temp. Temp. Wt. C.agg.lbs.1 Time Truck# Ticket# %Air (in.) (F) (F) (pcf) C.agg.lbs.2 - - C.agg.lbs.3 Sand lbs. Water lbs. Placement Area Air Ent.(oz) Location RAIN FOUNDATION Other(oz) - - Other(oz) - Other(oz) - Other(oz) Water Added on Job(gals.) Field Test Methods Remarks SAMPLED AND DELIVERED BY CLIENT ASTM C143 ASTM C138 ASTM C1064 ASTM C173 ASTM C31 Other Inspector CLIENT Laboratory Data Design Strength 4,000 @ 28 days Date Specimens Rec'd. 10/1/2010 Cyl. Test Field Max. Comp. Tested Break Laboratory Code Date Cure Age Dim. Area C.F. Load Str. (psi) Set# By Type Test Methods P18517 10/7/2010 7 4X8 12.56 46175 3,680 AC 3 X ASTM C39 P18517 10/28/2010 28 4X8 12.56 63380 5,050 ZL 3 ASTM C109 P18517 10/28/2010 28 4X8 12.56 63220 5,030 ZL 1 ASTM C617 P18517 X ASTM C1231 P18517 ASTM C780 P18517 Other P18517 P18517 Test Results Remarks X Conforming Results Reviewed By Date Reviewed Non-Conforming Codes for Break Types: 1: Cone 2: Cone&Split 3: Cone &Shear 4: Shear 5: Columnar(Split) Measurement Uncertainties: ASTM C-39+/-8% Form 03101 Revision 2