RE: Special Inspection Report for the Harstine Island Estates Association Emergency
Replacement of Water Storage Tanks, Mason County, Washington
Dear Mr. Martig,
Envirotech Engineering (Envirotech) has been authorized by Mason County to perform
special inspection duties for the referenced project. Inspection services included
observing and/or testing of the high strength bolting installation, anchor bolt operations,
and construction of the water storage tank's reinforced concrete foundation.
Special inspections were completed by Michael Staten, P.E. with Envirotech on several
occasions from September 30, 2010 to December 11, 2010. Concrete cylinders were
tested by Krazan & Associates upon 7 days and 28 days after placement of the concrete.
Water storage tank information was provided by Martig Engineering which included
plans and specifications from both Martig Engineering and Tank Connection, the tank
manufacturer.
Foundations were observed to bear on very dense glacial till, suitable for this type of
structure. Reinforcement steel for the foundation was observed to conform to plans and
specifications.
Poured concrete was tested and observed to be acceptable for the placement of the ring
foundation. Concrete testing revealed a slump of approximately 3 inches, and
temperature of 64 degrees. Test results for the 28-day concrete breaks exceeded the
required 4000 psi design strength. See attached.
Tank bolting was observed to meet or exceed specification requirements. Panel bolts
supplied by the tank manufacturer were torqued to an average of 90 ft-lb, which exceeded
tank requirements. Anchor bolts, 7/8" in diameter embedded 8 inches deep, were epoxied
(Hilte RE 500) into pre-drilled holes within the foundation. Anchor bolt installation
appeared to meet or exceed specifications.
Envirotech Engineering Special Inspection Report
Ph. 360-275-9374 Page 1 of 2 Harstine Island Estates Association
Fax 360-2754789 Water Storage Tank
December 14,2010
Please contact Michael Staten at 360-275-9374 if you have any questions, comments, or
require additional information.
Best Regards,
Envirotech Engineering
y CLYDE
��G��aF WAS}jl cTq�
rP 43045 <v4
01, R�°cIs
�SSI�NALE��`
Michael Staten, P.E.
Project Director
cc: Mason County Department of Community Development
Envirotech Engineering Special Inspection Report
Ph 360-275-9374 Page 2 of 2 Harstine Island Estates Association
Fax 360-275-4789 Water Storage Tank
December 14,2010
r
ATTACHMENTS
KRAZAN CONCRETE BREAKS
Krazan&Associates,Inc. 1230 FINN HILL RD. POULSBO WA 98370,(360) 598 2126
Project No. 106-10 Cyl.Code P 18517 Pour Date 9/30/2010 Report No. 48674
Weather Jurisdiction Permit No.
Project HARSTINE ISLAND ESTATES ASSOC. Engineer
Location Architect
Client ENVIROTECH ENGINEERING Contractor ENVIROTECH ENGINEERING
Field Data CYLINDER REPORT Reported Batch Data
Concrete X Other Design Actual
Weights Weights
Supplier BAYSIDE REDI Plant No. Site Mix Mix No.
Cem.lbs.
Mix Air Unit F.Ash lbs.
Slump Temp. Temp. Wt. C.agg.lbs.1
Time Truck# Ticket# %Air (in.) (F) (F) (pcf) C.agg.lbs.2
- - C.agg.lbs.3
Sand lbs.
Water lbs.
Placement Area Air Ent.(oz)
Location RAIN FOUNDATION Other(oz) - -
Other(oz) -
Other(oz) -
Other(oz)
Water Added on Job(gals.)
Field Test Methods
Remarks SAMPLED AND DELIVERED BY CLIENT ASTM C143 ASTM C138
ASTM C1064 ASTM C173
ASTM C31 Other
Inspector CLIENT
Laboratory Data Design Strength 4,000 @ 28 days Date Specimens Rec'd. 10/1/2010
Cyl. Test Field Max. Comp. Tested Break Laboratory
Code Date Cure Age Dim. Area C.F. Load Str. (psi) Set# By Type Test Methods
P18517 10/7/2010 7 4X8 12.56 46175 3,680 AC 3 X ASTM C39
P18517 10/28/2010 28 4X8 12.56 63380 5,050 ZL 3 ASTM C109
P18517 10/28/2010 28 4X8 12.56 63220 5,030 ZL 1 ASTM C617
P18517 X ASTM C1231
P18517 ASTM C780
P18517 Other
P18517
P18517 Test Results
Remarks X Conforming
Results Reviewed By Date Reviewed Non-Conforming
Codes for Break Types: 1: Cone 2: Cone&Split 3: Cone &Shear 4: Shear 5: Columnar(Split)
Measurement Uncertainties: ASTM C-39+/-8%
Form 03101
Revision 2