HomeMy WebLinkAboutWet Automatic Sprinkler Test Report - FIR Inspections - 8/29/2014 °i Fire One, Inc. I L�-'C530)j FIRE0I*099KW FIRE PROTECTION SERVICE/SALES 107 Washington Blvd. Algona,WA 98001 (206) 575-0311 FAX(253)735-4976 Bremerton (360)478-0428 WET AUTOMATIC SPRINKLER CONFIDENCE TEST REPORT (One System Per Report) Certification Given CONFIDENCE TEST El REPAIRS ❑ I ❑ RED ❑ WHITE ❑ GREEN Occupant Name North Mason School District: Sand Hill Elementary Property Address 791 NE Sand Hill Rd., Belfair, WA 98528 Building Owner/Mgmt Co NMSD Phone No. 360-277-2120 Responsible Person Tom IE-Mall Date of Inspection 8/7/20141 Inspection Type ❑ Annual ❑emi-Annual Duarterly(High Rise) Testing Technician Tom Phillips Location of System Office Design Density 0.00/ft(example .495/2000 sq. ft) Central Station Monitoring? El YES ❑ NO I Monitoring Company Name jAlarm Center Control Panel Manufacturer/Model I Mirtone 7800 Acct. No. 1 521-148 PROBLEMS FOUND: (If additional room is needed, please add a separate sheet) 2 water guages are outdated no tag for 5-year backflush and internal pipe exam CORRECTIONS MADE Date Made 8/29/2014 Corrected By Richard If additional room is needed, please add a separate sheet Performed 5-year backflush and internal pipe exam replaced outdated gauges This certifies that this fire and life safety system has been properly inspected for reliability to cover the items listed in this report and is consistent with Fire Department Fire Code standards, and that discrepancies are noted and have been reported to the building Owner/Manager for corrective action. Phone# 206-575-0311 Signature of Tester Testing Agency FIRE ONE INC. 107 WASHINGTON BLVD ALGONA WA 98001 Building Rep. Signature e The items on the checklists below shall be inspected and tested. This list does not constitute all of the required inspecting and testing of the fire and life safety system. Flow ; Yes No o test conducted Static pressure 120 psis Flow pressure 110 _psi_ Number Of sprinkler heads? _ 2 inch drain?. ❑ . .YES, ❑ OTHER Flow switches su erviso switches and alarm bells tested? ❑ N/A 21 Yes ❑ No p rY _ Pressure regulating valves tested? ❑` N/A ': ❑ Yes ❑ 'No _Alarm bell operates? ❑ N/A 0 Yes ❑ No System inspected-and lubricated? O. NSA Yes ❑ No Valves are sealed or supervised? 0 Yes ElNo _ Signs are pr`.ovided`on valves?° O ` Yes. ❑`` No Pumper connections and clapper valves unobstructed and turn freely? ❑ Yes ❑ No Wet t e sprinkler heads re laced or�successfuIl .sam' le tested in 'la'st 50 Yp p. p Y p ears?t YEAR 1988 Yes ❑ No Y -- Sprinkler coverage is acceptable? Yes ❑ No Proper number ofspare._sprinkler heads available? 1Z Yes El' , No System left in service? 0 Yes ❑ No System gauges.replaced or calibrated,every,5,years? YEAR, A988 ❑ .Yes 21 No. Sprinkler heads free of corrosion, paint,, obstructions and/or physical damage? 0 Yes ❑ No Was:debris found.in the:Fire,Department;Connectioh�,(FDC)? Q Yes p. _No_ Was the Fire Department Connection (FDC) back flushed within the last 5 years? Date Performed unknown ❑ Yes ❑ No Was an Internal pipe,and valve inspection;..performed every 5.yrs? ❑ CPCP;�❑Unknown' ❑ Yes ❑ No Was a signal received at the Central Station monitoring company? ❑ N/A l] Yes ❑ No Sprinkler wrench:available for each;type of sprinkler? ❑. Yes [] No INSPECTORS COMMENTS FOR OFFICE USE ONLY Received Repairs Scheduled Complete Sent