HomeMy WebLinkAboutFIR2024-00031 Fire Alarm Certification Final Test - FIR Inspections - 9/13/2024 Mason County Fire Marshal 615 W.Alder St. Shelton WA 98584 Phone: 360-427-9670 x 309 Fire Alarm Certific anon/Final Test FIR ZoZ4-Gvv3/ Location: 2yk7 i%, Contractor: Phone #: Contact: ,G,,G Test Date: L� CHECKLIST Verify panel is in "Normal" condition and clear of any signals ScC, Kill Power At Electrical Panel j AC Trouble/No Power i panel &verify dedicated circuit, red breaker& lockout Activate device(s), verify it activates the alarm and shows correctly on the panel Check the Notification Alarm Circuit(NAC) for activation of devices.Walk building while alarm is activated under battery load. Check for all lights and sounds to be in-sync V Silence Alarm ✓ Activate a few other devices in different areas to verify alarm reactivates after being silenced Reset Alarm Does panel still show trouble (due to AC power)? Disconnect Signal Loop Circuit (SLC)to create/verify a trouble for each device on circuit Reconnect SLC. System should reset& only AC trouble showing Disconnect the communication line &verify communication trouble 6ec 6--/"07r, ✓ Do batteries AMP/HR match plans? FACP Sign on Door(s) leading to panel location? Notification Device Device Test Log Time Comments Smoke detector at FACP Waterflow Inspector's Test Tamper Switch Manual pull at Z Manual pull at Manual pull at Heat Detector Heat Detector Heat Detector Heat Detector Heat Detector Smoke Detector C;y 4 Smoke Detector l,�crt 20 Smoke Detector Punch List/Comments: Z'alirx�­A ro ZL1^1 CA A� A,,/,,5 a/� Al /xf1� GoiYIM �i9LS �✓�%�,f,!/ �:�! �%i1G.S l�,�Y�C 9�.s�/ZY- Passed Final Test? Yes No 7/�/Z� L� r�ccPt"cT Go.•� ��c:�G.rrG,•,� Lnd,sys� r�;;r���/brr►�/ r >f MASON COUNTY FIRE MARSHAL Mason County Bldg.8 615 W Alder St,Shelton,WA 98584 (360)427-9670 Ext.309 F I R20 OQ�� Mason County Fire Protection System Permit Application To avoid any delays,please complete all anglicable sections Owner: Mary M Knight School Phone#: Mailing Address: 2987 Matlock-Brady Road City: Elma State: WA Zip: 98541 Site Address: 2984 Matlock-Brady Road City: Elma State: WA Zip: 98541 Parcel #: Legal Description: Contractor: Red Sky Security, LLC Phone#: 253-777-9173 Address: 5407 N 45th St City: Tacoma State: WA Zip: 98407 Contractor License#: REDSKSS796J7 Expiration Date: 5/10/2025 Email: ebloyd@redskysecurity.com System Being Installed (Please refer to the link below for all plan submittal and inspection requirements) https://masoiicountywa.gov/community-servicesTiire-marshallindex.php Fire Alarm X Designer NICET Certification# 146032 Level IV Fire Sprinkler Commercial (13): Designer Cert. of Competency# Level Multi-Plex (13R): Designer Cert. of Competency# Level Residential (13D): Designer Cert. of Competency# Level U/G Fire Main: Designer Cert. of Competency# Level Range Hood System: ICC/NAFED Certification# Building Use: Building Sq. Ft: IBC Occupancy Class: IBC Const. Type: Bid Price: Contractors Affidavit: I certify that I am currently registered as a contractor in the State of Washington and am aware of the ordinance requirements regulating the work for which the permit is issued and certify that all work will be in compliance with this ordinance. I acknowledge that no changes will be made without first obtaining written approval from the Mason County Fire Marshal. By: Eric Bloyd Date: 8/21/24 This submittal is for the adding devices to the existing fire alarm system located on the Mary Knight School property. The school has added a portable that will house a classroom and a bathroom. There is a horn strobe in the classroom,strobe only in the restroom and a horn strobe on the exterior of the building. There are two smoke detectors in the classroom. There is also a heat in the bathroom and a pull station at an exit door. The notification devices are connected to the existing nac circuit in the portable installed in 2022. There are 2 strobes,2 horn strobes and an exterior horn strobe on the existing circuit. The existing fire alarm system is a Silent Knight system that is conventional. INDEX Page 1 5601 Heat detector Page 2 Smoke Detector Page 3 Single Action Addressable Pull Station Page 4 Interior Horn Strobe/strobe Page 5 Exterior Horn Strobe � II r Fire Alarm Submittal Mary Knight School 2987 Matlock-Brady Road Elma, WA 98541 Central Mason County Jurisdiction August 1, 2024 L k T' Commercial Fire Alarm Communicators: a COMMERCIAL FIRE Standard & Mercantile Models • Universal full event sole path cellular commercial UL and NFPA 72 Fire Code-Compliant,the StarLink Series fire alarm reporting from any panel brand, virtually Wireless Commercial Fire Alarm Communicators provide universal support for any brand 12V to 24V fire alarm control anywhere panel, reporting in Contact ID and 4/2. With broadest coverage • For use as primary or backup communications on all footprint available in Verizon Network Certified TM CDMA or GSM 12V-24V control panels and FACPs that communicate 3/4G models on the AT&T network, as well as mercantile models, all provide the most economical solution and for easy,versatile using Contact ID and 4/2 (such as on legacy panels) installation. • Reports to any Central Station nationwide, with your Safeguard Accounts& Reliability. For applications currently choice of cellular networks: Verizon Network Certified relying upon quickly-disappearing traditional phone lines, CDMA Or GSM 3/4G on AT&T Starl-ink wireless communicators can be used for primary or backup communications, and will not only safeguard the fire • Easy, flexible installation, activation & online account alarm reporting transmissions for the future, but provide the management end-user monthly savings for each costly FACP-dedicated landline they replace. And,for upgrading older wireless fire alarm • Cost-saving cellular models and plans for any code communicators on 2G and other phased-out cellular networks, requirement. Substantial savings over monthly dedicated standard StarLink Fire Models, SLE-CDMA-FIRE and SLE-GSM- landline charges. And, $70 saving incentive with any 2G FIRE,offer a$70 tradeup incentive to help defray the cost of the Communicator upgrade (unlimited). hardware replacement to the advanced state-of-the-art Starl-ink model of choice. Flexible Performance&Reporting Options.StarLink Fire provides full data reporting,as a primary or backup,to any central station of your choice,without requiring any special equipment on premises. Ultra-affordable plans are available to meet various codes and requirements,with supervisory check-ins from 200 `IFS seconds,to 5-minutes,to an hour. The units are very easily ag`' activated,plans and options are selected,and 24/7 account management is provided all through www.napcocomnet.com. And,Starl-ink Fire Communicators are easily connected to any panel or Fire Alarm Control Panel(FACP)standardly operating between 12V and 24V. Flexible in any application, Starl-ink Fire also comes in standard,or Mercantile Models in metal housings,with code- compliant supervision,with or without using conduit;and choice of power options, powered by the panel or using its own 120V Power Supply. StarLink > compliant standard or mercantile metal models(right and left, respectively). Napco StarLink3 Universal Sole Path Fire Alarm Communicators • Choice of plans with varying supervisory check-ins from • Bonus: Full High-Speed Napco Panel remote 200 seconds,to 5-minutes to 1 hour,Verizon or AT&T uploading/downloading • Patented Signal BoostTM signal amplification circuit . COMPLIANCES: NFPA72 Editions:2013, 2010,2007; -gain performance antenna for longer range UL 864,9th Ed., UL1610, UL985, UL1023, and high and reliability nationwide NYFD(as back-up);CSFM • Money-saving 2G Tradeup incentive credit Q��Q At NETWORK i veri on CERTIFIED 4 StarLink Fire Specifications Ordering Information STANDARD SLE-CDMA-FIRE & SLE-GSM-FIRE MODELS: COMMERCIAL FIRE MODELS* • Durable ABS plastic housing includes three keyhole slots for p g y SLE-CDMA-FIRE Standard ABS Red Fire Sole Path Alarm mounting(fo r commercial application,aligns with triple gang Communicator CDMA Verizon-Network Certified boxes.) • Dimensions: 5-3/8"x 7-7/8"x 1-7/8" (HxWxD) SLE-GSM-FIRE as above, but GSM 3/4G on AT&T Network • Weight: 13.5 oz SLECDMA-CFB-PS Commercial Fire Mercantile model in red metal housing, CDMA,Verizon-Network Certified. Direct 120VAC • 3 LED Indicators-Green,Signal Strength;Amber-Busy/ Powered (w/provisions for backup battery/charger). Or, Optional Activation; Red-Trouble TRF-12 plug-in transformer may be used, where codes permit • Patented Signal BoostTM signal amplification circuit and high-g SLE 4G-CFB-P v 3/ S as above, but GSM 3/4G on AT&T Network gain performance antenna • Operating Environment:0 to 49'C(32-120'F), up to 93% SLECDMA-CFB Commercial Fire Mercantile model in red metal humidity(non-condensing) housing on CDMA,Verizon-Network Certified Powered directly from control panel • 12V-24V Universal FACP Support,auto-current sensing. SLE3/4G-CFB as above, but GSM 3/4G on AT&T Network Support all brands communicating in Contact ID and 4/2 • Powered by Panel, Low current draw,71 mA standby,200mA transmit ACCESSORIES: SLE-DLEXT Optional,as above,for downloading,extends distance MERCANTILE MODELS(similar to above,with): to Napco panel up to 100' • Locking Metal Enclosure with Hinged door& 2 key-slots for wall TRF-12 Optional Plug in AC Transformer, 16.5V/20VA(use is mounting(LED indicators, inside). subject to local code compliance) • Dimensions: 9-5/8"x 11-3/4"x 3-3/8"D(HxWxD) SLE-DLCBL Optional High-Speed Napco Panel Up/download cable • Weight:8 Ibs(max., power supply models) • Electrical Ratings for 120VAC, 60Hz • For Models with Power Supply: A150 Available: StarLink Intrusion Radios in standard and mercantile versions • Input Voltage: 120VAC Nominal • Input Current:400mA maximum SLE-GSM-3/4G Standard Burglary Radio(Black),GSM 3/4G on AT&T • Maximum Charging Current: 200mA Network powered by panel. • Electrical Ratings for+12V SLE-CDMA as above,but CDMA communications,Verizon-Network • For Models without Power Supply: Certified. • Input Voltage: 11-15VDC(power-limited output from listed SLECDMA-CB Commercial Burglary control panel) CDMA Radio,Verizon Certified,in white metal housing.Powered directly • Input Current:71 mA with peak RF transmission current of from control panel. 200mA. SLE3/4G-CB as above,but GSM 3/4G • Electrical Ratings for the IN 1 Burg/Fire Input: , on AT&T Network. • Input Voltage:9-15VDC SLE3/4G-CB-TFCommercial Burglary CDMA,Verizon Certified in white metal • Maximum Input Current: Up to 2mA from FACP NAC circuit housing with power supply powered • Electrical Ratings for IN 2 and IN 3: by plug-in 16.5V/20VA transformer& g provision for battery. • Maximum Loop Voltage: 15VDC s,a • Maximum Loop Current: 1.2mA • Electrical Ratings for 3 PGM Outputs: Z • Open Collector Outputs: Maximum voltage 3V when active; NAPCO 15V maximum when not active SECURMY TECHNOLOGIES,INC. • Maximum PGM Sink Current:50mA mount. 333 Bayview Ave.,Amityville,NY 11701 USA 1-800-645-9445 •Fax:1-631-789-9292 • Operating Environment 0 to 49'C(32-120'F), up to 93% www.napcosecurity.com humidity(non-condensing) � • 12V-24V Universal FACP Support,auto-current sensing. NETWORK Support all brands communicating in Contact ID and 4/2. NFPiC VOff On CERTIFIED COMPLIANCES:NFPA 72 Editions:2013,2010,2007; UL 864,9th Ed.,UL1610,UL985,UL1023;NYFD(as back-up);CSFM *StarLink Fire are also rated to support Intrusion/Burglary alarm reports where applicable.StarUnkT"and Signal Boost are trademarks of NAPCO.Pats.Pending.Specifications subject to change. CNAPCO,NAPCO Security Technologies Inc.(NASDAQNSSG A676 2016.1 *Verizon and Verizon Network Certified, UL,AT&T and other trademarks,are trademarks of their respective companies, and are unaffiliated with NAPCO. 5