HomeMy WebLinkAboutCOM2000-00120 Cancelled Change in Tenant - COM Application - 10/18/2000 >R Case number: -001 ao
(�
Mason Count Y
U
TENANT REVIEW APPLICATION
�'Eomplete the tenant view application and return with floor plan. site plan, pumpers report, and $100.00 fee to
the Mason C r rtt 'sance Center, attn. M MacSems, P.O. Box 186, Shelton, WA 98584. The tenant review
1iN&% ivated on Wednesday after the application has been received. During the evaluation Mason County
mbers from the Building, Fire Marshal, Environmental Health, Planning, and Public Works offices will identify
compliance requirements, if needed, and advise whether a separate building permit will be required.
Date: _, _ �J Assessor's Parcel Number: I2-3Z 61 - 1ttZ" 00
Legal Description:
Building Site Address: ,�E S/ PO.
Method of sewage disposal: O Septic O Sewer- name of district:
Water source: O Well O Community Well O Public System, name of system:
PEOPLE and FIRMS INVOLVED IN THE PROJECT
Name of property owner:
Mailing address:
Day phone: Contact Person: Message phone:
Name of applicant: C_0 ! `eg1UDA)� 11,4120w44,
Mailing address: Pp 43ax t-J
Day phone: 7 _0//3 Contact person: Message phone:
Name of Tenant:
Mailing address:
Day phone: Contact person: Message phone:
PROJECT INFORMATION
Proposed business name:
Proposed use: Number of employees:
Previous business name: -"
Previous use:
INFORMATION ABOUT STRUCTURE
Check one: ,$Detached single level/single tenant single level/multi tenant
Multi level/single tenant Multi level/multi tenant
Age of structure: Is structure currentl occupied? If not occupied, how long has it begin vacant?
aS ��S Circle one: es No Yrs mos. _
List square footage for each floor level
Basement: First:36 000 I Mezzanine: Second: Third:
Will structure a heated: Type heating fuel: Circle one: -- -
Circle one: es No ItIollaD Liquid Propane Natural Gas Oil
Type of he ircle one urnace Heat Pump Electric baseboard or wall mount Radiant
Will be any changes to the following? Circle yes or no, if applicable:
Floor lay-out: Yes CNDo Lighting: Yes �Roo
Heating: Yes
Exterior Finishes: Yes o Interior Finishes Yes Parking: Yes SNo
Number of restrooms provi Number of fixtures i each
Is structure ADA Accessible? circle one Yes No
Is the structure equipped with a fire sprinkler system? Yeo larm system? Yes No
Return this application with:
1 j Floor Plan, 2)Site Plan, 3) dumpers Report, and 4) $100 Fee
1) Floor Plan: Include existing walls,proposed walls,and walls that will be removed.
• Draw the floor plan to scale, '/4"= 1 foot min. • Use of rooms
• Room Dimensions • Location of all exits and windows (include dimensions)
• Location of plumbing and mechanical fixtures • Interior doors with swing radius
2) Site Plan: Note scale
• Property lines, easements, & right of ways • Location of all existing structures& dimensions
• Distance, in feet, from property line&structures Landscape buffer yards
• On-site sewage tanks and drainfields, & reserve • Well location
• Surface &stormwater run-off routes • Parking areas (number& arrangement
• Location of fire hydrants &vehicle access roads • Slope of property
3) Pumpers Report
4) Fee: $100.00 Intake fee will be collected when submitted. Additional fees will be collected when the permit is
issued.
1
' Office Use Only
Pre-Application Review Departmental Review
Env. Health Env. Health
Planning Planning
Public Works Public Works
Fire Marshal Fire Marshal
Building Building
NREC NREC
Pre Application required? (circle one) Yes No
Building Permit required? (circle one) Yes No Engineering Required? (circle one) Yes No
Occupancy Classification: Occupancy Change? (circle one) Yes No
Occupancy classification change from to
Type of construction
Occupant load calculated: persons. Existing occupant load design persons.
Fee Schedule
Building P"ermtt # MASON COUNTY
BUILDING 111 426 W. CEDAR
SHELTON, WASHINGTON 98584
(360) 427-9670
ORRECTION NOTICE
Job Locations
This structure has been inspected by Mason County Building Department
and the following VIOLATION of County Laws and Ordinances has been
found: Items Listed below must be corrected to gain code compliance
Z���i� � � �-�
i
You are hereby notified that the above corrections shall be made
BEFORE PROCEEDING WITH ANY FURTHER WORK
❑ Call for re-inspection when corrections are made before continuing
❑ Make corrections, items will be checked on next inspection
❑ OK to
❑ This is not a complete inspection Department
Date Inspector �i LL
nn NOT MnV ' TH1 TA,c ,G
Printed by Mike Barth 7/21/2000 1:46pm
-------- -------------------------------
From: Mike Barth
To: Dave Salzer, Kelly Mayo
Subject: fwd: Belfair Drug Building
---------------------------------------
===NOTE====------=====7/21/2000==11:02=
Dave, I was in the true value hardware
store yesterday and saw where they have
disassembled the self closers on the
fire doors between the two large
portions of building, and have propped
the doors open so that customers can
freely walk between the two sides.
This is a required fire wall between
what used to be Belfair Drug and the
hardware store, and the door is (or was
as the case may be) a 1 1/2 hour rated
door assembly. They have not yet
applied for a tenant change, nor have
they obtained any permits for
remodeling. It appears that there are
probably exiting issues that also need
to be looked at. They currently have
both sides open to the public.
According to Kelly, he spoke with
a Scott McLenden on several occasions
(5/30, 6/6, 6/21) about what will be
required for the change of use/change
of tenant, and Kelly told them not to
proceed until they have applied for the
tenant review and submitted all
necessary layouts, exiting, etc. Kelly
also talked to the contractor, Skip at
the counter about the same issues,
specifically about the fire wall and
how the building will exceed the
allowable areas allowed by the UBC if
this area separation wall is breached.
I know you are busy, but I thought
you would be interested in this, and
that this circumstance might warrant a
visit by you.
Fwd=by:=Dave=Salzer===7/21/2000==1:44=P
Fwd to: Mike Barth
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
I would ask that Building advise the
occupant that the issues you addressed
are significant and may result in the
revocation of an Occuapncy Certificate
unless resolved asap.
---------------------------------------
Page: 1
Mode : INQUIRY Personal Property Master
Parce h# 10 05300 COMMERCIAL
Bus . Name : BELFAIR TRUE VALUE #308 Loc : 51 NE STATE HWY 300 - BELFAIR
Assoc R/P: State of Incorporation: WA
Taxpayer: BELF 4475 BELFAIR TRUE VALUE #308 T/P Chg Dt :
Owner: K*K* 1000 KKLD, INC T/P Chg By:
Form Status : W WORKED Form Returned: 3022000 Penalty °s
Tax Code : 0276 1 403 A P3 F2 L C H W1 Tax Roll : R REGULAR
Land Use : 5251 HARDWARE Tax Status : TX TAXABLE
Comments :
ABS # Description Amount
2 MANUF & CONTRACT EQ Change Reason: AR ANNUAL REVALUATION
3 OTHER EQUIPMENT 35165 Change Date : 6/02/1998
4 SUPPLIES & MATERIALS 250 Change By: DLC
8 IMPROVEMENTS EX LAND
8a IMPROVEMENTS/LEASED
8b IMPROVEMENTS ONLY
8c LEASED EQUIPMENT
10 OTHER P/P H-O-W Exempt Cd
Total Assessed Value 35415 Sr Cit Code
H-O-W Exemption Sr Cit Exempt AV
Net Assessed Value 35415 CMD 6 - Comments
Inquiry Type VL CMD 7 - EOJ HELP Allowed
v
Vl�
Memorandum
To: Mason County Building Dept
From: Tom I lerstad
Date: 06/20/00
Re: Acc hardware in Belfair
Scott McLendon has asked me to look into the possibility of bleaching an existing
firewall between the new hardware store and the existing Pharmacy store. Being an
'M' occupancy and about 17,000 + square footage in each area I checked the
allowable floor area which is 14,000 sf and then the area increas allowable e fr o
sprinklers. Under the UBC sec. 505 2 unlimited area it says- "The area of any one-
or two-story building of Groups B: f, Division 1 or 2; M, S, Division 1, 2, 3, 4 or S;
And 11, Division 5 Occupancies shall not be limited if the building is provided with
an approved automatic sprinkler system throughout as specified in Chapter 9, and
entirely surrounded and adjoined by public ways or yards not less than 60 feet in
width " This building appears to meet this requirement It is sprinklered and has the
space around it Also, the Iwo spaces are the same occupancy and would not require
an area separation
If my observation is wrong, the openings are not going to be too large, the owner
could install fire doors that are activated by electromagnetic door holders that would
be activated by fire alarm or sprinkler,
Thank you for your consideration. If you have any questions please call at 876-6893
Respectfully submitted
Torn I Ierstad
296 Tremont St.
Port Orchard, WA 98366
t