HomeMy WebLinkAboutConfidence Test Report - FIR Inspections - 5/26/2010 05/26/2010 08: 58 3608953799 INTELLISYSTEMS, INC. PAGE 01/02 -S'o-©1e'00l C 3 l a �10(� Govcv-c� Fire Department Confidence Test Report Address- 18560 E.State Route 3 Date- 5/21/2010 Occupied As- Port Of Allyn Name Of Tester- AA Control Panel Manufacturer- Silent Knight Model' 5207 Type Of Inspection: Quarterly- Annual- X Acceptance- Other- Charge Voltage- 27.1 Battery Voltage- 26.9 Battery Load Voltage- _ 26.5 1 Trouble signal with AC power off..................................................... ...... Yes X No N/A 2 System operates satisfactory on standby power................ ........................ .....Yes X No N/A 3 All signals operate on AC power...........................................................................Yee X No N/A 4 Have all alarm notification appliances been checked for proper operation.....................Yes X No N/A 5 All circuits checked for electrical supervision ......Yes X No N/A 6 Control panel checks made per manufacturer's instructions........................... Yes X No N/A 7 All auxillary equipment operates(elevators,fans,dampers,etc.)................................Yes No N/A X B Central Station or remote connection....................................... .............. Yes X No N/A Name of Monitoring Company Alarm Center 9 Key to panel available................ .......................................................................Yes X No N/A 10 Operating instructions located at panel..................... ..............._.- ...._.....Yes X No N/A 11 Service label or tag........................................................................................... Yes X No N/A SATISFACTORY TYPE OF EQUIPMENT NO OF UNITS TESTED YES NO N/A TOTAL Audible Alarm Devices 4 X 4 Visual Alarm Devices 4 X 4 Trouble Indicators 1 X 1 Heat Detectors g 9 Smoke Detectors 2 X 2 Duct Detectors X Manual Pull Stations 5 X 5 Ventilation Controls X Central Station 1 X 1 Annunciators 1 X 1 Elevator Call Down X Auto Sprinkler Flow Switches X Auto Sprinkler Su srviso Switches X Fire Dampers/Smoke Dampers X Auto Door Release X Auto Door Unlocks(Failsafe) X Problems Found- Signature of Tester- o 09l[.,.�iscax IntelliSystems,Inc. P.O.Box 592-Port Orchard,WA 98386 Phone(360)895-7995 05/26/2010 08: 58 3608953799 INTELLISYSTEMS, INC. PAGE 02/02 6 So -- o$rb 0 cam# obo31,0 MP'CSC \j Gou Fire Department Confidence Test Report Address- 18560 E. State Route 3 Date- 5/21/2010 Occupied As- Port Of Alin Name Of Tester- AA Control Panel Manufacturer- Firelite Model, MP-24 Type Of Inspection. Quarterly- Annual- X Acceptance- Other- Charge Voltage- 27.7 Battery Voltage- 26.9 Battery Load Voltage- 26 1 Trouble signal with AC power off.......................................................................... Yes X No N/A 2 System operates satisfactory on standby power....................... Yes X No N/A 3 All signals operate on AC power...........................................................................Yes X No N/A 4 Have all alarm notification appliances been checked for proper operation.....................Yes X No N/A 5 All circuits checked for electrical supervision..........................................................Yes X No N/A 6 Control panel checks made per manufacturers Instructions.......................................Yes X No NIA 7 All auxiliary equipment operates(elevators,fans,dampers,etc.)................................Yes No N/A X 8 Central Station or remote connection.................................................................... Yes No N/A X Name of Monitoring Company 9 Key to panel available.......................................................... Yes X No N/A 10 Operating Instructions located at panel...................................•................_.___..___..__.Yes X No N/A 11 Service label or tag............................................................. Yes X No N/A SATISFACTORY TYPE OF EQUIPMENT NO OF UNITS TESTED YES NO N/A TOTAL Audible Alarm Devices 2 X 2 Visual Alarm Devices 1 X 1 Trouble Indicators 1 X 1 Neat Detectors X Smoke Detectors X Duct Detectors X Manual Pull Stations 1 X 1 Ventilation Controls X Central Station X Annunciators X Elevator Call Down X Auto Sprinkler Flow Switches X Auto Sprinkler Supervisory Switches X Fire Dampers/Smoke Dampers X Auto Door Release X Auto Door Unlocks(Failsafe) X Problems Found- Signature of Tester- IntelliSygtems, Inc. P_O. Box 592-Port Orchard,WA 98366 Phone(360)895-7996