HomeMy WebLinkAboutCOM2024-00017 Fire Marshal Review - COM Letters / Memos - 10/20/2023 Fire Marshal's Office 615 W. Alder St Shelton WA 98584 rcollins@masoncountywa.gov MEMORANDUM FROM: Randy Collins, Fire Marshal TO: Yuchun Santory yuchunsantory92()-gmail.com DATE: Oct 20, 2023 TOPIC: Fire Conditions, Misty Acres Rebuild, 220 E Misty Acres Ln (COM 2023-00073) The plans for the above-mentioned project have been approved subject to the following conditions: 1. Automatic Fire Sprinkler System: A fire sprinkler system conforming to NFPA 13R shall be required in the building covered under the scope of this permit. IFC 903.2.8 2. Fire Alarm System: A fire alarm system conforming to NFPA-72 shall be required. Said system shall also supervise the fire sprinkler system. IFC 907.2.9.1 3. Fire Pump &Tank: To serve the fire sprinkler system, a NFPA 20 compliant fire pump shall be provided that meets the demands of the sprinkler system. In addition, an approved water tank capable of providing the system demand for 30 minutes shall be provided. IFC 903.2.8 4. Fire Extinguishers: Fire Extinguishers having a minimum 2A-BC rating shall be installed at intervals not to exceed 75' IFC 906.1 If you have any questions regarding the plan review or these conditions, please contact me at: rcollins(aD-masoncountywa.gov