FIR2024-00027 - FIR Inspections - 8/26/2024
Mason County Fire Marshal 615 W. Alder St. Shelton WA 98584 Phone: 360-427-9670 x 309 Fire Alarm Certification/Final Test FIR 7 Location: Contractor: Phone Contact: f3'�«o Test Date: CHECKLIST Verify panel is in "Normal" condition and clear of any signals V Kill Power At Electrical Panel AC Trouble/ No Power,panel &verify dedicated circuit, red breaker& lockout Activate device(s), verify it activates the alarm and shows correctly on the panel Check the Notification Alarm Circuit (NAC) for activation of devices. Walk building while alarm is activated under battery load. Check for all lights and sounds to be in-sync V Silence Alarm -r Activate a few other devices in different areas to verify alarm reactivates after being silenced Reset Alarm Does panel still show trouble (due to AC power)? Disconnect Signal Loop Circuit (SLC) to create/verify a trouble for each device on circuit Reconnect SLC. System should reset & only AC trouble showing Disconnect the communication line & verify communication trouble y Do batteries AMP/HR match plans? / FACP Sign on Door(s) leading to panel location?' o�� ss�c/- =�v�si6�fio.,r�ca���rc✓ Notification Device Device Test Log Time Comments Smoke detector at FACP 5107 -/� v rfY✓ A/� Waterflow Inspector's Test Tamper Switch Manual pull at l y Manual pull at Manual pull at Heat Detector Heat Detector Heat Detector Heat Detector Heat Detector Smoke Detector 1�7 Smoke Detector ',*,sj Z Smoke Detector Punch List/Comments: scowl_ & CG� ,rile o%✓C.i�Jil�J /� oe,5,_7 7_4X AT, 6o V, v4!!f 15 11 of T-'Ef�6 �Z/& Y Passed Final Test? Yes ✓ No SYSTEM RECORD OF COMPLETION This form is to be completed by the system installation contractor at the time of system acceptance and approval. It shall be permitted to modify this form as needed to provide a more complete and/or clear record. Insert N/A in all unused lines. Attach additional sheets, data, or calculations as necessary to provide a complete record. Form Completion Date: 8/24/24 Supplemental Pages Attached: 1. PROPERTY INFORMATION Name of property: Sand Hill Elementary School Address: 791 NE Sand Hill Rd. Belfair,wa.98528 Description of property: School Name of property representative: Address: Phone: Fax: E-mail: 2. INSTALLATION, SERVICE, TESTING, AND MONITORING INFORMATION Installation contractor: Bird Electric Address: 22930 Stottlemeyer Rd.Poulsbo,Wa.98370 Phone: 360-779-2112 Fax: 360-779-2069 E-mail: brian@birdelectric.com Service organization: Guardian Security Address: Phone: Fax: E-mail: Testing organization: Same as service contractor Address: Phone: Fax: E-mail: Effective date for test and inspection contract: N/A Monitoring organization: Same as service contractor Address: Phone: Fax: E-mail: Account number: 77-57" 1 1277 Phone line 1: Phone line 2: Means of transmission: AES Radio Entity to which alarms are retransmitted: Phone: 3. DOCUMENTATION On-site location of the required record documents and site-specific software: NA 4. DESCRIPTION OF SYSTEM OR SERVICE This is a: ®New system ❑ Modification to existing system Permit number: FIR2024-00027 NFPA 72 edition: 2017 4.1 Control Unit Manufacturer: Firel-ite Model number: ES20OX 4.2 Software and Firmware Firmware revision number: N/A 4.3 Alarm Verification ®This system does not incorporate alarm verification. Number of devices subject to alarm verification: Alarm verification set for seconds Copyright®2012 National Fire Protection Association.This form may be copied for individual use other than for resale.It may not be copied for commercial sale or distribution. (p 1 of 3) 5. SYSTEM POWER SYSTEM RECORD OF COMPLETION (continued) 5.1 Control Unit 5.1.1 Primary Power Input voltage of control panel: 120vac Control panel amps: 20amps Overcurrent protection: Type: Breaker /� Amps: 20amps Branch circuit disconnecting means location: NNa )q Number: Breaker 213 5.1.2 Secondary Power Type of secondary power: Lead acid battery Location,if remote from the plant: in Panel Calculated capacity of secondary power to drive the system: In standby mode(hours): 24 In alarm mode(minutes): 5 5.2 Control Unit ® This system does not have power extender panels ❑ Power extender panels are listed on supplementary sheet A 6. CIRCUITS AND PATHWAYS Pathway Type Dual Media Pathway Separate Pathway Class Survivability Level Signaling Line b 0 Device Power Initiating Device Notification Appliance b 0 Other(specify): 0 7. REMOTE ANNUNCIATORS Type Location 8. INITIATING DEVICES Addressable or Type Quantity Conventional Alarm or Supervisory Sensing Technology Manual Pull Stations 6 Addressable Alarm Smoke Detectors 17 Addressable Alarm Photo Duct Smoke Detectors Addressable Supervisory Photo Heat Detectors Addressable Alarm Rate of Rise Gas Detectors Addressable Supervisory CO2 Waterflow Switches 2 Addressable Alarm Tamper Switches 2 Addressable Supervisory Copyright©2012 National Fire Protection Association.This form may be copied for individual use other than for resale.It may not be copied for commercial sale or distribution. ip 2of3i SYSTEM RECORD OF COMPLETION (continued) 9. NOTIFICATION APPLIANCES Type Quantity Description Audible Visible 1-7 System Sensor Strobe Combination Audible and Visible rj(/ System Sensor Speaker/Strobe 10. SYSTEM CONTROL FUNCTIONS Type Quantity Hold-Open Door Releasing Devices 6 HVAC Shutdown 1 Fire/Smoke Dampers Door Unlocking Elevator Recall Elevator Shunt Trip AES Radio 1 ECC50/100 Voice Evac Panel 1 11. INTERCONNECTED SYSTEMS ® This system does not have interconnected systems. ❑ Interconnected systems are listed on supplementary sheet 12. CERTIFICATION AND APPROVALS 12.1 System Installation Contractor This system ass cifie he rem has been installed according to all NFPA standards cited herein. Signed Printed name: Brian Rudebeck Date: 8/24/24 Organi n: ird Electric Title: Dept. Head Phone: 360-779-2112 Orga2��n 12.2 System Operational Test This system as ecified kerep has tested according to all NFPA standards cited herein. Signed: Printed name: Brian Rudebeck Date: 8/24/24 Organ' on Bird Electric Title: Dept. Head Phone: 360-779-2112 12.3 Acceptance Test Date and time of acceptance test: 8/26/24 9:00am Installing contractor representative: Brian Rudebeck Testing contractor repres`entatii e,:: I Brian Rudebeck Property representative: vN / - /AHJ representative: G� r r copyright©2012 National Fire Protection Association.This form may be copied for individual use other than for resale.It may not be copied for commercial sale or distribution. io 3 of Randy Collins From: Randy Collins Sent: Monday,August 19, 2024 7:42 AM To: 'Work' Cc: Moore,Joan Subject: RE: Fire Alarm Plan Approval Brian, I am replying here to memorialize our phone conversation of last week regarding this topic. Since the plans indicated there were fire doors, it created an obligation to meet the requirements of chapter 21.9 of NFPA 72, even if there are currently not any hold-open devices installed. My expectation (as alluded on the plan conditions) is that these will be included in the scope of work and be functioning when you call to schedule the acceptance test. Please let me know if you have any questions. Randy From:Work<brian@birdelectric.com> Sent: Wednesday, August 14, 2024 4:31 PM To: Randy Collins<RCollins@masoncountywa.gov> Cc: Moore,Joan <jmoore@northmasonschools.org> Subject: Re: Fire Alarm Plan Approval Caution: External Email Warning!This email has originated from outside of the Mason County Network. Do not click links or open attachments unless you recognize the sender, are expecting the email, and know the content is safe. If a link sends you to a website where you are asked to validate using your Account and Password, DO NOT DO SO! Instead, report the incident. Hi Randy, Thank you for the quick turn around on these. I do have one question on the conditions you have the door holders having to release and I want to make sure you know they don't have any on those doors. Is the intent of this condition for us to add those to those doors? Please let me know so we can plan accordingly. Thank you Sent from my iPhone On Aug 14, 2024, at 12:19 PM, Randy Collins<RCollns@mas_oncountywa_,gov>wrote: Brian,Joan, I know time is of the essence with this project, so I wanted to let you know the plans were approved today. Please note the conditions. Questions, let me know. i Randy Collins Fire Marshal Mason County 360 427-9670 x309 360 490-0167 Cell <image001.jpg> <FIR2024-00027 Sand Hill FA.pdf> 2 SG�GI I' 6e I Randy Collins From: Randy Collins Sent: Monday,July 22, 2024 11:21 AM To: 'Brian' Cc: Jmoore@northmasonschools.org Subject: Scope of Work for Fire Alarm at Sand Hill Elementary Attachments: FM Std-2 Fire Alarm Plan Submittal Req.pdf 71Z4Zf_ ZSa/"- r/��� C� F- S� OiG LJ4S 6cc , Brian, 7- Sn-, Nice speaking with you this morning. Forth e fire alarm project at this location and based on the requirements of IFC 907.2.3 as adopted by WA, here is the scope of work I have outlined for this project. • Demo all existing devices(smoke,heats, pulls, horn/strobes), • Install new speaker strobes and strobes throughout, • Install smokes on both sides of the three fire doors which upon system activation, close the doors, • Install a smoke and pull at office with new voice panel, • Install addressable modules in the sprinkler room which activate an alarm upon operation of a sprinkler flow • Provide HVAC shutdown on general alarm • Install smokes, pulls and notification in the three sets of un-sprinkled portables. I have also included a copy of our fire alarm standard so if you are awarded the job,you know exactly what are expectations are regarding the submittal and system testing. If you have any question, do not hesitate to contact me. Respectfully, r Randy Collins Fire Marshal Mason County c _ 360 427-9670 x309 Whwt$ Q4t�''�`'� d �t° -are-, 0-11 f 360 490-0167 Cell Gvf �l;ors f•( Randy Collins From: Randy Collins Sent: Monday,July 15, 2024 4:30 PM To: 'Mike Wade' Cc: Tony Staudt;Jmoore@northmasonschools.org Subject: RE: Sand Hill Elementary Fire Alarm Mike, I appreciate the call and the more detailed description you provided on the nature of the problem.After reviewing the IFC section pertaining to fire alarms for schools(907.2.3),there are two options that may be used to satisfy this problem.The first would involve the scope of work you are proposing below. Because the building is covered by the sprinkler system, as long as a sprinkler flow activates the voice communication system and there is a pull station in a normally occupied location(I.E. main office),this option would also permit you to omit all other manual pull stations(907.2.3 exception 5). The second option is to install a system that is consistent with that spelled out in the School's Safe School Plan as identified in RCW 28A.320.125(see link below). However, not being familiar with their plan, I cannot speak to whether this option represents a feasible alternative.To that end, I have cc'd Joan so she can share this with whomever would be involved in this decision process. It is important to note that they wish to pursue this, it will involve an analysis be performed of that plan along with your scope of work first to verify the two are consistent with each other. However, since this will almost certainly lengthen the approvals process so I would that should be taken into consideration. Lastly, if a raceway or conduit is found which permits the alarm to supervise the pump,that should also be addressed but due to time constraints and the need to get the alarm system operational before school resumes, I am willing to defer this for a short while. Please have this conversation with Joan and the those who will be authorizing this work at Sand Hill and let me know how all wish to proceed. Thanks Randy https//appsleg_wa.gov/rcw/default.aspx�cte 28A320.1.25 From: Mike Wade<mwade@guardiansecurity.com> Sent: Monday,July 15, 2024 12:55 PM To: Randy Collins<RCollins@masoncountywa.gov> Cc:Tony Staudt<tony@staudtelectric.com>;Jmoore@northmasonschools.org Subject:Sand Hill Elementary Fire Alarm Importance: High Caution: External Email Warning!This email has originated from outside of the Mason County Network. Do not click links or open attachments unless you recognize the sender, are expecting the i email, and know the content is safe. If a link sends you to a website where you are asked to validate using your Account and Password, DO NOT DO SO! Instead, report the incident. Hi Randy, Thank you for returning my call today. Existing fire panel is conventional 12 zone panel, my guess probably 30ish years old, it is no longer manufactured and there are no conventional panels available with that many zones that I know of. Guardian Security will be proposing a new addressable voice system. Scope would be to demo all existing devices(smoke,heats,pulls, horn/strobes), install new speaker strobes and strobes throughout, install smokes on both sides of the three fire doors,smoke and pull at office with new voice panel, install addressable modules in sprinkler room, provide HVAC shutdown on general alarm, install smokes, pulls and notification in the three sets of un-sprinkled portables. Currently the pump house with the fire pump is not connected to the fire alarm and this would be excluded from our proposal at this time. If during the project we find that there is usable raceway and/or wiring,we can provide the necessary equipment to monitor the fire pump through a change order, or separate project/PO. Guardian Security would be working with Staudt Electric on this project. I have attached a rough layout of what is currently in place now. Thankyou NOTE: ****Seattle Fire Inspections requests are taking up to 2-3 weeks for a response%nfirmed date. Please plan ahead for fire finals. ****AHJ permits can take up to 4-8 weeks for approval. Mike Wade Sales, Fire & Life Safety Systems P: 253-564-4564 Ext 404 F: 253-565-2007 C: 360-990-2043 mwade9guardiansecurity.com C GUARDIAN SECURITY LIFE AND PROPERTY P R O T E C T I O N 2 +� c GUARDIAN SECURITY L / F E A H D P H D P c R 7 Y Q F Q T E C r t 0 t. 1743 Frist Ave South Seattle, WA. 98134 206-622-6545 FIRE PUMP SYSTEM Certification Given (One System per Report) RED YELLOW WHITE ❑ CONFIDENCE TEST ❑ REPAIRS ❑ Occupancy Address. 791 NE SAND HILLROAD Occupancy Name: SAND HILL BELFAIR, WA. 98528 ELEMAENTARY Responsible Person First & Last Name, JOAN MOORE Phone Number: 360-277-7566 Responsible Person Responsible Party Address, City, State, Zip: SAME E—Mail Address Date of Inspection: Inspection Annual 07-11-2024 Frequency/Type: Testers Name (Please Print): JOEL NORRIS Certification Number: 117512 Identification Number: ELECTRIC FIRE PUMP System Location: PUMP HOUSE Central station monitoring? Yes ❑ No ® Monitoring Monitoring Required? Yes ® No ❑ Company Name: NWAMS System Make: System Model: FIRE CODE VIOLATIONS FOUND: (If additional room is needed, please add a separate sheet) 1) THE KUNKLE VALVE DIDN'T RELIEF (200H-E02-MG) AND NEED TO BE REPLACED. 2) JOCKEY PUMP IS THE AUTO SETTING BUT THJE AUTO, HAND AND OFF SWITCH IS INOP. NOTE: FIRE PUMPS ARE NOT SUPERVISED BY THE FACP. CORRECTIONS MADE: Date Corrected: Corrected By: (If additional room is needed,please add a separate sheet) Certification Number: This certifies that this fire and life safety system has been properly inspected for reliability to cover the Items listed in this report and is consistent with Fire Department Fire Code standards, and that discrepancies are noted and have been reported to the building Owner/Manager for corrective action. Signature of Tester: Phone # Building Representative (signature) Fire Pump Page 1 of 2 The items on the checklists below shall be inspected and tested. This list does not constitute all of the required inspecting and testing of the fire and life safety system. Refer to Fire Department Fire Code for inspecting and testing requirements. Electric Pump 1. Starting Amperage Leg 1 Leg 2 Leg 3 2. Running Amperage Leg 1 Leg 2 Leg 3 3. Was electric pump run for a minimum 10 minutes? Yes ® No ❑ Diesel Pump 4. Diesel fuel tank at least 2/3 full? N/A ® Yes ❑ No ❑ 5. Batteries fully charged? N/A ® Yes ❑ No ❑ 6. Oil level full? N/A ® Yes ❑ No ❑ 7. Coolant level full? N/A ® Yes ❑ No ❑ 8. Antifreeze protection adequate? N/A ® Yes ❑ No ❑ 9. Fuel filter/strainer serviced? N/A ® Yes ❑ No ❑ 10. Was diesel pump run for a minimum 30 minutes? N/A ® Yes ❑ No ❑ Pump Controller/s 11. Fire pump controller in service? Yes ® No ❑ 12. Controller voltage 480 VDC Interrupting-Capacity 1,000,000 amps: Yes ® No ❑ 13. Jockey pump controller in service? N/A ❑ Yes ® No ❑ Pump Test 14. Pump in service on inspection? Yes ® No ❑ 15. Pump starts from pressure drop? Yes ® No ❑ 16. Cut-in Pressure 110 psi Cut-out Pressure 240 psi 17. Was 300 GPM flow conducted? Yes ® No ❑ 18. Pressure gauges replaced or calibrated every 5 years? Yes ❑ No 19. Static pressure 20 psi 20. Discharge psi Suction psi IN LINE 21. Hose size: NA in. Tip size: NA in. Hose length: TEST METER ft. 22. Pitot reading: NA GPM: 1500 23. Churn suction 19 psi Churn discharge 145 psi 24. Has pump been tested weekly? Yes ® No ❑ 25. Jockey pump tested? Yes ® No ❑ 26. Shaft seals dripping water properly (1 drop per second)? Yes ® No ❑ 27. Pressure relief valve checked for proper operation? Yes ❑ No 28. Fire pump connected to fire alarm panel? Yes ❑ No 29. Suction screens inspected and cleared? N/A ® Yes ❑ No ❑ 30. Routine maintenance is performed and records kept? Yes ® No ❑ Transfer Switch 31. Power failure simulated during peak flow for automatic transfer switch activation? N/A ® Yes ❑ NO ❑ 32. Connection made to alternate source? N/A ® Yes ❑ NO ❑ 33. Emergency manual starting means operated without power? N/A ® Yes ❑ No ❑ Fire Pump Page 2 of 2 L Seattle Fire Marshal' s Office r 220 3``' Avenue S. Seattle, WA 98104-2608 SUM DE PT. Phone: 206-386-1450 Fax: 206-386-1348 �► System Test Report SPRINKLER STATUS Confidence Test Q Reacceptance Test Q Red Yellow White Occupancy Information Occupancy Name: Sand Hill Elementary contact Name:Joan Moore Occupancy Address: 791 NE Sand hill rd contact Phone: (360) 277-7566 Belfair, wa, 98528 Contact Email: Washington Sprinkler Inventory #of Wet Systems.in the Building:1 #of Wet Systems Tested:1 #of Dry Systems in the Building:0 #of Dry Systems Tested:0 #of Foam Systems in the Building:0 #of Foam Systems Tested:0 Standard Sprinkler Heads Sample Testing Quick Response Sprinkler Heads Sample Due Date: 2038 Testing Due Date: NA Dry Type Sprinkler Heads Sample Testing Due Date: NA Due Date For Next Gauge Comparison Test: 2028 Date For Next FDC Obstruction Investigation:2028 Date For Next Piping Obstruction Examination: 2028 Inspection & Testing Agency Information Name: Guardian Security Phone:(206) 622-6545 Address: 1743 1 st Avenue South, Seattle WA 98134 Emergency Phone: 1 (800) 487-0118 Email: inspections@guardiansecurity.com Inspector/Tester Information Name:Joel Norris Phone:206-622-6545 SFD Certification No.: SCP-N-04323 / 117512 Sprinkler System Date of Test:07/11/2024 The items in the checklists below shall be inspected and tested. This list does not constitute all of the required inspecting and testing of the fire and life safety system(s). Refer to the CURRENT FIRE CODE AND REFERENCED NFPA 25 STANDARD and the MANUFACTURER'S INSTRUCTIONS for weekly, monthly, and quarterly requirements for inspection and testing. PRE-TEST CHECKS AVOID UNNECESSARY ALARMS BY PUTTING THE FIRE ALARM SYSTEM IN TEST MODE. Failure to place the Fire Alarm System (FAS) into test mode and/or taking other precautions to may cause preventable alarms. 1. All signs, placards, and labels are provided on doors and system controls. • Yes No 2. There is an up-to-date log of any weekly, monthly, and quarterly inspections and testing of the system(s) covered by this report. • Yes No Sprinkler (06/17) SPRINKLER HEADS 3. All accessible sprinkler heads have been visually inspected and are free of corrosion, paint, obstructions and/or physical damage. O Yes O No 4. The sprinkler coverage is OK. (Note: If the coverage has not been altered after the last acceptance/reacceptance test it is OK.) O Yes O No O N/A 5. The standard sprinkler heads are less than 50 years old or within a prescribed testing period. If"No" have the heads sample tested or replaced per NFPA 25 and at the prescribed intervals thereafter. O Yes O No 6. The Quick Response sprinkler heads are less than 20 years old or within a prescribed testing period. If"No" have the heads sample tested or replaced per NFPA 25 and at the prescribed intervals thereafter. O Yes O No O N/A 7. The dry type sprinkler heads are less than 10 years old or within a prescribed testing period. If"No" have the heads sample tested or replaced per NFPA 25 and at the prescribed intervals thereafter. O Yes O No O N/A 8. The proper number of spare sprinkler heads is available, with the proper wrenches for each, at the riser or another designated location. • Yes No HEAT ACTIVATED DEVICES 9. Heat actuation devices function on re-action and deluge systems. Yes No • N/A FLOW TESTS 10. The system(s) passed the Main Drain flow test • Yes No 11. The Main Drain is the proper size. • Yes No Riser Static Pressure PSI Flow Pressure PSI Return to Static Pressure min/Sec Fire pump room 1 120 115 10 ALARMS AND SUPERVISORY DEVICES 12. Flow from the inspector's test valve activates the system alarms. • Yes No 13. All Supervisory and alarm devises [i.e. bell(s), flow switches, supervisory switches] function properly. Yes • No VALVES 14. Pressure regulating valves (PRV)are set properly. Yes No • N/A 15. All supply valves are secured or supervised. O Yes O No 16. All supply valves have been lubricated (where required) O Yes No 17. The maintenance on the system gauges is up-to-date. • Yes No Note: The system gauges are to be compared with a calibrated gauge every five (5) years. If a gauge is not within +/- 3% of the calibrated gauge it must be replaced or recalibrated. This check should be done for multiple floors at static pressure using one calibrated gauge and hydraulic OBSTRUCTION INVESTIGATION 18. The 5-year obstruction investigation of Fire Department Connection (FDC) piping is up-to-date in accordance with NFPA 25 Chap. 14. (eff. 10/21/2012). O Yes O No 19. The 5-year obstruction exam for the FDC(s) included testing and operation of the check valve. O Yes O No 20. The 5-year Obstruction Examination of the sprinkler piping is up-to-date in accordance with NFPA 25 Chap. 14. Yes • No FIRE DEPARTMENT CONNECTIONS 21. The Fire Department Connection(s) (FDC) is clear of bushes, guards, or other debris and is visible from the street. • Yes O No 22. All FDCs have protective plugs or covers. • Yes O No 23. If a plug or cover was missing from a FDC the piping was inspected for debris. (this is required) IYes O No 24. All caps and plugs have at least 12" clearance for operating wrenches. es No 25. All swivels turn free) . es _8No Sprinkler (06/17) RECALLS 26. The inspector did not find recalled devices during the visual inspection. Yes No Note: the technician's inspection is visual and from the floor level in accessible areas ALARM MONITORING 27. A signal was received at the Central Station monitoring company. Yes No • N/A FOAM GENERATING EQUIPMENT IF ANY SYSTEM IS EQUIPPED WITH THIS EQUIPMENT 28. Control valves, including all automatic and manual actuating devices operate properly. 0 Yes 0 No O N/A 29. All control valves are secured or supervised. 0 Yes 0 No • N/A 30. Supervisory switches operate properly. 0 Yes 0 No O N/A 31. The alarm indication device operates properly. Yes 0 No N/A 32. Alarm bells operate properly. 8 Yes O No O N/A 33. All of the proportioning devices, their accessory equipment, and foam makers have been inspected, tested, and are functioning properly. O Yes O No O N/A 34. A sample of the foam concentrate was sent to a testing laboratory and passed the analysis. O Yes O No O N/A 35. The above-ground piping is in good condition and drains properly. 0 Yes 0 No Q N/A 36. The Underground piping has been spot-checked for deterioration within the last 5 years as required by 2005 NFPA 11 Sec.11.3.3. O Yes O No O N/A 37. All the strainers have been inspected and cleaned quarterly(by maintenance)and as necessary during confidence testing. Yes 0 No • N/A DRY SPRINKLER SYSTEMS 38. The system(s) passed the trip test. 0 Yes O No N/A 39. Air compressor(s) refills system in 30 minutes or less. O Yes 0 No O N/A 40. The s stem's low points were drained and the system was restored to service. Yes No N/A System System Tripped In seconds FINAL CHECKS Put the Fire Alarm back into service and/or other precautionary measures that were made to restore fire alarm system to normal operation includes removal of protective coverings) 41. The system was left in service. • Yes No By accepting this statement I, the certified technician shown on this form, certify that this fire protection system(s) has been properly inspected for functional operation in accordance with the current Fire Code (FC) used by the department that has jurisdiction and NFPA Standards adopted by the FC for this system. Any deficiencies found are noted in the report and have been reported to the building Owner/Manager for corrective action. I am authorized to submit this report for the certified technician who has accepted this statement. SIGNATURE OPTIONAL Signature of Technician Signature of Building Representative Svstem Testing Reports Must Be Submitted Online Submit reports to http://www.thecomplianceengine.com/ Sprinkler (06/17) uericiencies Resolved ❑ Location: Outside bell Inop 1 Deficiency: 120 volt bell but a 24 volt bell is installed (Notifier KMS-6-24VDC/P) Recommended Resolution: replace and retest (Local notification only at pump/water tower) SFC and/or 2007 NFPA 72 reference: Resolved ❑ Location: Deficiency: Recommended Resolution: SFC and/or 2007 NFPA 72 reference: Resolved ❑ Location: Deficiency: Recommended Resolution: SFC and/or 2007 NFPA 72 reference: Resolved ❑ Location: Deficiency: Recommended Resolution: SFC and/or 2007 NFPA 72 reference: Resolved ❑ Location: Deficiency: Recommended Resolution: SFC and/or 2007 NFPA 72 reference: Page 4 of 4 �--- a GUARDIAN SECURITY LOFE AND P p O P E R t Y P A O T E 6 T / O N 1743 Frist Ave South Seattle, WA. 98134 206-622-6545 FIRE PUMP SYSTEM Certification Given (One System per Report) RED YELLOW WHITE ❑ CONFIDENCE TEST ❑ REPAIRS ❑ Occupancy Address. 791 NE SAND HILLROAD Occupancy Name: SAND HILL BELFAIR, WA. 98528 ELEMAENTARY Responsible Person First & Last Name: JOAN MOORE Phone Number: 360-277-7566 Responsible Person Responsible Party Address, City, State, zip: SAME E—Mail Address Date of Inspection- Inspection Annual 07-11-2024 Frequency/Type: Testers Name (Please Print): JOEL NORRIS Certification Number: 117512 Identification Number- DIESEL FIRE PUMP System Location: PUMP HOUSE Central station monitoring? Yes ❑ No ® Monitoring Monitoring Required? Yes ® No ❑ Company Name: NWAMS System Make: System Model: FIRE CODE VIOLATIONS FOUND: (If additional room is needed, please add a separate sheet) 1) FUEL IS LOW AT 1/4 (BELOW THE REQUIRED 2/3). 2) JOCKEY PUMP IS IN THE AUTO SETTING BUT TH AUTO,HAND AND OFF SWITCH IS INOP. NOTE: FIRE PUMPS ARE NOT SUPERVISED BY THE FACP. CORRECTIONS MADE: Date Corrected: Corrected By: (If additional room is needed,please add a separate sheet) Certification Number: This certifies that this fire and life safety system has been properly inspected for reliability to cover the Items listed in this report and is consistent with Fire Department Fire Code standards, and that discrepancies are noted and have been reported to the building Owner/Manager for corrective action. Signature of Tester: Phone # Building Representative (signature) Fire Pump Page 1 of 2 The items on the checklists below shall be inspected and tested. This list does not constitute all of the required inspecting and testing of the fire and life safety system. Refer to Fire Department Fire Code for inspecting and testing requirements. Electric Pump 1. Starting Amperage Leg 1 Leg 2 Leg 3 2. Running Amperage Leg 1 Leg 2 Leg 3 3. Was electric pump run for a minimum 10 minutes? Yes ® No ❑ Diesel Pump 4. Diesel fuel tank at least 2/3 full? N/A ❑ Yes ❑ No 5. Batteries fully charged? N/A ❑ Yes ® No ❑ 6. Oil level full? N/A ❑ Yes ® No ❑ 7. Coolant level full? N/A ❑ Yes ® No ❑ 8. Antifreeze protection adequate? N/A ❑ Yes ® No ❑ 9. Fuel filter/strainer serviced? N/A ❑ Yes ® No ❑ 10. Was diesel pump run for a minimum 30 minutes? N/A ❑ Yes ® No ❑ Pump Controller/s 11. Fire pump controller in service? Yes ® No ❑ 12. Controller voltage 12 VDC Interrupting-Capacity amps: Yes ® No ❑ 13. Jockey pump controller in service? N/A ❑ Yes ® No ❑ Pump Test 14. Pump in service on inspection? Yes ® No ❑ 15. Pump starts from pressure drop? Yes ® No ❑ 16. Cut-in Pressure 110 psi Cut-out Pressure 240 psi 17. Was 300 GPM flow conducted? Yes ® No ❑ 18. Pressure gauges replaced or calibrated every 5 years? Yes ❑ No 19. Static pressure 20 psi 20. Discharge psi Suction psi IN LINE 21. Hose size: NA in. Tip size: NA in. Hose length: TEST METER ft. 22. Pitot reading: NA GPM: 1500 23. Churn suction 20 psi Churn discharge 125 psi 24. Has pump been tested weekly? Yes ❑ No 25. Jockey pump tested? Yes ® No ❑ 26. Shaft seals dripping water properly (1 drop per second)? Yes ® No ❑ 27. Pressure relief valve checked for proper operation? Yes ® No ❑ 28. Fire pump connected to fire alarm panel? Yes ❑ No 29. Suction screens inspected and cleared? N/A ® Yes ❑ No ❑ 30. Routine maintenance is performed and records kept? Yes ® No ❑ Transfer Switch 31. Power failure simulated during peak flow for automatic transfer switch activation? N/A ® Yes ❑ No ❑ 32. Connection made to alternate source? N/A ® Yes ❑ No ❑ 33. Emergency manual starting means operated without power? N/A ® Yes ❑ No ❑ Fire Pump Page 2 of 2 Seattle Fire Marshal ' s Office Y 220 3"' Avenue S. Seattle, WA 98104-2608 J0I V Phone: 206-386-1450 Fax: 206-386-1348 Nk System Test Report SPRINKLER STATUS OConfidence Test Q Reacceptance Test O Red O Yellow 0 White Occupancy Information Occupancy Name: Sand Hill Elementary Contact Name:Joan Moore Occupancy Address: 791 NE Sand hill rd Contact Phone: (360) 277-7566 Belfair, wa, 98528 Contact Email: Washington Sprinkler Inventor #of Wet Systems in the Building:2 #of Wet Systems Tested:2 #of Dry Systems in the Building-0 #of Dry Systems Tested,0 #of Foam Systems in the Building:0 #of Foam Systems Tested:0 Standard Sprinkler Heads Sample Testing Quick Response Sprinkler Heads Sample Due Date: 2038 Testing Due Date: NA Dry Type Sprinkler Heads Sample Testing Due Date: 1998 Due Date For Next Gauge Comparison Test: 2019 Date For Next FDC Obstruction Investigation:2019 Date For Next Piping Obstruction Examination: 2019 Inspection & Testing Agency Information Name: Guardian Security Phone:(206) 622-6545 Address: 1743 1 st Avenue South, Seattle WA 98134 Emergency Phone: 1 (800) 487-0118 Email: inspections@guardiansecurity.com Inspector/Tester Information Name:Joel Norris Phone:206-622-6545 SFD Certification No.: SCP-N-04323 / 117512 Sprinkler System Date of Test:07/20/2022 The items in the checklists below shall be inspected and tested. This list does not constitute all of the required inspecting and testing of the fire and life safety system(s). Refer to the CURRENT FIRE CODE AND REFERENCED NFPA 25 STANDARD and the MANUFACTURER'S INSTRUCTIONS for weekly, monthly, and quarterly requirements for inspection and testing. PRE-TEST CHECKS AVOID UNNECESSARY ALARMS BY PUTTING THE FIRE ALARM SYSTEM IN TEST MODE. Failure to place the Fire Alarm System (FAS) into test mode and/or taking other precautions to may cause preventable alarms. 1. All signs, placards, and labels are provided on doors and system controls. • Yes No 2. There is an up-to-date log of any weekly, monthly, and quarterly inspections and testing of the system(s) covered by this report. • Yes No Sprinkler (06/17) SPRINKLER HEADS 3. All accessible sprinkler heads have been visually inspected and are free of corrosion, paint,obstructions and/or physical damage. O Yes O No 4. The sprinkler coverage is OK. (Note: If the coverage has not been altered after the last acceptance/reacceptance test it is OK.) O Yes O No O N/A 5. The standard sprinkler heads are less than 50 years old or within a prescribed testing period. If"No" have the heads sample tested or replaced per NFPA 25 and at the prescribed intervals thereafter. O Yes O No 6. The Quick Response sprinkler heads are less than 20 years old or within a prescribed testing period. If"No" have the heads sample tested or replaced per NFPA 25 and at the prescribed intervals thereafter. O Yes O No O N/A 7. The dry type sprinkler heads are less than 10 years old or within a prescribed testing period. If"No" have the heads sample tested or replaced per NFPA 25 and at the prescribed intervals thereafter. O Yes O No O N/A 8. The proper number of spare sprinkler heads is available, with the proper wrenches for each, at the riser or another designated location. • Yes No HEAT ACTIVATED DEVICES 9. Heat actuation devices function on re-action and deluge systems. Yes No • N/A FLOW TESTS 10. The system(s) passed the Main Drain flow test Yes No 11. The Main Drain is the proper size. • Yes No Riser Static Pressure PSI Flow Pressure PSI Return to Static Pressure min/Sec user room I pump house 175/140 1 170/135 05 ALARMS AND SUPERVISORY DEVICES 12. Flow from the inspector's test valve activates the system alarms. • Yes No 13. All Supervisory and alarm devises [i.e. bell(s), flow switches, supervisory switches] function properly. • Yes 0 No VALVES 14. Pressure regulating valves (PRV) are set properly. Yes No • N/A 15. All supply valves are secured or supervised. O Yes O No 16. All supply valves have been lubricated (where required) Yes No 17. The maintenance on the system gauges is up-to-date. Yes No Note: The system gauges are to be compared with a calibrated gauge every five (5) years. If a gauge is not within +/- 3% of the calibrated gauge it must be replaced or recalibrated. This check should be done for multiple floors at static pressure using one calibrated gauge and hydraulic OBSTRUCTION INVESTIGATION 18. The 5-year obstruction investigation of Fire Department Connection (FDC) piping is up-to-date in accordance with NFPA 25 Chap. 14. (eff. 10/21/2012). O Yes O No 19. The 5-year obstruction exam for the FDC(s) included testing and operation of the check valve. O Yes O No 20. The 5-year Obstruction Examination of the sprinkler piping is up-to-date in accordance with NFPA 25 Chap. 14. Yes • No FIRE DEPARTMENT CONNECTIONS 21. The Fire Department Connection(s) (FDC) is clear of bushes, guards, or other debris and is visible from the street. • Yes O No 22. All FDCs have protective plugs or covers. • Yes O No 23. If a plug or cover was missing from a FDC the piping was inspected for debris. (this is required) jYje s O No 24. All caps and plugs have at least 12" clearance for operating wrenches. s No 25. All swivels turn free) . s _8No Sprinkler (06/17) (RECALLS 26. The inspector did not find recalled devices during the visual inspection. Yes No Note: the technician's inspection is visual and from the floor level in accessible areas ALARM MONITORING 27. A signal was received at the Central Station monitoring company. Yes No N/A FOAM GENERATING EQUIPMENT IF ANY SYSTEM IS EQUIPPED WITH THIS EQUIPMENT 28. Control valves, including all automatic and manual actuating devices operate properly. 0 Yes No O N/A 29. All control valves are secured or supervised. 0 Yes 8 No • N/A 30. Supervisory switches operate properly. 0 Yes O No O N/A 31. The alarm indication device operates properly. Yes 0 No N/A 32. Alarm bells operate properly. 8 Yes O No O N/A 33. All of the proportioning devices, their accessory equipment, and foam makers have been inspected, tested, and are functioning properly. O Yes O No O N/A 34. A sample of the foam concentrate was sent to a testing laboratory and passed the analysis. O Yes O No Q N/A 35. The above-ground piping is in good condition and drains properly. 0 Yes 0 No 0 N/A 36. The Underground piping has been spot-checked for deterioration within the last 5 years as required by 2005 NFPA 11 Sec.11.3.3. O Yes O No O N/A 37. All the strainers have been inspected and cleaned quarterly(by maintenance) and as necessary during confidence testing. Yes No • N/A DRY SPRINKLER SYSTEMS 38. The system(s) passed the trip test. 0 Yes O No 0 N/A 39. Air compressor(s) refills system in 30 minutes or less. Yes 0 No 0 N/A 40. The s stem's low points were drained and the system was restored to service. Yes No N/A System System Tripped In seconds FINAL CHECKS Put the Fire Alarm back into service and/or other precautionary measures that were made to restore fire alarm system to normal operation includes removal of protective coverings) 41. The system was left in service. Yes No By accepting this statement I, the certified technician shown on this form, certify that this fire protection system(s) has been properly inspected for functional operation in accordance with the current Fire Code (FC) used by the department that has jurisdiction and NFPA Standards adopted by the FC for this system. Any deficiencies found are noted in the report and have been reported to the building Owner/Manager for corrective action. I am authorized to submit this report for the certified technician who has accepted this statement. SIGNATURE OPTIONAL Signature of Technician Signature of Building Representative System Testing Reports Must Be Submitted Online Submit reports to http://www.thecomplianceengine.com/ Sprinkler (06/17) uerictencies Resolved ❑ Location: In vault next to PIV Deficiency: Riser shut-off os&y was not locked or supervised. Recommended Resolution: Add chain and lock or supervisory switch to os&y valves SFC and/or 2007 NFPA 72 reference: Resolved ❑ Location: riser room Deficiency: 5 yr internal inspection, fdc scope, and gauge replacement due Recommended Resolution: perform 5 yr internal inspection, fdc scope and gauge replacement (2 wet gauges) SFC and/or 2007 NFPA 72 reference: Resolved ❑ Location: P I V Deficiency: NOT ABLE TO EXERCISE THE VALVE NO KEY TO UNLOCK PAD LOCK. Recommended Resolution: CUT OFF PAD LOCK AND EXERCISE PIV AND ADD NOW PAD LOCK. SFC and/or 2007 NFPA 72 reference: Resolved ❑ Location: 5 DRY TYPE FIRE SPRINKLERS ON THE EXERIOR OVER DOOR EXITS OF THE BUILDING. Deficiency: ALL 5 DRY TYPE FIRE SPRINKLERS NEED TO BE MEASSURED AND REPLACED.(FIRE SPRINKLERS ARE OVER 30 YEARS OLD). Recommended Resolution: SFC and/or 2007 NFPA 72 reference: Resolved ❑ Location: Deficiency: Recommended Resolution: SFC and/or 2007 NFPA 72 reference: Page 4 of 4 Randy Collins From: Randy Collins Sent: Wednesday, July 10, 2024 11:02 AM To: 'Moore,Joan' Cc: King, Dan;Scott Cooper Subject: RE: Sand Hill Elementary Fire Panel Attachments: Fire Watch Procedures.pdf Joan, I appreciate you apprising me of this situation and testing the waterflow alarm on the school's fire sprinkler system to verify it sounds an audible alarm on the premises even without the panel(FACP)working. Because school is currently not in session,there are no students present,the sprinkler system is fully operational and the waterflow alarm sounds on-site, I will waive the requirement to establish a fire watch at the facility. Please note that if the FACP is still non-functioning when school resumes, a fire watch will need to be established meeting the enclosed procedures. In the meantime, I would encourage you to act promptly to have the panel repaired ASAP to avoid this situation and ask you to remind whomever you contract with,that a permit for the panel's replacement will be required from our office. Any questions, please let me know. Thank you for your prompt attention to this matter. Randy From: Moore,Joan <jmoore@northmasonschools.org> Sent:Wednesday,July 10, 2024 9:53 AM To: Randy Collins<RCollins@masoncountywa.gov> Cc: King, Dan<dking@northmasonschools.org> Subject:Sand Hill Elementary Fire Panel Caution: External Email Warning!This email has originated from outside of the Mason County Network. Do not click links or open attachments unless you recognize the sender, are expecting the email, and know the content is safe. If a link sends you to a website where you are asked to validate using your Account and Password, DO NOT DO SO! Instead, report the incident. Morning Randy, Guardian is here doing their annual fire intrusion and inspections. At Sand Hill Joel called me to explain that our fire panel is not receiving any power and that it is dead and needs replacing. He stated that the auto that system is working, and the sprinkler system is working just not the panel. My question is this do we still need to do a fire watch if there is no one in the building? With the two systems up and running and not the panel what is your recommendation so we can be in compliance. Thank you for your assistance in this matter. 1 �11 Jaww M oorel Facilities&Maintenance Director North Mason School District (36o)277-2222 office (360)277-7566 work cell "Whole Child Whole School Whole Community" This communication,together with any attachments hereto or links contained herein, is for the sole use of the intended recipient(s)and may contain information that is confidential or legally protected.Any unauthorized review,disclosure,dissemination,distribution or use of this communication is prohibited and may be a violation of the Family Educational Records Privacy Act(FERPA)or other privacy protection laws and regulations. If you received this communication in error, please notify me immediately by email and delete the original message. 2 r' •' 907.2.3 Group E. Group E occupancies shall be provided with a manual fire alarm system that initiates the occupant notification signal utilizing one of the following: 1.An emergency voice/alarm communication system meeting the requirements of Section 907.5.2.2 and installed in accordance with Section 907.6; or 4�2^+1'7 sysr. - up►>� aau<rt«n. . Ac`7 J,,/,C--C- 2.A system developed as part of a safe school plan adopted in accordance with RCW 28A.320.125 or developed as part of an emergency response system consistent with the provisions of RCW 28A.320.126.The system must achieve all of the following performance standards: 2.1 The ability to broadcast voice messages or customized announcements; 2.2 Includes a feature for multiple sounds, including sounds to initiate a lock down; 2.3 The ability to deliver messages to the interior of a building, areas outside of a building as designated pursuant to the safe school plan,and to personnel; 2.4 The ability for two-way communications; 2.5 The ability for individual room calling; 2.6 The ability for a manual override; 2.7 Installation in accordance with NFPA 72; 2.8 Provide 15 minutes of battery backup for alarm and 24 hours of battery backup for standby; and 2.9 Includes a program for annual inspection and maintenance in accordance with NFPA 72. EXCEPTIONS: 1. A manual fire alarm system is not required in Group E occupancies with an occupant load of 50 or less. 2. Emergency voice/alarm communication systems meeting the requirements of Section 907.5.2.2 and installed in accordance with Section 907.6 shall not be required in Group E occupancies with occupant loads of 100 or less, such as individual portable school classroom buildings; provided that activation of the manual fire alarm system initiates an approved occupant notification signal in accordance with Section 907.5. 3.Where an existing approved alarm system is in place, an emergency voice/alarm system is not required in any portion of an existing Group E building undergoing any one of the following repairs, alteration or addition: 3.1 Alteration or repair to an existing building including, without limitation, alterations to rooms and systems, and/or corridor configurations, not exceeding 35 percent of the fire area of the building (or the fire area undergoing the alteration or repair if the building is comprised of two or more fire areas); or 3.2 An addition to an existing building, not exceeding 35 percent of the fire area of the building (or the fire area to which the addition is made if the building is comprised of two or more fire areas). 4. Manual fire alarm boxes are not required in Group E occupancies where all of the following apply: 4.1 Interior corridors are protected by smoke detectors. 4.2 Auditoriums, cafeterias, gymnasiums and similar areas are protected by heat detectors or other approved detection devices. 4.3 Shops and laboratories involving dusts or vapors are protected by heat detectors or other approved detection devices. V x s- nor rt 5. Manual fire alarm boxes shall not be required in Group E occupancies where all of the following apply: 5.1 The building is equipped throughout with an approved automatic sprinkler system installed in accordance with Section 903.3.1.1. 5.2 The emergency voice/alarm communication system will activate on sprinkler waterflow. 5.3 Manual activation is provided from a normally occupied location. 907.2.3.1 Sprinkler systems or detection. When automatic sprinkler systems or smoke detectors are installed, II such systems or detectors shall be connected to the building fire alarm system. Insert Facing Page 9-22 Effective March 15,2024 Front of school outdoor device ,SYSTEM SENSOR Outdoor, Selectable Output Speaker '� St robes and Dual- Voltage Evacuation Speakers for Wall SPECTF�Alert Applications o a SpectrAlert°Advance outdoor, selectable-output speaker strobes and dual-voltage evacuation speakers meet SpectrAlert Advance offers the broadest line of outdoor speakers and speaker strobes in the industry.From metal and plastic virtually any outdoor application requirement. outdoor back boxes,to white and red plastic housings,to wall and ceiling mounting options,SpectrAlert Advance can meet virtually any application requirement. Features • Weatherproof per NEMA 4X, IP56 Wall-mount outdoor speakers and speaker strobes can be used indoors or outdoors in wet or dry applications,and can provide • Rated from -40°F to 151°F reliable operation from—40°F to 151 OF.These speakers provide • Plug-in design reduces ground faults a broad frequency response range,low harmonic distortion and • Universal mounting plate with onboard shorting spring that tests maintain a high sound pressure level at all tap settings to provide wiring continuity before devices are installed accurate and intelligible broadcast of evacuation messages. • Field-selectable candela settings: 15, 15/75,30,75,95, 110, 115, Like the entire SpectrAlert Advance line,wall-mount outdoor speakers 135, 150, 177,and 185 and speaker strobes include a variety of features that increase • Automatic selection of 12-or 24-volt operation at 15 and application flexibility and simplify installation.First,field-selectable 15/75 candela settings,including candela,speaker voltage and power settings,and • Rotary switch for speaker voltage(25 and 70.7 Vrms)and power automatic selection of 12-or 24-volt operation enable installers to settings(1/4, 1/2, 1 and 2 watts) easily adapt devices to meet requirements. • Compatible with System Sensor synchronization protocol and Next,these devices use a universal mounting plate with an onboard legacy SpectrAlert products shorting spring that ensures wiring continuity before devices are • Tamper-resistant construction installed,so installers can verify proper wiring without mounting the • Listed for ceiling or wall mounting devices and exposing them to potential construction damage.Once the plates are mounted,all SpectrAlert Advance devices utilize a plug-in design with a single captured screw to speed installation and virtually eliminate costly ground faults. Outdoor devices ship with weatherproof plastic back boxes(metal back boxes are available separately)that accommodate in-and- out wiring for daisy chaining devices.Plastic back boxes feature removable side flanges and improved resistance to saltwater Agency Listings corrosion.Knock-outs located on the back eliminate the need to drill SIGNAUN6 holes for screw-in mounting.Plastic and metal weatherproof back MEA boxes come with 3/4-inch top and bottom conduit entries and 3/-inch LISTED approved knock-outs at the back.A screw-in NPT plug with an O-ring gasket MSS 7320-1663201 10-08-E for a watertight seal is included with each back box. SpectrAlert°Advance Outdoor Speaker and Speaker Strobe Specifications Architectural/Engineering Specifications General SpectrAlert Advance outdoor speakers and speaker strobes shall mount to a weatherproof back box.A universal mounting plate shall be used for mounting ceiling and wall products.The notification appliance circuit and amplifier wiring shall terminate at the universal mounting plate.Also,SpectrAlert Advance speaker strobes,when used with the Sync•Circuit"Module accessory,shall be powered from a non-coded notification appliance circuit output and shall operate on a nominal 12 or 24 volts.When used with the Sync•Circuit Module, 12-volt-rated notification appliance circuit outputs shall operate between 8.5 and 17.5 volts;24-volt-rated notification appliance circuit outputs shall operate between 16.5 and 33 volts.Outdoor SpectrAlert Advance products shall operate between-40*F and 151°F from a regulated DC,or full-wave rectified,unfiltered power supply. Speaker Speaker shall be a System Sensor SpectrAlert Advance Model dual-voltage transformer speaker capable of operating at 25.0 or 70.7 nominal Vrms.Speaker shall be listed to Underwriters Laboratories Standard S4048 for outdoor fire protective signaling systems.Speaker shall have a frequency range of 400 to 4,000 Hz and shall have an operating temperature from-40°F to 150.8°F.Speaker shall have power taps and wattage settings that are selected by rotary switches.The speaker must be installed with its weatherproof back box in order to remain outdoor approved per UL listing S4048.The speaker shall be suitable for use in air handling spaces and wet environments. Speaker Strobe Combination The speaker strobe shall be a System Sensor Model listed to UL 1638 and UL 1480 and be approved for fire protective signaling systems.Speaker shall be capable of operating at 25.0 or 70.7 nominal Vrms and shall have a frequency range of 400 to 4,000 Hz.Speaker shall have power taps that are selected by rotary switch.The strobe shall consist of a xenon flash tube with associated lens/reflector system and operate on either 12 or 24 volts.The strobe shall also feature selectable candela output,providing options for 15 or 15/75 candela when operating on 12 volts and 15, 15/75,30,75, 110, 115,135,150, 177 or 185 candela when operating on 24 volts.The strobe shall comply with the Americans with Disabilities Act requirement for visible signaling appliances,flashing at 1 Hz over the strobe's entire operating voltage range.The speaker strobe must be installed with its weatherproof back box in order to remain outdoor approved per UL.The speaker strobe shall be suitable for use in wet environments. Physical Specifications Operating Temperature -40°F to 151°F(-40°C to 66°C) Dimensions,Wall-Mount SPS Speaker Strobe 6.0-L x 5.0"W x 4.7-D(including lens and speaker) SIP Speaker 6.0-L x 5.0"W x 2.9-D Dimensions,Wall-Mount Weatherproof Back Box 6.5-L x 5.5-H x 2.9-D Electrical/Operating. Nominal Voltage(speakers) 25 V or 70.7 V(nominal) Maximum Supervisory Voltage(speakers) 50 VDC Strobe Flash Rate 1 flash per second Nominal Voltage(strobes) Regulated 12 VDC/FWR or regulated 24 DC/FWR Operating Voltage Range(includes fire alarm 8 to 17.5 V(12 V nominal)or 16 to 33 V(24 V nominal) panels with built in sync) Operating Voltage with MDL3 Sync Module 8.5 to 17.5 V(12 V nominal)or 16.5 to 33 V(24 V nominal) Frequency Range 400 to 4,000 Hz Power 1/4,1/2, 1,2 watts AVDS 11301 / UL Current Draw Data Candela Derating UL Max.Strobe Current • For K series products used at low 8 to 17.5 Volts 16 to 33 Volts temperatures,listed candela ratings must be Candela DC FWR DC FWR reduced in accordance with this table. Standard 15 123 128 66 71 Strobe • ' Candela Range 15/75 142 148 77 81 Listed Candela Candela rating at 30 NA NA 94 96 —40T 75 NA NA 158 153 15 95 NA NA 181 176 15/75 Do not use below 32°F 110 NA NA 202 195 30 115 NA NA 210 205 75 44 High 135 NA NA 228 207 95 70 Candela Range 150 NA NA 246 220 110 110 177 NA NA 281 251 115 115 185 NA NA 286 258 135 135 Sound Output 150 150 UL Reverberant(dBA @ 10 ft.) 2W 1 W 1/2 W 1/4 W 1 1 Outdoor Speaker 90 87 84 81 185 185 Outdoor SpeakerlStrobe 89 86 83 80 Dimensions .97` "" " 5.00� �1.84 5.00` 2.83�1.60"" 1.84"" •1 PMENEM 5.98" 5.97"" 0 0 o o Wall-Mount Outdoor Speaker Wall-Mount Outdoor Speaker Strobe AVDS11301 Surface Mounting Wall-Mount Speaker Strobe with Plastic Weatherproof Back Box Wall-Mount Speaker with Plastic Weatherproof Back Box 0 0 -Jim Wall-Mount Speaker Strobe with Metal Weatherproof Back Box Wall-Mount Speaker with Metal Weatherproof Back Box Ordering Information for SpectrAlee Advance Outdoor Speakers and Speaker Strobes White Red Description SPWK SPRK Outdoor Speaker(includes plastic weatherproof back box) SPWK-R SPRK-R Outdoor Speaker(does not include plastic weatherproof back box) SPSWK SPSRK Outdoor Speaker Strobe,Standard cd(includes plastic weatherproof back box) SPSWK-P SPSRK-P Plain Outdoor Speaker Strobe,Standard cd(includes plastic weatherproof back box) SPSWK-R SPSRK-R Outdoor Speaker Strobe,Standard cd(does not include weatherproof back box) SPSWK-CLR-ALERT — Outdoor Speaker Strobe,Standard cd,Clear Lens,ALERT Printed (includes plastic weatherproof back box) SPSRHK Outdoor Speaker Strobe,High cd(135,150,177,185)(includes plastic weatherproof back box) Accessories White Red Description MWBBW MWBB Wall,Metal Weatherproof Back Box Notes: All-P models have a plain housing(no"FIRE"marking on cover) "Standard cd"refers to strobes that include 15,15f75,30,75,95, 110,and 115 candela settings."High cd"refers to strobes that include 135,150,177,and 185 candela settings.When replacing standard outdoor units,both the device and back box must be replaced. SYSTEM 02012 System Sensor. 3825 Ohio Avenue•St.Charles,IL 60174 Product specrficata s subject to change vntlwut notice.Visit systernsensorcom SENSOR' Phone:800-SENSOR2•Fax:630-377-6495 'orcunentproductinformation,incloingthelatestversionofthisdatasheet. AVDS11301•09i12 SYSTEM SENSOR Indoor Selectable- Output Speaker 11 Strobes and Dual Voltage Evacuation Speakers for Wall Applications System Sensor t-Series selectable output speaker strobes and dual-voltage evacuation speakers can reduce ground faults and enable faster installation with lower current draw and modern aesthetics. The System Sensor L-Series of speakers and speaker strobes reduce costly ground faults using a plug-in design and universal Features mounting plate that allow the installer to pre-wire mounting plates. • Plug-in design and protective cover reduce ground faults dress the wires,and confirm wiring continuity before plugging in the speakers. In addition,a protective plastic cover prevents nicked • Universal mounting plate with an onboard shorting spring tests wires by covering exposed speaker components. wiring continuity before installation • No extension ring required These devices also enable faster installations by providing instant • Field selectable candela settings on wall units: feedback to ensure that wiring is properly connected,rotary switches 15.30,75,95, 110, 135, 185 to select voltage and power settings,and 7 field-selectable candela settings for wall speaker strobes. • Automatic selection of 12-or 24-volt operation at 15 and 30 candela The low total harmonic distortion of the speaker offers high fidelity • Rotary switch simplifies field selection of speaker voltage sound output while still offering high volume sound output for use (25 and 70.7 Vrms)and power settings(1i4,%2, 1 and 2 watts) in high ambient noise applications. • Seakers offer high fidelity and high volume sound output System Sensor L-Series makes installation easy • Compatible with System Sensor synchronization protocol .Attach a universal mounting plate to a 4 x 4 x 21/8 inch back box. • Electrical compatibility with existing SpectrAlert and SpectrAlert Flush-mount applications do not require an extension ring. Advance products •Connect the notification appliance circuit or speaker wiring to the • Tamper-resistant construction terminals on the mounting plate. •Attach the speaker or speaker strobe to the mounting plate by • Updated modern aesthetics inserting the product tabs into the mounting plate grooves. Hinge the device into position to lock the product pins into the mounting plate terminals.The device will temporarily hold in place with a Agency Listings catch until it is secured with a captured mounting screw. OcNauxs O ( � ��-Mf'• � I LISTED AP°aoVEo S4048 FM apomVed except TVO-165302_5 tot ALERT models 3p57493 L-Series Speaker and Speaker Strobe Specifications . General L-Series speaker and speaker strobes shall mount to a 4 x 4 x 2VS-inch back box.A universal mounting plate shall be used for mounting ceiling and wall products.The notification appliance circuit and amplifier wiring shall terminate at the universal mounting plate.Also,L-Series speaker strobes,when used with the Sync•CircuitTM Module accessory,shall be powered from a non-coded notification appliance circuit output and shall operate on a nominal 12 or 24 volts.When used with the Sync•Circuit Module, 12-volt rated notification appliance circuit outputs shall operate between 8.5 and 17.5 volts;24-volt rated notification appliance circuit outputs shall operate between 16.5 and 33 volts. Indoor L-Series products shall operate between 32°F and 120OF from a regulated DC,or full-wave rectified,unfiltered power supply.Wall- mount speaker strobes shall have field-selectable candela settings including 15,30,75,95, 110,135,185. Speaker The speaker shall be a System Sensor L-Series model dual-voltage transformer speaker capable of operating at 25.0 or 70.7 nominal Vrms.It should be listed to UL 1480 and shall be approved for fire protective service.The speaker shall have a frequency range of 400 to 4,000 Hz and shall have an operating temperature between 32°F and 120°F.The speaker shall have power taps and voltage that are selected by rotary switches. Speaker Strobe combination The speaker strobe shall be a System Sensor L-Series model listed to UL1480 and UL 1971 and be approved for fire protective signaling systems.The speaker shall be capable of operating at 25.0 or 70.7 nominal Vrms selected via rotary switch,and shall have a frequency range of 400 to 4,000 Hz.The speaker shall have power taps that are selected by rotary switch.The strobe shall comply with the NFPA 72 requirements for visible signaling appliances,flashing at 1 Hz over the strobe's entire operating voltage range.The strobe light shall consist of a xenon flash tube and associated lens/reflector system. Synchronization Module The module shall be a System Sensor Sync•Circuit model MDL3 listed to UL 464 and shall be approved for fire protective service.The module shall synchronize SpectrAlert strobes at 1 Hz.The module shall mount to a 411/16 x 41 IIA6 x 2W-inch back box.The module shall also control two Style Y(class B)circuits or one Style Z(class A)circuit.The module shall synchronize multiple zones.Daisy chaining two or more synchronization modules together will synchronize all the zones they control.The module shall not operate on a coded power supply. Physical Specifications Operating Temperature 32°F to 120°F(0°C to 49°C) Humidity Range 10 to 93%non-condensing Dimensions,Wall-Mount Length Width Depth SPL Speaker 6.5 in,165 mm 5 in,127 mm .97 in,23 mm With Surface Mount Back Box 6.6 in,168 mm 5.1 in, 130 mm 3.2 in,82 mm SPSL Speaker/Strobe 6.5 in,165 mm 5.0 in, 127 mm 2.3 in,58 mm (including lens and speaker) With Surface Mount Back Box 6.6 in, 168 mm 5.1 in, 130 mm 4.5 in, 116 mm Electrical/Operating Nominal Voltage(speakers) 25 Volts or 70.7 Volts(nominal) Maximum Supervisory Voltage(speakers) 50 VDC Strobe Flash Rate 1 flash per second Nominal Voltage(strobes) Regulated 12 VDC or regulated 24 DC/FWR1.2 Operating Voltage Range(includes fire 8 to 17.5 V(12 V nominal)or 16 to 33V(24 V nominal) alarm panels with built in sync) Operating Voltage with MDL3 Sync Module 8.5 to 17.5 V(12 V nominal)or 16.5 to 33V(24 V nominal) Frequency Range 400 to 4000 Hz Power 1/4,Yz, 1,2 watts 1.Full Wave Rectified(FWR)voltage is a non-regulated,time-varying power source that is used on some power supply and panel outputs. 2.Strobe products will operate at 12 V nominal only for 15 and 30 cd UL Current Draw Data UL Max Strobe Current Draw(mA RMS) 8 to 17.5 Volts 16 to 33 Volts Candela DC DC FWR 15 88 43 60 30 143 63 83 75 N/A 107 136 95 N/A 121 155 110 N/A 148 179 135 N/A 172 209 185 N/A 222 257 Sound Output Speaker Strobe 1/4W Y2W 1 W 2w UL Reverberant(dBA @10 ft) 77 80 83 86 UL Anechoic(dBA @10 ft) 77 80 83 86 Sound Output Y4 W 1/2 W 1 W 2 W UL Reverberant(dBA @10 ft) 79 82 85 88 UL Anechoic(dBA @10 ft) 79 82 85 88 L-Series Dimensions } 5.00 .97 1.63 63 -- 5.00 2.30 1.63 1.39 El 6.50 6.50 Wall-Mount Speaker Wall-Mount Speaker Strobe Surface Mounting ® ® 1°o°ao°o10eA111A11A;°oi11' pBI1oA011op.1°B.1°G °pgp1 BONIA° .11 BAAB 61A A'BpA6AeA BIA IN AAAA"Cal Ap° B®A °ABp1p°p010p010� OOAq a°o`0N. BBI A BBA ® Qo0 y A°B° ff 1 4 A11 14444r Wall-Mount Speaker Strobe with SBBSPL Surface Mount Back Box L-Series Ordering Information White Red Description SPWL SPRL Speaker only SPSWL SPSRL Speaker Strobe SPSWL-P SPSRL-P Plain Speaker Strobe SPSWL-ALERT — Speaker Strobe,Amber Lens SPSWL-CLR-ALERT — Speaker Strobe Clear Lens SPSRL-SP Speaker Strobe,Fuego Accessories White Red Description RFPW RFP 7 in x 9.5 in Retrofit Plate SBBSPWL SBBSPRL Surface Mount Back Box for Speakers and Speaker Strobes TR-2W TR-2 Wall Mount Trim Ring Notes: All-P models have a plain housing(no"FIRE"marking on the cover) �� SYSTEM 3825 Ohio Avenue•St. Charles,IL 60174 @2017 System Sensor. �4 SE�f_5OR Phone:800-SENSOR2•Fax:630-377-6495 Prod'jctspecificationssubjecttochangewtFautrVice.Visisystersensorcom I v for current product information,including the'atest version of this data sheet. www.systemsensor.com A'VDS86701°03i17 ,SYSTEM SEM SOR Indoor Selectable- Output Speaker Strobes and Dual Voltage Evacuation 1. Y Speakers for Ceiling ApplicationsAl ly System Sensor L-Series selectable-output speaker strobes a and dual-voltage evacuation speakers can reduce ground faults and enable faster installation with lower current draw and modern aesthetics. System Sensor L-Series of speakers and speaker strobes reduce costly ground faults using a plug-in design and universal Features mounting plate that allow the installer to pre-wire mounting plates. • Plug-in design and protective cover reduce ground faults dress the wires,and confirm wiring continuity before plugging in the speakers. In addition,a protective plastic cover prevents nicked • Universal mounting plate with an onboard shorting spring tests wires by covering exposed speaker components. wiring continuity before installation • No extension ring required These devices also enable faster installations by providing instant • Field selectable candela settings on ceiling units: feedback to ensure that wiring is properly connected,rotary switches 15,30,75,95, 115, 150,and 177 to select voltage and power settings,and 7 field-selectable candela settings for both wall and ceiling speaker strobes. • Automatic selection of 12-or 24-volt operation at 15 and 30 candela The low total harmonic distortion of the SP speaker offers high fidelity • Rotary switch simplifies field selection of speaker voltage(25 sound output while still offering high volume sound output for use in and 70.7 Vrms)and power settings(14,112, 1 and 2 watts) high ambient noise applications. • Speakers offer high fidelity and high volume sound output L-Series makes installation easy • 520 Hz capable with compatible FACP •Attach a universal mounting plate to a 4 x 4 x 2118 inch back box. • Compatible with System Sensor synchronization protocol Flush-mount applications do not require an extension ring. • Electrical compatibility with existing SpectrAlert and SpectrAlert •Connect the notification appliance circuit or speaker wiring to the Advance products terminals on the mounting plate. •Attach the speaker or speaker strobe to the mounting plate by • Tamper-resistant construction inserting the product tabs into the mounting plate grooves.Hinge • Updated modern aesthetics the device into position to lock the product pins into the mounting plate terminals.The device will temporarily hold in place with a Agency Listings catch until it is secured with a captured mounting screw. SIGNALING o �� IJSTED APPROVED Ij S4,148 FM apprcr ed euc Dt 7,320-1653,M for ALERT models 3057493 L-Series Speaker and Speaker Strobe Specifications , Architectural/Engineering Specifications General L-Series speaker and speaker strobes shall mount to a 4 x 4 x 21i8-inch back box.A universal mounting plate shall be used for mounting ceiling and wall products.The notification appliance circuit and amplifier wiring shall terminate at the universal mounting plate.Also,L-Series speaker strobes,when used with the Sync•CircuitTv Module accessory,shall be powered from a non-coded notification appliance circuit output and shall operate on a nominal 12 or 24 volts.When used with the Sync•Circuit Module, 12-volt rated notification appliance circuit outputs shall operate between 8.5 and 17.5 volts;24-volt rated notification appliance circuit outputs shall operate between 16.5 and 33 volts. Indoor L-Series products shall operate between 320F and 120°F from a regulated DC,or full-wave rectified,unfiltered power supply.Speaker strobes shall have field-selectable candela settings including 15,30,75,95, 115;150,177. Speaker The speaker shall be a System Sensor L-Series model dual-voltage transformer speaker capable of operating at 25.0 or 70.7 nominal Vrms. It should be listed to UL 1480 and shall be approved for fire protective service.The speaker shall have a frequency range of 400 to 4,000 Hz and shall have an operating temperature between 32°F and 120°F.The speaker shall have power taps and voltage that are selected by rotary switches. Speaker Strobe combination The speaker strobe shall be a System Sensor L-Series model listed to UL1480 and UL 1971 and be approved for fire protective signaling systems.The speaker shall be capable of operating at 25.0 or 70.7 nominal Vrms selected via rotary switch,and shall have a frequency range of 400 to 4,000 Hz.The speaker shall have power taps that are selected by rotary switch.The strobe shall comply with the NFPA 72 requirements for visible signaling appliances,flashing at 1 Hz over the strobe's entire operating voltage range.The strobe light shall consist of a xenon flash tube and associated lens/reflector system. Synchronization Module The module shall be a System Sensor Sync•Circuit model MDL3 listed to UL 464 and shall be approved for fire protective service.The module shall synchronize SpectrAlert strobes at 1 Hz.The module shall mount to a 41 V16 x 41 IA6 x 2W-inch back box.The module shall also control two Style Y(class B)circuits or one Style Z(class A)circuit.The module shall synchronize multiple zones.Daisy chaining two or more synchronization modules together will synchronize all the zones they control.The module shall not operate on a coded power supply. Physical Specifications Operating Temperature 32°F to 120°F(0°C to 49°C) Humidity Range 10 to 93%non-condensing Dimensions,Ceiling-Mount Diameter Depth SPC Speaker 6.8 in, 173 mm 1.0 in,25 mm With Surface Mount Back Box 6.9 in, 176 mm 3.5 in,89 mm SPSC Speaker Strobe 6.8 in, 173 mm 2.8 in,73 mm With Surface Mount Back Box 6.9 in, 176 mm 5.37 in,136 mm Electrical/Operating Nominal Voltage(speakers) 25 Volts or 70.7 Volts(nominal) Maximum Supervisory Voltage(speakers) 50 VDC Strobe Flash Rate 1 flash per second Nominal Voltage(strobes) Regulated 12 VDC or regulated 24 VDC/FWR 1.2 Operating Voltage Range(includes fire 8 to 17.5 V(12 V nominal)or 16 to 33 V(24 V nominal) alarm panels with built in sync) Operating Voltage with MDL3 Sync Module 8.5 to 17.5 V(12 V nominal)or 16.5 to 33 V(24 V nominal) Frequency Range 400 to 4,000 Hz3 Power '/4,Y2, 1,2 watts 1.Full Wave Rectified(FWR)voltage is a non-regulated,time-varying power source that is used on some power supply and panel outputs. 2.Strobe products will operate at 12 V nominal only for 15 and 30 cd. 3.520Hz capable with compatible FACR UL Current Draw Data UL Max.Strobe Current Draw(mA RMS) 8 to 17.5 Volts 16 to 33 Volts Candela DC DC FWR 15 87 41 60 30 153 63 86 75 NA 111 142 95 NA 134 164 115 NA 158 191 150 NA 189 228 177 NA 226 264 OutputCeiling-Mount Speaker S und Setting UL Reverberant(dBA 010 ft) UL Anechoic(dBA @10 ft) 1/4 W 79 79 112 W 82 82 1 W 85 85 2 W 88 88 • Setting UL Reverberant(dBA 010 ft) UL Anechoic(dBA @10 ft) 1/4 W 77 77 112 W 80 80 1 W 83 83 2 W 86 86 L-Series Dimensions 1.00' —--- --- 1.63' 6.80'dia Ell �1 Y Ceiling Speaker 2.87' 1.63' 6.80'dia 1.76' I I, Ceiling Speaker Strobe