HomeMy WebLinkAboutBLD2019-01064 Specs 3 Floats - BLD Engineering / Geo-tech Reports - 7/31/2019 UNDERHILL RESIDENTIAL PIER
422 E CRONQUIST RD
ALLYN, WA 98524
CALCULATIONS
PREPARED FOR
MARINE FLOATS
1208 EAST D STREET
TACOMA, WA 98421
° WcU.
35799
O+t rUh'AL
07/31/19
PREPARED BY
Sitts & Hill Engineers, Inc.
4815 Center Street
Tacoma, WA 98409
July 31, 2019
S & H Job Number: 18,469
SITTS& HILL ENGINEERS, INC. DESIGNED JMLS DATE 7/15/2019 JOB 18,469
TACOMA,WASHINGTON (253)474-9449 CHECKED CJT DATE 7/16/2019
PROJECT UNDERHILL RESIDENTIAL PIER PAGE 1
CALCULATION INDEX
BASIS 2
GEOMETRY 3
DESIGN LOADS 4 - 5
LATERAL DESIGN 6 - 9
APPENDICES
11 x 17 DRAWING
SITTS&HILL ENGINEERS, INC. DESIGNED JMLS DATE 7/15/2019 JOB 18,469
TACOMA,WASHINGTON (253)474-9449 CHECKED CJT DATE 7/16/2019
PROJECT UNDERHILL RESIDENTIAL PIER PAGE 2
BASIS FOR DESIGN
BUILDING CODE: 2015 Edition of the International Building Code
SCOPE OF WORK: Replace(3)existing float piles
LATERAL LOAD CRITERIA: Wind Speed=110 mph, Exposure: D.
Seismic Site Class: D.
Seismic Design Category: D.
STRUCTURAL STEEL: Bolts AS TM A307 unless otherwise noted
Piles ASTM A53 Grade B 35 ksi
All Other Structural Steel Shapes IASTIVI A36 36 ksi
WOOD: Joists 2x4 HF#2
2x6 and larger HF#2
Beams 4"width or less HF#2
Greater than 4"width DF#2
ledger 4"width or less HF#2
SITTS & HILL ENGINEERS, INC.
TACOMA, WASHINGTON (253)474-9449 JOB: 18.469
DESIGNED: JMLS DATE: 07/15/2019 3
PROJECT: UNDERHILL RESIDENTIAL PIER CHECKED: CJT DATE: 07/16/2019
PIER GEOMETRY:
EXISTING DOCK, RAMP AND PILES TO REMAIN.
REPLACE EXISTING
WOOD PILES WITH
STEEL PILES.
O � q
EXISTING FLOAT
^°^ TO REMAIN.
NA-M R4W AM FLOAT
SCIL 1LiS
M'IOR StAOM!■O11 xVNdC$.
aLNAIM-P6L RW NO FLOAT
;rr[ ,
SITTS & HILL ENGINEERS, INC.
TACOMA, WASHINGTON (253)474-9449 JOB: 18.469
DESIGNED: JMLS DATE: 07/15/2019 4
PROJECT. UNDERHILL RESIDENTIAL PIER CHECKED: CJT DATE: 07/16/2019
Wind Lateral Force(s):
Wind Load
Terrain Exposure Cunst:anls
Table 26.9-1
Exposure a k(ftl Q b c (tW
B 7.0 1200 V7 0.84 114.0 0.45 0.30 320 113.0 30
c U 900 U9.5 1110 116.5 0.65 0.20 500 115.0 Is
D 11.5 V) 1111.5 1-(r7 119A 0.80 0.15 650 U8.0 7
'z-$minimum height used to ensure that the equivalent height 2 is greater of 0.6h or z_.
For buildings with h<_z_.Z shall be taken as z...
Z9:=700 a:=11.5 Per ASCE 7-10 Table 26.9-1
2
Kz 15.75:=2.01- Z Kz=1.039 Per ASCE 7-10 Table 29.3-1
9
K-t:=1.0 Per ASCE 7-10 26.8
Kd:=0.85 Per ASCE 7-10 Table 26.6-1
G:=0.85 Per ASCE 7-10 26.9
B:=42 f t Length of pier
V:=110 mph
qz:=0.00256-Kz-Kzt-Kd-V2 -psf=27.357 psf
SITTS & HILL ENGINEERS, INC.
TACOMA, WASHINGTON (253)474-9449 JOB: 18,469
DESIGNED: JMLS DATE: 07/15/2019 5
PROJECT: UNDERHILL RESIDENTIAL PIER CHECKED: CJT DATE: 07/16/2019
Wind at float
B:=20 ft Length of dock
s:=10 ft height of craft
B
=2
s
Cf:=1.40 Per ASCE 7-10 Table 29.4-1 (interpolation)
Af._s. 30 ft + 32 ft .4 ft•0.75=198 ft2
Ffloati:=0.5•gz.G•Cf•Af•0.6=1.934 kip
Wind at end of float
B:=20 ft Length of dock
s:=10 ft height of craft
B
—=2
s
C f:=1.40 Per ASCE 7-10 Table 29.4-1 (interpolation)
s•30 ft
Af:= =150 ft'
2
Ff1oat2:=gZ.G•Cf•Af•0.6=2929.9 lbf Per pile, allowable
SITTS & HILL ENGINEERS, INC.
TACOMA, WASHINGTON (253)474-9449 JOB: 18.469
DESIGNED:,JMLS DATE: 07/15/2019 6
PROJECT UNDERHILL RESIDENTIAL PIER CHECKED: CJT DATE: 07/16/2019
PILE AT FLOAT- EMBEDMENT ANALYSIS:
The pile shall be analyzed as a non-constrained embedded pole foundation in accordance
with Section 1807.3.2.1 of the International Building Code
P:=Fftoati=1933.734 lbf (Lateral Load at Top of Single Pier Pile)
b:=10.8 in (Diameter of Pier Pile)
hl:=12.75 ft (Distance From Ground Surface to Point of Load Application)
h:=(hi+5 ft) (Distance from Fixity to Point of Load Application)
Sl:=100 ff (Allowable Lateral Bearing Pressure)
t
�C d:=15 ft (Guess a Value of"d")
V)
W
v
D
d_ 1 • 2.3 •P 1+ 1+ 4.36•h
N
4
2 Sj_ d•b 2.34•P (IBC Equation 18-1)
0 3 d
Sl•3•b
>C D:=Find(d)
0
D=17.754 ft
Use an Embedment Depth of 18'-0" Minimum
SITTS & HILL ENGINEERS, INC.
TACOMA, WASHINGTON (253)474-9449 JOB: 18.469
DESIGNED: JMLS DATE: 07/15/2019 7
PROJECT. UNDERHILL RESIDENTIAL PIER CHECKED: CJT DATE: 07/16/2019
STEEL PILE ANALYSIS: PILE AT FLOAT
THE DESIGN NOMINAL FLEXURAL STRENGTH, Mn/ S?,SHALL BE THE LOWER VALUE OBTAINED
ACCORDING TO THE LIMIT STATES OF YIELDING (PLASTIC MOMENT)AND LOCAL BUCKLING
Mnw .t:=Fft.ti•h M,,,,,, ,,t=411.885 kip•in The moment at pile base
Z:=36.9 in The plastic section modulus
M 35 ksi•Z Mn_773.353 kipn The limiting"�_ 1.67 �i g state of yielding
Check:=if(Mmrnraent<Mn,"Adequate","N.G.") Check="Adequate"
Do_D.:=10.8 in Outside Diameter
t:=0.340 in Design wall thickness
D°'D' =31.765 Width thickness ratio
t
0.07.29000 ksi
AP:= =58 Limiting width thickness ratios
35 ksi Com act( p ) per AISC Table B4.1
0.31.29000 ksi
=256.857 Limiting width thickness ratios
35 ksi (Noncompact) per AISC Table B4.1
Check:=if D O.D. <AP,"Compact",if D.D. >A,.,"Slender","Noncompact"
Since the cross section falls under Compact
Check="Compact" Sections,The limiting State of Flange Local
Buckling Does not Apply.
Therefore use (2) 10"Standard Weight Steel Pile
SITTS & HILL ENGINEERS, INC.
TACOMA, WASHINGTON (253)474-9449 JOB: 18,469
DESIGNED: JMLS DATE: 07/15/2019 8
PROJECT: UNDERHILL RESIDENTIAL PIER CHECKED: CJT DATE: 07/16/2019
PILE AT END OF FLOAT - EMBEDMENT ANALYSIS:
The pile shall be analyzed as a non-constrained embedded pole foundation in accordance
with Section 1807.3.2.1 of the International Building Code
P:=Ffl.t2=2929.9 lbf (Lateral Load at Top of Single Pier Pile)
b:=10.6 in (Diameter of Pier Pile)
hl:=15.75 ft (Distance From Ground Surface to Point of Load Application)
h:=(h1+5 ft) (Distance from Fixity to Point of Load Application)
S1:=100 f f (Allowable Lateral Bearing Pressure)
t
d:=15 ft (Guess a Value of"d")
U)
N
,3
V
d— 1 • 2.34•P l+ l+ 4.36•h
2 d•b 2.34•P S1 , (IBC Equation 18-1)
C 3 d
0 S, •3•b
> D:=Find(d)
0
D=21.785 ft
Use an Embedment Depth of 22'-0" Minimum
SITTS & HILL ENGINEERS, INC.
TACOMA, WASHINGTON (253)474-9449 JOB: 18.469
DESIGNED: JMLS DATE: 07/15/2019 9
PROJECT. UNDERHILL RESIDENTIAL PIER CHECKED: CJT DATE: 07/16/2019
STEEL PILE ANALYSIS: PILE AT END OF FLOAT
THE DESIGN NOMINAL FLEXURAL STRENGTH, Mn/ S?,SHALL BE THE LOWER VALUE OBTAINED
ACCORDING TO THE LIMIT STATES OF YIELDING (PLASTIC MOMENT)AND LOCAL BUCKLING
Mmo .t:=Ff1.t2•h M.nt=729.545 kip in The moment at pile base
Z:=36.9 in The plastic section modulus
M _ 35 ksi•Z M =773.353 kipin The limiting state of yielding
"'� 1.67 n • g Y� g
Check:=if(M,,,a„tent<Mn,"Adequate","N.G.") Check="Adequate"
D°_D.:=10.8 in Outside Diameter
t:=0.340 in Design wall thickness
D°'D' =31.765 Width thickness ratio
t
0.07.29000 ksi
A:_ 35
Limiting width thickness ratios
35 ksi (Compact) per AISC Table B4.1
0.31.29000 ksi
A,.:= =256.857 Limiting width thickness ratios
35 ksi Noncom act( p ) per AISC Table B4.1
Check:=if D O'D' <AP,"Compact",if D O'D' >�, ,"Slender","Noncompact"
Since the cross section falls under Compact
Check="Compact" Sections,The limiting State of Flange Local
Buckling Does not Apply.
Therefore use (1) 10" Standard Weight Steel Pile
APPENDIX A
11 x 17 DRAWINGS
SITTS & HILL ENGINEERS, INC.
1 4
GENERAL STRUCTURAL NOTES
SCOPE OF WORK:
REPLACE(3)EXISTING WOOD PILES AT FLOAT WrTH(3)STEEL PILES.
BUILDING CODE
2015 EDITION OF THE INTERNATIONAL BUILDING CODE SEE GENERAL STRUCTURAL NOTES.
MATH MARINE FLOATS DRAWINGS PRIOR TO START OF CONSTRUCTION; RESOLVE ANY
MINDLOADS..
SLOAD- 110 MPH BASIC WIND SPEED.EXPOSURE D WEER_
SEISMIC DESIGN CATEGORY D GS MAY NOT BE SHOWN ON THE FRAMING PLANS. FOR EXACT SIZE,NUMBER,AND
A GS.SEE MARINE FLOATS.MECHANICAL,ELECTRICAL AA PLUMBING DRAWINGS. FOR
11171 PIPE�S' EE TYPICAL STRUCTURAL DETAILS.VERIFY ALL SIZES,WEIGHTS AND LOCATIONS OF
ALL STEEL RUNG SHALL CONFORM TO ASTM A53 GRADE B(Fy=35 KSI)PIPE WITH PLAIN ENDS. VITH MECHANICAL ENGINEER AND MECHANICAL CONTRACTOR THROUGH MARINE
PILE DAMETER SHALL NOT VARY MORE THAN 1%(+/-)FROM THE SPECIFED DIAMETER.INCLUDING 0 REMAIN UNCHANGED o'
OUTSIDE DIAMETER AT WELDS. THE WEIGHT OF THE PILE SHALL BE NOT MORE THAN 15%HEAVIER NC H
5%LIGHTER THAN SPECIFIED PER ASTM A53. PILE NOMINAL WALL THICKNESS AT ANY POINT SHALL N;UNCHANGED..
BE LESS THAN 12.5%UNDER SPECIFIED WALL THICKNESS. PILE SHALL BE REASONABLY STRAIGHT. PI
SURFACE IMPERFECTION SHALL NOT EXCEED A DEPTH GREATER THAN 25%OF THE NOMINAL WALL V UNCHANGED
THICKNESS. PILE CWNG SYSTEM SHALL NOT BE DAMAGED UPON DELIVERY AND UNLOADING. REPAK
OF DEFECTS BY WELDING IS STRUCTURALLY ACCEPTABLE WHEN THE DEPTH IS NOT MORE THAN 33%OPILES WITH TO-NOMINAL STANDARD WEIGHT GALVANIZED STEII.PILES PER CSN
THE NOMINAL WALL THICKNESS. HAMMER TO A MINIMUM EMBEDMENT DEPTH OF 22'-0'OR UNTIL REFUSAL.
snwcTL%L SLffL 3
-- ALL STRUCTURAL STEEL SHALL BE ASTM A36(Fy=36 KSI). ALL BOLTS SHALL BE ASTM A307,
UNLESS NOTED OTHERWISE. ALL CONSTRUCTION PER LATEST MSC HANDBOOK ALL EXPANSION AND
EPDXY BOLTS TO HAVE I.C.C.RATING FOR MATERIAL INTO WHICH INSTALLATION TAKES PLACE ALL L BOLTS,ANCHOR BOLTS,EXPANSION BOLTS,ETC.,SHALL BE INSTALLED WITH STEEL WASHERS AT FACE Q�'o W"1, s
WOOD OR AT SLOTTED HOLES IN STEEL SECTIONS. ALL WELDING SHALL BE PERFORMED BY WELDERS `Ss o
HOLDING VNJD CERTIFICATES AND HAVING CURRENT EXPERIENCE IN THE TYKE OF WELD SHOWN ON Fill : m a m
DRAWINGS OR NOTES. CERTIFICATES SHALL BE THOSE ISSUED BY AN ACCEPTED TESTING AGENCY. AL -'
WELDING DONE BY E70 SERIES LOW HYDROGEN RODS UNLESS NOTED OTHERWISE. ALL WELDING PER
LATEST AM
ERICAN WELDING SOCIETY STANDARDS. THESE DRAWINGS DO NO-DISTINGUISH BETWEEN SHC
AND FIELD WELDS:THE CONTRACTOR MAY SHOP WELD OR FIELD WELD AT THEIR DISCRETION. SHOP
WELDS AND FIELD WELDS SHALL BE SHOWN ON THE SHOP DRAWINGS SUBMITTED FOR REVIEW. �F7 4R
e 6
JZ Z °
< a
_ .. In 3a
C • Q
� e
42'-0' � W �
H
�F
0W UN
I— Z Uf z o
_ w n
0 J
v 5 m
Z
0 0 W
o O
W °
C EXrnNC
REMAINIER, Q O' Z
TO O to 0
LL Z
r =
PLAN-PER,RAMP AND FLOAT z 3
SCALE:N.T.S. Q p Q
EXISTING PIER, o � U
g
W
(L Fw-J
J 0(L
1— Z L
v
J
W ILM) jr m
-rn �QUQ
Whofro �J
J 0 Z cr)OWa:in LLi
WW� = w°-
N- = DMZ
��a
ELEVATION -PIER, RAMP AND FLOAT
S1.0
�kaFa r,_
18,469