HomeMy WebLinkAboutBLD2022-01076 Foundation Pin Piles - BLD Application - 8/15/2022 MASON COUNTY COMMUNITY SERVICES Permit No:'�ICI G,11GZ - D I D-ko
PERMIT ASSISTANCE CENTER:
-BUILDING-PLANNING•PUBLIC HEALTH-FIRE MARSHAL RECEIVED
615 W.Alder Street,Shelton,WA 98584
Phone Shelton:(360)427-9670 ext 352•Fax:(360)427-7798 Phone
BefYair.(360)275-4467•Phone Ekna:(360)482-5269 A U G 15
2022
. BUILDING PERMIT APPLICATION
PROPERTY OWNER INFORMATION: CONTRACTOR INFORMA Q : Alder St,eet
NAME:Michael&Helen Lester NAME:TBD
MAILING ADDRESS:Po Box 921 MAILING ADDRESS:
CITY:Allyn STATE:WA ZIP:98524 CITY: STATE: ZIP:
PHONE#1:360-277-0476 PHONE: CELL: 360-275-56M
PHONE#2:n1a EMAIL:
EMAIL:mlester@farmersagent.com L&I REG# EXP.
PRIMARY CONTACT: OWNER❑ CONTRACTOR❑ OTHER❑
NAME Michael Staten EMAIL envsotech@geotechnicalirdo.com
MAILING ADDRESS Po Box 984 CITY Belfair STATE WA ZIP 98528
PHONE 360-275-9374 CELL 36"896045
PARCEL INFORMATION:
PARCEL NUMBER(12 Digit Number) 32025-5140008 ZONING Rural Residential
LEGAL DESCRIPTION(Abbreviated) CHANNEL PoiNT TRs&9&E 1tz oFTR 10&sre&mr fN TR 2&TR t of TR 14 FIRE DISTRICT Shelton
SITE ADDRESS 481 SE Channel Point Road CITY Shelton
DIRECTIONS TO SITE ADDRESS From Shelton on State Route 3,turn East onto SE Arcadia Road.Turn left on SE Channel Point Road.
IS THE PROJECT WITHIN 300 FT OF SLOPE(S)GREATER THAN 14%: YES❑+ NO❑ SNOW LOAD:25 psf
IS PROPERTY WITHIN 200 FT OF THE FOLLOWING: (Checkall than apply):
SALTWATER❑� LAKE❑ RIVER/CREEK❑ POND❑ WETLAND❑ SEASONAL RUNOFF❑ STREAM❑
TYPE OF WORK: NEW❑ ADDITION❑ ALTERATION 0 REPAIR❑ OTHER ❑
USE OF STRUCTURE(Residence,Gar2ge,Commercial Bldg,Etc.)Residence
IS USE: PRIMARY[] SEASONAL❑ NUMBER OF BEDROOMS NUMBER OF BATHROOMS
HEATED STRUCTURE? YES(Whole Bldg)❑ YES(Part[s]ofBldg)❑ NO❑
DESCRIBE WORK Add pin piles to portion of existing foundation for landslide protection
SQUARE FOOTAGE:(proposed)
I ST FLOOR sq.ft. 2ND FLOOR sq.ft. 3RD FLOOR sq.ft. BASEMENT sq.ft.
DECK sq,ft. COVERED DECK sq.ft. STORAGE sq.ft. OTHER sq.ft.
GARAGE sq.ft. Attached❑ Detached❑ CARPORT sq.& Attached❑ Detached❑
MANUFACTURED HOME INFORMATION: *4 COPIES OF THE FLOOR PLAN REQUIRED*
MAKE MODEL YEAR LENGTH
WIDTH BEDROOMS BATHS SERIAL NUMBER
ENVIRONMENTAL HEALTH:
SEWAGE/SEWER SOURCE: SEPTIC❑ SEWER❑ / NEW❑ EXISTING❑
PLUMBING IN STRUCTURE? YES❑ NO❑ If yes,attach completed Water Adequacy Form
PERIMETER/FOUNDATION DRAINS PROPOSED? YES❑ NC)[] EXISTING SQ.FT.
EXISTING BEDROOMS . PROPOSED BEDROOMS TOTAL BEDROOMS
OWNER acknowledges that submission of inaccurate information may result in a stop work order or permit revocation.Acknowledgement of such is by
signature below.I declare that I am the owner and I further declare that 1 am entitled to receive this permit and to do the work as proposed.I have
obtained permission from all the necessary parties,including any easement holder or parties of interest regarding this project. The owner or legal
representative,represents that the information provided is accurate and grants employees of Mason County access to the above described property
and structure(s)for review and inspection. This pernitlapplication becomes null&void if work or authorized construction is not commenced within 180
days orff construction work is suspended for a period of 180 days.
PROOF OF CONTINUATION OF WORK ON THIS PERMIT IS BY MEANS OF INSPECTION. INACTIVITY OF THIS
PERMIT APPLICATION OF 180 DAYS OF MORE WILL CAUSE THE APPLICATION TO BE EXPIRED.(MASON
COUNTY CODE 14.08.42)
x re �/�✓�2Z
Signature of OWNER(Must be signecrby the OWNERI Date
DEPARTMENTAL REVIEW APPROVED DATE DENIED DATE TAGS/NOTES/CONDTTIONS
BUILDING DEPARTMENT
PLANNING DEPARTMENT I
FIRE MARSHAL
PUBLIC HEALTH
RECEIVED
�vLv�rotech ��,�Twee►-�w�
ceoteehvdcal- C—vwCrovLnttv,.taL O DratvAt3e 0 Rnadwa� AUG 15 2022
r
615 W. Alder Street
August 8,2022
Mike and Helen Lester
481 SE Channel Point Road
Shelton,Washington 98584
Reference: Pin Pile Calculation Report
481 SE Channel Point Road,Shelton,Mason County Washington
Parcel 32025-51-00008
To Whom It May Concern,
Envirotech Engineering has completed the structural design for a foundation fortification of the
referenced project. The following analysis provides methods and calculations for this project, and meets
or exceeds the 2018 IBC.
Design Loads - The vertical and lateral loads of the structure provided below accounts for the factored
dead loads and factored live loads.
Snow=25 psf live
Roof= 15 psf dead
Floors=40 psf live
Floors= 12 psf dead
Walls= 10 psf dead
Wind=85 mph/110 mph peak gust
Seismic=Category Dl/D2
Roof Loads
w=27 ft wide x 15 ft depth(25 psf+ 15 psf)= 16,200 lb total load to be carried by pin piles
where 27 ft x 15 ft=conservative area requiring support
25 psf=snow load
15 psf=roof dead load
PO Sox9 84
gelfaCr, washivgtovL98s�g
off.
f: 360-2�5J°3�4
cell: 3r'O-689-6045
evevirotecl�@geotechwicaliv�,fo.covu.
c s,
Floor Loads
w=24 ft x 15 ft(40 psf+ 12 psf)= 18,720 lb total load to be carried by pin piles
where 24 ft x 15 ft=conservative floor area requiring support
40 psf=floor live load
12 psf=floor dead load
Wall Loads
w=0.5 ft(10 psf)781f=390 lb total load to be carried by pin piles
where 0.5 ft=width of wall
10 psf=wall load
781f=length of walls
Summation of Loads
W= 16,200 lb+ 18,720 lb+390 lb=35,310 lb
Floor Beam Analysis
Beam Parameters Maximum Bending Moment(ft-lb)
Span, L 4.00 ft PL/4(point load) 0 ft-lb
1,700,00
Moment of Elasticity, E 0 psi wL^2/8(dist. Load) 2,944 ft-lb
Moment of Inertia,1 443.6 in^4
El 7.54E+08 psi Mmax Total 2,944 ft-lb
Support ff Bending Moment Capacity(ft-lb)
(ff=fixed on ends, c=cantilever
ffc=fixed on ends and center) fb=Fb*Cr*...*Cv 932 psi
S=bd^2/6 0.0446 cf
Bending Design Value, Fb 900 psi
Repetative Member factor,Cr 1.15 M=fb*S 5,988 ft-lb
Size factor, CF 1.0
Load Duration factor,CD 0.9 M >Mmax
Beam Stability factor,CL 1.0
CV 1.0 5,988 > 2,944 o.k.
breadth, b 3.500 in
depth, d 11.500 in
Page 2 of 3
t r
Deflection
Applied Loads Ob, Ib/ft)
PL^3/48E1 0 in
Point Load, P 0 5wLA4/384EI 0.0112 in
P Location (c,x) x
c=center of beam Total Deflection 0.0112 in
Allowable
x=load dist from furthest support 0.0 Deflection 0.4 in
Distributed Load,w 1,472 Deflection<Allow ok
Conclusions
Design Pile Capacity= 12,000 lb
Design Load=35,310 IN 6 vertical piles=5,885 lb per pile o.k.
Envirotech appreciates the opportunity to be of assistance on this project.Please contact Michael Staten at
360-275-9374 if you have any questions or require additional information.
Sincerely,
Envirotech Engineering
CLYDC S
NVAS/f/.y�T9���
Q�
2� k 43045
FCISTER{
�SS�GNAL
8/8/22
Michael Staten,P.E.
Project Director
Page 3 of 3
t
RECEIVED
AUG 15 2022
615 W. Alder Street SCALE, 1 INCH = 50 FEET
0 25 50
HAMMERSLEY INLET
TOE OF BLUFF
TOP OF BLUFF
EXISITNG DECK
EXISTING SINGLE FAMILY
RESIDENCE
EXISTING DRIVEWAY
SE CHANNEL1� POINT RD
PROJECT/ OWNER/ LOCATIO14
CLYDe
�E sT LESTER PIN PILES
G� of%AS& �>
LESTER
481 SE CHANNEL POINT RD
PARCEL 32025-51-00008
MASON COUNTY WASHINGTON
ENGINEER.
2 k 43045 ` ENVIROT BOX ECH
ENGINEERING
GFf FGIs F, �T HELFAIR, WASHINGTON 98528
Ss/0,\'ALE`G 518122 360-275-9374
SITE PLAN - SH 1 OF 3
t
SCALE- I INCH = 20 FEET
0 Io 20
HAMMERSLEY INLET
TOP OF BLUFF
TOE OF BLUFF
\ NEW 6x12 FLOOR
\ BEAM TO SPAN
EXISITNG �� ENTIRE EXTERIOR
DECK — _ _ WALL SEGMENT,
-4F,FX 24' LONG.
FIELD VERIFY.
A A
(6) VERTICAL PIN
PILES @ 4' SPACING,
AND (2) BATTERED
PIN PILES, ONE EA.
END. SEE DETAILS
EXISTING SINGLE FAMILY AND NOTES,
RESIDENCE
PROJECT/ OWNER/ LOCATION
CL YL)psT�T� LESTER PIN PILES
`C C. 2 LESTER
481 SE CHANNEL POINT RD
4� PARCEL 32025-51-00008
MASON COUNTY WASHINGTON
ENGINEER
A- ?C 43045 ZF ENVPO BQXT9B4 ENGINEERING
GISTE� �r BELFAIR, WASHINGTON 98528
SS�01'.4LyG 8/8/11 360-275-9374
SITE PLAN-INSET SH 2 OF 3
}
SIMPSON J57 FLOOR BEAM
LEVELER WITHOUT THE BASE.
J' ROD TO BE INSERTED
INTO PIN PILE EXISTING FLOOR
BEAM (TYP)
SIMPS❑N CC❑B
(TYP)
NEW 4X12 DF #2
4' (TYP)
BATTERED PILES
TO BE BEHIND
(LANDWARD) OF
VERTICAL PILES,
AND D❑ NOT
REQUIRE AN
END CAP
PIER; 2' DIA.
X 0.12' STEEL
TUBING, ASTM
A513 (TYP).
SIX MINIMUM
BATTERED PIN PILES
ALL PIN PILES DRIV AS SHOWN, INCLINED 10
TO REFUSAL, S DEG, MIN. TO 20 DEG,
NOTES,, SECTION A—A MAX.
N.T.S. PROJECT,
GENERAL NOTES
1. LOCATE ALL UTILITIES, AND ACCOMMODATE AS LESTER PIN PILES
NECESSARY DURING PIER INSTALLATION. LESTER
2• EXPOSE F❑UNDATI❑N AT THE PROPOSED PIER 481 SE CHANNEL POINT ROAD
LOCATIONS. SHELTON, WASHINGTON
3• INSTALL PIERS AT THE L❑CATIONS PER PLAN. ANY ENGINEER,
CONFLICTS SHALL BE REPORTED TO THE ENGINEER. � CCYnF
4• RAISE HOME, OFFSET OR SLIGHTLY BEND PIERS IN �E S ENVIROTECH ENGINEERING
ORDER TO CONSTRUCT PER THESE PLANS, c` o�".as/l T'I PO BOX 994
,C 1�' BELFAIR, WASHINGTON 98528
5• SECURE ALL BRACKETS PER MANUFACTURERS PHONE, C360> 275-9374
RECOMMENDATIONS AND THESE PLANS. �- DRAWN BY- DATE-
6. PER THE IBC, FOUNDATIONS SHALL BE INSPECTED L,. Mcs 8i8i22
CONTINUOUSLY DURING INSTALLATION OF DEEP ? 43045 DESIGNED BY, DATE+
FOUNDATIONS (PIERS). Michaet Staten, P.E. 8/8722
7, CONTRACTOR RESPONSIBLE FOR SAFETY, AND SHALL SHEET
FOLLOW ALL APPLICABLE IBC AND LOCAL CODES. SHEET 3 OF 3