HomeMy WebLinkAboutCOM2018-00119 Cancelled Dorm Units - COM Permit / Conditions - 2/22/2021 MASON COUNTY DEPT. OF COMMUNITY DEVELOPMENT rnone: (3qu)4zt-ynru, ext. 3oz
soN CODA
Mason County
615 W Alder St
Shelton, WA 98584
IR54
COMMERCIAL BUILDING PERMIT COM2018-00119
OWNER: WASHINGTON STATE PATROL RECEIVED: 10/11/2018
CONTRACTOR: LICENSE: EXP: ISSUED: 12/11/2018
SITE ADDRESS: 631 W DAYTON AIRPORT RD SHELTON EXPIRES: 6/11/2019
PARCEL NUMBER: 420023260010
LEGAL DESCRIPTION: TR 1 OF N1/2 SW
PROJECT DESCRIPTION: DIRECTIONS TO SITE:
DORM C BLDG, DORM D BLDG. DORM E BLDG - PROVIDE US HIGHWAY 101 NORTH, L ON DAYTON AIRPORT RD FOLLOW TO SITE
REPLACEMENT UNITS FOR THE EXISTING CARRIER ADDRESS ON THE LEFT SIDE
5-TON UNITS THAT SERVE DORMS
General Information Co ruction&Occupancy Information
Type of Use: Dorms C and D Insp.Area: No ni Type of Constr.:
No. ro Occ. Group:
Type of Work: MEC Fire Dist.: 16 0. to s. Exit Design. Load:
Valuation:
)t44�
u in
Pre-Manufactured Unit Information Square Footage Information
Make: Length: Lot Size:
Model: Width: Building:
Year: Serial No.: Basement: Parking Spaces:
Setback Information
Shoreline& Planning Information
Front: Ft. Shoreline: Ft.
Rear: Ft. Slope: Ft. Water Body: Shoreline Desig.:
Side 1: Ft. SEPA?: Comp. Plan Desig.:
Side 2: Ft.
Fire Protection System Information
Auto Fire Alarm System?: Emergency Key Box?: Standpipe?:
Auto Fire Sprinkler System?: Access Road?: Fire Extinguishers?:
Fixed Fire Suppression System?: Fire Hydrants?: Fire Lanes?:
COM2018-00119 Please refer to the following pages for conditions of this permit. Page 1 of 5
Plumbing Fixtures Mechanical Fixtures rr-_a
Type Qty. Type Qty. Type By Date Amount Receipt
Furnace<100K 3 Plan Check Fee TIN 11/14/gn1; -t71 nn gggnlRnn
Building State Fee TIA/ 11/19/?Ol; 09r,nn S9?n1Rnn
Mechanical Permit Fee TAM 11/19/9ni; A5d Qn C7gnlRnn
Mechanical Base Fee TIN 11/1Q/9n1; ,t?R;n g99n1snn
Total $181.40
CASE NOTES FOR
COM2018-00119
CONDITIONS FOR
COM2018-00119
1) Contractor registration laws are governed under RCW 18.27 and enforced by the WA State Dept of Labor and Industries, Contractor Compliance
Division. There are potential risks and monetary liabilities to the homeowner for using an unregistered contractor. Further information can be
obtained at 1-800-647-0982. The person signing this condition is either the homeowner, agent for the owner or a registered contractor according to
WA state law. X I' 1_
2) All approved plans are required to be on-site for inspection purposes. If inspection is called for and plans are not on site, Approval WILL NOT be
granted. In addition, a reinspection fee, based on the current fee schedule, minimum one-hour will be charged and collected by the Mason County
Building Department prior to any further inspections being performed or approvals granted. X 1�_J,
3) Owner/Agent is responsible to post the assigned address and/or purchase and post private road signs in accordance with Mason County Title
14.28.,
X x) - -
4) Any changes in construction shall be reviewed by engineer of record and submitted in writing to the Mason County Building Department prior to
construction. All engineering documents are a part of the approved set of plans and must remain attached thereto. If engineering documents are
removed, approval will not be granted. In addition, a reinspection fee, based on the current fee schedule, minimum one-hour will be charged and
collected by the Mason County Building Department prior to any further inspections being performed or approvals granted.
X ,1_j =�
5) ALL CONSTRUCTION MUST MEET OR EXCEED ALL LOCAL CODES AND THE INTERNATIONAL CODE REQUIREMENTS AND OCCUPANCY
IS LIMITED TO THE PERMITTED AND APPROVED CLASSIFICATION. ANY CHANGE OF USE OR OCCUPANCY WOULD RESULT IN PERMIT
REVOCATION. CHANGE OF USE MUST BE APPROVED PRIOR TO CHANGE. x
6) Changes to approved building plans that affect compliance to the current Washington State Energy Code (WSEC), ventilation requirements),
Building/Plumbing/Mechanical Codes and/or Mason County Regulations shall be approved prior to construction.
X ;(_
COM2018-00119 Page 2 of 5
7). CONSI RUG I IUN NKUCtSS I U tit FItLU UUKKtU I to H,-,J KtUUIKtU t t:K IVI/AoUIN UUUIv I r bUILUIIVh UCY'Hrc I IVItIV I /UVU I nC
ADOPTED BUILDING CODE.
The construction of the permitted project is subject to inspections by the Mason County Building Department. All construction must be in
conformance with the international codes as amended and adopted by Mason County. Any corrections, changes or alterations required by a
Mason Qounty Building Inspector shall be made prior to requesting additional inspections.
X
8) New and replaced heating equipment shall meet the requirements of the Internation Energy Conservation Code as amended Washington State
Energy Code (WSEC), and applicable sections of the IBC and IMC. All new or replaced heating equipment shall meet the efficiency requirements
of WSEC C403.2.3.
Those parts of heating systems that are altered or replaced shall comply with the current Washington State Energy Code (WSEC), Section
C101.4.3.2. When a space-conditioning system is altered by the installation or replacement of space conditioning equipment (including
replacement of the air handler, outdoor condensing unit of a split system air conditioner or heat pump, cooling or heating coil, or the furnace heat
exchanger), the duct system that is connected to the new or replacement space-conditioning equipment shall be installed and sealed in
accordance with C403.2.7.
All new and replaced heating equipment shall comply with WSEC Section C403. Heating and design load calculations for the purpose of sizing
HVAC systems are required and shall be calculated in accordance with accepted practice, including infiltration and ventilation. Provide design
calculations during inspection.
Referencing WSEC C403.2.7 and IMC Chapter 6, all new ducts, air handlers, filter boxes, and building cavities shall be sealed. All joints of duct
systems and seams shall be made substantially air tight by means of tapes, mastics, liquid sealants, gasketing or other approved closure systems.
Closure systems used with rigid fibrous glass ducts shall comply with UL181A and shall be marked 181A-P for pressure-sensitive tape, 181A-M for
mastic or 181 A-H for heat-sensitive tape. Closure systems used with flexible air ducts and flexible air connectors shall comply with UL181 B and
shall be marked 181 B-FX for pressure-sensitive tape or 181 B-M for mastic. Duct connections to flanges of air distribution system equipment or
sheet metal fittings shall be mechanically fastened. Mechanical fasteners for use with flexible nonmetallic air ducts shall comply with UL 181 B and
shall be marked 181 B-C. Crimp joints for round metal ducts shall have a contact lap of at least 1-1/2 inches (38 mm) and shall be mechanically
fastened by means of at least three sheet-metal screws or rivets equally spaced around the joint. Closure systems used to seal metal ductwork
shall be installed in accordance with the manufacturer's installation instructions.
Duct tape is NOT permitted as a sealant on any new duct systems. When new ducts are located in unheated spaces the ducts shall be insulated to
R-8
L.
X
9) All building permits shall have a final inspection performed and approved by the Mason County Building Department prior to permit expiration. The
failure to request a final inspection or to obtain approval will be documented in the legal property records on file with Mason County as being
non-co pliant with Mason County ordinances and building regulations.
X x
10) All permits expire 180 days after permit issuance, or 180 days after the last inspection activity is performed. The Building Official may extend the
time for action for a period not exceeding 180 days, upon the receipt of a written extension request indicating that circumstances beyond the control
of the permit holder have prevented action from being taken. No more than one extension may be granted.
X -��)) -_1
COM2018-00119 Page 3 of 5
11;i Prior to obtaining final occupancy approval the registered design professional shall provide evidence of systems commissioning ana completon in
accordance with the 2012 International Energy Conservation/Washington State Energy Code (IECC/WSEC) Section C408.
Copies of all documentation shall be given to Mason County Department of Community Development prior requesting the final occupancy
inspection and shall include commissioning of the building mechanical system (C403), service water heating systems (C404), electrical power and
lighting systems (C405), and energy metering (C409). X A
12) System must be equipt with duct detections.
Separtate fire protection permit required.
System must be inspected and approved by the Flre Marshals office prior to final inspect.
=�
13) Prior to obtaining final occupancy approval the registered design professional shall provide evidence of systems commissioning and completion in
accordance with the 2012 International Energy Conservation/Washington State Energy Code (IECCNI/SEC) Section C408
Copies of all documentation shall be given to Mason County Department of Community Development prior requesting the final occupancy
inspection and shall include commissioning of the building mechanical system (C403). SEE PLANS FOR DETAILS
Do not call for final until commissioning documents are submitted to Mason County.
X L)
OWNER/BUILDER acknowledges submission of inaccurate information may result in a stop work order or permit revocation. Acknowledgement of such is by
signature below. I declare that I am the owner, owners legal representative, or contractor. I further declare that I am entitled to receive this permit and to do the
work as proposed. I have obtained permission from all the necessary parties, including any easement holder or parties of interest regarding this project. The
owner or authorized agent represents that the information provided is accurate and grants employees of Mason County access to the above described property
and structure(s)for review and inspection. This permit/application becomes null &void if work or authorized construction is not commenced within 180 days or if
construction work is suspended for a period of 180 days. PROOF OF CONTINUATION OF WORK IS BY MEANS OF INSPECTION. INACTIVITY OF THIS
PERMIT APPLICATION OF 180 DAYS WILL INVALIDATE THE APPLICATION.
Signature Date
OWNER - REPRESENTATIVE - CONTRACTOR
Print Name (Circle one to indicate)
COM2018-00119 Page 4 of 5
CONCRETE MECHANICAL MANUFACTURED HOME
tV CAI
=
Date t3 y
00 Footings J Setbacks Gag piping Ribbons
Z
o Inte;Tor Date By Interior-Date By Date By 0Exterw Date BY Exterior-Date B --i
Seta _
0
Point Load!Isolated Footings INSULATION Date By Z
BG t SLAB INSULATION __ _ _,_. N
Date By Data ey FIRE DEPARTMENT
Foundation Walls Floors Date By
Date gy Data By DECKS
FRAMING walls Date By
Date By Data By PROPANE TANKS X
PLUMBING vault Date By r-
__ — Date _ By _ OTHER
Groundwork Attic
Date By Type.
Date B y Date By
D.W.v DRYWALL Type 0
Int.Brace Wall 0
Date By Date By Date By K
FINAL INSPECTION O
Water Line Fire Seperation L
Date By Date By Date By io
O
Pass or Request Inspect.
Type of Insp. Fail Date Date Done By Comments
1
v
m
01
0
`aY-n GI✓to �9 �P
00 ,l 2015 Washington Sta a 9Y ner o li ce fo om ercia, er G Vdf
Plans
1-Mechanical Permit
2015 Washington State Energy Code Compliance Forms for Commercial Buildings including R2&R3 over 3 stories and all R1 Revised January 2017
Project Title: WSP Shelton Kitchen and Dorm HVAC Date 1/1/2 C 15
he following information is necessary to check a permit application for compliance with the mechanical systems and equipment requirements of the
Washington State Energy Code,Commercial Provisions.
Applicable Code Section Code Provision Information Required-Must be in permit documents Location in Building Department
es,no,na Documents Notes
NA C403.2.4.3 Stairway and shaft vent Indicate location of stairway and shaft vent dampers on plans;verify dampers are Class
dampers motorized;refer to HVAC System Controls for additional requirements
For systems serving areas>25,000 sf or spanning more than one floor,that include areas that-
NA C403.2.4.4 Zone isolation dampers are expected to be occupied non-simultaneously;identify isolation zone areas on plans and
locations of associated isolation dampers in HVAC distribution system;refer to HVAC System
Controls for additional requirements
For cooling systems with humidification equipment that are also required to have air
NA C403.2.3.4 Humidification economizer,indicate humidifier is adiabatic(direct evaporative or fog atomization),or
exception taken
Additional Efficiency Package Option,More Efficient HVAC Equipment&Fan Performance-
Must comply with all 3 provisions to be eligible
C406.2.1 To comply with additional efficiency package option,calculate the percentage of heating and
NA C403.2.3 HVAC system selection cooling equipment in the project(based on output capacity)that do not have a corresponding
WSEC listed efficiency;shall be less than 10%to comply
NA C406.2.2 Minimum equipment To comply with additional efficiency package option,indicate that all listed heating and cooling
C403.2.3 efficiency equipment have a rated efficiency that exceeds WSEC listed efficiency by at least 15%
C406.2.3 To comply with additional efficiency package option,indicate rated FEG of stand alone fans is z-
NA C403.2.11.3 Minimum fan efficiency 71;indicate these fans are sized so the fan efficiency at design conditions is within 10%of the
maximum total or static efficiency
HVAC System Controls
Indicate locations of thermostatic and humidity control devices and the zones they serve on 4MM4,Jg0
plans,including perimeter system zones
Where adjacent(neighboring)zones are controlled by separate thermostats(including
perimeter systems used to offset heat gain or loss),and are connected by permanent
Thermostatic controls openings>10%of either zone sf area,indicate controls configured to prevent adjacent zones
Yes C403.2.4.1 (thermostats and from operating in conflicting modes(one in heat,other in cool);applies to adjacent perimeter
humidistats) zones,adjacent nonperimeter zones,and adjacent perimeter and nonperimeter zones
If applying Exception 2 to nonperimeter zones adjacent to perimeter zones,indicate that
setpoints and deadband settings in these zones are coordinated so cooling in a nonperimeter
zone does not occur until the temperature in that zone is 5°F higher than the adjacent
perimeter zone temperature in heating
NA C403.2.4.1.1 Heat pump supplementary Indicate staged heating operation with compression as the first stage of heating and
heat supplemental heating controlled with outdoor lock-out temperature set to 40°F or less
Yes C403.2.4.1.2 Deadband Indicate zone thermostatic controls configured with 5°F minimum deadband for systems that MO.�
control both heating and cooling
If separate heating and cooling systems with separate thermostatic control devices are used to
Setpserve a zone,indicate locations of both thermostatic control devices and the zone they serve
NA C403.2.4.1.3 (thermostats)
tat))oved restriction on plans
(thermostats)
Indicate a limit switch,mechanical stop or DDC control with programming to prevent -
simultaneous heating and cooling
C403.2.4.2 Indicate zone thermostatic controls configured with required automatic setback and manual
Yes C403.2.4.2.1 Automatic setback and shutdown override functions,setback temperatures,and control method(automatic time clock or
C403.2.4.2.2 programmable controls);note exceptions taken
Indicate system controls that adjust equipment start time required to bring each area served M0.1
Yes C403.2.4.2.3 Automatic(optimum)start to design temperature just prior to scheduled occupancy
Indicate automatic controls configured to close OSA damper during unoccupied equipment 1149vi
Yes C403.2.4.3 Outdoor supply air dampers operation;not including economizer cooling,night flush or IMC required OSA/exhaust i
NA C403.2.4.3 Stairway and shaft vent Indicate method of activation of stairway and shaft vent dampers(fire alarm or interruption of
dampers power)
For systems serving areas>25,000 sf or spanning more than one floor,that include areas that-
NA C403.2.4.4 Zone isolation controls are expected to be occupied non-simultaneously;indicate controls that allow for independent
space conditioning of isolation zones;or exception taken
NA C403.2.12 Heating outside a building Indicate occupancy sensing or timer switch controls configured to automatically shut off
heating system when area served is unoccupied
NA C403.2.4.5 Snow melt systems Indicate automatic controls configured to shut off system when pavement temperature
exceeds 50'F and no precipitation is falling,and when outdoor air temperature exceeds 40'F
NA C403.2.4.6 Freeze protection system Indicate automatic controls to shut off system when outdoor temperature exceeds 407,or
controls conditions protect fluid from freezing
Group R 1 hotel/motel For hotels and motels with over 50 guest rooms,indicate automatic controls serving guest
NA C403.2.4.9 guest rooms rooms that are capable of setback(heating)and set-up(cooling)of temperature setpoint by at
least 5°F;indicate control method-activated by room entry or occupancy sensor
6:;2m ttv"', 44
141� I N
x •
2015 Washington State Energy Code Compliance Forms for Commercial,R2 and R3 over 3 stories and all R1 -Page 1 of 7
PermitMechanical
2015 Washington State Energy Code Compliance Forms for Commercial Buildings including R2$R3 over 3 stories and all R1 Revised January 2017
Project Title: WSP Shelton Kitchen and Dorm HVAC Date 1/1/2015
e following information is necessary to check a permit application for compliance with the mechanical systems and equipment requirements of the
Washington State Energy Code,Commercial Provisions.
Applicable Location in Building Department
s,no,na
Code Section Code Provision Information Required-Must be in permit documents Documents Notes
Equipment-Sizing,Performance and Type
Identify equipment to be used in manufacturing,industrial or commercial processes that do not -
NA C403.1 Exempt process equipment provide space conditioning;identify provisions applicable to this equipment per C403.1
exception
Provide load calculations performed per ASHRAE Sid 183 or equivalent,using design zs
Yes C403.2.1 Load calculations parameters per C302 and Appendix C;include load adjustments to account for energy
recovery
Equipment and system Indicate that output capacities of heating and cooling equipment and systems are no gre
sizing
Yes C403.2.2 than the smallest available equipment size that exceeds the calculated loads;note excep s
taken
C403.2.3 HVAC equipment Provide equipment schedules on plans or complete MECH-EQ forms indicating type,capa'fr ilia"
Yes C403.2.3.2 performance requirements rated and WSEC minimum efficiencies for all heating and cooling equipment;include supply
C403.2..3.2 (efficiency) and OSA cfms and operating hours for all air systems;identify heating and cooling equipment
that does not have a corresponding WSEC minimum efficiency(manufacturer rated)
List all motors t 1/12 hp(that are not integral to a rated piece of equipment)in the mechanical
C405.8 or electrical equipment schedules on plans;indicate hp,rpm,number of poles and rated
NA C403.2.14 Electric motor efficiency efficiency,or exception applied
For fractional hp motors(1/12-1 hp),indicate whether they are an electronically commutated -
motor,have rated efficiency of at least 70%,or exception taken
For all HVAC fan systems that provide heating and/or cooling,provide system total
nameplate hp in MECH-FANSYS-SUM form
Yes C403.2.11.1 Fan power limitation For all applicable HVAC systems with total fan motor hp>5hp,verify fan system motor hp or
bhp complies with fan power limits per equations in Table C403.2.11.1(1),provide MECH-
FANSYS form for each system
NA C403.2.11.2 Motor nameplate hp For all applicable HVAC systems with total fan motor hp>5hp,indicate fan motors specified
are the smallest available motor hp size greater than fan bhp,note exceptions taken
For all applicable HVAC systems with total fan motor hp>5hp,identify in equipment schedule
NA C403.2.11.3 Fan efficiency all fans required to comply with fan efficiency grade and indicate rated FEG is t 67,or
exception taken;indicate these fans are sized so total efficiency is within 15%of the fan
maximum total efficiency
NA C403.2.11.4 Group R occupancy exhaust For all exhaust fans<400 cfm in Group R occupancies,indicate in equipment schedule the
fan efficacy fan flow rate and efficacy(cfm/watt),or exception taken;refer to Table C403.2.11.4(CE-57)
Variable flow capacity- For fan motors a 7.5 hp,indicate method of variable flow control(VSD or equivalent method)in
NA C403.2.13 fans equipment schedule,or exception taken;for equivalent method for an HVAC system refer to
HVAC System Controls for additional requirements
NA C4032.3 Maximum air cooled chiller For chilled water plants and buildings with>500 tons of cooling capacity,indicate air-cooled
capacity chiller capacity is<_100 tons,or exception taken
Large capacity cooling For buildings with 2 300 tons of cooling capacity,indicate method of multi-stage or variable
NA C403.4 systems capacity control(VSD,multiple staged compressors,or max capacity of any single unit<66%
of the total)
Non-standard water-cooled For water-cooled centrifugal chillers not designed for operation at standard conditions,provide
NA C403.2.3.1 centrifugal chillers calculations documenting maximum full load and part load rated equipment performance
requirements
NA C403.2.13.1 Centrifugal fan open-circuit For open-circuit centrifugal fan cooling towers with z 1,100 gpm capacity,indicate cooling
C403.4.3.2 cooling towers towers comply with efficiency requirements for axial fan open circuit cooling towers
For single boilers with>500,000 Btu/h capacity,indicate multi-stage or modulating bumer
NA 0403.4.2 Large capacity boiler For boiler system(single or multiple)with>1,000,000 Btu/h capacity,indicate turndown ratio
C403.4.2.5 systems per Table C403.4.2.5 and method(multiple single input boilers,modulating boilers,or
combination)
Variable flow capacity- For pump motors z 7.5 hp,indicate method of variable flow control(VSD or equivalent method)-
NA C403.2.13 pumps in equipment schedule,or exception taken;for equivalent method for a hydronic system refer
to Hydronic System Controls for additional requirements
NA C403.2.3 Gas and oil-fired forced air For forced air furnaces with capacity Z 225,000 Btu/h and all unit heaters,indicate in
furnace and unit heaters equipment schedule intermittent ignition or IID,flue or draft damper,and rated jacket loss
NA C403.2.4.8 Combustion heating For combustion heating equipment with output capacity>225,000 Btu/h,indicate modulating
equipment or staged combustion control
NA C403.2.3.3 Packaged electric heating/ Verify all packaged electric equipment with>6,000 Btu/h cooling capacity and any amount of -
cooling equipment heating is a heat pump;include in equipment schedules
NA C403.2.12 Heating outside a building Indicate systems providing heating in non-enclosed outdoor occupied spaces are radiant
systems;refer to HVAC System Controls for additional requirements
NA C403.2.7.1 Kitchen exhaust hoods Indicate on plans the type,duty and exhaust air rate of each kitchen hood,refer to HVAC
System Controls for additional requirements
Yes C403.2.4.3
Outdoor supply air,exhaust Indicate locations of OSA intake,and exhaust and relief outlet dampers on plans;indicate am millium6iiii,
and relief dampers whether dampers are Class 1 motorized,or gravity and exception taken(include leakage
rating,ctm/sf);refer to HVAC System Controls for additional requirements for OSA dampers
Indicate locations of return air dampers that are integral to economizer operation;verify
Yes C403.2.4.3 Retum air dampers dampers are motorized;indicate whether dampers are Class 1,or within packaged equipment
eligible for leakage rating exception(include leakage rating,cfm/sf)
2015 Washington State Energy Code Compliance Forms for Commercial,R2 and R3 over 3 stories and all R1 -Page 6 of 7
' Mechanical Permit Plans Checklist MECH-CHK
2015 Washington State Energy Code Compliance Forms for Commercial Buildings including R2&R3 over 3 stories and all R1 Revised January 2017
Project Title: WSP Shelton Kitchen and Donn HVAC Date 1/1/2015
the following information is necessary to check a permit application for compliance with the mechanical systems and equipment requirements of the
Washington State Energy Code,Commercial Provisions.
Applicable Code Section Code Provision Information Required-Must be in permit documents Location in Building Department
_Lves,no,na Documents Notes
C402.4.1.4 Increased prescriptive
NA C403.6 maximum vertical Indicate that all occupied,conditioned spaces are served by a DOAS per C403.6
fenestration area with DOAS
Additional Efficiency Package Option,Dedicated Outside Air Systems(DOAS)
NA C406.6 Building provided with To comply with additional efficiency package option,indicate that 90%or more of all occupied,
DOAS conditioned spaces are served by a DOAS per C403.6
Multiple Zone Air Systems
Air systems serving multiple Identify supply air systems serving multiple zones and the zones they serve on plans;indicate
NA C403.4.4 whether system is VAV and method of primary air control;or provide supporting
zones documentation for applied exception to VAV
Provide equipment schedules on plans or MECH-EQ form that list all VAV air terminals and
types
VAV systems serving For each air terminal include:maximum airflow rates for primary supply air during zone peak
NA C403.4.4 multiple zones heating and zone peak cooling;maximum airflow during reheating,recooling or mixing;
minimum airflow rate to maintain required ventilation,and the basis for these values;N IMC or
ASHRAE 62.1 multiple zone equation is basis for minimum flow rates,provide calculation on
plans
NA C403.4.4.1 Single duct VAV terminal Indicate single duct terminal units are configured to reduce primary supply air before reheating
units or recooling
NA C403.4A.2 Dual duct systems-terminal For systems with separate warm air and cool air ducts,indicate terminal units are configured to
units reduce the flow from one duct to minimum before mixing with air from the other duct
Indicate locations of duct static pressure sensors on plans;include at least one sensor per
major dud branch;verify controller setpoint pressure at each sensor is 5 1.2 inch w.g.
C403.4.1.1 VAV system static
NA pressure sensor;- For systems with zone level DDC,indicate controls are configured to monitor zone damper
0403.4.1.2 sensors and DDC set points positions and reset static pressure setpoint baled on the zone requiring most pressure;include
control logic that automatically detects and generates an alarm If any zone excessively drives
reset logic,and allows building operators to exclude zones from reset logic
Multiple-zone VAV system For systems with zone level DDC controls,indicate controls are configured to automatically
NA C403.4.4.3 ventilation optimization reduce outdoor airflow in response to changes in system ventilation efficiency,or exception
controls taken -
NA C403.4.4.4 VAV system su Indicate controls automatically reset supply air temperature in response to building loads or
ys pply air reset outdoor air temperature;or exception taken
Multiple Zone HVAC Systems,High Efficiency VAV-Required for systems utilizing C403.6 DOAS Exception 2,must comply with all 16 provisions
C403.7, Indicate system is configured for 100%air economizer operation and complies with all related
NA Item 1 Air economizer economizer requirements per C403.3(without economizer exceptions) -
C403.7, Provide DDC controls for all components of system;identify all DDC system input/output
NA Item 2 Direct digital controls(DDC) control points;indicate capability for trending and graphical display
For systems with minimum OSA>2,500 cfm,indicate outdoor airflow monitoring station that
NA C403.7, Outdoor airflow measures OSA intake under all load conditions;indicate control sequence that increases or
Item 3 measurement and reduction reduces system OSA cfm based on VAV terminal feedback of ventilation efficiency(per
C403.4.4.3 without exceptions)or DCV(per C403.2.6.2)
C403.7, For systems with minimum OSA>2,500 cfm,indicate supply airflow monitoring station capable
NA hem 4 Supply airflow measurement of measuring supply su I air delivered to VAV terminals under all load conditions
C403.7, Zone isolation and Verify maximum area served by a single HEVAV system is:5 50,000 sf,or one entire floor,
NA Item 5 maximum area served whichever is greater,in addition if a system serves>25,000 sf,that includes areas that are
expelled to be occupied non-simultaneously,indicate zone isolation controls per C403.2.4.4
Interior/exterior zone
NA C403.7, desi n supply Verify that VAV terminals serving interior cooling driven loads are sized per design supply air
Item 6 g pply air temperature that is 5°F higher than VAV terminals serving exterior zones
temperature
C403.7, Maximum air terminal inlet Identify air terminals with minimum primary airflow setpoints>50%of maximum setpoint in
NA Item 7 velocity equipment schedule or MECH-EQ form;indicate air terminal inlet velocity does not exceed 900
fpm
NA C403.7, Sequence of operation Indicate DDC system sequences of operation are designed and configured per ASHRAE GPC
Item 8 36
NA C403.7, Maximum allowable system Verify fan system bhp is 5 90%of the bhp limit per Option 2 equation in Table C403.2.11.1(1),
Item 9 brake horsepower provide MECH-FANSYS form for each system
Indicate all series and parallel terminal fans have electronically commutated motors;indicate
NA C403.7, Fan-powered terminal unit DDC control system is configured to vary air terminal fan speed as a function of the load;
Item 10 motor and control indicate fan speed during periods of low heating,low cooling,or ventilation only is 5 66%of
peak design air flow or provide supporting documentation for applied exception
2015 Washington State Energy Code Compliance Forms for Commercial,R2 and R3 over 3 stories and all R1-Page 7 9f 7
Permit Plans Checklist MECH-CHK
2015 Washington State Energy Code Compliance Forms for Commercial Buildings including R2&R3 over 3 stories and all R1 Revised January 2017
Project Title: WSP Shelton Kitchen and Donn HVAC Date 1/1/2015
Tyhe following information is necessary to check a permit application for compliance with the mechanical systems and equipment requirements of the
Washington State Energy Code,Commercial Provisions.
Applicable Code Section Code Provision Information Required-Must be in permit documents Location in Building Department
es,no,na Documents Notes
C403.7, Application of single duct Indicate VAV terminal types on plans;verify fan-powered terminal units only serve perimeter
NA Item 11 and an-powered terminal zones with envelope loads;verify all other zones are served by single duct terminal units
0403.7, Fan-powered terminal unit Indicate DDC controls are configured to automatically reset the primary supply air cfm setpoint
NA Item 12 primary air reset of all fan-powered terminal units to the minimum required to maintain ventilation during
occupied heating or deadband,based upon the VAV air handling unit OSA ventilation fraction
For spaces>150 sf with occupant density 2 25 people/1000 sf,indicate space is served by a
NA C403.7, High occupancy space dedicated terminal unit with DCV control that resets terminal unit ventilation setpoint;also
Item 13 controls indicate occupancy sensor control that automatically reduces minimum ventilation to zero and
sets back room heating and cooling setpoints by 2 5"F
For server,electronic equipment,telecom or similar spaces with cooling loads>5 W/sf,
0403.7, indicate spaces are served by independent HVAC systems that are separate from HPVAV
NA Item 14 Dedicated HVAC systems systems serving rest of building;
ys g g;indicate dedicated HVAC systems have air economizer
controls or energy recovery per C403.3 Exception 9
Indicate whether systems are served by a high efficiency heating water plant,or a high
efficiency chilled water plant
If complying via high efficiency heating water plant:Indicate all VAV terminals have hydronic
heating coils served by heating water system with either gas-fired boiler(s)with thermal
NA C403.7, Central plant efficiency efficiency x 90%,air-to-water heat pumps,or heat recovery chillers
Item 15 If complying via high efficiency chilled water plant.Indicate all VAV air handlers have cooling
coils served by chillers with rated IPLV efficiency that exceeds WSEC listed IPLV by at least
25%per Table C403.2.3(7)(note water-cooled IPLV is max,all others are min);indicate
smallest chiller or compressor in plant is<_20%of total plant capacity,or provide thermal
storage sized for<20%of total plant capacity
C403.7, Fault detection and Indicate DDC system includes a fault detection and diagnostics(FDD)system configured to
NA monitor operation and provide fault reporting of required parameters for all VAV air handlers
Item 16 diagnostics and VAV air terminal units in the HPVAV system
HVAC Equipment Energy Use Metering
HVAC equipment energy For new buildings>50,000 sf and building additions>25,000 sf,verify energy use metering of
NA C409.3.1 all equipment used to provide space heating and cooling,dehumidification and ventilation will
use metering be provided per C409;indicate equipment eligible for exception
Documentation and System Specific Requirement To Support Commissioning
Indicate that all mechanical systems,equipment,and controls for which the WSEC requires
control functions and /or configuration to perform specific functions are required to be
Yes C408.2 Scope of mechanical
commissioned;
systems commissioning For buildings with t 240,000 Btu/h total output cooling capacity or 2 300,000 Btu/h total output
heating capacity,indicate that all mechanical systems regardless of individual capacity are
required to be commissioned;or provide building heating/cooling capacity calculation
demonstrating eligibility for exception
Indicate in plans and specifications that Cx per C408 is required for all applicable mechanical
systems; WNW
C403.2.10 Include general summary with at a minimum of Items 1 thru 4 of the Cx plan per C408.1.2
C408.1.1 Commissioning including:narrative description of activities,responsibilities of the Cx team,schedule of
Yes 0408.1.2 requirements in construction activities including verification of project close out documentation per C103.6,and conflict of
C408.1.4.2 documents interest plan(Krequired);
C103.6 Include in general summary that a Cx project report or Compliance Checklist(Figure
C408.1.4.2)shall be completed by the Certified Cx Professional and provided to the owner
prior to the final mechanical inspection.
Air system and hydronic Indicate in plans that air and fluid flow rates shall be tested and balanced within the tolerances
Yes C408.2.2 system balancing defined in the specifications;indicate systems shall be balanced in a manner to first minimize
throttling losses,then adjusted to meet design flow conditions Mo.1
Yes C408,2.2.1 Air system balancing Indicate devices that provide the capability to balance all supply air outlets,zone terminals and
devices air handling equipment requiring system balancing M4.1
NA 0408.2.2.2 Hydronic system balancing Indicate devices that provide the capability to isolate,balance and measure flow across all
devices hydronic equipment requiring system balancing including heating and cooling coils and pumps
Yes C408.2.3 Functional performance Identify in plans and specifications the intended operation of all equipment and controls during
testing criteria all modes of operation,including interfacing between new and existing-to-remain systems
Project Close Out Documentation
Documentation and project Indicate in plans that project close out documentation and training of building operations
Yes C 103.6 close out submittal personnel is required for all mechanical components,equipment and systems governed by this
requirements code;indicate close out documentation shall include:record documents,O&M manuals,
applicable WSEC compliance forms and calculations
2015 Washington State Energy Code Compliance Forns for Commercial,R2 and R3 over 3 stories and all R1-Page 3 Qf 7
PermitMechanical
2015 Washington State Energy Code Compliance Forms for Commercial Buildings including R2&R3 over 3 stories and all R1 Revised January 2017
Project Title: WSP Shelton Kitchen and Dorm HVAC Date 1/1/2015
The following information is necessary to check a permit application for compliance with the mechanical systems and equipment requirements of the
Washington State Energy Code,Commercial Provisions.
Applicable Code Section Code Provision Information Required-Must be in permit documents Location in Building Department
es,no,na Documents Notes
C403.2.4.10 Group R2/R3 dwelling For primary space conditioning system,indicate 5-2 programmable thermostats capable of two
NA C403.2.4.11 units,Group R2 sleeping setback periods per day;for all thermostats indicate purpose(heating only,cooling only,or
units both),required temperature range and at minimum a 10°F deadband;or exception taken
Indicate method of ventilation air delivery(natural or mechanical)for each zone M4.1
If mechanically delivered,indicate that systems are configured to provide not more than 150% M4.2
Yes C403.2.6 Ventilation of,but at least the minimum required volume of outdoor air to each zone per IMC,ASHRAE
C403.2.11.4 62.1 or other applicable code(WAC,OSHA,etc);or exception taken
If delivered via natural ventilation,identify required elements per IMC including minimum
openable area to the outdoors or qualifying adjoining spaces
Identify spaces>500 sf with occupant load>25 people/1,000 sf per IMC;for each space
Demand controlled indicate whether it is served by an HVAC system with total design OSA>3,000 cm,and/or
NA C403.2.6.2 the system has airside economizer or automatic modulating OSA damper,indicate OSA
ventilation controls are configured to provide demand controlled ventilation or provide supporting
documentation for applied exception
For gyms,classrooms,auditoriums and conference rooms>500 sf,indicate occupancy-based
NA C403.2.6.3 Occupancy sensors OSA control when space is unoccupied and method(closes OSA damper or shuts-off
equipment);or alternate means provided to automatically reduce OSA when space is partially
occupied
C403.2.6.4 Enclosed loading dock For enclosed loading docks,indicate ventilation/exhaust system method of activation(gas
NA C403.2.6.4.1 ventilation detection system for CO and NO2,or occupancy sensors),and control method(staged or
modulating)
NA C403.2.6.4 Enclosed parking garage For enclosed packing garages,indicate ventilation/exhaust system activated by gas detection
C403.2.6.4.2 ventilation system for CO and NO2,and control method(staged or modulating);or exception taken
M4.2
Provide calculations that show a balanced accounting of total kitchen exhaust(include all
hoods)with%of:supply air,transfer air from adjacent spaces,and make-up air,if applicable,
Yes C403.2.7.1 Kitchen exhaust hoods indicate that direct make-up air to each hood does not exceed 10%of hood exhaust
For kitchens with total hood exhaust exceeding 2,000 cfrn,indicate exhaust air rate per Table M4.2
C403.2.7.1 and compliance method(DCV,energy recovery,or transfer air that would
otherwise be exhausted)
NA C403.2.7.2 Laboratory exhaust systems Refer to Systems Requiring Energy Recovery for requirements
Variable flow capacity- For HVAC fan motors 2 7.5 hp,indicate method of variable flow control(VSD,or equivalent
NA C403.2.13 HVAC system fans control method that reduces design air volume by 50%at 113 static design pressure);note
exception taken
DX air handler variable For DX air handlers with economizer and cooling capacity 2 65,000 Btu/h,indicate number of
cooling control cooling stages provided and method(multiple compressors and/or variable speed
NA C403.3.1 (Under Integratedcompressors);indicate minimum displacement(capacity reduction)as%of full load
Economizer) Indicate control method(cooling capacity controlled in response to space temperature,space
temperature controlled by modulating supply airflow,or both)
For DX air handling units with cooling capacity z 65,000 Btulh and evaporative and chilled
water air handling units with fan 2 0.25 hp,indicate whether system is single zone or multiple
zone and related control method(cooling capacity controlled in response to space
temperature,space temperature is controlled by modulating supply airflow,or both)
For mechanical cooling systems(includes DX and chilled water coils)that control cooling
capacity in response to space temperature-Provide a minimum of two stages of fan control;
NA C403.2.11.5 Fan airflow control indicate minimum fan speed is 5 66%of full speed drawing 5 40%of full speed fan power
during periods of low cooling or ventilation only
For other mechanical cooling systems(includes DX and chilled water coils)that control space
temperature by modulating airflow(in lieu of,or in addition to,controlling capacity in response
to space temperature)-Provide fan controls for modulating supply airflow,indicate minimum
fan speed is<_50%of full speed drawing 5 30%of full speed fan power during periods of low
cooling or ventilation only;or exception taken
Provide central and zone level DDC controls as required based on system application,
NA C403.2.4.12 DDC system capabilities capacity or size thresholds and other qualification per Table C403.2.4.12.1
Identify all DDC system input/output control points;indicate capability for trending and
graphical display
Ducting Systems
C403.2.8.1 Indicate on plans that all ductwork is constructed and sealed per IMC am=or
Yes C403.2.8.3 Duct construction For OSA ductwork,also indicate on plans that ductwork meets air leakage requirements perk
0402.5 and vapor retarder requirements per the IBC M0.1
Yes C403.2.8.3 Duct pressure classifications Identify location of low,medium and high pressure ductwork on plans M0 1 "0
NA C403.2.8.3.3 High pressure duct leakage Indicate high pressure duct leakage testing requirements on plans;provide test results to
test 1jurisdiction when completed I- I :�:l
2015 Washington State Energy Code Compliance Forms for Commercial,R2 and R3 over 3 stories and all R1-Page 4 of 7,
PermitMechanical
2015 Washington State Energy Code Compliance Forms for Commercial Buildings including R2&R3 over 3 stories and all R1 Revised January 2017
Project Title: WSP Shelton Kitchen and Dorm HVAC Date 1/1/2015
yhe following information is necessary to check a permit application for compliance with the mechanical systems and equipment requirements of the
Washington State Energy Code,Commercial Provisions.
Applicable Code Section Code Provision Information Required-Must be in permit documents Location in Building Department
(yes,no,na) Documents Notes
For supply and return ductwork located in unconditioned space or outdoors,indicate R-value of
insulation on ductwork on plans;identify climate zone;note exceptions taken
C403.2.8.1 For supply ductwork located in conditioned space,identify if design supply temperature is<
Yes C403 2 82 Duct insulation 55°F or>105"F and indicate R-value of insulation on this ductwork on plans;note excepti
taken
For OSA ductwork,shafts and plenums,indicate R-value of insulation on these elements on
fans per Table C402.1.3 for steel-framed walls;note exception taken
Piping Systems
NA C403.2.9 Piping insulation Indicate design temperature range of fluid conveyed in piping and thickness of insulation(in
inches)on hydronic piping plans;or exception taken
NA C403.2.9.1 Piping insulation exposed to Indicate method of protection of pipe insulation from damage/degradation on hydronic piping
weather plans
Economizers
Identify in equipment schedules on plans or in MECH-EO forms all cooling systems requiring
air economizer controls
Yes C403.3 Air economizer required Provide MECH-ECONO form indicating systems utilizing air economizer exceptions,including
those with water-side economizer in lieu of air economizer,indicate on plans eligible
exception(s)taken and measures to comply with exception(s) vow
Yes C403.3.1 Integrated economizer Indicate air and water-side economizers are configured for partial cooling operation even
operation-air and water where additional mechanical cooling is required to meet the load
Yes C403.3.2 Economizer heating system Verify control method of HVAC systems with economizers does not increase building heating
impact-air and water energy usage during normal operation r M0.1
Yes C403.3.3.1 Air economizer capacity Indicate modulating OSA and return air dampers are configured to provide up to 100%OSA
for cooling k M0.2
Verify mechanical cooling controls are interlocked with air economizer controls so the outside
C403.3.1 air damper remains in 100%open position when mechanical cooling is also required to meet
Yes C403.3.3.2 Integrated air economizer the cooling bad,until the leaving air temperature is<45`F go am
For systems with cooling capacity 2 65,000 Btu/h,verify that control of economizer dampers is
not based only on mixed air temperature;or exception taken
Yes C403.3.3.3 Air economizer high limit Indicate high limit shut-off control method and required high limit per Table C403.3.3.3 AN
controls
For eligible systems where water-side economizer may be provided in lieu of air economizer,
NA C403.3.4.1 Water economizer capacity indicate system is capable of 100%design cooling capacity at 50'F db/45°F wb OSA
temperatures
NA C403.3.4.2 Water economizer Indicate pressure drop across precooling coils and heat exchangers in water economizer -7
maximum pressure drop system do not exceed pressure drop limit
NA C403.3.1 DX air handling equipment For DX air handlers with economizer and cooling capacity>_65,000 Btu/h,refer to HVAC
control System Controls for requirements
DX equipment economizer For DX air handlers with economizer and cooling capacity Z 54,000 Btu/h,provide a fault
NA C403.2.4.7 fault detection and detection and diagnostics(FDD)system to monitor economizer system operation and report
diagnostics faults
Systems Requiring Energy Recovery
For systems with design OSA>5,000 cfm,or design supply air cfm and%OSA exceeding the
values in Tables C403.5.1(1)or(2),indicate exhaust air ER method;or exception taken with
supporting calculations
NA C403.5.1 ventilation/exhaust Energy recovery - For rooms served by multiple systems with aggregate design OSA>5,000 cfm,or aggregate
systems design supply air cfm and°k OSA exceeding the values in Tables C403.5.1(1)or(2),indicate
exhaust air ER method;or exception taken with supporting calculations
Indicate ER rated effectiveness that increases OSA enthalpy by 2 50%based on delta
between OSA and return air enthalpies at design conditions
Laboratory exhaust systems For buildings with total lab exhaust>5,000 cfm,indicate method of energy recovery used to
NA C403.2.7.2 pre-condition laboratory make-up air,ER effectiveness(min 25°F);or alternative method per
(energy recovery) exception(VAV exhaust,semi-conditioned makeup,or CERM calculation)
For buildings with pools or spas with water surface area>200 sf,indicate exhaust air ER
0404.10.4 Pools and permanent spas method and use of waste heat(preheat ventilation air,pool water or service hot water);or
NA (under exhaust systems exception taken
C404.11) (energy recovery) Indicate ER system has the rated effectiveness and is configured to decrease the exhaust air
temperature at design conditions by a 36"F
Energy recovery- For buildings with on-she steam heating systems,indicate condensate water ER
NA C403.5.2 steam condensate systems For buildings that use off-site generated steam where condensate is not returned to the
source,indicate on-she condensate water ER
2015 Washington State Energy Code Compliance Fortes for Commercial,R2 and R3 over 3 stories and all R1-Page 5 of 7,
PermitMechanical Plans
2015 Washington State Energy Code Compliance Forms for Commercial Buildings including R2&R3 over 3 stories and all R1 Revised January 2017
Project Title: WSP Shelton Kitchen and Dorm HVAC Date 1/1/2015
Vie following information is necessary to check a permit application for compliance with the mechanical systems and equipment requirements of the
Washington State Energy Code,Commercial Provisions.
Applicable Code Section Code Provision Information Required-Must be in permit documents Location in Building Department
es,no,na Documents Notes
For buildings with food service,meat or deli departments that have a 500,000 Btu/h of remote
refrigeration capacity for coolers/freezers,indicate condenser ER and use of captured energy
(service water heating,space heating,or dehumidification reheating)
NA C403.5.3 Energy recovery-
cooler/freezer condensers For buildings with a 40,000 sf conditioned floor area and with a 1,000,000 Stu/h of remote
refrigeration capacity for coolers/freezers,indicate condenser ER and use of captured energy
for service water heating and also for space heating,or dehumidification reheating
For buildings with 24-hour operation and with>1,500,000 Btu/h of heat rejection capacity and
NA C403.5.4 Energy recovery- design service hot water load>250,000 Btu/h,indicate condenser ER to pre-heat service
condenser systems water,or exception taken.Provide calculations showing the amount of recovered heat that is
utilized(60%of peak neat rejection load or pre-heat service water to 85°F).
Hydronic System Controls
For hydronic system pump motors z 7.5 hp,indicate method of variable flow control(VSD or
C403.2.13 Variable flow control- equivalent method that requires 2 30%design wattage at 50%design fluid flow);note
NA C403.4.2.7 hydronic system pumps exception taken -
Identify whether hydronic coils have DDC controls and associated manner of pump speed
control(differential pressure,zone hydronic demand,etc) -
For boilers that provide building heating,indicate controls that provide heating water
temperature setback based on outdoor temperature -
For heating and chilled water systems 2 300,000 Btu/h,indicate systems are configured to
C403.2.5 Hydronic system setback automatically reset supply water temperature based upon demand;or exception taken. n
NA If system pump motor hp 2 3 hp,also indicate controls automatically reduce flow by a 50%.
C403.4.2.4 and part load controls
For chilled water systems(x 300,000 Btu/h,pump motor hp 2 3 hp)that serve water-cooled
unitary air conditioners,indicate VSD or staged pumps in chilled water system and heat
rejection loop that reduce pump flow so that one control valve is nearly wide open,or to
maintain a minimum differential pressure;or exception taken
C403.4.2 Boiler sequencing Indicate automatic controls that sequence operation of multiple boilers
NA For cooling equipment with hot gas bypass,provide either multiple step unloading or
C403.4.6 Hot gas bypass limitation continuous capacity ltYmodulation;indicate bypass capacity
ty per Table 0403.4.6
NA C403.4.2.2 Two-pipe changeover Indicate changeover deadband(min 15'F),heating/cooling mode scheduling and changeover
systems temperature range(limit 30°F)
NA C403.4.2.6 Chiller/boiler plant pump Indicate controls are configured to automatically reduce overall plant flow and shut-off flow
isolation through individual chillers and boilers when not in use
For cooling towers with fan motors z 7.5 hp,indicate VSD and method to adjust fan speed
C403.2.13.1.1 (adjusted based on leaving fluid temperature or condenser temperature/pressure of heat
NA C403.4.3.1.1 Heat rejection equipment- rejection device)
C403.4.3.1.2 variable flow control For multiple-cell heat rejection equipment with VSD,indicate controls that ramp all fans in
unison
NA C403.4.3.3 Heat rejection equipment- Indicate opencircult cooling towers with multiple pumps or VSD control are designed so all
cooling tower flow turndown cells can be run in parallel
NA C403.4.2.3.1 Water loop heat pump- Indicate capability of central equipment to provide minimum 20°F water supply temperature
deadband deadband between heat rejection and heat addition modes;or exception taken
Water loop heat pump- Indicate type of cooling tower(open-or closed-circuit)in equipment schedule;indicate method
NA C403.4.2.3.2.1 heat rejection equipment, used to limit system heat loss when heat rejection is not needed
Zone 4
Water loop heat pump- For open-or closed-circuit cooling towers,provide a heat exchanger that separates the cooling
NA C403.4.2.3.2.2 heat rejection equipment,
tower and heat pump loop
Zone 5
NA C403.4.2.3.3 Water loop heat pump- For hydronic heat pump systems with total system power>10 hp,indicate 2-way isolation
isolation valves valves on each heat pump and variable flows stem control
Dedicated Outdoor Air Systems(DOAS)-Optional through 6/30/16,Prescriptive 7/1/2016
For buildings with office,retail,education,library and fire station spaces,identify these spaces
NA 0403.6 Dedicated outdoor air on plans;indicate that ventilation air in each occupied space is provided via a DOAS system;
C403.6.3 systems or document compliance with C403.6.3 Impracticality;or exception taken(buildings complying
with C402.4.1.4 or C406.6 may not utilize exceptions)
For all DOAS systems,indicate exhaust air ER method;or exception taken with supporting
NA C403.6.1 Energy recovery ventilation calculations.Indicate ER rated effectiveness that increases OSA enthalpy by 2 50%based on
with DOAS delta between OSA and return air enthalpies at design conditions.
Indicate equipment associated with the delivery of zone level heating and cooling(fans,
Heating/cooling system hydronic pumps,primary air dampers,etc)are configured to shut off,and central equipment is
NA C403.6.2 controls with DOAS configured to turn down,when there is no call for heating or cooling in the zone they serve
If applying Exception to heating/cooling fans used for air mixing in the space during deadband
periods,include fan watts per cfm in equipment schedule