HomeMy WebLinkAboutFIR2003-00052 Hood and Duct - FIR Permit / Conditions - 2/2/2004 MASON COUNTY DEPT. OF COMMUNITY DEVELOPMENT Inspection Line(360)127-7262
Mason County Bldg. 3 426 W. Cedar P.O. Box 186 Phone: (360)427-9670,ext.352
Shelton,WA 98584
�4:1111,
FIRE PROTECTION PERMIT FIR2003-00052
APPLICANT: ALDERBROOK INN
CONTRACTOR: SANDERSON SAFETY (800) 551-4102 LICENSE: SANDESS240RO EXP: RECEIVED: 12/12/2003
SITE ADDRESS: 7101 ESTATE ROUTE 106 UNION ISSUED: 2/2/2004EXPIRES: 8/2/2004
PARCEL NUMBER: 322335000014
LEGAL DESCRIPTION: SUNNY BEACH LOTS: 10-11 &8-9 EX ALL N OF HWY
PROJECT DESCRIPTION: HOOD AND DUCT
GENERAL INFORMATION System Information
Type of Use: COMM Sprinkler Heads: 15 Audible Switches: 0 Pull Stations: 1
Fire District: 6 Flow Switches: 1 Visual Devices: 0 Door Releases: 0
Hood& Duct?: Y Pressure Switches:: 0 Smoke Detectors: 0 Duct Detectors: 0
Dry Chemical?: N
Zones: 1 Heat Detectors: 0
Wet Chemical?: N
Sprinkler?: N
Standpipe?: N SQUARE FOOTAGE FEES
Monitoring Company. First Floor: Type Amount Due Amount Paid
Monitoring Phone No.:() _ Second Floor:
Auto Fire Alarm?:N Third Floor;: Hood and Duct Plan $65.00 $65.00
Hood & Duct Permit Fee $100.00 $100.00
Total: $165.00 $165.00
FIR2003-00052 Please refer to the following pages for conditions of this permit. 1 of 3
CASE NOTES
FIR2003-00052
N
O
O '
CON DMONS FOR
FIR2003-00052
i
r-
112e
1.) [-food and Duct fire protection system to be connected to building fire alarm system. 12 ~=h
z Thus protect becomes null and xoid if work or mnslrucllon authorized is not commenced van IN days,or if conslrucfron or work Is suspended fora period of 160 days at any time after wwk is
capmenced. Evidence of continua1iond vxxkfsa progress' tion within the 180 day period,
Owner or oata p? 3 D
r+
a
E•
C1
w
a
0
v
z
0
rn
C
w
w
N
ME
Q
N
O
O
O
CV
M
_0
d
Ll_
FIR2003-00052
FWase refer to the following pages for conditions of this permit. 2 of 3
T
N '
O
O
CONCRETE MECHANICAL MANUFACTURED ITOME
0
C Footings 1 Setbacks Date By Ribbons
0
N Date By Gas Piping Date By
Foundation Walls Date B y Set-up
Date By INSULATION Date By
B G 1 Slab Insulation Floors Final
Date By Date B y Date B y
FRAMING Walls FIRE DEPT
Date By Date B y Date B y
PLUMBING Attic OTHER
Groundwork Date By
Date By WALLBOARD NAILING
D.W.V. Date By
f° Date By FINAL JN, PECTIIda
m Water Line Date O B y
m Date By Date By
L� r
m c n
3-0
-
o
0 O
0
c. O
o W
w O
O 0
y
3
w
0
W
FIRE & LIFE SAFETY INSPECTION: STATEMENT OF DEFICIENCY & CORRECTIVE ACTION
FACILITY ADDRESS CITY ZIP PHONE
NAME C
INSPECT _ AGENCY DAT
MAXIM I 36 -42 -96 0 X-273 MASON COUNTY FIRE MARSHAL FD 7 1e
ITEM STATEMENT OF CODE OR WAC CORRECTIVE ACTION CORRECTION
NO. DEFICIENCY REFERENCE REQUIRED REQUIRED BY
(n� , DATE
Y-r
Ono S
00
LU
oao �o /
U
z moo S CP
N O
O
0) O N 1
U mx o0oS
LLAJ
Z -E" o
O
U xr, CDC-
0 N
Q om7 S
v d�s3i
��s s
THE DEFICIENCIES DESCRIBED ABOVE HAVE BEEN SIGNA URE REINSPECTION DATE
EXPLAINED TO ME, AND I AGREE TO MAKE CORRECTIONS
NO LATER THAN THE DATES INDICATED IZ9
PAGE OF PAGES
White Copy: Occupant— Yellow Copy: Fire Marshal — Pink Copy: Fire District
FIRE & LIFE SAFETY INSPECTION: STATEMENT OF DEFICIENCY & CORRECTIVE ACTION
FACILITI� ADDRESS CITY ZIP PHONE
NAME 'C t,
INSPECTO AGENCY DAjE
DAVE SALZER 360-427-96 X-273 MASON COUNTY FIRE MARSHAL FD 11
ITEM STATEMENT OF CODE OR WAC CORRECTIVE ACTION CORRECTION
NO. DEFICIENCY REFERENCE REQUIRED REQUIRED BY
DATE
d�,- Cc,;�`^- Yee cSS J�z
�P'
cn
Q
W
00
Ln
a �
� c
U O
Z '0 L
� O
� 3
O _
c�
U ) ON
m L W
Z TN O
O O - T
U XN
a 0 co
o10
1,2
THE DEFICIENCIES DESCRIBED ABOVE HAVE BEEN SIGNATURE REINSPECTION DATE
EXPLAINED TO ME, AND I AGREE TO MAKE CORRECTIONS
NO LATER THAN THE DATES INDICATED -- G
PAGE OF PAGES
White Copy: Occupant— Yellow Copy: Fire Marshal — Pink Copy: Fire District
DUCT
NOZZLE NOZUZLE 1 �.r !�`•��Jr "�Yr,� •IO I �'/"r ' lam 1�7
nW I j2r 98592-
I
a
PLENUM
ZZLE
NOZZLE ELECTRICAL SERVICE FOR LIGHTS.
is AMP MAX MOST BE FUSED 21 F,i E-i) �PN( ) SEPARATELY FROM FAN CIRCUIT
!O !, 4 3 ! ��,.._ TO VENTILATOR I I E-2) THE
I �1` �1` �1 M r I AK R ' �'�`f E D LIGHTS I I S'
I I ms 1 nos 'V P 25 I PM , n5o ' Rb M v
' I I (REF)
� flr Qt� GQUi�T( I I
�riASHALS 0'� iG i I
S O e le 11]e4 51616 SLZS 1SS
-- I DATE 1 LL
1290 63 n90 U'anje Subject te. 2—pp.a-.i.
ER Approved p'xrs a rN4Jrad to '— ,
S -----_---"YOOEL)
O o O o O I I \ I� EIMAUST FAN(S).MOTOR
. `STARTER SVAT01 AM FA
00000-000oO I -�+�� SEE
SERVICE BY I
—�— SEE NOTE E-2
0
CKD =4 O O 59 ® O I f r\ t�--------
RANGE/CONY OVEN RANCE/CONV OVEN 12000LE I I h STARTERFSSWATCH AND FA
(VETdFY EOUP (VERTfY EVOI (VExsv EpUp. BROILER SPREADER FRYER FRYER I —
SFR.k MODEL SFR At YWEL LYR k YODEL) (VERIFY EX (vETeFr ODUAP VERIFY EOIAP vERIFr Eaw I \ ELECTRICAL SERVICE BY i
YiA k YODEL} LKiL k YODEL} k YOOEI .k MODEL I — � SEE NOTE E-2
u IQLL11 ---%j —
6 b b b 2 b 24 1125 IS.S tl 0
SUPPLY-TALE
ID-6•
'2 1 1 X1 120V
� ' 2�20Hj
---FIELD VANNO BY OTHERS X 60Hi
3A ELEVATION VIEW 43 —wroNO BY GAYLORD
DUCT DUCT
NOZZLE
nW NOZZIE
1 nW
�I I SG-�CA %134
`T NOZZLE
�hVC UARtsc�
(� JIM(TTP)
i
e e
01469 15.71!
0 I I Q ANSIJL R-102 SYSTE►
e
O i Q Fuu L
y'air mar m 4roN
MT NETTLE YAmr n RI[
I I VERFY EOUW � �Et trpsx u[ro rAONtCCu Qnuna
0
wrura n rAR r I k YODEL) I woNCwr COMmx= YA1L I
88`g'88888 a 88888888
® 0 !1
O O r
COYB12OWN O 215 Tl
CONV STEALER CONV OVEN _ rwR rwn rwr
( E01NP� (VERIFY EQUIP. !7 OO (VERIFY EOUIP. I A G L r I I
Z Lr MFR.At YODEL) STEAMER MFR. MODEL) L (f m.)„1A W) (7 CAL)l
j l O YFR kY MODEL)
It i
88888888 88888888I 16.5 16.5
C KI KFk YB
�I
EXHAUST Duct
43C VOL, 2313 CFu EXHAUST Ducr KETTLE
-------------- VOL., 3238 CFu
i ------------ .G, I.D. SIZE: 10" x 26'I.O. 43D
I ' '-----55.5 -------- SIZE: 10- x S.P.: 1.00'W.G r---- _ "' SP.: 1.00" W.G ,
EXH I Vj I
I EXH G I
pp 1
8.125 190
(FILLER BY GAYLORD)— p
111 - CUP GREASE _
L CUP
EXXH—
E
FUSE UNIX FEE 3 - - E 3�E-}— - - -1 - E__
OUTLET
TO HD 43C FUSE UNIX
48 _ _ * 18-- _ _ 26— INLET
CHEM. INLET Tx
INURE I^---- r-----� EM. INLET __ HD 43A DUCT 1
I I TANK /2 I ----- r---- ----- h EQUIP /55
I IHO 43A PLENUM, I I
43A j 15ow LT. i50w LT, 150W LT. 4 I 15oW lT. I I 150w LT, I 15Ow LT. I HD 43C PLENUt
FXTURE I FXTURE EO111P6 63 i FIXTURE I I FIXTURE j I FXTURE FlXIURE
1 I I
(II FLOW) I_-___J I 1 I
L-----J 1•-----J
43B
(�) (TYP)
10 to
(2) SUPPLY DUCTS
18(TYP) MA—lA 24 (TYP) (O SUPPLY Fu EA MA-1
MIN, OVERHANG 6 VOL, 925 CFM EACH SUP VOL: 129° CDU EACH
TO COOKING �SUP
SIZE 10'x 18'I.D. SIZE 10' x W.G. I.D.EOUIPMENT S.P.: 0.15"W.G. 27.75 SUP ILSUP
(lYP) L(REF) SP.: Q15 .G
27.75 55.5 55,5— 55,5-- L 12 MIN. OVERHANG
TO COOKING
9'-3- EOIJI 9'-3- 43BIPMENT
k 43D
AT 250 CFM/lF fff--- AT 350 CFmAl
.18'-6-
VIEW
18 48—— —
I I —10 M 6
I I
FIRE PROTECTION ;t0
`` I B I I -DETAIL 2
ANSUL• R-102—AS SYST .M NOTES 1zw HI —1
�� �� hL*-- FILTER I \\
--------------L_ -- -------- _-
-
v ZEE]
I11 I I
I 2)EXHAUST DUCTS I
55.5 VOu 2313 CFM
EXH (REF) EXH SIZE: 10"a 18'LO.
I
S.P.: 1.00"w.G I
6625 190(FILLER BY GAYLORD)
it _ GREASE -
CUPS -
® —E 3�E 3 - - - - - - CUP
EXH 10 TYP�
FUSE LINK INLET
FROM H0, 438
54
REF)CHEM. INLET TANK 11 _ _ __ _ _— _ T _ 18(TYP)
SERVES 430 PLENUM ONLY
(11FLOW) r-----� r-----� r------FIXTURE �WTIWRE]III
I . 1iI r
15OW LT, LT.
FIXTURE
r
CHEM. INLET TANK 13 ISOW . IiI -t 5-OW--LT-.
SERVES HD.430 DUCT, FIXTURE
�1
2
HD.43C DUCT k PLENUM L----- L_ JEQUIP 140(11 FLOW L- _
'
___
43D -J 43C
10
9 ( _
SUP �
(4)SUPPLY DUCTS
41N. OVERHANG SUP SUP
MA-1D 1B(�Pl yL VOL: 925 CFM EACH SUP
10 COOKING 27.75 SUP MA-1C
12 y SIZE: 10'z 18' .D.
EQUIPMENT (REF) SP,; 0.15' W.G 6 MIN, OVERHANG
27.75 -- ----55.5 55.5 55.5 To COOKING
EQUIPMENT
9'-3' 9'-3'
AT 250 CFM/LF AT 250 CFM/LF
18'-6'
PLAN VIEW
18 54
1 8 11 1 I
�` DETAIL 2
12 I6'HIGH
FIRE PROTECTION L FILTER
ANSUL R-102- sEF SYSTEM NC_1TE5
24 FULL-LENGTH 27 F.P.DROP
REMOVABLE
FP-1)LOCATION OF FIRE PROTECTION NOZZLES MUST INTERNAL BAFFLE - 11.25 STD J
PLENUM BE VERIFIED N RELATION TO THE COOKING .PLANS gyp pEgy6(�JOBS INSIDE� THE DE FAIL t
EQUIPMENT.PRKOR TO VENTILATOR IIUNITED STATES AND NON-MARNE JOBS)
T FABRICATION. PARTS AND INSTALLATION OF CFE1iM AND
COMPLETE SYSTEM NCLUDNO APPLIANCE DROPS AND DETECTION LINES FROM TANK(S) TO CONNECTION
SURFACE MOUNTED DETECTION BRACKETS,WITH FIELD PONTS ON HOOD L
INSTALLATION BY GAYLM •INSTALLATION OF TANKS AND RELATED COMPONENTS T
INSTALLATION OF DETECTOR CABLE AND FUSIBLE
ANSUL FIRE SYSTEM FACTORY PRE-PPEd CHEMICAL
f
SECTION IV — SYSTEM DESIGN
UL EX. 3470 ULC CEx747 Page 4-30
4-30-02 REV. 2
NOZZLE PLACEMENT REQUIREMENTS(Continued)
Nozzle Application Chart
The following chart has been developed to assist in calculating the
quantity and type of nozzle required to protect each duct,plenum,
or appliance.
NOTICE
This chart is for general reference only. See
complete details for each type of hazard.
Nozzle Tip
Maximum Hazard Nozzle Nozzle Nozzle Stamping—
Hazard Dimensions Quantity Heights Part No. Flow No.
►1@016�PTransition Length— 1 — 430912
(Single Nozzle) _22D wM er`—'!C'f (127 cm)
Diameter—16 in. (40.6 cm)
Duct or Transition Length—Unlimited 1 — 419337/78078' 2W/2WH•
(Single Nozzle) Perimeter—100 in.(254 cm)
Diameter—31 718 in. (81 cm)
Duct or Transition Length—Unlimited 2 — 419337(78078' 2W/2WH'
(Dual Nozzle) Perimeter—150 in. (381 cm)
Diameter—48 in. (122 cm)
Electrostatic Precipitator Individual Cell 1 — 419334 1/2N
(At Base of Duct)
►Plenum Length—10 ft. (3.1 m) 1 — 4193351417332 1 N/1 NSS
(Horizontal Protection)
Plenum Length—4 ft. (1.2 m) 1 — 419336/417333 1W/1WSS
(Vertical Protection) Width—4 ft. (1.2 m)
Fryer/Split Vat Fryer" Maximum Size
(without drip board)
15 in. (38 cm)x
14 in. (36 cm)
High Proximity 1 27—47 in. 419339 230
Medium Proximity 1 20—27 in. 419340 245
Maximum Size
(without drip board)
19 1/2 in.(49.5 cm)x
19 in. (48.2 cm)
High Proximity 1 21 —34 in. 419338 3N
Low Proximity 1 13— 16 in. 419342 290
Maximum Size
(without drip board)
18 in. (45.7 cm)
x 18 in.(45.7 cm)
High Proximity 1 25—35 in. 419338 3N
(64-89 cm)
Use 2WH nozzle on 1.5 gallon,6 flow,duct and plenum protection only.
For multiple nozzle protection of single fryers,see detailed information on Pages 4-12 through 4-14.
SECTION IV - SYSTEM DESIGN
UL EX.•3470 ULC CEx747 Page 4-31
7-1-98 REV.4
NOZZLE PLACEMENT REQUIREMENTS(Continued)
Nozzle Application Chart (Continued)
Maximum Hazard Nozzle Nozzle Nozzle Tip
Hazard Nozzle Stamping Dimensions Quantity Heights p . -
�—� �� Part No. Flo_ w No -
.Fryer/Split Vat Fryer" Maximum Size
(with drip board)
21 in. (53 cm)x
14 in. (36 cm)
(Fry Pot must not exceed
INK 15 in.x 14 in.
(38 cm x 36 cm))
High Proximity 1 27-47 in. 419339 230
Medium Proximity 1 20-27 in. 419340 245
Maximum Size
(with drip board)
25 3/8 in. (64.4 cm)
x 19 1/2 in. (49.5 cm)
(Fry pot side must not
exceed 19 1/2 in.
(49.5 cm) x 19 in.
(48.2 cm)
High Proximity 1 21 -34 in. 419338 3N
Low Proximity 1 13- 16 in. 419342 290
Maximum Size
+s (with drip board)
18 in. (45.7 cm)
x 27 5/8 in. (70.2 cm)
High Proximity 1 25-35 in. 419338 3N
(64-89 cm)
Range Longest Side - 1 30-50 in. 419333 1 F
28 in. (71 cm) (76- 127 cm)
Area-336 sq. in. 40-48 in.
(2168 sq. cm) (102- 122 cm)
(With Backshelf)
Longest Side (High Proximity) 1 40-50 in. 419340 245
28 in. (71 cm) (102- 127 cm)
Area-672 sq. in.
(4335 sq. cm)
Longest Side
(Medium Proximity) 1 30-40 in. 419341 260
28 in. (71 cm) (76- 102 cm)
Area-672 sq. in.
(4335 sq. cm)
Longest Side (Low Proximity) 2 15-20 in. 419342 290
36 in. (91 cm) (38-51 cm)
Area-1008 sq. in.
m
r
" For multiple nozzle protection of single fryers.see detailed information on Pages 4-12 through 4-14.
SECTION IV - SYSTEM DESIGN
UL EX.3470 ULC CEx747 Page 4-32
7-1 98 REV. 2
i
NOZZLE PLACEMENT REQUIREMENTS (Continued)
Nozzle Application Chart (Continued)
Nozzle Tip
Maximum Hazard Nozzle Nozzle Nozzle Stamping-
Hazard Dimensions Quanti Heights Part No. Flow No.
Griddle Longest Side(High Proximity) 1 30-50 in. 419341 260
48 in. (122 cm) (76-127 cm)
Area-1440 sq. in. (perimeter
(9290 sq.cm) located)
Longest Side(High Proximity) 1 30-50 in. 419342 290
30 in. (76 cm) (76-127 cm)
Area-720 sq. in. (center located)
(1829 sq.cm)
Longest Side (High Proximity) 1 35—40 in. 419335/417332 1 N/1 NSS
36 in. (91 cm) (89-102 cm)
-Area---#080-sq: in..- (perimeter located) _
(2743 sq.cm)
Longest Side 1 20-30 in. 419342 290
(Medium Proximity) (51 -76 cm)
48 in. (122 cm) (perimeter
Area-1440 sq. in. located)
(9190 sq. cm)
Longest Side(Low Proximity) 1 10-20 in. 419343 2120
48 in. (122 cm) (25-51 cm)
Area-1440 sq. in. (perimeter
(9290 sq. cm) located)
Chain Broiler' Longest Side-34 in. (86 cm) 2 10-26 in. 419336/417333 1 W/1 WSS
(Overhead Protection) Area-1088 sq. in. (25-66 cm)
(7019 sq. cm)
Chain Broiler. Length 43 in. (109 cm) 2 1 -3 in. 419335/417332 1 N/1 NSS A
(Horizontal Protection) Width-31 in. (79 cm) (3-8 cm)
Gas-Radiant Char-Broiler Longest Side-24 in. (61 cm) 1 18-40 in. 419340 245
Area-528 sq. in. (46-102 cm)
(3406 sq.cm)
Longest Side-24 in. (61 cm) 1 26-40 in. 419335/417332 1 N/1 NSS UMIT
Area-528 sq. in. (66-102 cm)
(3406 sq. m)
Electric Char-Broiler Longest Side-34 in. (86 cm) 1 20-50 in. 419335/417332 1 N/1 NSS
Area-680 sq. in. (51 -127 cm)
(4388 sq.cm) -
Lava-Rock Broiler Longest Side-24 in. (61 cm) 1 18-35 in. 419335/417332 1 N/1 NSS
Area-312 sq.in. (46-89 cm)
(2013 sq.cm)
Natural Charcoal Broiler Longest Side-24 in. (61 cm) 1 18-40 in. 419335/417332 1 N/1 NSS
Area-288 sq. in. (46-102 cm)
(1868 oq. om)
Lava-Rock or Natural Longest Side-30 in. (76 cm) 1 14-40 in. 419338 3N
Charcoal Char-Broiler Area-720 sq.in. (36-102 cm)
(4645 sq.cm)
Minimum chain broiler exhaust opening—12 in.x 12 in.(31 cm x 31 cm),and not less than Bo%of internal broiler size.
SECTION IV — SYSTEM DESIGN
UL EX. 3470 ULC CEx747 Page 4-33
4-30-02 REV. 4
NOZZLE PLACEMENT REQUIREMENTS (Continued)
Nozzle Application Chart (Continued)
Nozzle Tip
Maximum Hazard Nozzle Nozzle Nozzle Stamping—
Hazard Dimensions Quantity Heights Part No. Flow No.
Mesquite Char-Broiler Longest Side—30 in. (76 cm) 1 14—40 in. 419338 3N
Area—720 sq. in. (36— 102 cm)
(4645 sq. cm)
Upright Broiler Length—32.5 in. (82.5 cm) 2 — 419334 1/2N
Width—30 in. (76 cm)
Salamander Length—32.5 in. (82.5 cm) 2 — 419334 1/2N
Broiler Width—30 in. (76 cm)
Wok 14 in.—30 in. (36—76 cm) 1 35—45 in. 419341 260
Diameter _ (89—114 cm)
3.75—8.0 in. (9.5—20 cm)
Deep
11 in. —24 in. (28—61 cm) 30—40 in. 419335/417332 1 N/1 NSS
Diameter (89—102 cm)
3.0—6.0 in. (8— 15.2 cm)
Deep
HW.3ULA I tU HtLtASE ASSEMBLY (MtLnv.r41t Awl -
The ANSUL AUTOMAN Regulated Mechanical Release
Assembly (3.0 gallon — Part No. 79290 or 1.5 gallon — Par,
No. 79291) contains the regulated release mechanism, agent f a ®_1 02 RESTAURANT
RANT
tank,expeliant gas hose for agent tank hookup,and enclosure AN r�- E�� GG �7 ! �j
knockouts to facilitate installing actuation piping; expellant FIRE ✓
piping;detection system;and additional equipment.This regu SUPPRESSION
lated release assembly is used in single,double,and multiple- SYSTEM
tank systems and must be mounted to a rigid surface. The i ! iVf1
release mechanism can be used to interconnect both the actu- (Standard 1 1 L 300 Listed)
ation and expellant gas lines as required per system design.The EJ
regulator is designed to allow a constant flow of gas into the
tank at 100 psi (690 kPa) when the system is actuated.
In single,double,and multiple-tank systems,the provided expel-
lant gas hose connects the agent tank to the bottom outlet of
the regulator.In double and multiple-tank system configurations, Nozzle Identification Chart
the back outlet of the regulator is used as an expellant gas feed Nozzle Nozzle Noz;
for one additional tank-enclosure or tank-bracket hookup.The Nozzle Type Part No. Stampina FloA
enclosure contains the required knockouts to facilitate this con- 1 W Nozzle 419336 1 W 1
nection. If a pressure switch is to be attached to the regulator,
additional fittings are required. 1 WSS Nozzle 417333 1 W 1
The tank is mounted within the enclosure. The tank contains 1 N Nozzle 419335 1 N 1
an adaptor/tube assembly with a burst disc union.The burst disc 1 NSS Nozzle 417332 1 N 1
helps prevent siphoning of the agent up the pipe due to signifi-
cant temperature fluctuations in the area where the tank is 1/2N Nozzle 419334 1/2N 1/2
located. The tank is mild steel and, under normal conditions, 3N Nozzle 419338 3N 3
-requires hydrostatic testing every fwelve years:- " -"
2W Nozzle 419337 2W 2
The agent tank is shipped uncharged and must be filled with 2WH Nozzle 78078 2WH 2
1.53 gallons(5.8 L)or 3.06 gallons(11.6 L)of only ANSULEX
Low pH Liquid Fire Suppressant during installation. j�00 bo22 1100 '
The detection and additional equipment required per system 1
230 Nozzle 419339 230 2
design are connected to the release mechanism.The enclosure
contains knockouts to facilitate detection and additional hookups. 245 Nozzle 419340 245 2
The system can be actuated automatically or manually. Auto- 260 Nozzle 419341 260 2
matic actuation occurs when a fusible link within the detection
I 290 Nozzle 419342 290 2
system separates in a fire condition. Manual actuation of the
jsystem occurs when personnel pull on the remote manual pull 2120 Nozzle 419343 2120 2
station pull ring. 1 F Nozzle 419333 1 F 1
EXTINGUISHING AGENT
ANSULEX Low pH Liquid Fire Suppressant(1.5 gallon - Part
o. 196V4 or TO gallon - Pant IQo.--=2)is-a po assiumUa eed
solution designed for fast knock-down and suppression of
grease-related fires.The agent is shipped in plastic containers
I which provide one complete tank charge. Agent storage life
expectancy is twelve years.The distributor must record the batch
numbers and date of shipment receipt to be filed with each instal-
lation record.
Total Tank Type of Nitrogen Carbon Dioxide
Flow No.' Quantily System Type of Hardware Cartridge Required Cartridge Required
1-5 1 Single 1.5 G-�AI. Reg. Release LT-20-R (7032) 101-10(15850)
i
6-11 1 Single 3.0 Gal. Reg. Release LT 30-R(5373) 101-20(17492)
ELECTRICAL SWITCHES -LOCATED ItJ Ef}G{ Rip, ,,S
The electrical switches are intended for use with electric gas
valves, alarms, contactors, lights, contractor supplied electric
fer-edevicesare
designed to shut off or turn on when the system is actuated.
Switches are available in kits: One Switch Kit, Part No. 423878,
Two Switch Kit, Part No. 423879, Three Switch Kit, Part No.
423880,and Four Switch Kit, Pail No.423881. Each switch has a
set of single-pole, double-throw contacts rated at 21 amp, 1 HP, W� �I�/"►,1�'125,250,277 VAC or 2 HP,250,277 VAC. Mounting hardware is
f provided with each kit.
2 �j►ir 1 �/r"
j COMMON -i / N.C. SUPPLY kII` WT5 OF{ s/ 1u cr
o � Po�� (CA.)►1.�TS) UNDG-& �D �J nut ow
o N.C. �} �1F1� 5 jCINAL IS Sg- rl
i
I
SECTION IX - APPENDIX
UL EX. 3470 ULC CEX747 Page 9-1
7-1-98 REV. 3 «
SYSTEM SELECTION GUIDE
NOTE:System options do not cover all conceivable variations. They are listed here as a general guideline to show the most common
type arrangement for multiple systems, Based on certain system designs utilizing manifolding, non-man ifolding, 3-tank systems,
etc., other tank/cartridge combinations can be designed. The combinations below are based on 11 flow, 3.0 gallon tanks and 5
flow, 1.5 gallon tanks. More competitive designs may be available by utilizing 12 flow and 6 flow systems when appropriate.
Total Tank Type of Nitrogen Carbon Dioxide
Flow No.' Quantity System Type of Hardware Cartridge Required Cartridge Required
1-5 1 Single 1.5 Gal. Reg. Release LT-20-R (7032) 101-10 (15850)
6-11 1 Single 3.0 Gal. Reg. Release LT-30-R (5373) 101-20 (17492)
12-16 2 Double 1.5 Gal. Reg. Release Double(73022) 101-30 (15851)
3.0 Gal.Additional Tank
17-22 2 Double 3.0 Gal. Reg. Release Double(73022) 101-30 (15851)"'
3.0 Gal.Additional Tank
23-27 3 Multiple 1.5 Gal. Reg. Release LT-20-R (7032) 101-10 (15850)
3.0 Gal. Reg.Actuator LT-A-101:30(29187) 101-30 (15851)"'
3.0 Gal.Additional Tank
28-33 3 Multiple 3.0 Gal. Reg. Release LT-30-R (5373) 101-20(17492)
3.0 Gal. Reg.Actuator LT-A-101-30(29187) 101-30(15851)'"
3.0 Gal.Additional Tank
28-33 3 Multiple 3.0 Gal. Reg. Release Double (73022) N/A
(Optional) (2) 3.0 Gal.Additional Tanks
34-38 4 Multiple 1.5 Gal. Reg. Release Double (73022) 101-30 (15851)
3.0 Gal.Additional Tank
3.0 Gal. Reg.Actuator LT-A-101-30(29187) 101-30 (15851)""
3.0 Gal Additional Tank
39-44 4 Multiple 3.0 Gal. Reg. Release Double(73022) 101-30 (15851)"
3.0 Gal.Additional Tank
3.0 Gal. Reg.Actuator LT-A-101-30 (29187) 101-30 (15851)"
3.0 Gal.Additional Tank
T, 45-49 5 Multiple 1.5 Gal. Reg. Release LT-20-R (7032) 101-10 (15850)
3.0 Gal. Reg.Actuator LT-A-101-30 (29187) 101-30 (15851)"'
3.0 Gal.Additional Tank
3.0 Gal. Reg.Actuator LT-A-101-30 (29187) 101-30 (15851)"*`
3.0 Gal.Additional Tank
50-55 5 Multiple 3.0 Gal. Reg. Release LT-30-R (5373) 101-20 (17492)
3.0 Gal. Reg.Actuator LT-A-101-30(29187) 101-30 (15851)""'
3.0 Gal.Additional Tank
3.0 Gal. Reg.Actuator LT-A-101-30 (29187) 101-30 (15851)"`
3.0 Gal.Additional Tank
56-60 6 Multiple 1.5 Gal. Reg. Release Double (73022) 101-30 (15851)
3.0 Coal-6dditinnal Tank
3.0 Gal. Reg.Actuator LT-A-101-30 (29187) 101-30 (15851)""
3.0 Gal.Additional Tank
3.0 Gal. Reg.Actuator LT-A-101-30 (29187) 101-30 (15851)...
3.0 Gal.Additional Tank
61-66 6 Multiple 3.0 Gal. Reg. Release Double (73022) 101-30(15851)--
3.0 Gal.Additional Tank
3.0 Gal. Reg.Actuator LT-A-101-30 (29187) 101-30 (15851)"'
3.0 Gal.Additional Tank
3.0 Gal. Reg.Actuator LT-A-101-30 (29187) 101-30(15851)"*
3.0 Gal.Additional Tank
Based on 5 flow numbers for a 1.5 gal.system and 11 flow numbers for a 3.0 gal.system.See Pages 4-39-4-42 for exceptions.
If tanks are manifolded,only a"double tank"nitrogen cartridge(Part No.73022)can be used.
" If tanks are manifolded,either an LT-A-101-30 nitrogen cartridge(Part No.29187)or a double tank cartridge(Part No.73022)can be used.
s