Loading...
HomeMy WebLinkAboutCOM2008-00078 Propane - COM Permit / Conditions - 7/30/2008 MASON COUNTY DEPT. OF COMMUNITY DEVELOPMENT Inspection Line(360)427-7262 Phone: (360)427-9670,ext.352 Mason County Bldg. 3 426 W. Cedar P.O. Box 186 Shelton,WA 98584 COMMERCIAL BUILDING PERMIT COM2008-00078 OWNER: HOOD CANAL COMMUNICATIONS RECEIVED: 7/2/2008 CONTRACTOR: LICENSE: EXP: ISSUED: 7/30/2008 SITE ADDRESS: 9470 E STATE ROUTE 106 UNION EXPIRES: 1/30/2009 PARCEL NUMBER: 322357500340 LEGAL DESCRIPTION: TR 34 OF SURVEY VOL 1 PGS 210-213 PROJECT DESCRIPTION: DIRECTIONS TO SITE: 250 gallon Propane Tank, underground. Hwy 106 to address. General Information Construction &Occupancy Information Type of Use: Ip tank Insp.Area: No. of Units: Type of Constr.: Type of Work: MEC Fire Dist.: No. of Bathrooms: Occ. Group: Valuation: No. of Stories: Occ. Load: Building Height: Pre-Manufactured Unit Information Square Footage Information Make: Length: Lot Size: Model: Width: Building: Year: Serial No.: Basement: Parking Spaces: Setback Information Shoreline&Planning Information Front: Ft. Shoreline: 60.00 Ft. Rear: Ft. Slope: Ft. Water Body:Hood Canal Shoreline Desig.: Side 1: Ft. SEPA?: Comp. Plan Desig.: Rural Side 2: Ft. Fire Protection System Information Auto Fire Alarm System?: Emergency Key Box?: Standpipe?: Auto Fire Sprinkler System?: Access Road?: Fire Extinguishers?: Fixed Fire Suppression System?: Fire Hydrants?: Fire Lanes?: COM2008-00078 Please refer to the following pages for conditions of this permit. 1 of 5 Plumbing Fixtures Mechanical Fixtures FEES Type Qty. Type Qty. Type By Date Amount Receipt Propane Tank 1 Mechanical Fee KKK 7/9/9nnR It157 Sn C77nnAnn IFC Plan Check Fee I AIN 7/11/7nnA (�7A 7F C77nnR0n Total $236.25 CASE NOTES FOR COM2008-00078 CONDITIONS FOR COM2008-00078 1) The 250-gallon LP tank, located underground, is approved provided the pressure relief valve and filling connection is located at least 10-ft from a building or property line that can be built upon. The tank and all apputenances shall be provided with an approved barrier to prevent vehicle damage. X 2) Contractor registration laws are governed under RCW 18.27 and enforced by the WA State Dept of Labor and Industries, Contractor Compliance Division. There are potential risks and monetary liabilities to the homeowner for using an unregistered contractor. Further information can be obtained at 1-800-647-0982. The person signing this condition is either the homeowner, agent for the owner or a registered contractor according to WA state law. X 3) Owner/Agent is responsible to post the assigned address and/or purchase and post private road signs in accordance with Mason County Title 14.28. X 4) The approved site plan is required to be on-site for inspection purposes. If inspection is called for and the site plan is not on site, Approval WILL NOT be granted. In addition, a reinspection fee, based on the current fee schedule, minimum one-hour will be charged and collected by the Mason County Building Department prior to any further inspections being performed or approvals granted. 5) ALL CONSTRUCTION MUST MEET OR EXCEED ALL LOCAL CODES AND THE INTERNATIONAL CODE REQUIREMENTS AND OCCUPANCY IS LIMITED TO THE PERMITTED AND APPROVED CLASSIFICATION. ANY CHANGE OF USE OR OCCUPANCY WOULD RESULT IN PERMIT REVOCATION. CHANGE OF USE MUST BE APPROVED PRIOR TO CHANGE. x COM2008-00078 2 of 5 6) Provisions for surface/subsurface drainage control must be implemented with new construction or development on site and MUST NOT adversely impact adjacent parcels. Under the requirements of Mason County Stormwater Ordinance, either private ditches and drains will meet requirements of the stormwater ordinance or prior approval will be granted to use an existing utility and drainage easement dedicated for that specific purpose. For further information regarding this ordinance and the REQUIREMENT to obtain an ACCESS PERMIT for the installation/construction of a driveway or access connecting from a Mason County Road, Contact the Mason County Public Works Department prior to construction at Ext 450. For any construction which is proposed to be located within 25' of a Mason County road right of way, it is suggested to contact that office to review future planned work whigh2ay affect your project. X 7) Changes to approved building plans that affect compliance to the current ), Building/Plumbing/Mechanical Codes and/or other Mason County Regulations s all be approved prior to construction. X • J' 8) CONSTRUCTION PROCESS TO BE FIELD CORRECTED AS REQUIRED PER MASON COUNTY BUILDING DEPARTMENT AND THE ADOPTED BUILDING CODE. The construction of the permitted project is subject to inspections by the Mason County Building Department. All construction must be in conformance with the international codes as amended and adopted by Mason County. Any corrections, changes or alterations required by a Mason Coun u ding Inspector shall be made prior to requesting additional inspections. X 9) If the tank size is between 125 and 500 gallons you must follow these guidelines: 1. Tank is to be 10 feet from any buidling, public way or property line. 2. If the tank is exposed to probable vehicular damage, provide protective All weeds, grass, brush, trash and other combustible material shall be kept a minimum of 10 feet away from LP containers. X 10) All property lines shall be clearly identified at the time of foundation inspection. X 11) All permits expire 180 days after permit issuance, or 180 days after the last inspection activity is performed. The Building Official may extend the time for action for a period not exceeding 180 days, upon the receipt of a written extension request indicating that circumstances beyond the control Xthe permit holder have prevented action from being taken. No more than one extension may be granted. 12) PER TITLE 14 MASON COUNTY BUILDING CODE -CHAPTER 14.17, STANDARDS FOR FIRE APPARATUS ACCESS ROADS- 14.17.110: A fire apparatus access road in excess of 14% grade and more than 150' to new residential or commercial structures will require an automatic fire sprinkler system-,installed. Contact the Mason County Fire Marshal at(360)427-9670, extension 273, for further information. x 13) Provide an emergency power shutoff switch within 75 feet, but no closer than 25 feet from the dispensing station. Provide a NO SMOKING sign on tank. Provide a 20 BC rated fire extinguisher located within 75 feet of dispensing station. Provide protective bollards as follows: Guard posts constructed if steel not less than 4 inches in diameter and concrete filled, Spaced not more than 4 feet between posts on center, Set not less than 3 feet feep in a concrete footing of not less than 15 inches in diameter, Top of posts not less than 3 feet above ground, Located not less than 5 feet from the tank. inspection by the Mason County Fire Marshall is required before the tank ios put into service. X 14) Water quality i n t to be degraded to the detriment of the aquatic environment as a result of this project. X 15) Prior to final approval, all upland areas disturbed or newly createJ by construction activities shall be seeded, vegetated or given an equivalent type of erosion protection (silt fencing or straw matting). X COM2008-00078 3 of 5 16) Temporary erosion control measures must be implemented to prevent water quality degradation of adjacent waters or wetlands. Silt fencing must be installed and maintained until upland vegetation has become established. X This permit becomes null and void if work or construction authorized is not commenced within 180 days,or if construction or work is suspended for a period of 180 days at any time after work is commenced. Evidence of continuation of work is a progress inspection within the 180 day period. Final inspection must be approved before building can be occupied. Proof of continuation of work is by means of a progress inspection.The owner or the agent on the owners behalf, represents that the information provided is accurate and grants employees of Mason County access to the above described property a ucture for review and inspection. Z OWN ER OR AGENT: DATE: J 7 l i II i I I I I i COM2008-00078 4 of 5 IL -- n •.= CONCRETE MECHANICAL MANUFACTURED HOME 0 pDate By - - 0o Footings I Setbacks Ribbons Gas Piping n o Interior Date By interior-Date By Date By D 4 Extew Date By Exterior-Date B Z ..... Sot-up D Point load I Isolated Footings INSULATION Date By r BG I SLAB INSULATION 0 Date By Data By FIRE DEPARTMENT 3 Foundation Walls Floors Date By 3 Date. By Data By DECKS C FRAMING Walls Date By Z Date By Data By PROPANE TANKS PLUMBING vault Date By O Date By OTHER Z Groundwork Attic N Date By Date By Type- Date By O.W.v DRYWALL Type- 0 Int.Brace Wall Date By 3 Date By Daie ey FINAL INSPECTION ha p Water Line Fire Seperation O Dale By Date By Date ?-Ire By Co O Pass or Request Inspect. O Tyjop of Insp. Fail Date Date Done By Comments coo I 0 C T. t M N MASON COUNTY PE PLUMBING/MECHANICAL PERMIT APPLICATION 426 W. Cedar• P.O. Box 186, Shelton, WA 98584 Shelton (360) 427-9670• Belfair (360) 275-4467 • Elma (360) 482-5269 + On the web www.co.mason.wa.us APPLICANT INIFOP#ATION .� � CONTRACTOR INFORMATION Owner r A► a i A:`� Company Name -�Y1� Mailing Address, 4 Mailing Address City to AIA Zip Code City Mate Zip Code Phone . �' 2 Other Ph. 1Y9D - Sy7S Phone Other Ph. Lien/Title Holder Contractor Reg.4— Exp. E mail address 01 OM E Mail Address Drivers Lic.# 1. 7_'7 AVI 1FDOB (/ �F:) Drivers Lic.# DOB SEPTIC INFORMATION - Connect to New Septic Existing Septic. Connect to Sewer System Name of Sewer System PARCEL INFORMATION - 12 Digit Parcel No. Fire District Legal Description Site Address (Pleas include Et t name, street number and city) Directions to site c' f t Is property within 200'of Saltwater Lake River/Creek Pond Wetland Seasonal Runoff Stream Slopes or Bluffs > 15% TYPE OF JOB - New Add Alt Repair Other_ Use of Building Location of Fixtures/Units - 1st Floor 2nd Floor Basement Garage Closet PLUMBING FIXTURES (Show Number of each) MECHANICAL UNITS Type of Fixture No. of Fixtures Fees Fuel Type:ElectriG_ ,LPG— Natural Gas_ Heat Pump_ Toilets Type of Unit No-.-of Units Fees Bathroom Sink Furnace Bath Tubs Heatpumps Showers Spot Vent Fan �--- Water Heater Propane Tank Clothes Washer Gas Outlets Kithen Sinks Wood/Gas/PelletStove Dishwasher Kitchen Exhaust Hood Hosebibs Dryer Vent Other Other Base Fee Base Fee TOTAL PLUMBING TOTAL MECHANICAL OWNER/BUILDER Acknowledges submission of inaccurate information may result in a stop work order or permit revocation.Acknowledgement of such is by signature below.I declare that I am the owner,owners legal representative,or the contractor.I further declare that I am entitled to receive this permit and to do the work as proposed in the application.I declare that I have obtained the permission from all the necessary parties.If permission is required from any easement holder or any other party in interest regarding this application or the work proposed in the application, I have obtained permission from them to apply for this permit and conduct the work proposed. The owner or agent on owners behalf,represents that the information provided is accurate and grants employees of Mason County access to the above described property and structure for review and inspection. PROOF OF CON)Il4PATION OF WORK IS BY MEANS OF A PROGRESS INSPECTION.%Z () Date: � / ` X Owner/Owners Representative/Contractor (indicate which one) FOR OFFICIAL USE BEYOND THIS POINT Accepted by: Planning Pd Ck# Date Bld Pd Receipt No. DEPARTMENTAL REVIEW APPROVED DENIED NOTES Building Department Occ Grou Type Constr.- 7 �.t Planning Department If=� Environmental Health Department FEES Plumbing & Base Fee Site Inspection Mechanical & Base fee UFC Plan Review Fee Wood/Gas/Pellet Stove Fee Other Violation Fee TOTAL FEES �00A Car,al APPROVED I tf, /OGMASON COUNTY DCI) PLANNING Con a ov8 - v Q v--] SITE PLAN kE°'�UIRED TO BE ON SITE CHANGES SUWET TO APPROVAL a-0 y - AP � -,� gNNlNG N REQ EDTO 41 IT HANG SUBJ T O _.s._ BY 'boo, WsboT- vel 190 ENE] 1J►�d r .�� vt� rat � �� �� z.1-�1,� �� c e T4 n soC 3 4c � �°LANNING: ALL SETBACKS ARE ME URED �:..,.—..E.Rfi3��' � rc HEST PROJECTION OF HE BUILDING �1� IC�Co ve� 2SO �`� T� � yapC, 3 4C� 6ax k Mason County Map Output Page Page 1 of 1 Mason Count Ma ,322352222222 3223500050l3• ]22351400030 3223aa202005 322351400031 3223114100040 N00) CANAL 322355202006 / 1t2335202905 32235azbboO ✓ r' ��312339100020 �✓� 322353100078 3=55100017 £10fi ]z2a+ 51 1322355100016fE�tAT'fkoko 322355100012w^""-322350000000 i 'i 3223STS00321 322335100009 � 3 000000" 32235at0000a �r,<. 3223S510b005,,,i t =r��J � ' t 3f77I18f0300 3 ! i 322257000310 T � i 32239T0003]0 # b $ f127{f000300 i� �I =357590354 i 322357590353/ 3223575903SZ ! tlt 22353290301 322357590351 f a at ti r 3n3a3290304 f p §Z233ft r DISCLAIMER AND LIMFI ATION 01:LIABILITY: 'I he data used to make this map have been tested for accuracy,and every effort has been made to ensure that these data are timely,accurate and reliable.However,Mason County LEGEND makes no guarantee or warranty to its accuracy as to labeling,dimensions,or placement or location of any map features contained herein.The boundaries depicted by these data are 140845 [ F1,001 t Land$ approximate,and are not necessarily accurate to surveying or engineering standards,and are intended for informational purposes only.Mason County does not assume any legal liability Higbnays ,- City of Shelton or responsibility arising from the use of this map in a manner not intended by Mason County. In no event shall Mason County he liable R1r direct,indirect,incidental,consequential, kwam 8 Streams County ri0urttl>+ry(L1Nk) special,or tort damages of any kind,including,but not limited to,loss ol'anticipated profits parcels COMMIS5rorwr Dsytncts or benefits arising from use of or reliance on the information contained herein 41 Serfn.)n5 r Lakes «,21Hr6-Mason County r^ 415 N.Sixth Street 1�- j_J Townships �► Pugot Sound&Melor Lakes Shelton,WA 98584 http://mapmason.co.mason.wa.us/servlet/com.esri.esrimap.Esrimap?ServiceName=amason_... 8/8/2007 Iry`-'mil l�3/� DV r 01A.STA MASON COUNTY o P� A o - DEPARTMENT OF COMMUNITY DEVELOPMENT 1p o N Z Planning Division Zoo N y o~ P O Box 279, Shelton, WA 98584 (360)427-9670 1864 NOTIFICATION OF INCOMPLETE APPLICATION July 17, 2008 0 I HOOD CANAL COMMUNICATIONS PO BOX 249 UNION WA 98592 Parcel No.: 322357500340 Project Description: 250 gallon Propane Tank, underground. Dear Applicant: You have submitted a permit application (case no. COM2008-00078) for proposed construction or development in the county. Upon review of your application, I have determined that the contents of the application are incomplete or do not provide enough detail for review. Therefore, review of your application will not proceed until the necessary information is provided (see the comment section of this letter for details.) Once the information is submitted and the application is complete, I will continue to process your application accordingly. If the additional information is not provided to the County within 180 days of this request, the application shall expire and no further action on the proposed development shall take place. Please contact me at (360) 427-9670, ext. 287 if you have questions. Sin erely, vV Pam Bennett-Cumming Land Use Planner Mason County Planning Department 7/17/2008 Page 1 of 2 COM2008-00078 NOTIFICATION OF INCOMPLETE APPLICATION 7/17/2008 Case No.: COM2008-00078 Comments: Planning is currently reviewing your proposal to install a propane tank within a 5ft wide easement over Brook Point Water company land. Please verify the width of the easement - 5ft does not seem wide inough to fit a propane tank...? You would need to work with the underlying property owner to enlarge the easement if it does not fit. Site plan: it is not clear from the site plan what the proposed tank distance is from the property boundary. "Front yard" setbacks are 25 feet, however we recognize that what you are instlling could be considered part of the "utility" for which you have an easement. The site plan needs to clearly show the location of the tank with 1. distances to the easement edges, and 2. distances to the property boundary. Easement: we have not been able to find a copy of the easement in question, please provide that information. 7/17/2008 Page 2 of 2 COM2008-00078 �'O's co MASON COUNTY DEPARTMENT OF COMMUNITY DEVELOPMENT Mason County Bldg. III, 426 West Cedar Street PO Box 186, Shelton, WA 98584 18Sd www.co.masonma.us 360)427-9670 Belfair(360)275-4467 STANDARDS FOR INSTALLTION OF PROPANE TANKS Intake to direct- o_ v t appliance -�- Window air conditioner ° 10 It(min) 5 _ (source of ignition) 0 0 (Note 1) (min) 10 It min Note 1 Central A/C � •:.•- Uhb �(Nate 2)� - (min) ( ) compressor 10 It(min — $� >2 (source of ignition) (Note 1) 'daf t25 a. 5ft loft •' :°.e (min) g / S7? (min) ,n°' (Note 2) /- �ga/ 25 ft Crawl space opening, Nearest line of adjoining a window,or exhaust fan property that can be / (Note 3) 10 ft(min) built upon \ / 25 ft(min) For SI units,1 It=0.3048 m (Note 3) Note 1:Regardless of its size,any ASME container filled on Note 2:Refer to 6.3.9. site must be located so that the tilling connection and fixed maximum liquid level gauge are at least 1011 from any Note 3:This distance may be reduced to no less than 10 ft for a external source of ignition(e.g.,open flame,window A/C, single container of 1200 gal(4.5 m3)water capacity or less, compressor),intake to direct-vented gas appliance,or intake provided such container is at least 25 it from any other LP-Gas to a mechanical ventilation system. container of more than 125 gal(0.5 m3)water capacity.Refer Refer to 6.3.9. to 6.3.3. FIGURE 1.1(b) Aboveground ASME Containers. (This figure for illustrative purposes only;code shall govern.) NFPA 58 Table 6.3.1 Separation distanced between containers,important buildings and other properties. Minimum Distances Water Capacity Mounded or Underground b Containers per Container Containers Gallons Feet Feet Feet <125 d10 Oe 0 125—250 10 10 0 251 —500 10 10 3 501 —2000 10 25 3 2001 —30,000 50 50 5 Footnote a: Distances for mounded or underground tanks shall be measured from the pressure relief valve and the filling connection.No part of an underground ASME container shall be less than 10-ft from a building or property line that can be built upon. (NFPA58 6.3.4) Footnote b:The horizontal distance between the portion of a building that overhangs out of the building wall and an ASME container of 125 gallons or more shall comply with the following: (1) The horizontal distance shall be measured from a point determined by projecting the outside edge of the overhanging structure vertically downward to grade or other level upon which the container is installed. (2) This horizontal distance shall be at least 50%of the separation distance required in Table 6.3.1. (3) This requirement shall apply only when the overhang extends more than 5-ft.from the building. (4) This requirement shall not apply when the overhanging structure is 50-ft or more than the relief valve discharge outlet. (5) This requirement shall not apply to ASME containers,2002 to 30,000 gallons,where the container distance from a building is in accordance with NFPA 58 6.24.2. Footnote c: Access at the ends or sides of individual underground containers 125 gallons or more shall be provided in multi- container installations to facilitate working with cranes.or hoists. (NFPA 58 6.3.11) Footnote& The distance measured horizontally from the point of discharge of a container pressure relief valve to any building opening below the level of such discharge shall be in accordance with Table 6.3.9.and figure I.1(b).(NFPA 58 6.3.9) Footnote e: Cylinders installed alongside of buildings shall be positioned so that the discharge from the cylinder pressure relief device is located as follows:(1)At least 3-ft horizontally away from any building opening that is below the level of such discharge.(2)At least 5-ft in any direction away from any exterior source of ignition,opening to direct-vent(sealed combustion system)appliances,or mechanical ventilation air intakes. Cylinders shall not be located and installed underneath an building unless the space is open to the atmosphere for 50%or its perimeter or more. The distance measured horizontally from any point of discharge of a container pressure relief valve to any building opening below the level of such discharge shall be in accordance with Table 6.3.9 and Figure I.1(b).(NFPA 58 6.3.7,6.3.8,and 6.3.9) ADDITIONAL REOUIREMENTS: 1. A building permit shall be required for the installation of any sized tank serving a fixed appliance within any structure. 2. All LP tanks shall be installed in accordance to NFPA 58 and the International Fire Code. 3. Weeds,grass,brush,trash and other combustible material shall be kept not less than 10-feet from LP tanks in any direction. 4. When exposed to probable vehicular damage due to proximity to driveways,parking areas,or alleys,LP containers,regulators and piping shall be protected. � Intake to ';'` dhecbverd^���— Window air appliance ­_Z conditioner(source a n 5H —of lgniAon) Central A/C min (min (3 H 10 H min)(Note 2)' compressor (Moto 1) fJote 3�I (source of ignition) min Cylinders not filled on alte rO.Q ;�`o"e� (Note 3) Cylinder filled on site from bulk truck Crawl space oponing, windows,or exhaust fan For 81 units,1 H.0.3048 m Note 1:5-H minimum from relief valve in any direction away Note 2:It the cylinder is filled on site from a bulk truck,the from any exterior source of Ignllon,openings Into direct- filing connection and vent valve must be at least 10 H from vent appliances,or mechanical ventilation air Intakes, any exterior source of ignition,openings into direct-vent Refer to 6.3.7. appliances,or mechanical ventilation air intakes. Refer to 6.3.B. Note 3:Refer to 6.3.7. FIGURE 1.1(a) Cylinders.(This frktrre for illustrative purposes only;code shall fgovenr.) 07-22-2008 11:17 FERRELLGAS 3608775076 PAGE2 What Our Tank Install��i�ons Above Ground Installst_ • First Year Tank Rental'FIEF ♦ Tank-delivery, set up,and.1nal hookup ♦ Installation of Regulators (first and second or twin stage) ♦ •Parks,Ettings, and up to 30 ft of 112"exterior UG.aoly]lne ($1.00/f7 Add'I) ♦ Manual Shut-off-valve ♦ Ferrellgas Safety inspection which.lacludes: complete leak,flow lock..-up test( done with water manometer.) and piping pr- s.sure test ♦ 'Customers have the option of our progxaffls-su.ch.asKeep:Full .(No 1.20'$) and-Level pay (oiusfWA-0eP F0lr) Above ground—anim jtaget rig" ♦ 120 each: �50.00 + tax ♦ 250+ each. $6DXD + tax ♦ 1000 gallon: $100.00 + tax Underground'Tank Ingalls- ♦ tink�Delivery, Set Up, and:FlrW,H0okup * Up to 30 feet exterior.-UG 1/2 In. ,poly line ( $1:00/foot.additiional) ♦ 1'and 21d or"TW.In.Stage Regulators ♦ 2 Risers and ServiceHead Adapters • Anode - . ♦ Manual Shut Off Valve ♦ Complete Leak test,-flow &lock.up test(-done with water manometer) and piping 1 r i pressure test '� ` ���K" ♦ Ferrellgas Installatipn�Ravlew Wolo, bff t`a:�5:: ar 6:Q rDlitl )� ( TEREST FREE Lease-tp�.Own on all >U i h+d�t r�k�s..( n; pp. iva1-.,0'c.00it).see pricing bita.kdown on the es i�ICtt7+�5 t66t. a , 01 dtlj�eks:. prop a fine, an T All tanks larger�th�ai :.a 1ZD need::'to set�10-fe'et�f om,anyperm.anent structure, pop rCy source of lgnitlon. They must provl4p an W trepiait•from tfte-stub out-of the-home-ta the location of the tat k, 120s can sit neXtto the home,:b�t-m, be 10.feet from any source-iif ignition and 5 feet from any o.penatile.door,whdovu, or trawl..spate vent) UG Tank Setbacks., The tank'needs to set a minimum.-of 10 feet.from any permanent structure, property.line; and source of Ignition. They must provide an 18"trench from the stub out of the home to the location of the tank. In addition, there needs to be a hole with the following dimensions c_� ccording to tank size with one cubic yard of sand or pea gravel (or equivalent) leveled in the ttom of the hole. The remaining must go over the tank for drainage purposes. _ UG Tank Hale Dimensions: Tank Size TznkQbCfl1IM Hole 01messioII SardNeeded ----�250 30 x 94"L 4'W x 91 x SD 5 cubic yards 325 4'W x.121 x 5'D 5 cubic yards 5o0 37"W x 119"L 4'W x 121 x 5'1/21) 6 cubic yards 1000 41''W x 192"L 51N x 181 x 5'1/2D 12 cubic yards