HomeMy WebLinkAboutFire Protection Plan - FIR Permit / Conditions - 6/13/2002 06/13/2002 11:59 FAX 3604279438 SHELTON FIRE Z 02
FIRE PROTECTION PLAN FOR
HARMONY HILL WELLNESS CENTER
EMERGENCY VEHICLE ACCESS
Intent is to provide for emergency vehicle access (fire engine or v
ater
tender) to within '160 feet of any portion of the exterior walls of t e
following buildings:
BLDG. C, D, K, E, H, G, F, I, L, M, Q
The Mason County Fire Code requires a 20 foot wide access road. The
applicant was advised to work towards achieving that width forte road
system serving the major building core(s), as identified on the attached site
plan.
Mason County FD 6 will conduct some on-site surveys to evaluat' the
access.
FIRE ALARM SYSTEMS
I
The following buildings are to have automatic fire alarm systems �nstalled to
Mason County standards:
i
BLDG. C, D, K, E, H, G, F, I, L, M, Q
A copy of Mason County Standards for Fire Alarm Systems is attached.
It is recommended that a location be established for a single fire alarm panel
that would collect and transmit fire alarm signals for all buildings IThis panel
should be installed in the first building to be constructed.
i
A Fire Alarm System Performance Standard sheet is also attached.
06/13/2002 11:59 FAX 3604279438 SHELTON FIRE fj03
I
COMMERCIAL COOKING SYSTEMS
Any commercial range is required to be protected by a Class I Ho d and fire
suppression system. The suppression system is to be connected to the site
fire alarm system and transmitted as a separate zone.
A copy of the Mason County Standards for Fixed Fire Suppression Systems
is attached.
BUILDING IDENTIFIERS
To aid in identification by emergency responders, each occupied building
should have a visual identifier; i.e., a number or letter, that is visible from the
primary access road. It is understood that this visual designation Beds to fit
the esthetics of the campus concept.
PORTABLE FIRE EXTINGUISHERS
Each occupied building is required to have one portable fire extinguisher at
each exit door. Specific locations will be noted on construction pi ns.
LIGHTED EXIT SIGNS AND EMERGENCY LIGHTS
I
Buildings with occupant loads over 50 and buildings where peopl are
sleeping (except the small 8x10 cottages and the single-family re$idence)
will be require to have lighted exit signs and emergency lights. Specific
locations will be noted on construction plans.
KNOX BOX EMERGENCY KEY BOX
A KNOX BOX emergency key box will be required if requested by FD 6.
Contact FD 6 for details.
I
I
i
harmony2.doc
I
i
06/13/2002 11:59 FAX 3604279438 SHELTON FIRE Z 04
f
Fire Alarm System Performance Standard
for Harmony Hill Wellness Center
SYSTEM COMPONENTS
1 . Fire alarm installation must comply with NFPA 72 and must me t all
appropriate ADA requirements.
2. Provide a single fire alarm control panel with sufficient capacit to monitor
and transmit fire alarm signals from multiple buildings and multiple zones
within some buildings.
3. A site annunciator with LED readouts is required at a readily accessible
location that will provide a visual representation of the alarm or tr uble signal
location.
4. A 10 inch bell and white strobe light is to be installed on each uilding at
a location facing the primary fire department access point.
P
occupied o i
5. Smoke alarms are requiredP in all spaces and exit c rri ors. Rate
of rise or fixed temperature heat detectors are required in all areas where
smoke alarms are not suitable, including attics, restrooms, and storage and
mechanical rooms. A smoke alarm is required to protect the fire al rm panel.
r
6. System is to monitor a fixed fire suppression system in a com ercial
kitchen hood.
SYSTEM OPERATION
1 . All defined zones are to be transmitted to an approve central re eivin
PP � 9
station. A list of UL Central Receiving Stations approved for monitoring fire
alarm systems in Mason County is included in the Mason County ire Alarm
Standards document.
harmonyTdoe