HomeMy WebLinkAboutMIS99-0497 Spray Booth - MIS Permit / Conditions - 8/13/1999 i
MASON COUNTY
Mason County Bldg. III 426 W. Cedar
P.O. Box 186 Shelton, Washington 98584
M I S C E L L A N E O U S P I T FOR INSPECTIONS CALL 427-9670
MIS99-0497 PARCEL :42O1724J PLAT : DIV : BLK : LOT :
JOB ADDRESS : 6651 W SHELTON MATLOCK RD SHELTON
APPLICANT : KIRK PETERSEN 426-3082
OWNER : KIRK PETERSEN 426-3082
LEGAL : TR 1 OF SE NA
PROJECT DESCRIPTION :
SPRAY BOOTH
PROJECT LOCATION :
APPROX 5 MILES WEST OF FREEWAY EXIT ON LEFT .
PROJECT NOTES :
INSTALL PRE—FAB SPRAY BOOTH .
TYPE AMOUNT BY DATE RECEIPT
PLCK $ 42 .00 KW 08 / 13/99 51201
PRMT $ 74 .75 KS 09/29/99 51737
STFE $ 4 .50 KS 09/29/ 99 51737 ! —�/
PCFE $ 6 .59 KS 09/29/ 99 51737 `l
TOTAL : 127 .84 OWNER W AGENT DATE
MIS—PRMT, rev: 04 10 1/92 COMPLIANCE TO ATTACHED CONDITIONS IS
REQUIRED
MASON COUNTY
Mason County Bldg. III 426 W. Cedar
P.O. Box 186 Shelton, Washington 98584
PERM I T C ONO I T I O N S
Case No . : MIS99-0497
For : KIRK PETERSEN
Page : 1
1 ) Site is within a type III moderately susceptible aquifer area which is regulated by
Mason County ' s Resource Ordinance chapter 17 .01 .080, Critical Aquifer Recharge Areas .
Sto� or handling of hazardous materials needs to comply with these regulations .
X
�W
2 ) 1 . FIXED FIRE SUPPRESSION SYSTEM REQUIRED IN THE BOOTH . SEPARATE PLANS AND PERMIT
REQUIRED .
2 . THE SPRAY BOOTH CAN BE LOCATED DIRECTLY AGAINST AN INTERIOR WALL THAT HAS A FIRE
REST TANCE RATING OF NOT LESS THAN ONE HOUR .
X
3 ) All approved plans are required to be on-site for inspection purposes . If inspection
is called for and plans are not on site , Approval WILL NOT be granted . In addition , a
Re- Inspection fee in the amount of $42 .00 per hour (minimum 1 hour ) will be charged and
must be collected by this department prior to any further inspections being performed or
approval granted .
X
MASON COUNTY
Mason County Bldg. III 426 W. Cedar
P.O. Box 186 Shelton, Washington 98584
4 ) PURSUANT TO 1997 UNIFORM BUILDING CODE , ALL SITE MUST BE MARKED WITH APPROVED NUMBERS
OR ADDRESSES PROVIDED IN SUCH A POSITION AS TO BE PLAINLY VISIBLE AND LEGIBLE FROM THE
STREET OR ROAD FRONTING THE PROPERTY . MASON COUNTY BUILDING DEPARTMENT REQUIRES THAT
THIS BE COMPLETED PRIOR TO CALLING FOR ANY SITE INSPECTIONS . A REINSPECTION FEE , BASED
ON RATES ADOPTED FEE SCHEDULES AND THE 1997 UNIFORM BUILDING CODE WILL BE ASSESSED IF
OWNER/CONTRACTOR FAILS TO POST ADDRESS ON SITE PRIOR TO REQUESTING INSPECTIONS .
X
5 ) ALL CONSTRUCTION MUST MEET OR EXCEED ALL LOCAL CODES AND UBC
XEQ�l EMENTS
6 ) THIS STRUCTURE IS CONSIDERED UNHEATED SPACE ( NOT TO EXCEED 1 WATT/ SQUARE FOOT OR 3 .4
BTU/ HR/ SQUARE FOOT ) . AT SUCH TIME THIS CONDITION CHANGES , A CHANGE OF USE PERMIT AND A
MECHANICAL PERMIT SHALL BE APPLIED FOR AND APPROVED PRIOR TO THE CHANGE . X-12,09
7 ) ALL FURNACE INSTALLATIONS SHALL MEET THE MINIMUM EFFICIENCIES SET FORTH IN THE 1994
WASHINGTON STATE ENERGY CODE (WSEC ) . ANY PORTION OF THE MECHANICAL SYSTEM THAT IS
ALTERED OR REPLACED SHALL MEET T MINIMUM STANDARDS SET FORTH IN THE 1994 WSEC AND
1997 UNIFORM MECHANICAL CODE . X
8 ) CONSTRUCTION PROCESS TO BE FIELD CORRECTED REQUIRED PER MASON COUNTY BUILDING
DEPARTMENT AND UNIFORM BUILDING CODE . x
PLEASE PRESS HA� LJ V PERMIT NO 1 r o ql
MASON COUNTY
PLU ING/MECHANICAL PERMIT APPLICATION i3
426 W.Cedar/P.O.Box 186,Sheiton,WA 98584 Mo,b,'IL
67p Ifatr. 360 275-4467 Elma 360 482-5269 Seattle 206 464.6968
Fly
APPL'CA T INF A CONTRq FORMATION �f Cj O-3q
Owner 1 rc �r S Contractor Names
Mailing Address ✓�.` Mailing Address
City �Ik
Phone(3 C. )�1<4=- he Ph Code
< � City State Zip Code
Lien/Title Holder �"", Contractor Reg. #--) Other Ph.(__�
Contractor
Address Expiration
SEPTIC INFORMATION-Connect to New Septic istirig Sep�TC Connect to Sewer System Name of
Sewer System
PARCEL INFORMATION-12 digit Tax Parcel No. DOp/0. _ Fire District
Legal Description 'f 2- I o,' .S'. ,-z IV,La"
Site Address(Please include street name,street number and city) 6, L4. s•44,, �
Directions to site_ ��n�ox .,� Ir w �sr �F . QZ�AY •i,�,t y��i-
Is your property within 200' of the following: Body of Water(Name) Saltwater
Lake River/Creek Pond Wetland Seasonal Runoff Stream Slopes or
Bluffs
TYPE OF JOB New Add Alt Repair Other Use of Building �(P2'�
Location of Fixtures/Units 1st Floor 2nd Floor Basement Garage Closet
PLUMBING FIXTURES(Show Numbe-of each) MECHANICAL UNITS Fuel Type: Electric
Type of Fixture No. of Fixtures Fes LPG Natural Gas Heatpump
Toilets Type of Unit No. of Units Fees
Bath Basins Furnace
Bath Tubs Heatpumps
Showers Vent Fans------ -7 —
Water Heater Propane Tank
Laundry Wsher Gas Outlets
Sinks I Wood/Gas/Pellet Stove
Dishwasher Dire Vent?
Other Othemw
Other Other
Base Fee Base Fee
TOTAL PLUMBING TOTAL MECHANICAL
A FLOOR PLAN AND PLOT PLAN MAY BE REQUIRED DEPENDING ON THE TYPE OF FIXTURE/UNIT.
NOTICE: THIS PERMIT BECOMES NULL&VOID IF WORK OR CONSTRUCTION AUTHORIZED IS NOT COMMENCED WITHIN 180 DAYS OR IF
CONSTRUCTION WORK IS SUSPENDED OR ABANDONED FOR A PERIOD OF 180 DAYS AT ANY TIME AFTER THE WORK IS COMMENCED.
PROOF OF CONTINUATION OF WORK IS BY MEANS OF A PROGRESS INSPECTION. The owner or agent on owner's behalf,represents that the
information provided is accurate and grants employees of Mason County access to the above described property and structures for review and
inspection of this project. Acknowledgment of such is by signature below:
OWNER AFFIDAVIT-[certify that I am exempt from the requirements of the CONT 'S AFFIDAVIT-I certify that I am currently registered as a
Contractor Registration Law RCW 18.27 and am aware of the ordinance contractor in th ate of Washington and that I am aware of the ordinance
requirements for which this permit is issued and that all work will be done in requirements regulating the work for which this permit is issued and all work
conformance therewith. No changes shall be made without first obtaining shall be done in conformance therewith. No changes shall be made without
approval. first obtaining approval.
X �t X
Date C`�'I\- Date
FOR Off ICIAL USE BEYOND THIS POINT
Accepted by Da =/ /-7) Submittal Amount Due 1 Receipt No.
DEt'AR?MEiVTAt #t 1f# V11.. >APPROVVWC ?: NIED7703001TOt : btltwS:;
Building Department f T vrt y /t-A}L 3e-OG PC Pi-
Occ Group t ypq Lonstr.
Planning Department
Other
Other �+b
t- G�7' :j'rititi?YIS::•i ::ij:•Yt+
..._ _
.�_..v - ..«............ ''.::. .........:??•iiY:•:•YY':^i:•i::::::::::•::.�:::.�:::v::::::::::::::::::Y:4:6:w:.+.•::::??....Yi:::::.::•iiiii::b.....
Permit Fee , Site Inspection
Plan Review Fee L1 1_5UFC Plan Review Fee
Plumbing&Base Feel Other
Mechanical&Base Fee Other
Wood/Gas/Pellet Stove Fee Pre-Paid at Submittal
Violation Fee TOTAL FEES
----- - _--EXTERIOR BRACED 'v1lALL PAi`dEL---- �-�-1—�-- —___---: ----�_—=:-1-I
i
16" O.C. 2X4 STUDS, SHf=A H!NG GLUED AI'D I
SHEAR "TAILED. POST1`,"-= CONNECTIONS AT TOP AND BOTTOM. Ii is
l
EX S
�
7 _y/l "' _- - -- TYPICAL 2X6 @ 24" O.C.
NOT TO EXCEED 10' IN HEIGHT.
y 3 ,-lvold1,� - '0'0 �,�Zo 0
J -._-._. _..
O:
�j S3SS(1 l J008 CIA?MNI0NA-'3&i o
3 �
o
i 0 4> 10 HEADER
--
aC � ! _ I• N
ii
ACCESS
LL-
m 22X30 MIN. I
j Cj O
i � 0 � !
ji
11' t-ilGl•-i CEIC.i'vGS
2909
i _ HR. IFFIRE NALL
SEE Al DETAIL /
-� 4X6 HEADER
i „O--,Zi 1.5 HR FIRE DOOR. �
I i
i iJ0° Mn JREMY i .— ; :_'mot' cJ=IN ti'GLSt S+iELTON HAYCOCK ROAD
-- -- CONS--P ,; "T 1 O?�\ 54Ei TON VASHfHGl"OH 9858�f ' t I O R i H FLOOR P i^A
rSCAM 1 „_ C O'1:I A i V Y Q) TEL (340) 424-3002
I 5 a'-8 a'► -----i ---- ----- C.r._ _ ---- -- �__ -_ PLANS AND DETAILS i
M
I i
I 1
I I
� � I
I
I
TAELE E1:1. 9 �
O
FIL
14, 4 9 PAINT WA. 2 C Copy
N-jSCRNOZZLE
130 " i c IcaT- '- T
4 IDUCT -NOZZLE PIPING -
5 PYRO CHEM- PCIX O X 25
6 MCH - MECHANICAL CON7ROLH A
7 R M T- PULL STATI N
° STANDARD INK DETFCTION 0 I�
91 —TF TOTAL I
ic I "- 3A�GA VANIZEG PIP
T
11 I MT CON IT !T 1
121 MICRO SWITCH - FAN SHUTDOWN
13 DUCT NOZZLES L
14
16 13
6651 W SHE TON MA LG K RD. S ELTON
KNIGHT FIRE PROTECTION, INC. JO. P E T E R S E N C AI i_N E T S
6436 Mullen Road SE SHEET NO.
Olympia, WA 98503 CALCULATED ByJON FAGERGREN DArE9-I-99(360) 456-2162 FAX 456-2151
CHECKED BY DATE
SCALE NOT TO SCALE
"QUALITY IS RE:vIEMBERED
LONG AFiTR PRICE IS FORGOTTEN!"
"ON GUARD
24 HOURS A DAY" LICENSE NO K.NIGHFP044LK
1 � fl
�l
I 0 ,WNi!Sr-:P 2C
I .
i
i",,D SHEERRY PETERSEN'
901001042— oC
/ Pi'll.RCE S ;; 1 AINID 2 I
i
WFLL
PROPOSED BOI�Di,A
i NORTH I;
20'—0"
26' — 20 -�
� o
SH`LTON MA FLOCK ROAD
�`- JBZFNIY" E T��E R S E N 'J6651 SHELTON '-ATLOCK
SHELTON. VASHWGTON 98554 ! # S I TF
� is
L�y COMPANY TEL (340) 426-3082
i $ �� PLAJ4sD DETAILS
;�iJ-s
1')81'Lip-99 12:09 V910 230 0384 STANDARI) TOOL 001
T11t _
_.► TOOLS AND EQUIPMENT Co.
' 4810 CLOVER RD, GREENSBORO, NC 27405
INSTALLATION & MAINTENANCE
MANUAL
r
"l-N!"'ODUSTRIAL PAINT
A
f
WA
LL
.t
Y
J 1•,
C
qi
Thoroughly Read Before Installing Your New Booth
For questions or problems related to your new spray booth, call our
n Customer Service Department at i-800--451-2425, Please have the
ID number available when you call.
f
1
NOTE; State and local codes vary. All paint p spray booths,
exhaust ducting, light fixtures, electrical motors and
1' switches, and etc., should be installed to conform
with all applicable cedes for location of ins
t
fiallation, k
f
t�,. •'ir• •.,ku. ';, • • STANDCO.
� € � ': :� • .
ARD 7QOLS '& EQUIPMENT CO
.•'}� .�}{� rk:. _ ,.. t'r
DUSTRIAL FAINT WALL
111N EX
yet xl._,<.Y.,• j .:! COri#E .. [ .� .
.. F j }• f.
10, Pr'otectiort Notification
fi r, •.:..•,x llction & Precautions
•�4�'^ :Y i } to- 1��"•Y
¢oathiiPl�cement
'Fools;&assembly dints '
,Jkssernbl�, Astructions .
aj
�.w.I, .r meµ ,. . lac sr�ai.1w L :j :: }•
j " sembiy Sequence Drawing
y.. ;•. 7 _
`7 ASserhbly Sequence >~=
Details
i
st
' S��S• i ,
�s� .I •.�%�r. '.�. .`.. � � �, .� � fi 1 .
0$/10/99 12:10 $910 230 0384 STANDARD TOOL 0Q s
44
, :^
.if Ai sl. rr
PLEASE � •. � .�, :.
L READ' CAREFULLY t.
. y,. i s 'l��tlo?la
1 , , F Fire Codes require a fire protection system to be installed in a paint spray area, For more refer to Chapter#7
p of the NFPA-33 Standard for Spray A f
pplication.
SFJJI TOOLS &E UIPMEIIT
Q CO. does not supply fire r
< ecommend pp y protection systems due to th=01
f.vns of skate and local codes. We r that the Purchaser contact a X licensed Fire- !
S !slet'provzder in the area where this equipment is to:be installed. Should the Purchaser have further
=.q Cs s and/or requires additional assistance in prgcurin-STANg this equipment, please feel froe to contact t
z
l✓S &EQIJIPMEN3`CU, Purchaser may also want to contact the city..or caun?y
gi3vemment offices and/or Fire Marshal in the local area for applicable codes and regulations.
n {j•
:7... L;Vv
13
irk Y��. `�;::. '- [ ;� •' . .�t
Y. •C� '. J..
r
J
>. INDUSTRIAL PAINT WALL
L. D"' ODUCTION
Pa;xtt
,Spray Booths equipped with filters are used to confine and limit the escape spray,of s vapor, 1
Y� por,and ,
s residue, and safely collect or direct them to an exhaust system. Paint Spray Booths are available in a
variety of sizes(width, depth and height)and man different specific type depends on the t
�) y types. The s cific
amount and kind of material to be sprayed and the method of application.
You have.purchased a Dry Type Spray Paint Wall designed for intermittent t� or limited paint spraying in
locations where air filtration is of priority to the surrounding environment. This Paint Wall provides your
personnel with a Workstation, if properly constructed and maintained,will meet this objective.
Ile-Paint Wall panel sections are manufactured from IS GA galvanized steel and shipped tivith necessary
hardware and components for easy construction. A Paint Wail package consist of materials and
components that meet requirements of the Underwriters Laboratories,National Board of Fire
Underwriters,National Fire Protection Association(NFPA 33), and NFPA's National Electric Cole. If
constructed and maintained properly,this equipment meets OSHA requirements as well as most ow the `
:... Codes,regulations and requirements of local and state fire, health and environmental agencies, It is the i
responsibility of the user to ensure that this equipment is installed and maintained in accordance with '
current local regulations.
r :i
E
°-lI. PRECAUTIONS
As per NFPA 33 there are precautions that should be observed when operating spray booths equipped
with dry orverspray collection filters. s
" i -.
1 1•- .
A. Precautions pertaining to materials and filters are as follows:
1. Filters should not be used when applying materials known to be highly susceptible to
• r.
spontaneous heating or spontaneous i0tion. ;
2. •.When replacing filters, only noncombustible type of materials should be used for sufiports=
• and holders. {
f.•i
3. Filters should not be alternately used for different types of coating materials if the
combinations of materials might result in spontaneous heating or ignition. i
4.;..
4. The same Paint Wall shal I not be alternately used for different s of coating materials if r
type g s:
the combination of the Materials is conducive to spontaneous ignition, unless all deposits of
the first-used coating material are removed from the walls and exhaust ducts prior to --
spraying witb the second coating. a
2 s �.
6
B. I r r
S
Genera operating'n pr
ecautions ecatrt ons are as follows:
p SP
0 ows:
r
, 1.
I. `Do not erect and/or operate this spraying equipment near open flames, spark-producing
equipment or other hazardous operations. Open flames, spark-producing equipment of
other hazardous operations should be adequately partitioned from the spray area at a
distance that is in compliance with local and state codes and regulations.
2. Spray area to be kept free of the accumulation of combustible residue deposits. To
i
> facilitate the cleaning overspray and impede corrosive action of the wail surfaces, one of
several available commercial booth coatings should be applied to the interior of the booth.
10
>i Due to potential fire hazards, the use of grease and paper are not recommended.
3. The exhaust fan filter system of the Paint Wall is designed to provide adequate airflow to ;.
meet national standard. It is necessary that maintenance procedures be established to
re P P Y lace overs ra collector filters before excessive restriction to airflow occurs.
Periodically checking the draft gauge is recommended as an indicator for replacing;filters.
Therefore it is essential to ensure that the draft gauge is installed properly and maintained
as per the manufacturers instructions.
f _
I. ASSEMBLY INSTRUCTIONS } `
Asper NFPA", here area few guidelines to aid in erecting this Paint Wall. It is advisable that a copy of
" the latest NFPA 33 Standard be acquired prior to erecting your Paint Wall, The address is National Fire
Protection Association, 1 Batterymarch Park, P.O. Box 9101, Quincy,M.A.02269-9101. To order, call I-
800-344-3555.
A. Booth Placement
1. Select an area to erect your Paint Wall having substantial floor and ceiling clearances. .
Remove all obstructions that may interfere with the exhaust fan and ducting. Depending,
4 on the constniction materials of the building that is to house this Paint Wall,the three
enclo:ted sides should have at least 3 feet or more of clearance from nearest wall or
partition. This clear space should be kept free of any storage or combustible construction.
1 S
2• For closed-top,open-front Paint Wall, having clearance of 10 foot horizontally out from
opening and 3 foot vertically, should satisfy most fire and electrical codes and standards.
It is owners' responsibility to check with local planning and development agencies to
confirm all local and state codes and standards.
F
- i
3. Floor surface of work area inside Paint Wall must be of noncornbustible material_
4. After the floor space has been determined and meets all fire and safety criteria,use a chalk .
line and layout the outer perimeter of Paint Wall, J.
' ' f
08/10/99 12:18 '$910 230 0384 STANDARD TOOL `VJU.c.4__r
f:
f .•
i'
B. Tools and Assembly Hints
. .
r y 1 - �•,
1. Recommended tools include: chalk line, 3/8" screw gun, extension cord,minimum, of ,
"C" clamps, level,rubber hammer,drill and 3f 16"masonry bit(to install Tapcons),
caulking gun,and two 8 ft. ladders.
k
2. Begin the erection at the outside corner of the exhaust plenum wall with panels#I and# .
3. Panels to be assembled by fastening the flange joints(exterior) using Tek screws. ipace'
Tek screws approximately 8 to 12 inches apart. 'Use care in not stripping out screv(s whr. {{
assembling; '
' includes isometric drawings showing the faint Wall assembled(see page 6) an' pan jl
y Note: This packet u�c des g o `� � . s
iA breakdown with its relationship to the adjoining panels (see page 7). Each panel is identified by numbed
and corresponds to the Item No. listed on the Industrial Paint Wall Assembly Sequence page(see page 8). !
On page 9 are the details that are referred to in the Direction of Assembly section of the Paint Wall
Assembly Sequence on page 8. Parts List on page 10 provides a listing of materials and hardware-that
makes up a unit and also serves as the packing list. ,j[LbLF[F
A. Assembly Instruction
1. Uncr'ate all components and stack panels of the same size together. As indicated oi,r pare
8 (Industrial Paint Wall Assembly Sequence), sire and description identify each panel,
Check inventory of all components prior to starting.
7
2. Before starting, thoroughly review the drawings and instructions. Each component {
indicated on the drawing(page 7)corresponds to the Item No listed on Industrial Paint
Wall Assembly Sequence(page 8). These two pages will guide you through the
assembling of the Paint Wall.
3. Start the assembling by connecting Item No's. 1 &2 (Exhaust Plenum Walls) as shown in
Detail II on page 9. This will be the right rear corner of the Paint Wall. Note,it is very
important to stay on the chalk outline during the assembly process.
4. Space Tek Screws approximately 8-- 12 inches apart.
1
i 5. Seal a!1 panel joints with caulk(provided)after the Paint Wall has been completely
i erected. Tighten all bolts and secure the booth to the floor. Seal all seams from the
interior of the Paint Wall. s
1 6. Mount the exhaust fan and motor. Ensure that there are not obstructions inside the;fan
unit. After the fan motor has been properly wired,check fan rotation as indicated by the l
l -
label on the unit.
4
7. Install exhaust ducting. Where more than 25 feet of ducting is required,the static,pressure
i is increased so that air flow may be hindered when using the standard exhaust unit '
recommended for this Paint Wall. Where a ducting arrangement of an unusual nature .
j employed or where two or more elbows are used,a similar condition may exist.
Therefore, if either of tlkese situations arise, contact your local distributor or the
1 manufacturer for correct recommendations_ ,. .,
n 8. STANDARD TOOLS &EQUIPMENT CO. does not provide an electrical
P package with .t
the unit. It is suggested that the owner contact a licensed electrical contractor to provid
services to do all wiring,hardware and components necessary to make the unit operable
9.. Manometer(draft gauge)setting:
a) Calibrate the gauge with the exhaust fan running and new exhaust filters in place. Note { .
the heig
ht of the 'I ox column� in inches of water on the a( ) gauge, Mark this point;with a
piece of tape, t,
b) Take pieces of cardboard and partially cover the filter wall in a checkerboard fashion.to f' .
simulate clogged filters, Add sufficient pieces of cardboard until the surface velocity; t
1 drops to the minimum allowable 100 feet per minute using a velometer. Note tie
reading on the manometer and mark it with another piece of to This is the p� tape. point c.
(pressure measurement)at which to change out exhaust filters. Also the liquid in the,,
t
manometer should read approximately.75 in.w.c. difference which is another ixethod t'
1. .
to use as an indicator to change out exhaust filters.
c) Upon removal of all cardboard,the pressure should return to its original point ckn the
manometer marked with tape.
d The Paint Wail is now re
) ready for operation. �
T. IvlA3lvrTENANCE .
Tbe,fregcency of the following maintenance checks depends on the amount and kind of materials being
tsprayed. Linder all circumstances, however, these checks should be made at regular intervals to reduce
fire hazards,to maintain the efficiency of the Paint Wall,to prevent freshly painted objects from
becomip2 blemished and to impede rusting of the Paint Wall. {_
t 1. Daily or when overspray accumulates—remove overspray and coating from the;Paint' t
Wall interior, operator's floor area,baffles, fan and exhaust ducting. Use anon,
ferrous,non-sparking scraper to eliminate any possibilities of igniting combustible y l
material. To prevent'fue hazards do not allow overspray and piles of paint sweepings'
to accumulate in the Paint Wall area. t
2. When overspray accumulates—remove and clean the blade of the exhaust fan.
3, Clicuk brlt tension on exhaust fan periodically, Fan and motor bearings may wear
unnecessarily when belts are too tight. = l
• SpYL� aN-waaq�uaa.x9-`[Pa .�a�Q1�`r �• _
VVV L^AkdEl
MM junvd FLasnpul
E£
I£
zE
SE
8I S[ 4I iT OT 6 9
Li 91
SZ
EZ
ZZ
Z L
t 6 4 5 4
9Z
EI
ZiLZ
. •- s_ ..... ...... ... '.._...-._�.:.. - '- - -- •• "-:.. ...... . , .--:_. =�.: ..er.',. •.- 1;-r-'4r� -v�_fi;.�ti'...'.f::. .:+<.. rs*:,ta.,...:.Ca.v'%�,.-.,3::a'4.,t:J.:�_.- :+�.a-:-+_ :-"�•�-'=•.. -- �. -tom ,
�,.;:�_?:•�.�-;::2 R..•��-�.-..X�.�:i'7..---E.-;-.rn=2or.:.r...r�+er-...�.:.d.[. -r x�}:.--" � . . - -.
..... ......
r S. _ .. - - r... -��.i•�w h v».:Yc�,n-.a:..r�r�i.._..,..r:.v.v:,�.Y..a..'�i.....•. .w-.. ........
- r
Rail Assembly SequeneLs -"'. .�':».:: ,.:_ ___ r
o
rAD
.�'�`�-)3.^ic .�"'+..•1'f'34T!ir.. ;L'isl'i^3�+tCr.:+'7:-_`�,•'^v�f: cw •�'�;���:r`.' f' -
• � .v AQ_},'.`�.,�`'J�pna�.�:��.��_x.�. `..� .. .ra.._�:. -s;.- tea... - .. .. -
!M.a YYrrr-.' 4.+r.IY.+iL Y�. [LV[B�O.�^ Mw4`n.S+ .+i^h ... .. ;,,,.:. •.,. • •Y..^'S-; w.r-,f;_ ..�.`i.. ..-. - ... i
IZ" Exhaust P�enrym Wt►il Qaeriap and connect to ( - ick tnwaid} ,._
4 -108":--, _.,..._ srriooths
W :}
haustFlentsnrl n _ SeeBE`F:-Ufbr--LnnmctittZMR�+fiER,19 4,— �t `C1;it�B
3 4b"x lb9 1/Z" Exhaust Plenum Wall. Connect to#1
4 4t3"x 109-1R" Exhaust Plenum-Wall Connect to#3
5 40"x 109-1/2" Exhaust Plenum Wall Connect to#4
6 25-1/2"x 109-ur Exhaust Plenum Wall
Connect to#5,Overlap and connect to-#7
Exhaust Plenum Wa11 Connect to#6
8 2v x 94" Exhaust Filter Grid Square comer with and connect to 07&#l2(smooth side inward)
9 24"x 84" Exhaust Filter Grid Connect to 48 l
10 24" x 84" Exhaust Filter Grid Connect to#9
11 24" x 84" Exhaust Filter Grid Connect to#10
12 24"x 84" Front Exhaust Plenum Square corner with and connect to#7(smooth side outward)
13 24" x 84" Front Exhaust Plenum Square corner.with and connect to#2(smooth side,outward)
14 24"x 84" Exhaust Filter Grid Connect to#11
Is 24"x 84" Exhaust Filter.grid _ Connect to#14
16 1-1/2 s 1-1/Z x I 081PSupport:Tee tiv/JFoot Connect to#12 attd.inner.seam of:#9 8E#IO
17 I-1/2"x 1-l/2"x 108" Support Tee W/foot Connectto#13 and inner seam of#14&#I5.
18 24"x 84" Exhaust Filter Grid Connect to#18,square corner with and connect to#2
19 45"x 57" Top Exhaust Plenum Connect edge flush to#1 &03,to top of#2-
-
20 45"x 57" Top Exhaust Plenum w/fan opening Connect edge flush to#3,#4,to top of 412
21 45"x 57" Top Exhaust Plenum Connect edge flush to#5,.to top of VA#12
22 44" x 84" Side Wall Connect:to#2
23 44.' x 84 - -Side Wall Connect°too#22
-
24 44"x 84" Side Wall- Connect to#7 -
25 44"x 84" Side Wall Cbnecct to#24
26 1-1/2"x 1-1/2"x 88" Formed Hip Angie Connect to.#27(see DET.N)
27 34"x 88" Hi Panel, Connect to#22(see DET. III)and#13--(Temp.support required)
28 1-1/Z"x 1-112"x 89" Formed Hip Angle Connect to#29(see DET-.IV)
29 34"x 88" Hip Panel Connect to.#24 see DET.III and#12.- -.. ..
( _ ) (Temp:support required) -
30 44"x 120" Ceiling Panel with(2)Light Fixtures Connect to#26.&028(see DET.VI)and#12
31 1-1/2"x I-lt2'x 84" Door Jarn Angle,(with Gusset) Connect to#25
32 1-1 ''x I. m•34" . -Door Jain_Angie(with.Gtwet) ' Connect to°#29
33:: "1-1/2'"x 1-1 ,.x.84":
Door Jam tlr�gle(with(russet)
-1/Z..x 1x .. Door us
Jam Angle( th G we, set) Conte
Connect to:
ttect to.#27.
Connect to'936.
. . ' Pate. _ _ . . .. :. ''. Ceilui$ Conned to,426;#2$(set PET. IV).&030-
-
8 . .. •
. .. - +-„—�.----�a-+�'r;-•+..�T+.r- +?�ie!�s.-3?�...-stir--"`:_ =.�L .e.q-s,.x=3
• �� r.
MUSTRIAL PAINT WALL- PARTS LISTT.
� <'
OTY. FINISHED SIZE DE CRIPTION
s 2 25_1/2"x 109-112" Exhaust plenum wall E
2 44"x IW' Exhaust plenum wall .
3 40"x 100,1/?' Exhaust plenum wall ;
7 24"x 48" Exhaust filter grid k
2 24"x 48" Front exhaust Ienum :
2 1-1/2"x 1-11z"x 106-1/2" Suppor Tees with foot f. .
2 44"x 5T Top exhaust plenum
a 1 44"x 57"with fan opening To_p exhaust plenum ±
4 44"x 84 Side walls
-
2 1-1/2"x 1-112"x 88' Form hi an les :.
2 34'x Be' HIP Panels
1 44"x 120"will htfixture openings Ceiling panel
1 44"x 120" Ceiling panel
2 1-UT x 1-1/2"x 34" Door' m Angle withgusset)
2 1-1f2"x 1-1 PZ'x 84" Door-am Angle(with usset
i 1-1/2"x 1-1/2"x 120" Door header Angle '
t r,.
a
i
HQRDWQRiw
QTY. ITEM DESCRIPTION 4
2 47-3/4"x 23-1/2"x 1/4" Glass for light fixtures k
2 24-1)(48" ht fExtures
58 CT-1012 Exhaust filter g6ds
28 GA10 20"x 20" Exhaust filters f
1 7FS41 30"fan with 2 hp- Motor
500 14-:14 x 1"HWH TEK screws
4 5E079 coulking Tubes of caulking
f
1 2T650(Dwyer Mark 11 Model#25 Manometer a
25 1/4'x 1-1/4" {TH1412C Conmto screws a con}
1 Installation&Maintenance Manual
y, 10 y
j
AI
i it a`!r
Gtneti l Instruetions to-Assemble
Exhaust.Duckwork
'r %iihibloith Ezhaast ductwork
-` The ftillowirig is a suggested method to aid in assembling;tbe air exhaust ductwork sections
atigie v using the angle rmF.: RIaceithhevertical�leguponalove surface. Take the pre-rolled 4&inch section of sheet metal andwrap stth :rl.:.,.
d
around ftewertical,leg(outer surface)ofthe.angle ring. If is suggested that a utility tie down(ratchet type)be.use4 to drag
. . .•ttieaML,'rnetal tightly to the vertical leg of angle ring, Once the sheet metal has been drawn to fit the outer diameter of the
: • angle-*n' g,.fasten the seam of the.pre-rolled sheet metal;about three inches above the vertical ring's edge,with.a Ta .
acre- 0See Detail I,step— I. At this point,remove the angle ring and'turn the pre-rolled sheet metal section end fpr end f .
Again, draw:the sheet metal tightly to the.ve'ttical leg and place a TEK screw-about three inches above the A rin$'s a ge. S ` r:•.
Detail L step-.2, After co this step;place TEK screws.about every sir to eight inches apart along the sea See "1
Detail Y,,�tep.--3 Seal seams with duct tape.
-dnce all sections are campl.eted, slip the angle ring back into one of the assembled duct sections and TEK screw to the 1 ;
angle riag.:'This section will then be fastened to the fan outlet. See Detain I',step-4.
' ;`'. 'txfaster.the ductwork sections together,insert the 4"wide Companion Band two inches into one end, clamp inapt
'EEK :See Detail H. ;
EL
- Aasem
Take ai'sok ion ofassembled duct(Detail I, Step-3),"C" clamp.the"Z', Brackets(Detail III)at 90 apart and Bush with
Lipper edge and:TEK screw into place(Detail M. Place the two End.Caps(D;!4 V) 180 degiees apart and:tnidway
between the"E'Brackets with the'flat side flush with the.edge and secure with two TEK screws(Detail VI). PlacgFlappr�r- r.
Sectionr(Detail.V.TI)on the flat surface of End Caps and TEK screw from underneath(Detail VM . Next," ") C clatttp one,r 1
: end of the 16 inch wide:pre-formed skirt to one of the"Z"brackets,form it around the remaining"Z"brackets withgthe
bottom:edge flush with.the bower edge of the"Z'Brackets. Draw the skirl tight.using a utility tie down(ratchet type)and
: secure:wrtir-7—Ea1C screws at each"Z"Bracket(Detail Di).
Cut opening in roof approximately %z"larger-in.diameter than the Roof Flange duct, Install Roof Flange and:thoroughly ; ^
caulk:(Detail':X),. Extend formed duct throughthe Roof Flange. Place a single TFK screw in
Rain Collar(Detail - as
: •show in.Dctai)XII. Slip the Rain Collar down over the extended duct,form a cone and secure both ends with TEK Acre
ws .. . .. . .:t...'
{Detail 7ttD: Slide the Rath Collar down to top of Roof Flange duct and caulk(Octal!3CIV).
e
Seepage 2 aiad 3'for Detailxand Pictures to aid in assembling and installation of..Ductwork
R.
7 Ti i!
�'• A •�,`
- -_ ..:1" :ou u�5� STANDARD TOOL
Q 008
S
o
xr ;• 3 ,``'_' STEP'- 2 :
STEP - 3 �,' 4 :.:
�' iRMING Duerr,, LF STEP SING; A:�- ,
. y� w 1,�}7,{�r ING
Lip.:F.. 1' STEP
! •$'.i. �ii..• t Aw ��`I SILL'
f:. DETAIL••: . ' .�
.,� i :k
.. . GtEI' .
1' p �r
��• �,£� s-..:.e _ ' .. . . It
(2) END CAP FL
.. '!•M� J
,k �1_APPeR SUPPORTS
END CAP
_... II DETAIL DETAIL VIT
IV DETAIL V DERAIL VI F
Ski(
FLAPPEI? 26, Vide
i CAULK
r •,a y .,: .;.,..,.•, ROOF FLANEE � a
DETAI
DE
L IX .• TAIL X °
;- ------ DE:TAIL r'
f CAILK
�•: x.I�ETAIL =IL .. 4 :�: �•a�:
GENERAL. INSTRUCTIONS. . ..
0 s;
° ASSEMBLE EXHAUST •
FAR DUCT NGJ . w .
' �.U.CTW�RK
INSTALLA
: ', :. : .
4870 Ctover Rd., Greensboro ,NC 4D5
DETIL . 1'I•' Phone
DETAIL ''XIV Phone 366972477 Fes' eDs7- i�$' . ':'-
�.
: - �t
!s Ir
401 ) • .flue >, .` F�'`,�'�,,y, r•,,.,J..•i'•' t I .1 �-t•'. ^�: �,.
All
' , .�. �f3 a yy ,�l.it.;�i<���+ �r ' !' f k• `.� .. •• •sa7.ti .t� a
J.
Z_t
'� :.r t 4 w.�yy � w w y �,._ls•• '� .� i S,•. _,�..:fr f ':*s
i
� i`v S t f is � ., Yi t ,.-,s • � } ,d..
1 t ••'-
VP
I 'i;�i ��!�`,�:,.i as is t t L4)t� „ ���:. 'b + �k 1:�-�� •1
P re-Engineered--90 -Fire Suppression Systems Report
SERVICE COMPANY DATE OF SERVICE ME A.M. P.M.
Z -L8 r
/ z / :O0 X
ANNUAL SEMI-ANNUAL RECHARGE INSTALLATION RENOVATION
PIONEER '`
LOCATION OF SYSTEM CYLINDERS UL 300
FIRE9SECURITY INC . Le / S,�e � �` 300 �
EAST OLYMPIA WA 98540 []YES WNO
P O B O X 5 9 7 MANUFACTURER MODEL NUMBER WET DRCHEMICAL 360 -491 -8141
PC
� [[ CYLINDER SIZE MASTER CYLINDER SIZE SLAVE CYLINDER SIZE SLAVE
� 7" Z�1_ �I SO L,C3 SO LQ Z S <i
<
`T� `l (l FUSE LINKS 360'F FUSE LINKS 450'F. FUSE LINKS 500'F OTHER
CUSTOMER 3 _ /6 S o
Name a*C-r_ee,1 abl`�E f5
L L FUELS/HUT-0FF ELECTRIC GAS SIZE
Address A 6 7 l SL+e�6C)'I /qa T1 I/UCI, X
1 1 SERIAL NUMBER LAST HYDRO TEST DATE LAST RECHARGE DATE
City e +oo State � ZIP �5ey I R C/
MANUFACTURER'S MANUAL REFERENCE
Telephone J,0_ 14 2-6-cis U Store No.
PAGE NUMBER: DRAWING NUMBER: DATE
Owner or Manager A-I C h
COOKING APPLIANCE LOCATIONS: LEFT TO RIGHT
1 a ►,,, -4- Qov�
130o+ y
4Nap{aliafl 1. , - properly covered w/correct nozzles \� 20. Replaced fuse links
2. Duct and plenum covered w/correct nozzles 21. Check travel of cable nuts/S-hooks
3. Check positioning of all nozzles. 22. Piping&conduit securely bracketed y
4. System installed in accordance w/MFG UL listing Y 23. Proper separation between fryers&flame
5. Hood/duct penetrations sealed w/weld or UL device 24. Proper clearance-flame to filters AIA
6. Check if seals intact, evidence of tampering �T- 25. Exhaust fan in operating order y _
7. If system has been discharged, report same 2e. All filters in place
8. Pressure gauge in proper range(If gauged) 27. Fuel shut-off in on position `,�`
9. Check cartridge weight(If applicable) � 28. Manual&remote set/seals in place V
10. Hydrostatic test date 29. Replace systems covers y
11. 6 year maintenance date 30. System operational&seals in place V_
12. Inspect cylinder and mount V 31. Slave system operational y _
13. Operate system from terminal link Y 32. Clean cylinder&mount k/
14. Test for proper operation from remote Y 33. Fan warning sign on hood
15. Check operation of micro switch y 34. Personnel instructed in manual operation of system P P Y
16. Check operation of gas valve 35. Proper hand portable extinguishers Y
17. Clean nozzles 36. Portable extinguishers properly serviced y
18. Proper nozzle covers in place _ 37. Service&Certification tag on system 4__
19. Check fuse links and clean F /V NOTE DISCREPANICES OR DEFICIENCIES BELOW k
COMMENTS: Uf- S�/51 �✓`'1 �y ��/ee� �� VC�/C��P�j�
On this date, this pre-engineered fire suppression system was inspected and operationally tested in accordance with the fire
suppression system requirements of NFPA17 or 17A, 96 and the manufacturer's manual with the results indicated above.
SERVICE TECHNIC PERMIT NO. DATE: TIME: AM PM CUSTOMER'S AUTHORIZED AGENT
The above s e technician certifies that the system was personally inspected and found conditions to be as indicated on this report.
AUTHORITY HAVING JU191SDICTION