HomeMy WebLinkAboutMIS99-0784 Dry Chemical - MIS Permit / Conditions - 12/30/1999 MASON COUNTY
Mason County Bldg, III 426 W. Cedar
P.O. Box 186 Shelton, Washington 98584
M 1 SCE L L A N E O U S P E I T FOR INSPECTIONS CALL 427-9670
MIS99-0784 PARCEL :42O17240!&D—M PLAT : DIV : BILK : LOT :
JOB ADDRESS : 6651 W SHELTON MATLOCK RD SHELTON
APPLICANT : KIRK PETERSEN 426-3082
OWNER : KIRK PETERSEN 426-3082
LEGAL : TN 1 OF SE NN
PROJECT DESCRIPTION :
DRY CHEMICAL SUPPRESSION SYSTEM FOR SPRAY BOOTH
PROJECT LOCATION :
SIX MILES DOWN SHELTON MATLOCK RD FROM HWY 101 OVERPASS . BUILD SITE AND EXISTING SHOP ON LEFT .
PROJECT NOTES :
TYPE AMOUNT BY DATE RECEIPT
WETC $ 100 .00 KS 12/30/ 99 2056
Z 3 o —yq
TOTAL : 100 .00 OWN R OR AGENT DATE
NIS_PRNT, rev; 04101192 COMPLIANCE TO ATTACHED CONDITIONS IS
REQUIRED
MASON COUNTY
Mason County Bldg, III 426 W. Cedar
P.O. Box 186 Shelton, Washington 98584
PERM I T" CONED I T 1 ONS
Case No . : MIS99-0784
For : KIRK PETERSEN
Page : 1
1 ) 1 . TRIP TEST REQUIRED .
2 . P OVIDE NON A-RATED 4013C DRY CHEMICAL FIRE EXTINGUISHER LOCATED NEAR THE MANUAL PULL .
X
I
b
V
HAL
4
MASON COUNTY FIRE�A�j R
ft
Mason County Bldg.III 426 W.Ced �-
P.O.Box 186 Shelton,Washington 9UL ECOpy
(360)427-9670 N
CODE ENFORCEMENT FIRE INSPECTIONS FIRE INVESTIG N PUBLIC EDUCATION
PERMIT NO.
l
m�s99.o��f
MASON COUNTY FIRE PROTECTION SYSTEM
PERMIT APPLICATION
PLEASE NOTE:This application must be completed and accompanied by a minimum of three (3) copies of
plans,specifications, and applicable calculations per Mason County Fire Protection Standards, and
submitted to the office of the Mason County Fire Marshal. This is not a permit and failure to submit all
necessary information Will cause a delay and/or rejection of your submittal. When a permit has been
issued,you will be notified.
PLEASE PRINT
OWNERj<I.a4_Vr,rr a&crj PHONE: �/Z(o `3uS2- FIRE DISTRICT
SITE ADDRESS: MgLawC MITY S14 rb J STATE D' ZI gam`
MAILING ADDRESS: GK 3 TgL CITY STATE ZIP
LIEN/TITLE HOLDER: ?marred"
ADDRESS: As /t40,1 L CITY STATE ZIP
CONTRACTOR 11:�kj i ci' T
ADDRESS:
✓��ytG[.r;�-� pCITY OL�ihP�/} STATE ZIPSo
CONTRACTOR PHONE# CONTRACTOR REG# &-V 1 a=q- ?4`/yLK
PARCEL# &40 _ LEGAL DESCRIPTION: _
?RR cif l+z or s carr y Pc,K- tk 171 <, F A 3 w-r r,tt o r -r-t c- N vv cZ u xAr lc(t, o C
.S CCvrf o.J 1-7/ TO ur-$S-41 P 7.00 IV, b✓,
BLDG. SQ. FT. (EXISTING/PROPOSED)lST FLq%;, / 2ND / 3RD /
USE OF BUILDING L jA 6dW&-j�►,.jr S?RAY
DESCRIPTION OF WORK: SPRINKLER: WET DRY STANDPIPE: WET DRY
AUTOMATIC FIRE ALARM HOOD & DUCT DRY CHEMICAL_X�—
WET CHEMICAL HALON NEW SYSTEM MODIFICATION FlKE VVVAP
MONITORING STN PHONE
I
YOUR SUBMITTAL MUST INCLUDE:
1. DIMENSIONS, SCALE, NORTH ARROW
2. FLOOR PLAN AND CROSS SECTIONAL ELEVATION
3. ALL CONCEALED SPACES (LABELED COMBUSTIBLE AND NON-COMBUSTIBLE)
4. CUT SHEETS OR REFERENCES FOR ALL NEW DEVICES
5. LOCATION/DESCRIPTION OF ANY EXISTING DEVICES
6. BATTERY CALCULATIONS FOR FIRE ALARM SYSTEMS
7. RISER/WIRING DIAGRAM FOR FIRE ALARM SYSTEMS
8. HYDRAULIC CALCULATIONS FOR SPRINKLER SYSTEMS
PLEASE NOTE: WORK MAY PROCEED ONLY IN ACCORDANCE WITH A VALID FIRE PROTECTION
SYSTEM PERMIT ISSUED BY THE MASON COUNTY FIRE MARSHAL. A VALID PERMIT AND AN
APPROVED SET OF PLANS MUST BE ON THE JOB SITE DURING CONSTRUCTION AND MUST REMAIN
THERE UNTIL A FINAL INSPECTION IS DONE BY THE MASON COUNTY FIRE MARSHAL. FAILURE TO
OBTAIN A VALID PERMIT PRIOR TO WORKING ON A FIRE PROTECTION SYSTEM AND/OR FAILURE TO
PROVIDE THESE PLANS AND PERMIT FOR THE MASON COUNTY FIRE MARSHAL MAY RESULT IN A
CITATION AND FINE.
OWNER'S AFFIDAVIT
I certify that I am exempt from the requiremer}t�of the Contractor's Registration Law RCW 18.27, and am
aware of the Mason County ordinance requirementt for which this permit is issued and that all work will be done
in conformance therewith. No changes will be nja ithout first obtaining approval from the Mason County
Fire Marshal.
i
OWNER: / DATE: I`!. 4� `
CONTRACTOR'S AFFIDAVIT
I certify that I am a currently registered contractor in the State of Washington and I am aware of the ordinance
requirements regulating the work for which the permit is issued and all work done will be in conformance
therewith. No changes will be made without first obtaining approval from the Mason County Fire Marshal.
BY: DATE:
.`.- .•-m-:.-..Y,>nc;.it•xe y�,r..Y,�: .,s+•:x;r.t�.rE':-...'.. .,r..r .v.'�t ri�i �rM<- 5 .•wt�4p5-aY:"'�.r:•ir.wyx'kw-rrn,v.*-,tiL'r�y0r _ _ _-
.. - - - .. _.. .. =1.ro._,,,r�7?4,n„4,M.i•-fit•
a• tn
,,.
,
k
"A• ..-sftit}Mmrw�., w�a+w.rti--�Y+iw,-a'-:t.N,�vr•Ir.W�anAw�.tea,'..,.vf.., - _ ... .. ._... ... -
�{.�.T.Wran..n{.r 'S N.•a,v,w sWr:a..�:It'.'i'.�n�n.�,�..,......J.-.,...w+ .Y..,�Mr�.vfn.y4Y/./v..i. ��Ntw , a.�Fi+.
.. ..a .__ ..�..a .a._. t..-.�....__....rr��-_.b.•ri:uw.,�.�u--..r.a...r.•v.�a.a..�.,..:,r.w�...•....wru,.��..a�.�..b..�.-.
FAN WITH Mum f lli'm YOOEI{3C412 �.
7UBEAVAL 30' FAN. 2HP s MAlSE MOTOR
(UL APPROVED)
ctTa: t,,aoa o.25, Sp
EXHAUST FILTER: 98'SQ
14.
S
�Ay
H
A �•
A
E+
va _
w
A
N
z
a
co .- :-
n
N
0 14' I11SiDE WIDTH
INDUSTRIAL ''PAINT' WYALL
N IPA- 10,0 a
a 7Ws and E t j CO
�. 4�10 Clover Rd., Greensboro,A}C ! C 2-17743085
Phone -697 7177 F 97
Phone 800-45 -
�4� -AX BQO- 7-2543
-. .a..a .. .:`..�. -.-:4,•: 17 _ _ �..•.- -ray- .,rn.._.. _ _
:
FILE COPY AdO3 3111
SCOPE OF WORK `
This is in reference to the design, installation, operation, testing and maintenance of pre-
engineered, dry chemical fire extinguishing systems that discharge from fixed nozzles and
piping by means of expellant gas, where applied in connection with hazardous storage
facilities, spray paint booths, industrial or commercial applications to be protected as per
both national and local codes and standards.
All operating devices designed, located, installed, shall be protected so that they are not to
be subjected to mechanical, environmental, or other conditions that could render it
inoperable or cause inadvertent operation of the system.
Where two or more hazards may be simultaneous involved in the fire by reason of
proximity. The hazard shall be protected by individual systems installed to operate
simultaneously, or by a single system designed to protect all hazards that may be
simultaneously involved. Any hazard that will allow fire propagation from one area to
another shall constitute a single fire hazard.
All systems must have both automatic and manual methods of activation.
Automatic detection and system activation may consist of either electrical or fuse link type
devices. Pipe and fittings will be of non-combustible materials having physical and
chemical characteristics compatible with the dry chemical powder. Dry chemical
containers and expellant gas assemblies shall be installed and located as to the accessibility
for inspection, maintenance and charging. All fuel source shut down may consist of either
electrical micro switch, pressure switch, mechanical gas valve or electrical solenoid gas
valve.
In case, Knight Fire Protection isn't supplying the device or material, Knight Fire
Protection requires it be supplied and/ or installed by a licensed contractor, all materials
shall be in accordance with the manufacturers listed installation and maintenance manual,
and meet all codes and standards pertaining to the integrity, function and operation of the
system designed and installed by Knight Fire Protection.
Materials supplied by an outside source other than Knight Fire Protection have no
warranties nor will Knight Fire Protection assume any liabilities stemming from their
installation.
,
A. Clarifications:
1. Its the owner responsibility to provide a UL listed paint spray booth and have
approved by the authority having jurisdiction.
2. The booth, listed dampers, ducts and baffles devices shall be designed,
constructed and installed to meet NFPA- 33, NFPA - 96 and local codes and
standards.
3. The booth will be installed and approved by the local building department or
Fire Marshal depending on authority having jurisdiction prior to the fire system
installation.
4. The extinguishing system, if provided, will be connected to the alarm system in
accordance with the requirements of NFPA- 72 National Fire Alarm code and
local standards, so that the activation of the extinguishing system will sound
the alarm as well as provide the function of the extinguishing system.
5. The spray booth and its installation is sufficient to support the installation of
the fire suppression system.
6. All work to be performed during normal business hours unless agreed to by
Knight Fire Protection.
7. The work area is to be accessible at all times during the system installation.
8. Any added time or travel due to construction, electrical work, gas piping,
and/or any re-scheduling will be in addition to the proposed bid.
9. Changes in the booth design and construction or fire protection criteria after
acceptance of this proposal will be reflected in an increase or decrease in the
form of a contract change order.
B. Exclusions:
1. Installation and connecting of all electrical devices, alarm system, and fan shut-
down unless contracted to do so.
s '
■ OPEN FACE
PAINT SPRAY BOOTH #`yrom
PROTECTION ii
Chem
A tLIC0INTERNATIONAL LTD.COMPANY
MONARCHTM INDUSTRIAL
FIRE SUPPRESSION SYSTEM
TECHNICAL MANUAL
• COMPONENTS
• DESIGN
• INSTALLATION
• MAINTENANCE
Manual No. PC98201
Chapter 1 —General
Page 1-1
CHAPTER I
General Information
INTRODUCTION
Pyro-Chem Open Face Paint Spray Booth automatic dry chemical fire suppression system is of
the pre-engineered type as defined by the NFPA Standard for Dry Chemical Extinguishing
Systems, NFPA-17. The extinguishing units described in this manual are intended to be
installed, inspected, and maintained in accordance with NFPA-17. Limitations detailed in this
manual have been established through extensive testing by Underwriters Laboratories, Inc.
Installation and maintenance of the system must conform to the limitations detailed in this
manual and be performed by an Authorized Pyro-Chem dealer.
The Pyro-Chem Open Face Paint Booth System utilizes a monoammonium phosphate based dry
chemical agent (specifically designed to suppress carbonaceous solid, liquid, gas or electrical
fires). The system provides mechanical or electrical automatic actuation and can be manually
actuated through a remote mechanical pull station. Upon actuation, the system discharges a
pre-determined amount of agent to the hazard area.
The shutdown of fuel and power to the hazard area is required upon system actuation. Exhaust
fan(s) in the ventilation system must be shut off during system discharge to allow the proper
concentration of agent to build up in the hazard area.
The Pyro-Chem Open Face Paint Booth System is designed to accommodate a mandatory
factory pre-set time delay. This time delay is required based on the UL 1254 compliance testing.
TEMPERATURE LIMITATIONS
The operating temperature range of the Pyro-Chem Open Face Paint Booth System is 32 °F
(0 °C) minimum to 120 °F (49 °C) maximum.
UL LISTING
The Pyro-Chem Open Face Paint Booth Industrial Fire Suppression System has been tested to
the UL Standard for Pre-Engineered Dry Chemical Extinguishing_System Units. UL1254 (Revised
Sept. 29, 1998), and Listed by Underwriters Laboratories, Inc.
ULEX 3437 CEx732
September 29, 1998
Chapter 2—Components
Page 2-1
s '
CHAPTER II
COMPONENTS
CYLINDERS & VALVE
Pyro-Chem Open Face Paint Spray Booth automatic dry The valve shown in Figure 2-2 is a pressure sealed, poppet
chemical systems are supplied in 15 pound, 25 pound, type valve. It is on all cylinders and also the PAC-10 and the
35 pound, 50 pound, and 70 pound capacity cylinders. They PAC-200 cylinders. The valve discharge port is 3/4" NPT.
are the Models PCI-15ABC, PCI-25sABC, PCI-35ABC,
PCI-50sABC, and PCI-70ABC. Each cylinder must be sepa-
rately piped to its own nozzles. All models are charged with
dry nitrogen to 350 psi @ 701 F. These systems are for
indoor hazard protection only.
All are rated to protect "A", °B", and "C" Class Hazards.
The dimensions of the cylinders and valve assemblies are
shown in Figure 2-1. The cylinder is manufactured, tested,
and marked in accordance with DOT specification 46350.
F1
MOUNTING
BRACKET
MODEL NO. A B C D WEIGHT USED
C PCI-15ABC 6.00 21.75 27.50 19.00 30lbs. MB-15
B PCI-25sABC 8.00 24.75 30.50 22.00 58lbs. MB-15
D PCI-35ABC 10.00 30.00 35.75 27.75 71 lbs. MB-1
PC]-50sABC 10.00 30.00 35.75 27.75 86lbs. MB-1
PCI-70ABC 12.00 34.75 40.5 32.5 130lbs. MB-1
ALL DIMENSIONS IN INCHES
Figure 2-1 Cylinder and Valve Assemblies
ITEM PART NO. DESCRIPTION
1 VALVE BODY
9 5 2 490-020870 DRY VALVE CAP & STEM
3 ASSY
4 1 3 385-020002 CONICAL SPRING
li 4 975-320261 RETAINING WASHER
5 733-020024 E-RING
6 732-020025 PRESSURE GAUGE
7 240-002026 HIGH TEMPERATURE
RELIEF PLUG
2 8 325-020029 VALVE BODY O-RING
$ 9 741-020805 PISTON
10 325-020636 PISTON O-RING
Figure 2-2 Valve Cross Section
M28s 2Pc
ULEX 3437 CEx732
September 29, 1998
Chapter 2-Components
Page 2-3
s
MODEL ECH -
ELECTRIC CONTROL HEAD O
The Model ECH electric control head is an electrically oper-
ated control head which can be connected to the
PCI-15/25s/35/50s/70 cylinder valve. This control head will
support an electric thermal detection system, a remote °
mechanical pull station (Model RPS-M), and a mechanical or 0
electric gas shutoff valve. It will not support a fusible link ° 0
detection system. A miniature electric switch (Model
MS-DPDT) is included. The Model ECH control head is
available in both 120 VAC (Model ECH-120) and 24 VDC
(Model ECH-24). It is equipped with a local manual control
handle that allows for mechanical system actuation. Figure 2-7. Model MB-P2 - Control Head
Operation of the local manual control requires removing the Mounting Bracket.
pull pin and rotating the handle clockwise. The Model ECH 0028<6PC
control head can actuate a maximum of three (3) cylinders.
See Figure 2-6. PNEUMATIC ACTUATING
a CYLINDERS
Py o O 1. Model PAC-10.
0 Clhem
iRED _
The Model PAC-10 is a pneumatic actuating cylinder that
0REL-FFE O can actuate a maximum of ten (10) agent cylinders simulta-
JR"GIIISM"G SYSfEw
ModN ECH neously. The Model PAC-10 includes a DOT 413350 cylinder
ConimlH°d pressurized with dry nitrogen to 350 PSIG @ 70' F., a brass
valve with pressure gauge, and a wall mounting bracket. A
m - ® Model MCH, NMCH or ECH control head must be purchased
----_ separately and connected to the PAC-10 to open the valve.
Figure 2-6. Electric Control Head. See Figure 2-8.
002844P'
MODEL ECH
CONTROLHEAD
MODEL NMCH - MECHANICAL CON- (SOLD SEPARATELY)
TROL HEAD
The Model NMCH Mechanical Control Head is a fully
mechanical control head which can be connected to the PCI- z R_. 3/4" DISCHARGE
15/25s/35/50s/70 cylinder valve. This control head will sup- -__ - PORT
port a fusible link detection system, a remote mechanical
pull station (Model RPS-M), and a mechanical or electric
shut-off valve. A miniature electrical switch (Model MS-SPDT 20.25
or MS-DPDT) can be ordered separately and field installed.
There is no local manual actuation for the Model NMCH. 14.50
The Model NMCH control head can actuate a maximum of 12.25
three (3) cylinders. The Model NMCH can be used as a
direct replacement for the Model MCH.
MODEL MB-P2 - CONTROL HEAD 4.00
MOUNTING BRACKET Figure 2.8. Model PAC-10 Pneumatic Actuating Cylinder.
02847PC
The Model MB-P2 mounting bracket must be used to mount
the Model MCH, NMCH or ECH control head if the control
head is not mounted directly on a cylinder valve. See Figure
2-7.
ULEX 3437 CEx732
September 29, 1998
Chapter 2—Components
Page 2-5
DETECTION EQUIPMENT 3. Model FLH-1.
The Model FLH-1 fusible link hanger is an accessory
1. Model FLK-1. designed to simplify the installation of fusible links in the
fusible link line. It can be used with the Model FLK-1/1A
The Model FLK-1 fusible link kit includes a 10" steel bracket, fusible link kit (kits must be ordered separately). The
two (2) 1/2" EMT connectors, four (4) cable crimps, and two Fusible Link Hanger makes it possible to install fusible links
(2) "S" hooks. Fusible links must be ordered separately. without cutting and crimping loops in the fusible link line for
See Figure 2-10. each link. They are available in packages of 25 (FLH-25)
only. See Figure 2-11.
2. Model FLK-1 A.
The Model FLK-1 A fusible link kit includes an 8" steel brack-
et, two (2) 1/2" EMT connectors, four (4) cable crimps, and
two (2) "S" hooks. Fusible links must be ordered separately.
LINK DETECTOR BRACKET
TERMINAL LINK
SHOOK
1/2"EMT
CONNECTOR
3164"OR 1/16"STAINLESS STEEL CABLE
FUSIBLE LINK CABLE CRIMP
SERIES LINK
Figure 2-10. Model FLK-1 Fusible Link
002849PC
FUSIBLE LINK KIT
(SOLD SEPARATELY)
FUSIBLE LINK
(SOLD SEPARATELY)
FLH-1
FUSIBLE LINK
HANGER
Figure 2-11. Model FLH-1 Fusible Link Hanger
G0285OPC
ULEX 3437 CEx732
September 29, 1998
Chapter 2-Components
Page 2-7
GAS SHUTOFF VALVES 2. Electric Gas Shutoff Valve.
A gas shutoff valve is required on all systems used to pro-
tect a as fueled appliance to stop
g pp p gas flow in the event of
system actuation. A UL Listed electric gas valve can be
A gas shutoff valve is required on all systems used to pro- used with either the Model MCH, NMCH or ECH control
tect a gas fueled appliance to stop gas flow in the event of head. The valves are rated for natural and LP gas. Valves
system actuation. A mechanical gas valve can be used with are available in 120 VAC. Electric gas valves are available
either the Model MCH, NMCH or ECH control head. It is in the following sizes:
connected to the system control head by stainless steel
cable. This cable is enclosed in 1/2" EMT with a corner pul- Maximum
ley at each change in direction. The valves are rated for Valve Operating
natural and LP gas (see Figure 2-14). Mechanical gas Model No. Size Pressure
valves are available in the following sizes:
EGVSO-75 3/4" 50 psi
Maximum EGVSO-100 1" 25 psi
Valve Operating EGVSO-125 1-1/4" 25 psi
Model No. Size Pressure EGVSO-150 1-1/2" 25 psi
GV-75 3/4" 5 psi EGVSO-200 2" 25 psi
GV-100 1" 5 psi EGVSO-250 2-1/2" 25 psi
GV-125 1-1/4" 5 psi EGVSO-300 3" 25 psi
GV-150 1-1/2" 5 psi Note: A UL Listed manual reset relay is required when using
GV-200 2" 5 psi an electric gas valve. The Pyro-Chem Model SM-120 sole-
GVSO-250 2-1/2" 5 psi noid monitor may be used for this purpose.
GVSO-300 3" 5 psi
CORNER PULLEYS
1. Model MCP-1.
A corner pulley is used whenever a change in stainless steel
0 o cable direction is required. The Model MCP-1 corner pulley
Pyro Chem is equipped with a set screw fitting for connection to 1/2"
GAS VALVE SHUT-OFF EMT. See Figure 2-15.
1.925—-�
o O
O
Figure 2-15. Model MCP-1 Corner Pulley.
002855PC
Figure 2-14. GV-Series Mechanical Gas Valve.
002853PC
ULEX 3437 CEx732
September 29, 1998
Chapter 2—Components
Page 2-9
s
ELECTRICAL SWITCHES MODEL SM-120/24 SOLENOID
MONITOR
1. Model MS-SPDT.
The Model SM-120/24 solenoid monitor is used in conjunc-
The Model MS-SPDT is a miniature electrical switch which tion with the Model ECH control head to supervise the actu-
can be field mounted in the Model MCH, NMCH, or ECH ation and detection circuits. In the event of a problem in the
control head. When used with the Model MCH or NMCH circuit, a light on the monitor goes out. The Model SM-120 is
control head, it provides one set of NO/NC dry contacts. It is used with the Model ECH-120 control head. The Model
intended for use with electric power shutoff devices (dealer SM-24 is used with the Model ECH-24 control head. Two
supplied), electric gas valves, alarms, bells, lights, contac- sets of NO/NC dry contacts are provided. The unit mounts
tors, and other electrical devices designed to shut off or turn directly to a three gang wall outlet box. The Model SM-120
on upon system actuation. The switch is rated for 20 amps acts as a reset relay when used with an electric gas valve.
@ 125/250 VAC, 1/2 hp @ 125 VAC, and 1 hp @ 250 VAC. Electric gas valve wiring instructions are provided in the
See Figure 2-19. installation section of this manual. See Figure 2-21.
Pyre-Chem Solenoid Monitor
e It I
rt«.�t uc»r urcac:ur r+c>awu
!RISH 1C fESE*
f
Figure 2-19. Model MS-SPDT Miniature Switch.
002858PC
2. Model MS-DPDT. 0 0
The Model MS-DPDT is a miniature electrical switch which
can be field mounted in the Model MCH or NMCH control
head and is included in the Model ECH control head. When
used with the Model MCH or NMCH control head, it provides
two sets of NO/NC dry contacts. When used with the Model 0 0 0
ECH control head, it provides one set of NO/NC dry con-
tacts. It is intended for use with electric power shutoff Figure 2-21. Model SM-24/120 Solenoid Monitor.
devices (dealer supplied), electric gas valves, alarms, bells, 00286OPC
lights, contactors, and other electrical devices designed to
shut off or turn on upon system actuation. The switch is PIPE & FITTINGS
rated for 20 amps @ 125/250 VAC, 1/2 hp @ 125 VAC, and
1 hp @ 250 VAC. See Figure 2-20. Pipe and fittings must be furnished by the installer.
Schedule 40 black, galvanized, chrome plated, or stainless
steel pipe must be used. Standard weight malleable, galva-
nized, chrome plated, or stainless steel fittings must also be
6 r used.
Figure 2-20. Model MS-DPDT Miniature Switch.
002859PC
ULEX 3437 CEx732
September 29, 1998