HomeMy WebLinkAboutFire Alarm Control Panel - FIR Letters / Memos - 12/17/2014 ;V
SMITH FIRE SYSTEMS
1 106 54T"AVENUE EAST, TACO MA, WA 98424
RECEIVED
DEC 17 2014
426 W. CEDAR ST.
STONE AGE GARDENS
50 W. WESTFIELD CT, BLDG A
SHELTON, WA 98584
PARCEL# 420022490070
SFSM PROJECT# FA141 12
OVERVIEW
THE SCOPE OF THIS PROJECT IS TO INSTALL A FIRE ALARM CONTROL PANEL,
NOTIFICATION AND INITATING DEVICES FOR TENANT IMPROVEMENT.
CONTENTS
I. SIEMENS (FCM901-U3) FIRE ALARM CONTROL PANEL
2. SIEMENS (ZR-MC-W/ZH-MC-CW/ZR-MC-CW) HORN/STROBE
3. SIEMENS (AS-75-R-WP) WEATHER PROOF HORN/STROBE
4. SIEMENS (OP921) SMOKE DETECTOR
5. SIEMENS (H1921) HEAT DETECTOR
6. SIEMENS (HMS-S) MANUAL PULL STATION
7. WERKER(WKA 12-7F) BATTERY
Data Sheet
Cerberus PRO Fire Safety
50-Point Addressable Fire Alarm Control Panel
Model FC901
ARCHITECT AND ENGINEER SPECIFICATIONS
• An addressable fire alarm control panel(FACP)
comprised of the following three(3)system
components:
• Main board(Model FCM901-U3)
• 170-Watt power supply(Model FP2011-U1)
• System enclosure(Model FH901-U3/R3)
• System features:
• Supports 50 addressable devices on one(1)'Class A', •
a.
or one(1)—two(2)'Class B'circuits , t
• Includes one(1)'Class A',or two(2)'Class B'
notification appliance circuits(NACs)
• Built-in digital alarm communication transmitter
(DACT)
• Built-in RS-485 connection for remote annunciators
• Resettable and non-resettable 24VDC auxiliary
power • Alphanumeric keypad
• Optional connectivity to a leased-line/city-tie • for manual configuration
module . WL 864 9ch Edition Listed;
• Off-normal warning message prior to reset
• Fast and easy set-up with custom-configuration tool FM,CSFM &NYC Fire Department Approved
Product Overview Main Board
Model FC901 is an addressable FACP that The Model FCM901-U3 main board provides system
provides a cost-effective solution for simple fire- display and control,as well as connections for
alarm system applications. system field wiring,via removable terminal blocks.
Small and compact in design, Model FC901 is The 3.5-inch (8.9 centimeters) by 1.5"(3.8
ideal for small fire-protection applications using centimeters) liquid-crystal display(LCD) screen
less than 50 addressable devices: shows all system messages and event status. Each
• retail outlets/strip malls • doctors'offices event may have a custom message up to 28
• dry cleaner shops restaurants,etc. characters that describes the event's location.
With its built-in DACT and two(2) NACs, Model The backlit LCD screen illuminates on any system
FC901 is powerful enough to economically event or manual key press. New,'unacknowledged'
meet the needs of these applications. Each 50- events are indicated by a flashing exclamation point
point FACP is FM (43010); FDNY(*6104)and ('I'). Once'acknowledged,'the exclamation point
CSFM (117165-0067:0259)Approved. changes to a check mark(V'). A system-status line
Specifications shows the quantity of events presently active.
The Model FC901 FACP consists of a main board The main board supports system-status light-
(Model FCM901-U3);a 170-Watt power supply emitting diodes(LEDs), based upon the following
(Model FP2011-U1),and a Model FH901-U3 1 conditions of Model FC901:
R3 system enclosure. The programming Power
software for Model FC901 is held in flash rm Trouble
• Trouubb
le
electrically erasable programmable read-only Supervisory
memory(EEPROM). Ground Fault
CerberuSTM PRO 9813
Fire Safety&Security Products FACP for simple-size buildings
Answers for infrastructure SIEMENS
Specifications — (continued)
There are also LEDs to indicate when audible circuits Model FC901 can be configured using the
are'active'or'silenced.' The main board supports four configuration tool or manually from the
(4)system-control buttons, including: Acknowledge; alphanumeric keypad on the main board. An auto-
Alarm Silence; Unsilence, and Reset. configuration feature creates a basic system
The system offers an off-normal warning feature, configuration of all connected devices to accelerate
alerting users when active devices are not ready for initial system commissioning.
reset. These active devices may include manual
stations that have not been reset;smoke detectors with 170-Watt Power Supply
smoke remaining in the optical chamber,etc. The Model FCM901-U3 main board also supports
Additionally, the main board supports an alphanumeric connection to the system power supply. The 170-
keypad, as well as navigation keys,which are used for Watt power supply(Model FP2011-U1) incorporates
scrolling maintenance functions and system a 4.OA, non-resettable slow-blow fuse on the
configuration. primary input, and includes a built-in AC-line filter
for surge and noise suppression. Model FP2011-U1
The main board supports connection for up to 50 mounts in a standard Siemens—Fire Safety
addressable devices,via one(1)'Class A',or one(1)to enclosure,and there are no serviceable Siemens—
two (2)'Class B'circuits. The loop supports all C-NET Fire Safety parts to be maintained.
devices, including the Cerberus PRO Fire Safety and
Model'H'-series devices. The main board also supports
one(1)'Class A'or two (2)'Class B'NACs. 50-Point Addressable System Enclosure
Each NAC supports a maximum 2.5 Amps—with 2.5 The Model FH901-U3 I R3 enclosure for the 50-point
Amps, max. allowed between the NACs. Each NAC addressable fire system, Model FC901, supports all
can be set to a synchronized strobe, for horn-strobe system modules. The enclosure also supports 12AH
devices, or for audible devices. Audible devices can batteries.
be set for: Note: For systems requiring larger than 12AH batteries,
• 'STEADY' use a OJL Listed battery box.
• 'ANSI Temporal 3' The Model FH901-U3 I R3 enclosure for the 50-point
• 'March Time 30 1 60 1 120 Codes' panel is comprised of a dual-mounting setup that
The main board supports four(4)'Form C' relays for allows the main board to be partially mounted in a
Alarm, Trouble, Supervisory and user-programmable lower-to-upper position. When temporarily installed
events. Each relay is rated at 2 Amps at 30VDC in the lower position, technicians are allowed more
maximum, resistive. The main board supports two space to install field wiring at the time of system set-
(2) auxiliary 24VDC connections. Upon system reset, up. When field-wiring installation is complete, the
one (1) connection interrupts the power for five main board shall be moved to the upper position for
seconds for use with (4) four-wire conventional standard mounting prior to applying power to the
detectors. Each auxiliary-power output is 24VDC, system.
nominal—rated at 0.75 Amps. Additionally,the enclosure supports an optional
The main board contains a built-in DACT(Model battery bracket(Model FHA901-U1) that can be used
FCA2015-U1),which provides communication between to secure batteries up to 12AH. Model FHA901-U1 is
Model FC901 and with the central or remote required to comply with seismic certification,
monitoring station. The built-in DACT supports two(2) pursuant to ASC I SEI 7-05, Section 13.2.2.
separate programmable accounts,as well as two(2) A flush-mount trim kit(Model FHA902-Ul 1 R1) is
connections to the public-switched telephone network. also available for use when flush mounting Model
The connections support RJ31 X male connectors. FH901-U3 I R3.
The main board contains a battery-charging circuit, Optional Accessories
providing connection to lead-acid batteries rated at The Model FC901 FACP has the capability of
24VDC, nominal. The main board can charge up to operating an optional leased-line, city-tie module
18 AH batteries. (Model FC12020-U1) that provides a local-energy
The main board contains a universal serial bus(USB) output for municipal call-box connection. The
connector that supports connection for system leased-line, city-tie module is installed on the back of
configuration and module firmware upload, via the the main board of the Model FC901 FACP, and all
custom-configuration tool. field wiring is connected to the main board.
SIEMENS Industry, Inc. CerberusTM PRO
Building Technologies Division
Specifications — (continued) Temperature and Humidity Range
Model FC901 contains a built-in RS-485 connection Model FC901 is mUL 864 91h Edition Listed for
on the main board, thus eliminating the need for an indoor dry locations within a temperature range of
additional communication module. The fire-system 120+1-3°F (49+I-2°C) to 32+I-3°F (0+I-2°C) and a
displays (FSD901-U3 I R3) are remote LED 1 LCD units relative humidity of 93+I-2%at a temperature of
that show the existing status of the Model FC901 FACP. 90+1-3°F(32+1-2°C).
The Model FSD901-U3 I R3 optional display supports
the following LEDs for system-status conditions: Related Documentation
• Power
• Alarm
• Trouble 170-Watt power supply 9806
• Supervisory Leased-Line 1 city-tie module 9810
• Ground-Fault 50-Point Remote Annunciator 9817
There are also LEDs to indicate when audible circuits
are'active'or'silenced.' The main board supports four Details for Ordering
(4) system-control buttons, including: Acknowledge;
Alarm Silence; Unsilence, and Reset. e e �� Description
umber Number
For Model FSD901-U3 I R3, a LED will illuminate for any cerberus PRO Main Board
given Alarm,Supervisory and Trouble Cerberus PRO- FCM901-U3 S54433 B101-A1 {for 50-point FACP}
system event. A 3.5-inch (8.9 centimeters) by 1.5" FP2011-Ul S54400-Z59-A1 170-Watt Power Supply
(3.8 centimeters) LCD screen will give details of the FH901-U3 S54433-B103-A3 System Enclosure,Black
event in alphanumeric form. The display screen can be {for 50-point FACP}
scrolled to reveal additional events. Optional remote- FH901-R3 554433-B103-A4 System Enclosure,Red
system-control capabilities are also available. {for 50-point FACP}
The dimensions (based upon connection to a one- Optional Accessories
height-unit enclosure)for Model FC901 are as follows:
Approximate size: 16.25"(41.3 cm.) [H];
18"(46 cm.) [W]; FHA901-Ul S54433-B107-A1 Battery Bracket
5"(41.3 cm.) [D] FHA902-Ul S54433-B106-A1 Flush-Mount Trim Kit,Black
The weight(without operating unit or batteries) is FHA902-RI S54433-Bl06-A2 Flush-Mount Trim Kit,Red
approximately 9 Lbs [4082 g]. F02020-U1 S54400-A57-A1 Leased-Line I City-Tie Module
FSD901-U3 S54433-C102-A1 System Display,Black
{for 50-point system}
FSD901-R3 S54433-C102-A2 System Display,Red
{for 50-point system}
SIEMENS Industry, Inc. CerberusTM PRO
Building Technologies Division
SIEMENS CerberusTM PRO NOTICE—The information contained in this data-sheet document is intended only as a summary,and
is subject to change without notice. The devices described here have specific instruction sheets that
cover various technical,limitation and liability information.
Siemens Industry, Inc.—Building Technologies Div. Copies of these instruction sheets and the General Product Warning and Limitations document,
8 Fernwood Road• Florham Park, NJ 07932 which also contains important information,are provided with the product and,are available from
7 the Manufacturer.
Tel:(973) 593-2600 • Fax: (908) 547-687
Information contained in these documents should be consulted before specifying or using the
Web:www.USA.Siemens.com/Cerberus-PRO product. For further information or assistance concerning particular problems contact the Manufacturer.
Building Technologies Division
February 2013—Supersedes sheet dated 1/13
(Rev.7)
SH—Fire Safety
[Printed in U.S.A j
SIEMENS Catalog Sheet
Fire Safety & Security Products
`08 Series Notification Appliances
ZH & ZR — Strobes, Horns, & Horn / Strobes Application: Indoor
ON
.
(ZR & 7>]11i
ZH Series ZR Series Mounting)
Product Overview
— Strobes can be synchronized using the Siemens DSC sync modules, FS-250 panel,
XLS panel, or PAD-3 power supply with built-in sync protocol
— Selectable Continuous Horn or Temporal (Code-3)Tones with 90 or 95 dBA selectable setting (ZH)
— Ceiling-mount models feature field-selectable Candela settings of 15130175195cd and 1 151177cd
— Wall-mount models feature field-selectable Candela settings of 1 5130/7 511 1 0cd and 135/185cd
— Base plate is protected by a disposable cover, and the appliances can quickly snap
onto the base after the walls are painted
— Strobes produce 1 flash per second
— "Special Applications" listed with Siemens panels
— EZ Mount Universal Mounting Plate (ZBB) — uses single plate for ceiling and wall mount installations
— EZ Mount design —with separate base plate — provides ability to pre-wire the base
and test the circuit wiring before the walls are covered
— ®UL Listed &®ULC Listed;
FM, CSFM & NYMEA Approved
— ADA 1 NFPA compliant
Specifications
• General
Audible/Visual notification appliances shall be listed for indoor use only
— Appliances shall be listed under OUL Standard 1971 (Standard for Safety Signaling Devices
for Hearing Impaired) and(PUL Standard 464 (Fire Protective Signaling)
— Appliances shall use a universal back plate, which shall allow mounting to a
single-gang, double-gang, 4-inch-square, 4"-octal, or a 3-112"-octal backbox
Two-wire appliance wiring shall be capable of directly connecting to the mounting back plate
— Continuity check shall occur for entire NAC circuit prior to attaching
any audible I visual-notification appliances
Dust cover shall fit and protect the mounting plate
— Dust cover shall be easily removed when the appliance is installed over the back plate
Removal of an appliance shall result in a trouble condition by the Fire Alarm Control Panel (FACP)
`08 Series Notification Appliances 2584
SIEMENS Industry, Inc.
Building Technologies Division
Specifications — (continued)
• Strobes
Strobe appliances shall produce a minimum flash rate of 60 flashes per minute
(1 flash per second) over the Regulated Input Voltage Range,and shall incorporate a
Xenon flashtube enclosed in a rugged Lexan® lens
Strobes shall be available with two or four field-selectable settings in one unit, and shall be
rated — per®UL 1971 —for up to:
• 15130/75/1 10cd for wall mounted
• 1351185cd for wall mounted
• 15130175195cd for ceiling mounted
• 1151177cd for ceiling mounted
Strobes shall operate over an extended temperature range of 320F to 120°F (0°C to 49°C), and be listed
for maximum humidity of 95% RH
Strobe inputs shall be polarized for compatibility with standard reverse-polarity supervision of circuit
wiring by a Fire Alarm Control Panel (FACP)
Audibles and Audible/Strobe Combinations
Horns and horn 1 strobes shall be listed for Indoor use under®UL Standard 464
Horns shall be able to produce continuous synchronized output or a
temporal code-3 synchronized output
Horns shall have at least 2 sound-level settings of 90 and 95 dBA
Synchronization Modules
The strobe portion, when synchronization is required, shall be compatible with
DSC sync modules, FS-250 panel, XLS panel, or PAD-3 power supply with built-in sync protocol
The strobes shall not drift out of synchronization at any time during operation
Audibles and strobes shall be able to synchronize on a 2-wire circuit with the capability
to silence the audible, if required
Strobes shall revert to a non-synchronized flash-rate, if the sync module or
Power Supply should fail to operate (i.e. —contacts remain closed)
— All notification appliances shall be listed for Special Applications:
■ Strobes are designed to flash at 1-flash-per-second minimum over their
"Regulated Input Voltage Range"
➢ Note: NFPA-72 specifies a flash rate of 1-to-2 flashes per second, and ADA Guidelines
specify a flash rate of 1-to-3 flashes per second
■ All candela ratings represent minimum-effective Strobe intensity, based on®UL Standard 1971
■ Series ZH Strobe products are listed under®UL Standards 1971 and 464 for indoor use
with a temperature range of 320F to 120OF (0°C to 49°C) and maximum humidity of 93% (± 2%)
■ Series ZH horns are listed under(&UL Standard 464 for audible signal appliances (Indoor use only)
SIEMENS Industry, Inc.
Building Technologies Division
Mounting Diagram
Ora 1.>!r� ttia 294� 4M
0
0
(Shown In Inches)
Mounting Options
lECURPO
sloe ommm rvr
MT 9CP" RrM
Fgae 3:botallitihn FWn4:Rmmvg(See sup 8 below)
1. Install mounting plate as stho m in figure 1 to a single-gag. Q trnportant:Device only has one moabg orientation.blatdh the
dale-gagL 4"square.4"od.-qpm or a 3 V octagon hackbor top of the base to the tarp of the device.
with the provided pan head sonars To rename dust cover. 7. ■it is desired to firl er secure the device to the base.then two
Place thhnb and index anger on top erlm of corer and pull of optional screws are pmvded To instal these screws punch out
cower- the screw holes located at the top and bottom of the device-
2. Connect field wiring per figures 2 and 1 8. To rernove the appliance,push a small tat-bladed screwdriver
3. Address vies bark into badrbox_ into the side cpemq The screwdriver rust dear the snap
4. PUmm dust cover over mounting plate to protect the terminals release openng by W to disengage the map. Do not pry off
while I—imhig ring mnfinuty check-- hoar$g win the screw drover.Apply pressure wah screw driver.
5- Ft mh IF dart cover before snapping or installing the appliance in in either side opening,as shorn in Fig 4 to release the
onto the mountrg plate per fig 3. housing.
Technical Data
ZH and Z"GMom
Rem,bmerrt dBA
per 0 UL464 ZH Horn Gwreot Draw
[ZHWC and ZH at 24V] t'AIn M 16-M Vows
1611V 24V 33.0V DC ligh• 0-044
Con6nious High 83 87 90 LOW 0.018
Hom Low T7 81 83 FwR Kl' o.G75
79 82 86 goer o-ohs
Coniinuous
March Tme� Low 72 76 79 Ali Code33 lam and kw�Tine Settings.
'Available in sync mode wdy
SIEMENS Industry, Inc.
Building Technologies Division
Technical Data - (continued)
®UL Listed Models and Ratings
(special1 ® Strove
[Per® {`c�UL1971] S526M] Horn Mounting Cad)
Models' M3UVRMS) (VDCNRMS)
ZR-MC 16.0-33.0 20.0-31.0 - Wal 1 5/301 75/1 1 0
ZR4-MC 16.0-33.0 20.0-31.0 - Wal 1351185
ZR-MG,C 16.0-33.0 20.0-31.0 - Ce&M ISr 75195
ZRa-MC-C 16.0-33.0 20.0-31.0 - CeftV 1151177
ZH-Kgc 16.0-33.0 20.0-31.0 X Wal 15/30rM110
ZH-HMC 16.0-33.0 20.0-31.0 X Wal 135/185
ZH-MCA 16.0-33.0 20.0-31.0 X Cei>Ig 15/30f75/95
ZH4-#AG-C 16.0-33.0 20.0-31.0 X Ceikg 11S1177
ZH 16.0-33.0 20.0-31.0 1 X I Wall or Ge&V - -
*Avad*1e in red and white
OUL Current Ratings (ZR Strobe Only)
Maximum RMS Current(AAFPS)
MC IFIII/C MCA FMAC-C
15cd 130cd I 75cd 111acd 135od 185ad 15cd 130cd I 75cd I 95cd 115cd 177cd
DC 16-33VDC 0.064 0.098 0-175 0233 0.318 0.445 0.069 0-111 0200 0264 0-318 0.445
FWR 16-33VRMS 0.108 0.164 0_M 0.368 A482 O 0.684 0.117 0-180 0297 0.398 0-482 0.684
0 UL Current Ratings ZH Horn/Strobe
Maximum RMS Currerd(AMPS)
Horn MC hiMC MC-C t•MC-C
Setting 15cd Wcd 75cd 110cd 135cd 185cd 15cd 30cd 75cd 95cd 115cd 177cd
' 0.078 0.113 0-195 0259 0.371 0.506 0.087 0.131 0222 0.292 0-371 0.506
DC 16-33VDC Lair►. 0.070 0.107 0-188 0246 0.324 0.455 0.075 0.121 0213 0.277 0-324 0-45
FWR 16-33VRAAS 00.141 0200 0-302 0.406 0-521 0.722 0-149 0216 0-331 0A36 0-521 022
069Low- 0-123 0-179 029 0.391 0-497 0.699 0.131 0.195 0319 0.421 0-497 7*Current Draw s the sarne for the C onlim ors Han;
Code 3 Han and Mardi Tine Settrgs
Details for Ordering - (Including Mounting Options & Agency Approvals)
Agency Approvals
Model Part Description Mounting UL ULC FM CSFM
Number Number Options*
ZH-R 500-636159 Z Horn: Red B,D,E,F X X X X
ZH-W 500-636160 Z Horn: White B,D,E,F X X X X
ZH-MC-R 500-636161 Z Horn: Multi Candela(Wall),Red B,D,E,F X X X X
ZH-MC-W 500-636162 Z Horn: Multi Candela(Wall),White B,D,E,F X X X X
ZH-HMC-R 500-636163 Z Horn: Hi Multi Candela(Wall),Red B,D,E,F X X X X
ZH-HMC-W 500-636164 Z Horn: Hi Multi Candela(Wall),White B,D,E,F X X X X
ZH-MC-CR 500-636165 Z Horn: Multi Candela(Ceiling),Red B,D,E,F X X X X
ZH-MC-CW 500-636166 Z Horn: Multi Candela(Ceiling),White B,D,E,F X X X X
ZH-HMC-CR 500-636167 Z Horn: Hi Multi Candela(Ceiling),Red B,D,E,F X X X X
ZH-HMC-CW 500-636168 Z Horn: Hi Multi Candela(Ceiling),White B,D,E,F X X X X
ZR-MC-R 500-636169 Z Strobe:Multi Candela(Wall),Red B,D,E,F X X X X
ZR-MC-W 500-636170 Z Strobe:Multi Candela(Wall),White B,D,E,F X X X X
ZR-HMC-R 500-636171 Z Strobe:Hi Multi-Candela(Wall),Red B,D,E,F X X X X
ZR-HMC-W 500-636172 Z Strobe:Hi Multi-Candela(Wall),White B,D,E,F X X X X
ZR-MC-CR 500-636173 Z Strobe:Multi Candela(Ceiling),Red B,D,E,F X X X X
ZR-MC-CW 500-636174 Z Strobe:Multi Candela(Ceiling),White B,D,E,F X X X X
ZR-HMC-CR 500-636175 Z Strobe:Hi Multi Candela(Ceiling),Red B,D,E,F X X X X
ZR-HMC-CW 500-636176 Z Strobe:Hi Multi Candela(Ceiling),White B,D,E,F X X X X
ZBB-R 500-636193 Accessory-(Includes base,dust cover,mounting screws and installation sheet)
ZBB-W 500-636194 Accessory-(Includes base,dust cover,mounting screws and installation sheet)
X =listed I approved *=Refer to catalog sheet#:2585 for detailed mounting options
Notice: This marketing catalog sheet is not intended to be used for system design or installation purposes.
For the most up-to-date information, refer to each product's installation instructions.
Fire Safety Fire Safety
8 Femwood Road 2 Kenview Boulevard
SIEMENS Industry, Inc. Florham Park,NJ 07932 Brampton,Ontario
Tel:(973)593-2600 Isle) L6T 5E4/Canada March 2010
Building Technologies Division shee[dated 12/09des
FAX:(908)547-6877 Printed in U.S.A. Tel:(905)799-9937 Sup- Re,,.2)
URL:www.SBT.Siemens.com/FIS FAX:(905)799-9858
SIEMENS g
Catalo Sheet
Fire Safety & Security Products
`08 Series Notification Appliances
AS / AH & AS —Audible Strobe Appliances and AH Audibles [Application: indoor/ Outdoor
r
AS-MC-CW AS-MC-R AH-W AH-R
Product Overview
— Fast installation with In 1 Out screw terminals using #12 to #18 AWG wires
— Synchronization can be accomplished using the Siemens DSC sync modules, FS-250 panel,
XLS panel, MXL panel, or PAD-3 power supply with built-in sync protocol
— 3 Selectable dBA settings of 90/95/99 dBA Anechoic in both tones
— Selectable Continuous Horn or Temporal (Code 3)
— Wall mounts are available with field-selectable Candela settings: 1 5130/75/1 1 0cd or 135/185cd
— Ceiling-mount models are available with field-selectable Candela settings: 15130175/95cd or
115/177cd (multi-Candela ceiling models)
— Weatherproof models are available for outdoor use
— -OUL Listed &®ULC Listed;
FM, CSFM & NYMEA Approved
— ADA 1 NFPA 1 UFC/ANSI compliant
Specifications
— Notification appliances shall be Siemens Series AS Audible Strobe appliances and Series AH Audible
appliances or approved equals
— Series AS Audible be listed for-OUL Standard 1971 (Emergency Devices for the Hearing-Impaired for
Indoor Fire Protection Service)
— Series AH Audible shall be®UL Listed under Standard 464(Fire Protective Signaling)
All inputs shall be compatible with standard reverse polarity supervision of circuit wiring
by the Fire Alarm Control Panel (FACP)
The audible portion of the appliance shall have a minimum of three(3) field-selectable settings for
dBA Anechoic levels, and shall have a choice of continuous or temporal (Code 3) audible outputs
Strobe portion of the appliance shall produce a flash rate of one(1)flash per second over the
Regulated Input Voltage Range, and shall incorporate a Xenon flashtube enclosed in a rugged
Lexan@ lens
`08 Series Notification Appliances 2578
SIEMENS Industry, Inc.
Building Technologies Division
Specifications - (continued)
— Series AS shall be of low-current design
— Strobe intensity, where Multi-Candela appliances are specified, shall have field-selectable settings,
and shall be rated per®UL Standard 1971 for:
■ 1 5130/75/1 1 0cd
■ 1351185cd
— The appliance, when synchronization is required, shall be compatible with Siemens' DSC Sync
Modules or Siemens PAD-3 Power Supplies with built-in Siemens Proprietary Sync Protocol
— The strobes shall not drift out of synchronization at any time during operation
— The strobes shall revert to a non-synchronized flash-rate, if the sync module or Power Supply
should fail to operate (i.e. —contacts remain closed)
— The appliance shall also be designed so that the audible signal may be silenced while maintaining
strobe activation when used with Siemens synchronization
— The Series AS Audible Strobe and Series AH Audible shall incorporate a Patented Universal
Mounting Plate that shall allow mounting to a single-gang,double-gang, 4-inch square, 100mm
European type backboxes, or the SHBBS Surface Backbox
— All notification appliances shall listed for Special Applications:
■ Strobes are designed to flash at 1-flash-per-second minimum over their"Regulated Input Voltage Range'
➢ Note: NFPA-72 specifies a flash rate of 1-to-2 flashes per second,and ADA Guidelines specify a flash rate
of 1-to-3 flashes per second
■ All Candela ratings represent minimum-effective Strobe intensity, based on®UL Standard 1971
Mounting Diagram
Series AS SeriesAH
480 480
1
4.80 4.80 4.80
(Shown In Inches) (Shown In Inches)
Mounting Options
B FLUSH WM*n n1-- D Rug,ORsuMACE NOMO HJG F Rug,OR suwACC NDuw*r- X summm mmmlYYGG
STD_ 4'Sa x 11-72- ppXX3LE-4r-%4G SH ERM
uNN62SAL ClaEP nXCMMOI!! SA� 1Cu .nSCL 37-5... I OffP sA
2i
ELWCOPEAN PLATE
6Aa
0
L4CXJN W
UHA/@ L
�� N
LKNUNTINGPLATE
� PLATE� G
n 0 kki I. ,O
b
SCREW SCREW SCREW SCREW
LV�a
4-SCREW SCREW L4 4 --A SCREW SCFOL
WORM OF OlQJCFM LIUMwr KNIMR 1f CCMDIlC,t7S t��ff CCNOL C1M U%="NLEMBER 1f CONDIJCT(=
AWA>s AVG.If A1GOW A1GO2 MGM ANGM A1Gs14 AMM AM = AIG4,i AMGs14 AAfGs12 MGM A AG AIGAM MG912
4 . . 4 4 4 4 4 . . . . . 4 4
SIEMENS Industry, Inc.
Building Technologies Division
Technical Data
OUL dRA Sound Output
Reverberant �
OUL Listed Ratings V�LEVEQ
[Per 19UL 464 a 10 Ft]
Operabng Voltage(Special Application) Strobe DeSCFOb°f1 i6AYDC 24.0VDC 33AVDC
Model* [Per®UL 1971/464] Candela 80 83 86
(VDCNRMS) (od) Coninuous Horn 85 88 91
AS-MC 16.0-33.0 88 91 93
`Avaiable in red and while Code 3 Hcm or Low 75 79 82
Mach Tone" Median 80 84 86
High 84 87 89
"Available in sync geode only
Notes: 1.Strobe will produce 1 flash per second over the Input Voltage range.
2.This strobelhorn model meets the required light distribution patterns defined in OJL 1971
3.This model is OUL Listed for indoor use with a temperature range of+32°F to+120°F(0°C to+49°C)and maximum
humidity of 93%+2%RH.The effect of shipping and storage temperatures shall not adversely affect the
performance of the appliance when it is stored in the original cartons and not subjected to misuse or abuse.
...........................................................................................................................................................................................................................
®UL/®ULC Listed Models&Ratings ®ULC CwTent Ratings
®Operating (for Model AH)
Voltage
®ULC Maidmurn Average Current
Model (Special Voltage RMS Currertt(AMPS) vol
ume (AKGIS)
AH Application) Range (LEVEL) 20.0 VDC 24.0 VDC 31.0 VDC
[Per®UL 464] Lo Med Hi Low .014 .017 _021
DC 16 33VDC 20-31 VDC 0.021 0.043 0.080 �m 020 025 030
FWR 16-33VRMS 2D-31VRMS 0.041 0.051 0.090 High .035 .050 _065
11
OUL/0ULC dBA Sound Output
Reverberant Anechoic dBA
DeSCFiptivoh'^e [Per ®UL 464 010 Ft] [Per®ULC-S525-99]
O1 (LEVEL) 16.0 VDC 24.0 VDC 33.0 VDC 20.0 VDC 24.0 VOC 31.0 VDC
Law 80 83 86 88 90 92
Con wogs Horn Medium 85 88 91 90 95 97
Kigh 88 91 93 92 97 99
Low 75 79 82 88 90 92
Code 3 Horn or Medium 80 84 86 90 95 97
Mach Time'• High 84 87 90 92 97 99
"Available in sync mode only
ULC Dkecdona/Characraisrics
3 dBA: 48 degrees left,41 degrees right
dBA 50 degrees left,58 degrees
Note: All models are®UL 1 OULC Listed for indoor use with a temperature range of+0°C to+49°C(+32°F to+120°F)and
maximum humidity of 93%.
SIEMENS Industry, Inc.
Building Technologies Division
Technical Data — (continued)
®UL Current Ratings (AMPS)
Maadmum RMS CureFd
with H dBA Sefting
15cd I 30cd I 75cd I 95cd
DC I If)-33VDC 0.101 0.147 0235 0.303
FM I 16-33VRMS 0.144 1 0.202 0.324 0.424
�UL Current Ratings (AMPS) SUL Current Ratings (AMPS)
Mauamum RMS Current MaWmum RMS Current
with Mod dBA Seffing with Law cOA Se"
15cd 30cd 75cd 95cd 15cd I 30cd I 75cd 95cd
DC 16-33VDC 0.0% 0.130 0213 0.285 �DG I&33VDC 0-0791 Q 120 0.210 0.279
FWR 16-33VRMS 0.132 0.185 0.312 0.414 FWR 16-33VRMS 0.122 0.180 0.308 1 0.409
Note: These notification appliances are OJL Listed as"Special Application".They are intended to be used only
with Siemens notification appliance circuits.
...........................................................................................................................................................................................................................
0UL Listed Ratings
OPerahng Voltage(Sped APPticahm) Strobe
Mom [Per(&UL 1971] Candela
( S) (Cd)
AS-HMC-C' 16A-33.0 115J177
•Available in red and white
®UL d8A Sound Output
Reverberard
Vak [Per ®UL 464 Q 10 Ft_]
(LEVEL) 16.0 VDC 24.0 VDC 33.0 VDC
Low 80 83 86
Cams Horn Medium 85 88 91
FSO 88 91 93
Code 3 Hama Law 75 79 82
Mwch Tur►e'• Medium 80 84 86
F p 84 87 90
••Available in sync mode
sY only
Notes: 1.Strobe will produce 1 flash per second over the Input Voltage range.
2.This strobe/horn model meets the required light distribution patterns defined in mUL 1971
3.This model is®UL Listed for indoor use with a temperature range of+32°F to+120°F (0°C to+49°C)and
maximum humidity of 93%+2%RH.The effect of shipping and storage temperatures shall not adversely
affect the performance of the appliance when it is stored in the original cartons and not subjected to
misuse or abuse.
SIEMENS Industry, Inc.
Building Technologies Division
Technical Data — (continued)
®UL Current Ratings (AMPS)
Maximum RMS Current
with K dBA Setting
135cd 185M
DC 16-33VDC 0.335 0.460
FWR 16 33VRMS 0.470 0.665
®UL Current Ratings (AMPS) SUL Current Ratings (AMPS)
Mammum RMS Current Mammum RMS Current
with Med dBA Setting with Low d13A Seting
135cd 185cd 135cd 185cd
DC 16-33VDC 0.340 0-465 DC 16-33VDC 0.335 0.470
F1NR 16-33VRMS 0.480 10-675 FWR 16-33VRMS 0.460 0 665
Details for Ordering — (Including Mounting Options & Agency Approvals)
Agency Approvals
Model Part Wall Ceiling Description Mounting UL ULC FM CSFM
Number Number Mount Mount Options*
AS-MC-R 500-636010 X — AS Horn: Multi-Candela, Red A,B,D,E,F,G,J,N,R,X X X X X
AS-MC-W 500-636011 X — AS Horn: Multi-Candela,White A,B,D,E,F,G,J,N,R,X X X X X
AS-HMC-R 500-636012 X — AS Horn: Hi Multi-Candela,Red A,B,D,E,F,G,J,N,R,X X X X X
AS-HMC-W 500-636013 X — AS Horn: Hi Multi-Candela,White A,B,D,E,F,G,J,N,R,X X X X X
AS-MC-CR 500-636006 — X AS Horn: Multi-Candela Ceiling,Red A,B,D,E,F,G,J,N,R,X X X X X
AS-MC-CW 500-636007 — X AS Horn: Multi-Candela Ceiling,White A,B,D,E,F,G,J,N,R,X X X X X
AS-HMC-CR 500-636008 — X AS Horn: Hi Multi-Candela Ceiling,Red A,B,D,E,F,G,J,N,R,X X X X X
AS-HMC-CW 500-636009 — X AS Horn: Hi Multi-Candela Ceiling,White A,B,D,E,F,G,J,N,R,X X X X X
AS-HMC-CR-WP 500-636181 — X AS Horn: Hi Multi-Candela Ceiling I X X X X
Weatherproof,Red
AS-HMC-CW-WP 500-636182 — X AS Horn: Hi Multi-Candela Ceiling I X X X X
Weatherproof,White
AS-HMC-R-WP 500-636183 X — AS Horn: Hi Multi-Candela Wall I X X X X
Weatherproof,Red
AS-HMC-W-WP 500-636184 X — AS Horn: Hi Multi-Candela Wall I X X X X
Weatherproof,White
AS-75-R-WP 500-636016 X — AS Horn: 75CD Weatherproof,Red I X X X X
AS-75-CR-WP 500-636015 — X AS Horn: 75CD Ceiling I X X X X
Weatherproof,Red
AH-R 500-636003 X X AH Horn,Red A,B,D,E,F,G,J,N,R,X X X X X
AH-W 500-636004 X X AH Horn,White A,B,D,E,F,G,J,N,R,X X X X X
AH-R-WP 500-6360051 X X AH Horn:Weatherproof,Red K X X X X
X =listed I approved *=Refer to catalog sheet#:2585 for detailed mounting options
Notice: This marketing catalog sheet is not intended to be used for system design or installation purposes.
For the most up-to-date information, refer to each product's installation instructions.
Fire Safety Fire Safety
8 Femwood Road 2 Kenview Boulevard
SIEMENS Industry, Inc. Florham Park,NJ 07932 Brampton,Ontario
March 2010
Building Technologies Division
Tel: 973)593-2600 (SillL6T 5E4 I Canada
9 FAX: 908 547-6877 Printed in U.S.A. Tel: 905 799-9937 Supersedes sheet dated uiov
( ) ( ) (Rev.2)
URL:www.SBT.Siemens.com/FIS FAX:(905)799-9858
Data Sheet
t Intelligent Detection Devices
Photoelectric Smoke Detector
Model OP921
ARCHITECT AND ENGINEER SPECIFICATIONS
• Compatible with Siemens Model 'H'-series devices on the same loop (with Cerberus PRO
fire-alarm control panels [FACPs] or FireFinder XLS FACPs)
• Compatible with Model 8720/ DPU (device programmer/loop tester)
• Utilizes advanced microprocessor-based signal processing
• Extended temperature and humidity operating range
• Each detector is self-testing: Oil
• Self monitored for sensitivity within VUL Listed limits
• Complete diagnostics performed every 10 seconds3
• Polarity insensitive utilizing SureWire'"'technology
• Compatible with Model DB-11—series mounting bases
• Tri-color detector-status LED with 360'viewing
• Field-selectable application sensitivity profiles •
• Remote sensitivity-measurement capability
• Utilizes advanced signal processing Automatic environment compensation
• Superior EMI / RFI immunity OUL268A Listed [for direct air-duct use],
• RoHS compliant 61JLC Listed; FM and CSFM Approved
Product Overview
The Photoelectric Smoke Detector(Model OP921)uses Model 87201 DPU eliminates the need for cumbersome,
state-of-the-art microcontroller circuitry and surface- unreliable mechanical programming methods,such as dials
mount technology for maximum reliability. Model or switches,and reduces installation and service costs by
OP921 incorporates an optical sensor using a light- electronically programming and testing the detector prior to
scattering detection principle. The device utilizes installation.
advanced software algorithms to analyze the signals, For proper operation of the field-device programmer/test
and provides highly stable and accurate smoke unit,the technician selects the accessory's program mode,
detection. and enters the desired address. In turn,Model 87201 DPU
Further,Model OP921 uses state-of-the-art automatically sets and verifies the address,as well as tests
microprocessor circuitry with error check;detector self- the detector. When in the'test'mode, Model 8720/DPU will
diagnostics,and supervision programs. perform a series of diagnostic tests without altering the
Field-Device Programmer/Test Unit address or other stored data,allowing technicians to
determine if the detector is operating properly.
Model OP921 is compatible with the Siemens field- Model 87201 DPU operates on AC power or rechargeable
device programmer 1 test unit(Model 87201 DPU),
which is a compact,portable, menu-driven accessory batteries,providing flexibility and convenience in
for electronically programming and testing detectors programming and testing equipment from practically any
easily and reliably. location.
CerberusT" PRO 9902
Fire Safety&Security Products Photoelectric Smoke Detector
Answers for infrastructure SIEMENS
Product Overview — (continued) Sensitivity Settings
Model 8720 I DPU operates on AC power or rechargeable Application Parameter Sets
batteries, providing flexibility and convenience in Model OP921 provides four(4) pre-programmed
programming and testing equipment from practically any sensitivity parameter sets that can be selected by the
location. FACP to match the expected application or
Model OP921 is a plug-in, two-wire and addressable environmental conditions:
photoelectric smoke detector. Model OP921 is • Sensitive
0Underwriters'Laboratories Listed [® • StandardUL268A Listed for . Robust
direct in-air duct usage]. •Air-duct
Each detector consists of a dust-resistant photoelectric Sensitive: This application parameter set is practically
chamber and microprocessor-based electronics with a suitable for areas where few misleading sources of false
low-profile plastic housing. Every Model OP921 fire alarm are present, and is appropriate where priority is
detector is shipped with a protective dust cover: given to detecting open fires as soon as possible(e.g.—
typically a clean application with controlled
environmental conditions.)
1
Standard: This application parameter set is practically
apt for normal office, hotel-lobby-type applications,
and is the default setting.
2 Robust: This application parameter set offers
improved resistance to false alarms in areas where
misleading sources, such as cigarette smoke or exhaust
fumes, may cause a nuisance alarm.
Air-Duct: This application parameter set is used when
1. Dust cover the detector is used a 4OUL268A(DI) compliant direct in-
2. Smoke detector air duct application without a duct housing.
Model OP921 does not require a field sensitivity test.
Operation Model OP921 is(UL Listed as a self-testing device and
Model OP921 is a wide-spectrum, photoelectric smoke complies with NFPA 72 as a self monitoring detector
detector incorporating an infrared light-emitting diode and control panel arrangement. This parameter set is
(IRLED), and infrared light sensing photodiode. Under also used when Model OP921 is used in air-duct
normal conditions, light transmitted by the LED is housings (Models FDBZ492 and FDBZ492 HR).
directed away from the photodiode and scattered The visible LED flashes green every 10 seconds to
through the smoke chamber in a controlled pattern. indicate communication with the FACP, and to notify
Model OP921 has passed its self-test. Should Model
The smoke chamber is designed to manage light OP921 sense a fault or failure within its system,the LED
dissipation and extraneous reflections from dust particles will flash amber, and the detector will transmit the data
or other non-smoke, airborne contaminants in such a
way as to maintain stable, consistent detector operation. t the FACP.
When smoke enters the detector chamber, light emitted quick visual inspection is sufficient to indicate the from the IRLED is scattered by the smoke particles, and i condition of Model OP921 at any time. If more detaileds information is required, a printed report can be
received by the photodiode: provided from the compatible FACP, indicating the
status and settings assigned to each individual detector.
When Model OP921 moves to Alarm mode,the detector
will flash red and continue flashing until the system is
reset at the FACP. At that same time, any user-defined,
system-alarm functions programmed into the system
O t'` are activated.
Model OP921 contains a tri-color LED indicator, capable
of flashing any one (1) of three (3) distinct colors:
green,yellow,or red. During each flash interval, the
1. Labyrinth microprocessor-based detector monitors the following:
2. Optical transmitter
3. Optical receiver
SIEMENS Industry, Inc. Cerberuslm PRO
Building Technologies Division
Operation — (continued)
•Smoke sensitivity is within the range Model OP921 can be applied within the maximum 30-
indicated on the nameplate label feet center spacing (900 sq. ft. areas), as referenced in
• Smoke in its sensing chamber NFPA 72. This application guideline is based on ideal
• Internal sensors and electronics are functional conditions—specifically, smooth ceiling surfaces,
Based on the monitoring results, the LED indicator minimal air movement, and no physical obstructions
flashes the following colors based on the following between potential fire sources and the actual detector.
conditions: Do not mount detectors in close proximity to
Flash ventilation or heating and air-conditioning outlets.
Flash Condition Interval Exposed joints or beamed ceilings may also affect safe
Color in seconds spacing limitations for detectors.
Normal supervisory operation. Should questions arise regarding detector placement,
reen*. Smoke sensitivity is within rated 10 observe NFPA 72 guidelines. Good fire-protection
limits. system engineering and common sense dictate how
Detector is in trouble and needs 4 and when fire detectors are installed and used.
Yellow: replacement. Contact your local Siemens—Fire Safety distributor or
R Alarm condition. 1 sales office whenever you need assistance applying
Model OP921 in unusual applications. Be sure to
No Flash: Detector is not powered. -- I follow NFPA guidelines and®UL Listed 1®ULC Listed
*LED can be turned OFF. installation instructions—included with every Siemens—
Please follow the corresponding description of the panel used. Fire Safety detector—and local codes as for all fire-
A quick,visual inspection is sufficient to indicate the condition of protection equipment.
the detector at any time. If more detailed information is required, Note: For Model OP921 compatibility to FireFinder'XLS,the XLS
a printed report can be provided from the respective Cerberus PRO FACP requires Model PMI-2(no firmware upgrade is required),
FACP that indicates the status and settings assigned to each or Model PMI(firmware Rev.9 or higher is required). The
Individual detector. detector's compatibility also requires both of following:
-Rev.9(or higher)ZEUS custom-configuration software
Installation - Rev.6(or higher)Device Loop Card(DLC)firmware
All Model OP921 detectors use a surface-mounting base, Technical Data
Model DB-11 or Model DB-11 E,which mounts on a 4-inch
octagonal,square or single-gang electrical box. The base Operating
utilizes screw-clamp contacts for electrical connections and Temperature +32'F (0°C) to 120°F (49°C)
self-wiping contacts for increased reliability. Range:
The Model DB-11 base can be used with the optional Model LK-11 Relative Humidity: 0—95%; non-condensing
detector locking kit,which contains 50 detector locks and an
installation tool to prevent unauthorized removal of the detector Air Pressure: No effect
head. Model DB-11 has decorative plugs to cover the outer-
mounting screw holes. Air Velocity: 0—4,000 ft. 1 min (0-20m I sec)
Model OP921 may be installed on the same initiating circuit Input Voltage Range: 16VDC—30VDC
with the Siemens Model'H'series detectors[when used with
the Cerberus PRO FACPs]— Alarm Current(max.): 410NA
• Model HFP-11
• Model'HMS!-series manual stations Standby Current(max.): 250pA, max. (average)
•Model'HTRI'-series interfaces Maximum Spacing: 30-foot centers(900 sq.ft.),
•Model HCP output-control devices per NFPA 72
• Model'HZM'-series of addressable, P
conventional zone modules Detector Weight: 0.317 lbs. (0.144 kg.)
Application Data
Installation of Model OP921 detectors requires a two-wire Mechanical Protection Guard:
circuit. In many retrofit cases,existing wiring may be used. ®UL Listed 1®ULC Listed
[with STI Guard Model STI-9604]
T-tapping'is permitted only for Style 4(Class B)wiring.
Model OP921 is polarity insensitive,which can greatly reduce
installation and debugging time.
SIEMENS Industry, Inc. CerberuSTM PRO
Building Technologies Division
Mounting Diagram Details for Ordering
Dimensions Model Part
N— .4.13" (10-5 cm.)
9 0*100, OP921 S54320-F4-A2 Photoelectric Smoke Detector
DB-11 500-094151 Detector Mounting Base
4
ca-seal DB-1 1 E 500-094151 E Detector Base{small}
caa� DB2-HR 554320-F12-A1 Relay Base
RL-HC 500-033230 Remote Alarm Indicator:
4"octagon-box mount, red
Remote Alarm Indicator:
RL HW 500 033310 single-gang box mount, red
Detector Compatibility Table FDBZ492 S54319-B22-A1 Addressable Air-Duct Housing
Data FDBZ492-HR S54319-B23-A1 Addressable Air-Duct
Model Sheet Description Detector with Relay
umber NUITibe LK 11 500 695350 Base Lockin Kit
— 6300 FireFindero XLS(system overview) In Canada, OIdeI:
DLC 6312 Device Loop Card Model Part
FC901 9813 50-point panel Number Number Description
FC922 9815 252-point system(networkable)
D13-11 C 500-095687 Detector Mounting Ba_c
FC924 9815 504-point system(networkable) for OU LC(Listed)
SIEMENS CerberusTM PRO NOTICE—The information contained in this data-sheet document is intended only as a summary,
and is subject to change without notice. The devices described here have specific instruction sheets
that cover various technical,limitation and liability information.
Siemens Industry, Inc.—Building Technologies Div. Copies of these instruction sheets and the General Product Warning and Limitations document,
8 Fernwood Road • Florham Park, NJ 07932 which also contains important information,are provided with the product and,are available
Tel: (973) 593-2600 • Fax: (908) 547-6877 from the Manufacturer.
Information contained in these documents should be consulted before specifying or using the
Web:www.USA.Siemens.com/Cerberus-PRO product. For further information or assistance concerning particular problems contact the Manufacturer.
Building Technologies Division
March 2013—supersedes sheet dated 2/2013
(Rev.2)
SII—Fire Safety
[Printed in U.S.A j
Intelligent Detection Devices
Thermal (Heat) Detector
Model HI921
ARCHITECT AND ENGINEER SPECIFICATIONS
• Provides seven (7)field-selectable settings in the 1350-1740F(57.20-78.9°F)temperature range
• Tri-color detector-status light-emitting diode(LED)with 360'viewing
• Compatible with Model DPU (device programmer/loop tester)
• Utilizes advanced microprocessor-based signal processing �q
• Provides a low-temperature warning at 40°F(4.4°C)
_44
• Each detector is self-testing:
• complete diagnostics performed every 10 seconds
• Polarity insensitive utilizing Sure WireT"'technology
Et
• Compatible with Model DB-11-series mounting bases ,
• Field programmable as rate-of-rise or fixed temperature
• Compatible with Siemens Model W-series devices on the "T
same loop(with Model FC9-series fire-alarm control panels)
• Superior EMI/RFI immunity
• SUL Listed and®ULC Listed;
• RoHS compliant CSFM Approved
Product Overview
The Intelligent Thermal(Heat)Detector(Model Additionally, Model H1921 can be configured to provide a
HI921)provides an advanced method of detection, low-temperature warning signal at 40°F(4.4'C). This
address programming and supervision—combined feature-along with a compatible FACP(either Model FC922
with sophisticated FACP communication. Model or Model FC924)-serves as prevention of water freezing in
HI921 uses a state-of-the-art thermistor, pipes for sprinkler systems,meeting NFPA 72.
microprocessor and advanced signal analysis, Model DPU
providing high reliability and accuracy.
Model H1921 is compatible with the Siemens field-device
Further, Model H1921 is a cost-effective,two-wire 1 programmer I test unit(Model DPU),which is a compact,
addressable thermal detector that provides a portable, menu-driven accessory for electronically
distinctive,advanced feature: field-selectable programming and testing detectors easily and reliably.
temperature settings specially tailored for application-
specific detection needs. Model DPU eliminates the need for cumbersome,unreliable
Model H1921 provides seven(7)field-selectable mechanical programming methods,such as dials or
temperature-range settings: 135°F(57°C)—174°F switches,and reduces installation and service costs by
(79°C)with fixed and rate-of-rise programmability.
electronically programming and testing the detector prior to
installation.
This variance provides the customer with maximum
flexibility to program the temperature settings to suit Each detector consists of a solid state,non-mechanical
multiple application needs and changing thermal sensor,and microprocessor-based electronics with a
environmental conditions. low-profile plastic housing. The Model H1921 thermal(heat)
detector is Underwriters'Laboratories(&UL)Listed.
CerberUST11 PRO 9901
Fire Safety&Security Products Thermal (Heat) Detector
Answers for infrastructure SIEMENS
Product Overview — (continued)
Each Model HI921 detector base also contains a provision for an A quick,visual inspection is sufficient to indicate the condition of
optional,concealed locking mechanism to prevent unauthorized the detector at any time. If more detailed information is
removal of the detector head(Model LK-11). required,a printed report can be provided from the Model FC9-
For proper operation of Model DPU,the technician selects the series FACPs indicating the status and settings assigned to each
accessory's program mode,and enters the desired address. In individual detector.
turn,Model DPU automatically sets and verifies the address,as Installation
well as tests the detector. When in the'test'mode,Model DPU will
perform a series of diagnostic tests without altering the address or All Model HI921 detectors use a surface-mounting base,Model
other stored data,allowing technicians to determine if the detector DB-11 or Model DB-11 E,which mounts on a 4-inch octagonal,
is operating properly. square or single-gang electrical box. The base utilizes screw-
Model DPU operates on AC power or rechargeable batteries, damp contacts for electrical connections and self-wiping
providing flexibility and convenience in programming and testing contacts for increased reliability.
equipment from practically any location. The Model DB-11 base can be used with the optional Model LK-
11 detector locking kit,which contains 50 detector locks and an
Operation installation tool to prevent unauthorized removal of the detector
Model HI921 also utilizes a modern,accurate and shock-resistant head. Model DB-11 has decorative plugs to cover the outer
thermistor to sense temperature changes: mounting screw holes.
Model H1921 may be installed on the same initiating circuit
with the Siemens Model'H'-series detectors[when used with
the Model FC9-series of FACPs]-
- Model HFP-11
•Model'HMS'-series manual stations
•Model'HTRI'-series interfaces
•Model HCP output-control devices
.- • Model'HZM'-series of addressable,
conventional zone modules
Thermister Application Data
Each Model H1921 detector provides seven(7)pre-programmed Installation of Model H1921 detectors requires a two-wire
parameter sets that can be selected bythe FACP. circuit. In many retrofit cases,existing wiring may be used.
Detector Supervision and Testing 7-tapping'is permitted only for Style 4(Class B)wiring.
Model HI921 is polarity insensitive,which can greatly
Model HI921,which is listed as a self-testing device,contains a tri- reduce installation and debugging time.
color light emitting diode(LED)indicator,capable of flashing any
one(1)of three(3)distinct colors: Green,Yellow,or Red. Model H1921 can be applied within the maximum 50-feet
During each flash interval,the microprocessor-based detector center spacing (Hine i sq. s areas),perondi This
monitors the following: application guideline is based on ideal conditions,
•Temperatures reaching programmed thresholds specifically,smooth ceiling surfaces, minimal air movement,
• Internal sensors and electronics are functional and no physical obstructions between potential fire sources
and the actual detector. Do not mount detectors in close
Based on the monitoring results,the LED indicator flashes the proximity to ventilation or heating and air conditioning
following colors based on the following conditions: outlets. Exposed joints or beamed ceilings may also affect
Flash safe spacing limitations for detectors.
Flash Condition Interval
Color Should questions arise regarding detector placement,
(in seconds) observe NFPA 72 guidelines. Good fire-protection system
Normal supervisory operation. engineering and common sense dictate how and when
Green*• Temperature has not reached 10 fire detectors are installed and used. Contact your local
programmed alarm thresholds Siemens—Fire Safety distributor or sales office whenever
or set points. you need assistance applying Model H1921 in unusual
Detector is in trouble and needs applications. Be sure to follow NFPA guidelines and$>UL
Yellow: 4 PP�
replacement. Listed 1®ULC Listed installation instructions—included
Red:AAlarm condition. 1 with every Siemens—Fire Safety detector—and local
No Flash: IDetector is not powered. —_ codes as for all fire-protection equipment.
*LED can be turned OFF.
Please follow the corresponding description of the panel used.
SIEMENS Industry, Inc. Cerberuslm PRO
Building Technologies Division
Specifications Technical Data
Model H1921 is a plug-in,(2)two-wire thermal(heat)detector, Operating
compatible with Model FC9-series FACPs. Each Model HI921 Temperature +32oF (0oQ to 100°F (38°C)
detector has microcomputer-chip technology and highly stable, Range: [with 135°F (57°C) alarm-
solid-state electronic circuitry. threshold setting]
The Model HI921 detector utilizes a modem,accurate and shock- Relative Humidity: 0-95%; non-condensing
resistant thermistor to sense temperature changes.
This electronic-sensing method virtually eliminates thermal lag Air Pressure: No effect
associated with mechanical temperature-sensing devices,and
provides almost instantaneous temperature status to the FACR Input Voltage Range: 16VDC-30VDC
Model H1921 provides seven(7)field-selectable,pre-programmed Alarm Current(max.): 410NA
temperature settings:
• Fixed 135'F(57'C) Standby Current(max.): 250pA, max. (average)
• Fixed 145'F(63'C)
• Fixed 155°F(68'C) Maximum Spacing: 50-foot centers(2,500 sq. ft.), per
• Fixed 165°F(74°C) NFPA 72 and OULC-5524
• Fixed 1747(79'C)
Thermal Rating:
•Rate-of-Rise:15oF I min.(8.3°C)at fixed 135oF(57oQ Model HI921 provides up to seven(7)field-selectable,pre-
•Rate-of-Rise:15oF 1 min.(8.3oQ at fixed 174°F(79°C)
programmed temperature settings:
Additionally,the Model H1921 detector has the following optional . Fixed 135°F(57°C)
feature: • Fixed 145°F(63'C)
• Model H1921 provides indication of potential water • Fixed 155°F(68°C)
freezing for sprinkler systems,via configuration for • Fixed 165°F(74°C)
reporting a low-temperature warning of 40°F(4.4°C). • Fixed 174'F(79°C)
This feature is compatible with Models FC922 and FC924. • Rate-of-Rise: 1 YF I min.(8.3°C I min)
at fixed 135°F(57°C)
• Rate-of-Rise: 1 5"F I min.(8.3'C I min)
at fixed 174°F(79'C)
Detector Weight:
0.317 lbs.
(0.144 kg.)
SIEMENS Industry, Inc. CerberusTM PRO
Building Technologies Division
Mounting Diagram Details for Ordering
Dimensions Model Part Description
4-13— (10.5 cm.)
' H1921 S54320-F5-A2 Thermal(Heat)Detector
DB-11 500-094151 Detector Mounting Base
04 °`i DB-11 E 500-094151 E Detector Base{small}
RL-HC 500-033230 Remote Alarm Indicator:
4"octagon-box mount, red
RL-HW 500-033310 Remote Alarm Indicator:
single-gang box mount, red
LK-11 1 500-695350 1 Base Locking Kit
In Canada, order:
Number Number Description
DB-11C 500-095687 Detector Mounting Base
(OULC Listed)
SIEMENS CerberusTM PRO NOTICE—The information contained in this data-sheet document is intended only as a summary,
and is subject to change without notice. The devices described here have specific instruction sheets
that cover various technical,limitation and liability information.
Siemens Industry,Inc.—Building Technologies Div. copies of these instruction sheets and the General Product Warning and Limitations document,
8 Fernwood Road • Florham Park, NJ 07932 which also contains important information,are provided with the product and,are available
Tel: (973) 593 2600 • Fax: (908) 547 6877 from the Manufacturer.
Information contained in these documents should be consulted before specifying or using the
Web:www.USA.Siemens.com/Cerberus-PRO product. For further information or assistance concerning particular problems contact the Manufacturer.
Building Technologies Division February 2013—supersedes sheet dated 9/2011
(Rev.1)
SII—Fire Safety
[Printed in U.S.A I
SIEMENS Catalog Sheet
Fire Safety&Security Products
FireFinder XLS
HMS Series Intelligent Initiating Devices
Manual Fire Alarm Boxes
ARCHITECT AND ENGINEER SPECIFICATIONS
• Durable design
• Shock-and-vibration resistant
• Pull-down lever is down,until manually reset l
• Reset with Allen Key
• No break rods necessary M
• Custom microcomputer-chip technology
• Dynamic supervision to the fire-alarm control
panel (FACP) PUSH HERE
• Polarityinsensitive via SureWireTM technology
9YTHEN
•
Two-wire operation
• Surface or semi-flush installation
• Model DPU programs and verifies address
and tests functionality of the each device
■ Electronic-address programming is easier,
more efficient and more dependable
• Comes in single-action(Model HMS-S)and
double-action (Model HMS-D)stations Model HMS-D Model HMS-S
• @UL Listed and®ULC Listed; Dual-Action Station Single-Action Station
FM,CSFM &NYMEA Approved
Product Overview
Models HMS-S and HMS-D intelligent manual fire- Models HMS-S and HMS-D operate with FireFinder
alarm boxes provide the most advanced method of XLS-series control panels. The microcomputer chip
address programming and supervision;combined to the manual fire-alarm box has the capacity of
with sophisticated control-panel communication. storing—in memory—identification information; as
Each HMS-series manual fire-alarm box achieves the well as important operating-status data.
state of an'intelligent-initiating device'by Innovative technology from Siemens Industry Inc.—
incorporating custom microcomputer-chip Fire Safety also allows all HMS-series intelligent
technology with sophisticated, bi-directional manual fire-alarm boxes to be programmed by using
communication capabilities with the FACP. the Programmer 1 Test Unit(Model DPU). Model DPU
Specifications is a compact, portable and menu-driven accessory
Models HMS-S and HMS-Dare constructed of
that makes programming and testing of a manual
durable, molded polycarbonate material that is matte fire-alarm box device faster, easier and more
finished in red with raised white lettering. The dependable than previous methods.
housing accommodates a'pull-down'lever,which— Model DPU eliminates the need for mechanical-
when operated—locks into position; indicating the addressing mechanisms of a device because Model
manual fire-alarm box has been activated. DPU electronically sets the address of the manual
The pull down lever remains down 1 in the'locked' fire-alarm box into its microcomputer chip, non-
position, until the fire-alarm box is manually reset. volatile memory. Hence, vibration, corrosion and
The manual fire alarm box can only be reset by other conditions that can compromise or even
opening the hinged housing cover with an Allen key; deteriorate mechanical-addressing mechanisms are
followed by closing and locking the cover. no longer a cause for concern.
FireFinder XLS 6306
SIEMENS Industry, Inc.
Building Technologies Division
Specifications — (continued) Details for Ordering
Models HMS-S and HMS-D are fitted with screw Model Pen Shipping weight
terminals for connection to an addressable circuit, Number Number Lbs. kg. Description
and can be either surface or semi-flush mounted. � HMS-S 5004MMO 20 .90 Addressable Manual Fire
The HMS Series manual fire-alarm boxes derive their Alarm Box Single Action
HMS-D 500-OMO 2.5 1.13 Addressable Manual Fire
power, communicate information and receive Alarm Bo&Double Action
commands over a single pair of wires. SB-SR 310-019880 1.5 .68 Surface Mounting Box
The HMS Series is compatible on the same circuit LTP 500-62049D .5 .23 ResetTool Package
with all W-series detectors, interfaces or I I I(Contains 2 tools)
addressable, conventional zone modules. Electrical Ratings
Current Draw(Active or Standby): 1.5mA
Mounting Diagram
SURFACE-MOUNTING ENCLOSURE
�
HOUSING 4 in
NAMEPLATE
HINGED TO SB-5R
BACKPLATE .� /
1-3Yia in. I
wo
0A
00 C �
k t
.00
HOUSING
`� \040 NSLOCKING p 3 in.
SCREW BACKPLATE
00 .0000-0
�
1
i 3-1h in DEEP
� � SWITCH BOX'00 (USER SUPPLIED)
Notice: This marketing catalog sheet is not intended to be used for system design or installation purposes.
For the most up-to-date information, refer to each product's installation instructions.
Fire Safety Fire Safety
8 Femwood Road 2 Kenview Boulevard
SIEMENS Industry, Inc. Florham Park,NJ 07932 Brampton,Ontario Juno 2010
Building Technologies Division Tel:(973)593-2600 (sill L6T 5E4/Canada Supersedes sheet dated 8/05
FAX:(908)547-6877 Printed in U.S.A. Tel:(905)799-9937 (11-1)
URL:www.SBT.Siemens.com/FIS FAX:(905)799-9858
w JtWff Sealed Lead Acid Absorbed Glass Mat
RATTER/ES Technical Specifications
WKA1 2-71F Discharge Characteristics
Duration of Discharge @ 77°F
194
1313
lie
^f26
� 1eo
ILA
l0E
9,c 3 1.76A U.TA 0.36A
9n TA
c 9.4 14+1 7s '21A
�z
6b
tiA
5.4
0 1 2 4 6 a10 20 40 60 2 4 6 910 20 40
1 -4ftute5 CHour> -
DKailon o4 d6ctwgr
Discharge Duration vs. Discharge Current
Duration of Discharge @ Various Temperatures
21A
.. 10A ....'_ ..
C -
104'F—
7
Specifications 3A 32'F 77 All Specifications are Rated at 77°F Unless Otherwise Noted 1A
L
Nominal Voltage 12V y 50ornA S-F
Ampere Hour Capacity(20hr Rate to 1.75VPC) 7Ah 3oonrA
inches millimeters
Length 5.94" 151 mm ioomA
g 3 5 10 20 40 BO 2 4 8 10 15 20 30
Dimensions Width 2.56" 65mm min rhr�
Height 3.70" 95mm Discharge Time
Height w/Term. 3.94" 101 mm
Weight 4.52lbs
Case Plastic ABS Resin Capacity Ratings
Maximum Charge Current 0.3C or 2.25A 20 hour rate 7.OAh
Float Use Voltage 2.28V/Cell Capacity 10 hour rate 6.5Ah
Recommended Float Use Current <1.1A @ 77°F 5 hour rate 6.OAh
Charging Cycle Use Voltage 2.45V/Cell 1 hour rate 4.2Ah
Cycle Use Current <2A
1 Month 97% Wattage Ratings
Shefl Life 2 Months 91% End Voltage
3 Months 83% Discharge Rate
1.75V/Cell 1.67V/Cal I
Range 32°F to 104°F 5 min.rate 39.05 42.12
Temperature Charge 50F to 122°F 10 min.rate 26.52 28.38
Discharge YF to 104°F 15 min.rate 21.43 22.46
Capacity Affected 77°F 100% 30 min.rate 13.52 14.13
by Temperature 32°F 85% 45 min.rate 10.02 10.65
(20hi rate) 5°F 64% 60 min.rate 8.06 8.37
The information contained on this specification is generally descriptive only and is not intended to make
or imply any representation guarantee or warranty with respect to any cells and batteries.Cell and battery Ascent Battery Supply,LLC
design/specification are subject to modification without notice. page 1 of 2 925 Walnut Ridge Drive • Hartland,W 153029
i
Sealed Lead Acid Absorbed Glass Mat
sarrERiEs �� Technical Specifications
WKAl2-71F Cycle Life vs. Depth of Discharge
Physical Dimensions 120% -
A & 100%
- T a0%
m
c D m 60%
U 100% 50% 30%
Depth 01 Depth a Depth at40% Dbtlwge Dlxl�rge DbWr9e
20%
0 200 400 600 800 1000 1200 1400
m mm Charge/Discharge Cycles
A 5.94 151
65
C 3.70 95
D 3.94 101
-- Effect of Temperature on Float Life
10
Terminal -
5
f _Ain�. mm 3
O � A 0.185 4.70 y
B 0.250 6.35 y
C 0.031 0.79 �
C
— J 1
U
a7
Open Circuit Voltage vs. Capacity 0.5
Estimated Residual Capacity @ 77°F
0.3
14.OV
13.5V -
m
0 13.OV 0.1
> 12.5V 50' 68' 86' 104' 1220 140' 158°
12.Ov --- Temperature (F')
U 11.5V -
c
c 11.OV
0 10.5V — -- ISO O
10.0v 9001
o% 20 % 100%
Approximate Capacity(96) QUALITY
MH 2O720
BAZR2 Approved
The information contained on this specification is generally descriptive only and is not intended to make
or imply any representation guarantee or warranty with respect to any cells and batteries.Cell and battery Ascent Battery Supply,LLC
design/specification are subject to modification without notice. page 2 of 2 925 Walnut Ridge Drive • Hartland,WI 53029