HomeMy WebLinkAboutFIR2008-00036 - FIR Permit / Conditions - 10/3/2008 MASON COUNTY DEPT. OF COMMUNITY DEVELOPMENT Inspection Line(360)427-7262
Mason County Bldg. 3 426 W. Cedar P.O. Box 186 Phone: (360)427-9670,ext.352
IP10 Shelton,WA 98584
FIRE PROTECTION PERMIT FIR2008-00036
APPLICANT: EXTREME AUTO RECEIVED: 5/23/2008
CONTRACTOR: SOUND GUARD SECURITY 357-6014 LICENSE: SOUNDGS984BW EXP ISSUED: 10/3/2008
SITE ADDRESS: 1383 E SHELTON SPRINGS RD SHELTON EXPIRES: 4/3/2009
PARCEL NUMBER: 420122190102
LEGAL DESCRIPTION: LOTS 1 &2 OF SP#2968 PTN TR 10 NE NW - DPC#07-32 -
PROJECT DESCRIPTION: AFA
GENERAL INFORMATION System Information
Type of Use: COMM
Fire District: 11 Sprinkler Heads: Audible Switches: Pull Stations:
Hood& Duct t: N Flow Switches: Visual Devices: Door Releases:
Pressure Switches:: Smoke Detectors: Duct Detectors:
Dry Chemical?: N
Zones: Heat Detectors:
Wet Chemical?: N
Spdnkler'2: N
Standpipe?: N SQUARE FOOTAGE FEES
Monitoring Company: ACI First Floor: Type Amount Due Amount Paid
Monitoring Phone No.:(360)456-1441 Second Floor:
Auto. Fire Alarm Permit $157.50 $157.50
Auto Fire Alarm?:Y Third Floor;:
Auto. Fire Alarm Plan $102.38 $102.38
Total: $259.88 $259.88
FIR2008-00036 Please refer to the following pages for conditions of this permit. 1 of 4
CASE NOTES
FIR2008-00036
CONDITIONS FOR
FIR2008-00036
1.) The automatic fire alarm system is required to be designed and installed per NFPA 72 standards. A final compliance report is required to be submitted to
the fire marshals office, the report must be clear on how the system complies with NFPA 72 standards. The system must be fully monitored by a UL
approved monitoring company.
X /'+A c?
All equipment, apparatus or appurtenances that are part of the system must be fully compatable with one another.
X APO
This permit becomes null and void if work or construction authorized is not commenced within 180 days,or if construction or work is suspended for a period of 180 days at any time after work is
commenced. Evidence of continuation of work is a progress inspection within the 180 day period. Final inspection must be approved before building can be occupied. Proof of continuation of work is
by means of a progress inspection.The ownerorthe agent on the owners behalf, represents that the information provided is accurate and grants employees of Mason County access to the above
described property and structure for review and inspection.
OWN ER OR AGENT: DATE:
FIR2008-00036 Please refer to the following pages for conditions of this permit. 2 of 4
m M
N CONCRETE MECHANICAL MANUFACTURED HOME - X
O Footings !Setbacks Dale By Ribbons m
Gas Piping C �
Interior Date By Interior.Date By Date By nl
OC Exterior Date By Exterior-Date B
Setup
Point Load I Isolated Footings INSULATION Date By -I
BG!SLAB INSULATION �
Date By Data By FIRE DEPARTMENT
Foundation Walls Floors Date By
Date By Data By DECKS
FRAMING Walls Date By
Date Ry Data By PROPANE TANKS
PLUMBING vault Date _ dy
Date By OTHER
Groundwork Attic
Date By Type.
Date By Date By
D_w.v DRYWALL Type
Int.Brace Wall T
� Date B y
Date By Date By X
FINAL INSPECTION c
Water Line Fire Seperation C
Late By Date By Date �_��-08 By C
o Pass or Request Inspect. w
Type of Insp. Fail Date Date Done By Comments a,
o '
� I
rG S -
0
0 S M e' 'c- e � C A
O
sHIgA-T /N j
W
O
w
- m
N CONCRETE MECHANICAL MANUFACTURED HOME x
p Footings I Setback* Date By Ribbons m
Ga s Piping -
oInterior Date By interior-Date By Date By 3
- -
m
Oo Exterior Date By Exterior-Date B �� D
Point Load/Isolated Footings INSULATION Date By
C
Date By Date SLAB INSULATION By FIRE DEPARTMENT 0
Foundation Walla Floors Date By
Date By Date By DECKS
FRAMING Walls Date By
Date By Date By PROPANE TANKS
PLUMBING vault Date By
Date By OTHER
Groundwork Attic ..
Date By Date By Type.
Date By
D.w.v DRYWALL Type.
Int.Bro Wall Date B T
w*
Date B y y X
(A Date By FINAL INSPECTION N
y Water Line Firer Separation QC
Date By Date By Date By do
O
o Pass or Request Inspect. o
Type of Insp. Fail Date Date Done By Comments
0
0
cc
v
m
m
0
0
a
0
N
O
7
N
M
fD
3
r:
w
0
MASON COUNTY FIRE MARSH
,11 t.'.�li• Mason County Bldg.III 426 W Cedar St
PO BOX 186 Shelton,WA 98584 �fi1_C �L
� (om)427-9670 mot.273 MAC '�3 2008
C;o
UNT,Imit# ► ;l 7IXV�n��
Mason County Fire Prot V�ystem Permit Application
Incomplete gMlication will not be accented
Owner: j &d Phone#:
Mailing Address: l�GJ — /OU Ci State: Zip:
Site Address:Zl;'j Arl City: Stater//) Zip:
Parcel#A%::2 0 Legal Description:
Lien/Title Holder:
Address: City: State: Zip:
Contractor: vP1r_'�Va►'d Sc U Phone#36 -6a
Address: 06, lJaql) City: V4 State: Zip:
Contractor Registration#: ,Snom d 6�590� �� Expiration Date:
Building Square Footage(existing&proposed): 1qX/ 2°d / 3M /
Building Use: BOccupancy Classification: Construction TypeX-j
Type of System: Type of Work:
Sprinkler: Wet Dry New System:
Standpipe: Wet Dry Modification:
AFA:
Hood&Duct:
Dry Chem:
Wet Chem:
Fire Pump:
UL certified Monitoring company: Phone#:
Contractors Bid Price: $ lam 0
Plan Submittal Requirements
Your plan submittal shall include the following:
• Plans shall be on standard 24" x 36"paper, drawn to scale with dimensions and north arrow.
• Site and Floor plan with cross sectional and exterior elevations.
• Location of occupancy and/or area separation walls, partitions, stairway enclosures, concealed spaces, etc.
• Cut sheets and/or references for all new devices.
• Location/description of all new and existing devices.
• Battery calculations.
• Wiring diagrams per floor or zone overlaid on an accurate floor plan.
• Electrical riser diagram showing all zones, circuits, devices, and end —of— line resistors.
• Hydraulic calculations.
• Copy of Contractors bid.
Fees
The permit fee will be assessed based on the submitted contractor bid for the project or a minimum of$157.50.
A plan review fee will be calculated at 65%of the permit fee and is due upon submittal of permit application.
Contractor's Affidavit
I certify that I am a currently registered contractor in the State of Washington. I am aware of the ordinance requirements regulating
the work for which the permit is issued and certify that all work will be in compliance with this ordinance. No changes will be made
without first obtaining approval from the Mason County Fire Marshal.
By: ; Date:
\\CLUSTER I_HOME_SERVER\HOME\COMMON\BUILDING\Fire Protection System Permit Application.doc
Aw MASON COUNTY FIRE MARSHAL
Mason County Bldg. III 426 W Cedar St
PO BOX 186 Shelton,WA 98584
(360)427-9670 Ext.273
Permit #
Mason County Fire Protection System Permit Application
Incomplete application will not be accepted
Owner: Phone #:
Mailing Address: City: State: Zip:
Site Address: City: State: Zip:
Parcel #: Legal Description:
Lien/Title Holder:
Address: City: State: Zip:
Contractor: Phone k
Address: City: State: Zip:
Contractor Registration #: Expiration Date:
Building Square Footage(existing & proposed): l" / 2nd / 3rd /
Building Use: Occupancy Classification: Construction Type:
Type of System: Type of Work:
Sprinkler: Wet Dry New System:
Standpipe: Wet Dry Modification:
AFA:
Hood & Duct:
Dry Chem:
Wet Chem.-
Fire Pump:
UL certified Monitoring company: Phone k
Contractors Bid Price: $
\\CLUSTERI—HOMES ERVER\HOME\COMMON\BUILDING\Fire Protection System Permit Applicatioadoc
Section 4.5 Documentation 83
FIRE ALARM SYSTEM
RECORD OF COMPLETION
Name of protected property:
Addriss:
Representative of protected property(name/phone):
Authority having jurisdiction: _
Address/telephonenumber:
Organization name/phone Representative name/phoffe
Installer
Supplier
kervice organization
Location of record(as-built)drawings:
Locati
on of operation and maintenance manuals:
Location of test reports: _
A contract for test and inspection in accordance with NFPA standard(s)
Contract No(s): Effective date: Expiration date:
System Software
(a)Operating system(executive)software revision level(s):
(b)Site-specific software revision date:
(c)Revision completed by: _
(name) (firm)
1.Type(s)of System or Service
a
NFPA 72,Chapter 6—Local
If alarm is transmitted to location(s)off premises,list where received:
NFPA 72,Chapter 8—Remote Station
Telephone numbers of the organization receiving alarm:
Alarm:
Supervisory:
Trouble:
If alarms are retransmitted to public fire service communications centers or others,indicate location and telephone
numbers of the organization receiving alarm:
I
Indicate how alarm is retransmitted:
NFPA 72, Chapter 8—Proprietary
Telephone numbers of the organization receiving alarm:
Alarm:
Supervisory:
Trouble:
If alarms are retransmitted to public fire service communications centers or others,indicate location and telephone
numbers of the organization receiving alarm:
Indicate how alarm is retransmitted:
NFPA 72,Chapter 8—Central Station
Prime contractor:
Central station location:
(NFPA 72,1 of 4)
i FIGURE 4.5.2.1 Record of Completion.
k
84 Chapter 4 • Fundamentals of Fire Alarm Systems
Means of transmission of signals from the protected premises to the central station:
McCulloh Multiplex One-way radio
Digital alarm communicator Two-way radio Others
Means of transmission of alarms to the public fire service communications center:
(a)
(b)
System location:
NFPA 72,Chapter 9—Auxillary
Indicate type of connection: Local energy Shunt Parallel telephone
Location of telephone number for receipt of signals:
2. Record of System Installation
(Fill out after installation is complete and wiring is checked for opens,shorts,ground faults,and improper branching,
f but prior to conducting operational acceptance tests.)
This system has been installed in accordance with the NFPA standards as shown below,was inspected by
d
on includes the devices shown
in 5 and 6,and has been in service since
NFPA 72, Chapters 1 2 3 4 5 6 7 8 9 10 11 (circle all that apply)
NFPA 70,National Electrical Code,Article 760
Manufacturer's instructions
Other(specify):
Signed: Date:
Organization:
3.Record of System Operation
Documentation in accordance with Inspection Testing Form,Figure 10.6.2.3,is attached
All operational features and functions of this system were tested by date
and found to be operating properly in accordance with the requirements of.
_NFPA 72,Chapters 1 2 3 4 5 6 7 8 9 10 11 (circle all that apply)
_NFPA 70,National Electrical Code,Article 760
Manufacturer's instructions
Other(specify):
Signed: Date:
Organization:
4.Signaling Line Circuits
Quantity and class of signaling line circuits connected to system(see NFPA 72, Table 6.6.1):
Quantity: Style: Class:
(NFPA 72,2 of 4)
FIGURE 4.5.2.1 Continued
2002 National Fire Alarm Code Handboc
1
Section 4.5 • Documentation 85
5.Alarm-Initiating Devices and Circuits
Quantity and class of initiating device circuits(see NFPA 72,Table 6.5):
Quantity: Style: Class:
MANUAL
(a)Manual stations Noncoded Transmitters Coded Addressable
(b)Combination manual fire alarm and guard's tour coded stations
AUTOMATIC
Coverage: Complete Partial
Selective Nonrequired
(a)Smoke detectors Ion Photo Addressable
(b)Duct detectors Ion Photo Addressable r�
(c)Heat detectors FT RR FT/RR RC Addressable
(d)Sprinkler waterflow indicators: Transmitters Noncoded Coded Addressable
(e)The alarm verification feature is disabled _or enabled ,changed from seconds to seconds.
(f)Other(list):
6.Supervisory Signal-Initiating Devices and Circuits(use blanks to indicate quantity of devices)
GUARD'S TOUR
(a) Coded stations
(b) Noncoded stations
(c) Compulsory guard's tour system comprised of_ transmitter stations and intermediate stations
Note:Combination devices are recorded under 5(b),Manual,and 6(a),Guard's Tour.
SPRINKLER SYSTEM
Check if provided
(a) Valve supervisory switches
(b) Building temperature points
(c) Site water temperature points
(d) Site water supply level points
Electric fire pump:
(e) Fire pump power
(f) Fire pump running
(g) Phase reversal
Engine-driven fire pump:
(h) Selector in auto position
(i) Engine or control panel trouble
G) Fire pump running
ENGINE-DRIVEN GENERATOR:
(a) Selector in auto position
(b) Control panel trouble
(c) Transfer switches
(d) Engine running
Other supervisory function(s)(specify):
(NFPA 72,3 of 4)
FIGURE 4.5.2.1 Continued
National Fire Alarm Code Handbook 2002 `
86 Chapter 4 • Fundamentals of Fire Alarm Systems
7.Annunciator(s)
Number:_ ___ Type: _ _ Location:
8.Alarm Notification Appliances and Circuits
NFPA 72,Chapter 6—Emergency Voice/Alarm Service
Quantity of voice/alarm channels: Single: Multiple:
Quantity of speakers installed: Quantity of speaker zones:
Quantity of telephones or telephone jacks included in system:
Quantity and the class of notification appliance circuits connected to system(see NFPA 72,Table 6.7):
Quantity: Style: Class:
Types and quantities of notification appliances installed:
(a) Bells With Visible
(b) Speakers With Visible
(c) Horns With Visible
(d)Chimes With Visible
(e) Other: With Visible c
(f) Visible appliances without audible:
9.System Power Supplies
(a) Fire Alarm Control Panel: Nominal voltage: Current rating:
Overcurrent protection: Type: Current rating:
'Location:
(b) Secondary(standby):
Storage battery: Amp-hour rating:
Calculated capacity to drive system,in hours:
Engine-driven generator dedicated to fire alarm system:
Location of fuel storage:
(c) Emergency system used as backup to primary power supply:
Emergency system described in NFPA 70,Article 700:
10.Comments
Frequency of routine tests and inspections,if other than in accordance with the referenced NFPA standard(s):
System deviations from the referenced NFPA standard(s)are:
i
i
(signed)for installation contractor/supplier (title) (date)
(signed)for alarm service company (title) (date)
(signed)for central station (title) (date)
Upon completion of the system(s)satisfactory tests)witnessed(if required by the authority having jurisdiction):
(signed)representative of the authority having jurisdiction (title) (date)
(NFPA 72,4 of 4)
FIGURE 4.5.2.1 Continued
2002 National Fire Alarm Code Handbook
GENTEX
CORPORATION
Commander3 Series GEC3/GES3
Selectable Candela Evacuation Signals 12 & 24 VDC
Applications S E R I E S
The Commander Series is a low profile strobe and horn/strobe combination that
offers dependable audible and visual alarms and the lowest current available.
The GE3 Series 24VDC offers tamperproof field selectable candela options of
15, 30, 60, 75, and 110 candela. The 12VDC offers tamperproof field selectable "
candela options of 15, 30, 60, and 75 candela.
The Commander3 Series horn offers a continuous or synchable temporal three in •.
2400Hz and mechanical tone, a chime and whoop tone. All tones are easy for III��III�,
the professional to change in the field by using switches.
The GE3 Series has a minimal operation current and has a minimum flash rate
of 1 Hz regardless of input voltage.
The Commander3 Series is shipped with the standard 4" metal mounting plate Product Listings
which incorporates the popular Super-Slidefeature that allows the installer to SIGNALING _
easily test for supervision.The product also features a locking mechanism which
secures the product to the bracket without any screws showing.
The Commander3 also features the Checkmate- Instant Voltage Verification LISTED APPROVED
feature which allows the installer to check the voltage drop draw and match it to .UL 464&UL 1971 Listed
the blueprint. •CAN/ULC S526-M87 Listed
The GE3 Series appliances are UL 464 and UL 1971, listed for use with fire pro- ULSZ7.S3406 Listed(GEC3-24,
tective systems and are warranted for three years from date of purchase. •FM Approved GEH24&GEH12)
Standard Features •CSFM:7135-0569:122(GEC3-24&GEH-24)
7125-0569:123(GES3-24)
• Nominal voltage 12VDC and 24VDC 7125-0569:129(GES3-12)
•24VDC units have field selectable candela options of 15, 7135-0569.130(GEC3-12&GEH-12)
30, 60, 75, and 110 candela •BS+AIMEA:285-91-E(GEC3-24&GES3-24)
• 12VDC units have field selectable candela options of 15, 580-06-E(GEC3-12&GES3-12)
30, 60, and 75 candela •BFP(City of Chicago)
• GEH horn is available in 12VDC or 24VDC Product Compliance
•Super-Slide" Bracket- Ease of Supervision Testing • NFPA 72
•Checkmate""- Instant Voltage Verification • Americans with Disabilities Act(ADA)
•Unit Dimensions: 5" high x 4.5"wide x 2.5" deep
•Synchronize strobe and/or horn with Gentex Seriesram
Control Module (12VDC product must use the AVSM MEMBER
Module)
• Prewire entire system, then install signals
• Lower installation and operating costs
•Input terminals 12 to 18 AWG • Surface mount with the GSB (Centex Surface Mount Box)
•Switch selection for high or low dBA • Silence horn while strobes remain flashing
•Switch for chime,whoop, mechanical and 2400Hz tone • Wide voltage range 8-17.5VDC (12VDC units) 16-33VDC
•Tamperproof re-entrant grill or FWR (24VDC units)
•Switch for continuous or temporal 3 (not available on • Faceplate available in red or off-white
whoop tone)
GEH 12VDC or 24VDC Low Profile Evacuation Horn
Model art Nominal Reverberant n nec olc Room
Number Number Voltage 1Oft., per UL 464 dBA @10ft.
GES3 12VDC or 24VDC Selectable Candela Low Profile Evacuation Strobe
Modelallominal an e a Model Designations:
Number Number Voltage (UL 1971) W=Wall mount
R=Red faceplate
W=Off-white faceplate
P=Plain(no lettering)
All units are available in plain(no lettering).
When ordering add a"P"to the end of the model
number. Plain units are non-returnable.
ALERT bezel available
AGENT bezel available.
GEC3 12VDC or 24VDC Selectable Candela Low Profile Evacuation Horn/Strobe
Model allominal an e a ever eran n Anechoic Room
Number Number Voltage (UL 1971) 1Oft.,per UL 464 dBA @ 10ft.
Product Strobe Current Ratings GIE3-24 Product Strobe Current Ratings
Candela 15cd 30cdc Candea I 15cdc cd 7Scd 110cd
11115MA IJIMAm m7F_ 24VDC 55MA 63MAm m m
UL Max' 163MA 212MAm m UL Max' 16MA 9bMAm m m
Product orn Current Ratings Product orn Current Ratings
minimum minimumRegulatedMinimum MinimumRegulated
Horn Mode @ 1Oft.,per @ 1Oft.,per Max.Operating @ Horn Mode @ 1Oft.,per @ 10ft.,per Max.Operating
UL 464(HIGH) UL 464(LOW) High Setting(mA) UL 464(HIGH) UL 464(LOW) High Setting(mA)
Temp z emp z
emp Mechanical Temp Mechanical
Temp Chime Rontinuous
Chime 15
on Inuous z zon Inuous ec anica anicaon Inuous me eoop bb
NOTES:
•To obtain the horn/strobe current draw,add the strobe current draw and the horn current draw.
•Operating temperature:32°to 120°F(0'to 491 C). The GE3 Series is not listed for outdoor use.
•The sound output for the temporal 3 tone is rated lower since the time the horn is off is averaged into the sound output rating. While the horn is
producing a tone in the temporal 3 mode its sound pressure is the same as the continuous mode.
•For nominal and peak current across UL regulated voltage range for filtered DC power and unfiltered(FWR[Full Wave Rectified])power,see
installation manual. 12VDC models are DC only.
•Gentex does not recommend using a coded or pulsing signaling circuit with any of our strobe products(see Technical Bulletin 014).
'Operating the horn in this mode at this voltage will result in not meeting the minimum UL reverberant sound level required for public mode fire protection service. These
settings are acceptable only for private mode fire alarm use. Use the high dBA setting for public mode application(not applicable when using the chime tone.The chime tone
is always private mode).
RMS current ratings are per UL average RMS method. UL max current rating is the maximum RMS current within the listed voltage range(16-33VDC for 24VDC units)(8-1 NDC for
12VDC units). For strobes the UL max current is usually at the minimum listed voltage(16VDC for 24VDC units)(8VDC for 12VDC units). For audibles the max current is usually at
the maximum listed voltage. For unfiltered FWR ratings,see installation manual.
Mounting Super-Slide TM Switch Locations
SMTCH POSITION
3 4 5
/ Mech anica47arrp. ON ON ON
chani Meo4Co nl. OFF ON
HrTemp. ON OFF ON
HlCont. OFF OFF ON
Chime Temp. ON ON OFF
Chico Cont OFF ON OFF
Whoop ON OFF OFF
Mfieop OFF OFF OFF
4 Switch Position 6
w ON>HIGH dB
M OFF>LOW dB
Switch positions t and 2
/ In the off poeltlon to select
isolated horn and strobe
�j add power Inputs.
Die Cast Metal Mounting Plate:Mounts to single gang,
double gang 4"square boxes or GSB box. ON
II.
IL
Checkmate TM - Instant Voltage Verification CQ
1 2 3 4 5 6
1�
S+ Candela Selection
S+
Se e�
H# 3� Candela selection slider
® switch s]Ac t center ^
i �{- and slide switch to desired /`�F'(S�]I
brightness level.
Y
Break off pin and insert into to
hole at the bottom of the
The access holes are provided in the back of the terminal seledortolookcandelasetting. Iss
block to allow the voltage to be measured direct) without Signal must be removed rran
g y bracket and pin pushed forward �
removing the device.Typically this would be done at the from backside att of hole I ^-�
end of the line to confirm design criteria. Most measure- 'O change Gd"dela
ments will be taken using the S+and S-locations
although access is provided to other locations. NOTE:
Care should be taken to not short the test probes.
Conventional GES3/GEC3 Series Wiring Diagrams
UL Listed
UL Listed
Control Signet
Control Signal Signal Panel S. S+ S. H. 1+ s+ S. S. H+ H-
Panel S+ S+ S- H+ H- S+ S+ S- H+ H- Supervised
Supervised sl B a 0 signal Circuit
Signal Circuit \ Oe
\ +
ENO OF LWE
RESISTOR \ + [ND OF lii!
REaCnMt
Wiring Diagram GE3 Series with Gentex Synchronization Module
F.A.C.P.
TO NEXT SIGNAL I TO NOTIFICATION ALARM ORWIT
wwooNLv. ___ ______________------------—____-
I TO NFM SIGNAL TO NOTIFICATION ALARM CIRCUIT
REMOVE JUMPER
FOR RJDEPE'DENT
YNCHRONRED STROBE 00
AUDIBLE SIGNAL + �ys,ogpm AND HORN OPERATION
CIRCUIT atisse SYNCHRONIZATION
Wwelo orAT LEAVE JUMPERNI RJIC
0— 11 1 Lit L TO ELIMINATE NEED FOR MODULE LEAVE JUMPER IN WJ10E ON
a HORN INPUT ON AVSM $LAVE UNITS UNLESS SEPARATE
AND OPERATE SIGNAL a CONTROL DYER NORN CNT
pus. IN UNISON MODE ® I$REQURED.
SYNCHRONIZATION
MODULE slBnal sip,tal
S+ S+ S- H+ µ S+ S. SS H+ K.
B B B B
x
VISIBLE SIGNAL + I r I �ssroarrn 'i
CIRCUIT _ y
i I I I
I I I
tt-------_---_---______________ __—________---_----------- I
rEssroa ran '
c wss A
vwo+c oats. ' '
Note: See Technical Bulletin 015 for proper synchronization module for application.
Note: When synchronizing the GE3 12VDC Series,the AVSM synchronization module MUST be used.
Architect & Engineering Specifications
The audible and/or visible signal shall be Gentex GE3 Series or approved equal and shall be listed by Underwriters Laboratories,Inc.per UL 1971
and/or UL 464.The notification appliance shall also be listed with Factory Mutual Listing Service(FM),the California State Fire Marshal(CSFM)and the
Bureau of Standards and Appeals(NYC).
The notification appliance(combination audible/visible)shall produce a peak sound output of 100dBA or greater at 12VDC or 24VDC as measured in
an anechoic chamber.The signaling appliance shall also have the capability to silence the audible signal while leaving the visible signal energized with the
use of a single pair of power wires.Additionally,the user shall be able to select either continuous or temporal tone output with the temporal signal having
the ability to be synchronized.
Unit shall be capable of being installed so that any unauthorized attempt to change the candela setting will result in a trouble signal at the fire alarm
control panel.
The audibletvisible and visible signaling appliance shall also maintain a minimum flash rate of 1 Hz or up to 2Hz regardless of power input voltage. The
appliance shall have an operating current of 55mA or less at 24VDC for the 15Cd strobe circuit and 106mA or less at 12VDC for the 15Cd strobe circuit.
The appliance shall be polarized to allow for electrical supervision of the system wiring.The unit shall be provided with a mounting bracket with termi-
nals and barriers for input/output wiring and be able to mount to a single gang or double gang box or double workbox without the use of an adapter plate.
The unit shall have an input voltage range of 16-33 volts with either direct current or full wave rectified power for 24VDC models or a voltage range of
8-17.5 volts for 12VDC models.
The appliance shall be capable of testing supervision without disconnecting wires.Also the appliance shall be capable of mounting to a surface back
box. The unit shall also be able to verify voltage at the unit without removing unit.
24 units per carton
28 pounds per carton
Important Not—
Those E N T E X These material,have been p epa ed by Centex Co as le n('Centex')for ould n It be purposes on y,are 5 51-0050 03
necessary su mary,and are not purported to serve as legal advice aM should not De used as such.
Genie%makes an reprasenlahona and wamarthes,express or implied,that these materials are complete
ccurate,up-to-date,or in compliance with all relevant bcal,stale and federal laws,regulations and
CORPORATION and a
rules.The maleials do not address all legal considerations as there is inevitable uncertainty regarding
inferprelation of laws,regulations and rules and the applicallon of such laws,regulations and rules to panic-
Fire Protection Products Group•www.gentex.com ular tact patterns. Each person's activities can differently affect the oblgalons that exist under applicable
laws,regulahons or rules. Therefore,these materials should be used onty for infomtatkanal purposes and
10985 Chicago Drive •Zeeland, Michigan 49464 should rot be used as a substllum for seellng professional legal aWlee Gentex will not he responsmle for
616.392.7195• 1.800.436.8391 •616.392.4219 Fax any action or failure to act In reliance upon lire information contained in this material.
Gentex Corporation reserves the right to make changes to the product data sheet at their discretion. r",,Printeri on Recycled Paper
Plan Submittal Requirements
Your plan submittal shall include the following:
• Plans shall be on standard 24"x 36"paper, drawn to scale with dimensions and north arrow.
• Site and Floor plan with cross sectional and exterior elevations.
• Location of occupancy and/or area separation walls,partitions, stairway enclosures,concealed spaces, etc.
• Cut sheets and/or references for all new devices.
• Location/description of all new and existing devices.
• Battery calculations.
• Wiring diagrams per floor or zone overlaid on an accurate floor plan.
• Electrical riser diagram showing all zones,circuits, devices, and end—of—line resistors.
• Hydraulic calculations.
• Copy of Contractors bid.
Fees
The permit fee will be assessed based on the submitted contractor bid for the project or a minimum of$157.50.
A plan review fee will be calculated at 65%of the permit fee and is due upon submittal of permit application.
Contractor's Affidavit
I certify that I am a currently registered contractor in the State of Washington. I am aware of the ordinance requirements regulating
the work for which the permit is sueVnd certify that all work will be in compliance with this ordinance. No changes will be made
without first bta' ing rov fro a Mason County Fire Marshal. �y
By: Date:
SYSTEM
�30 SENSOR®
5600 Series Mechanical
Heat Detectors f x
System Sensor' 5600 series mechanical heat detectors
offer a low-cost means for property protection against
fire,and for non-life-safety installations where smoke
detectors are inappropriate.
Featum Multiple configurations.The 5600 series offers a full-line of
•Multiple configurations for installations: configurations to accommodate a broad range of applications.Both
-Single-and dual-circuit models single-and dual-circuit models are available for low-and high-
-Fixed temp and combination fixed-temp/rate-of-rise temperature ratings with either fixed temperature or combination
135°F or 1947 ratings. fixed temperature/rate-of-rise(ROR)activation.The ROR element of
Plain housing for residential installations(Model 5601 P) the fixed/ROR models is restorable to accommodate field-testing.
•
•Easy-to-use terminal screws Installation flexibility.To satisfy a variety of installation needs,
•A broad range of back box mounting options: the 5600 series easily mounts to single-gang and octagonal back
-Single gang boxes.And these models accommodate four-square back boxes,
-3.5"and 4-Octagonal when used with a square to round plaster ring.The reversible
4"square with square to round taster ring mounting bracket permits both flush-and surface-mount back box
installations.
•Reversible mounting bracket
Visual identification.The 5600 series provides clear markings on
the exterior of the unit to ensure that the proper detector is being
used.Alphanumeric characters identify the activation method,as
well as the temperature rating,in Fahrenheit and Celsius degrees.
Fixed temperature models are identified FX,while combination
fixed/rate-of-rise units are marked FX/ROR.The 5600 series also
provides a post-activation indicator in the form of a collector.When
the detector is activated,the collector drops from the unit,making it
easy to identify the unit in alarm.
Agency Listings
& < F M> MEA
LISTED APPROvEU approved
7 27 0-1 209-2 27
Specifications
Architectural/Engineering Specifications
Mechanical heat detector shall be a System Sensor 5600 series model number listed to Underwriters Laboratories UL 521 for Heat Detectors for Fire
Protective Signaling Systems.The detector shall be either a single-circuit or a dual-circuit type,normally open.The detector shall be rated for activation at either
135°F(57C)or 194F(90C),and shall activate by means of a fixed temperature thermal sensor,or a combination fixed temperature/rate-of-rise thermal sensor.
The rate-of-rise element shall be activated by a rapid rise in temperature,approximately 15°F(8.3°C)per minute.The detector shall include a reversible mounting
bracket for mounting to 31/2-inch and 4-inch octagonal,single gang,and 4-inch square back boxes with a square to round plaster ring.Wiring connections shall
be made by means of SEMS screws that shall accommodate 14-22AWG wire.The detector shall contain alphanumeric markings on the exterior of the housing
to identify its temperature rating and activation method.The rate-of-rise element of combination fixed temperature/rate-of-rise models shall be restorable,to
allow for field-testing.The detectors shall include an external collector that shall drop upon activation to identify the unit in alarm.
Physical/OperatingSpecifications
Maximum Installation Temperature 5601P,5603,5621,and 5623:100°F(38Q
5602,5604,5622,and 5624.150'F(65.6C)
Operating Humidity Range 5 to 95%RH non-condensing
Dimensions with mounting bracket Diameter:4.57 inches(11.6cm)
Height: 1.69 inches(4.3cm)
Alarm Temperature 5601 P,5603,5621,and 5623:135°F(57 C)
5602,5604,5622,and 5624:194°F(90C)
Weight 6 oz.(170 grams)
Rate-of-Rise Threshold 15°F(83C)rise per minute(models 5601 P,5602,5621,and 5622 only)
Mounting 31h-inch octagonal back box
4-inch octagonal back box
Single gang back box
4-inch square back box with a square to round plaster ring
Electrical Specifications
Operating Voltage/Contact Ratings 6-125VAC/3A
6-28VDC/1 A
125VDC/0.3A
25OVDC/0.1 A
Input Terminals 14-22 AWG
noe w u xr aovxi
O O O O O
�
5601 PP 5602,5622 ,�5 04,5624 5621
Orals in"f' g Information
5601 P Single None 135°F(57°C) Fixed Temperature/Rate-of-Rise 50 feet x 50 feet(15.24m x )
5602 Single Lettering 194"F(90C) Fixed Temperature/Rate-of-Rise 50 feet x 50 feet(15.24m x 15.2
5603 Single Lettering 135`F(57C) Fixed Temperature 25 feet x 25 feet(7.62m x 7.62m)
5604 Single Lettering 194-F(90-C) Fixed Temperature 25 feet x 25 feet(7.62m x 7.62m)
5621 Dual Lettering 135-F(57°C) Fixed Temperature/Rate-of-Rise 50 feet x 50 feet(15.24m x 15.2m)
5622 Dual Lettering 194"F(90C) Fixed Temperature/Rate-of-Rise 50 feet x 50 feet(15.24m x 15.2m)
5623 Dual Lettering 135-F(57C) Fixed Temperature 25 feet x 25 feet(7.62m x 7.62m)
5624 Dual Lettering 194T(WQ Fixed Temperature 25 feet x 25 feet(7.62m x 7.62m)
'NOTE:Refer to NFPA72 guidelines for spacing reductions when ceiling heights exceed 10 feet.
SYSTEM 020a6 sy't m5ensoc
3825 Ohio Avenue•St.Charles,IL 60174 arodu speaf �:�a=06-gewd, nda for
SENSOR' Phone:800-SENSOR2•Fax:630-377-6495 "�'P°a "bndtl-05 h,c rgthcaiSt 'm'"R`
Gbbal Project Values:
Project Name:I Extreme Auto Body Standby Hours: 24
KNIGHT Project ID:1 Alarm Mins:�
Prepared By:I Mark Derating Factor: 12
1:Calculations Date: 5/23/2008 Voltage Drop Warning
Threshold%: 10
Panel ID: SK-5208 Model: SK-5208 Fire Alarm Control Panel Max NAC Current: 3.0 Amps
Location: I Volts: 24 VDC Max Panel Current: 6.0 Amps
Current Draw Wire AWG Ohms Per Length(ft) Actual Volts @ %Dro
Ckt.# Circuit Name Qty StandbyAlarm &Type 1000 Ft. One-WayOhms EOL p
SK-5208 SK-5208 Main Control 1 0.140 0.160
NAC-CKT SK-5208 Pr m'd NAC's 0.000 0.000
ALM-RLY SK-5208 P m Alm Rly 0.000 0.000
SK-5217 SK-5217 Zone Ex dr 0.000 0.000
SK-5235 SK-5235 LCD Remote 1 0.035 0.050
SK-5280 SK-5280 Display Mod 0.000 0.000
SK-5220 SK-5220 Dir Con Mod 0.000 0.000
SK-7181 SK-7181 Zn Cnvtr 0.000 0.000
IDC-1 Initiating Device Ckt 1 0.000 0.000
IDC-2 Initiating Device Ckt 2 0.000 0.000
IDC-3 Initiating Device Ckt 3 0.000 0.000
IDC-4 Initiating Device Ckt 4 0.000 0.000
IDC-5 Initiating Device Ckt 5 0.000 0.000
IDC-6 Initiating Device Ckt 6 0.000 0.000
IDC-7 Initiating Device Ckt 7 0.000 0.000
IDC-8 Initiating Device Ckt 8 0.000 0.000
IDC-9 Initiating Device Ckt 9 0.000 0.000
IDC-10 Initiating Device Ckt 10 0.000 0.000
..................... ..
.......................
IDC-11 dactWt,a AWSK Z17> 0.000 0.000
IDC-12 Inactive M&SK.5217:[ 0.000 0.000
IDC-13 #iacty !#ddK521? 0.000 0.000
IDC-14 #iiaGtiu :Add$ 5217 0.000 0.000
.......................
.......................
IDC-15 ltiactive .AddSK 5217:;:; 0.000 0.000
IDC-16 t#iactiSie .AddSK 5217; 0.000 0.000
IDC-17 kiaetive AldSi<52j7 0.000 0.000
IDC-18riaetive;.Add5K5z1:7' 0.000 0.000
IDC-19 3nactivia :Add SK 5217 : 0.000 0.000
IDC-20 In a ative':..Add.SK-52.17 0.000 0.000
IDC-21 faactiV6 Add SIG521? 0.000 0.000
IDC-22 #t18Ctiv _Atl(1'SK5i7 0.000 0.000
IDC-23 iC18CtiYeAtidSfC:52i7 0.000 0.000
IDC-24 buctive;.Add SK 5217.. 0.000 0.000
IDC-25 biactive;Add SK 5217.- 0.000 0.000
IDC-26 Inactive,',:Add 5K 5217 0.000 0.000
.......................
IDC-27 lnactivia'Add 5K-521 0.000 0.000
IDC-28 1bactive'Add M.52.1.7 . 0.000 0.000
IDC-29 MaGtiv6* iA l$K 5217. 0.000 0.000
IDC-30iactiu AddiSK-52i7: 0.000 0.000
NAC-1 #tiactiva Add.NAGgk.-t: 0.000 0.000 #16 Solid 4.02 0.00 20.40 0.00%
NAC-2 1;iactive Add NA0-CKT 0.000 0.000 #16 Solid 4.02 0.00 20.40 0.00%
NAC-3 #iactive;`AddNAGKT: 0.000 0.000 #16 Solid 4.02 0.00 20.40 0.00%
NAC-4 1haiaWk Add NA£GKT is 0.000 0.000 #16 Solid 4.02 0.00 20.40 0.00%
Aux Aux Power Out 0.000 0.000 #16 Solid 4.02 0.00 20.40 0.00%
Total Standby Current(Amps) 0.175 0.210 Total Alarm Current(Amps)
Standby Time In Hours 24 0.083 Alarm Time In Minutes/60 5 Mins
Total Standby AH Required 4.200 0.018 Total Alarm AH Required
Total Combined AH Required 4.22 Command Shortcuts
Multiply By The Derating Factor 1.20
Minimum Battery AmpHours Required 5.06 Configure Circuits Print Page