Aboveground Piping Report Bld 1-6 - FIR Inspections - 10/24/2008
i HYDROSTATIC: HYDROSTATIC TEST SHALL BE MADE AT NOT LESS THAN 200 PSI FOR TWO HOURS OR 50 PSI ABOVE STATIC PRESSURE IN EXCESS OF 150 PSI FOR TWO HOURS. DIFFERENTIAL DRY—PIPE VALVE CLAPPERS SHALL BE LEFT OPEN DURING TEST TO PREVENT DAMAGE. ALL ABOVEGROUND PIPE TEST LEAKAGE SHALL BE STOPPED. DESCRIPTION PNEUMATIC: ESTABLISH 40 PSI AIR PRESSURE AND MEASURE DROP WHICH SHALL NOT EXCEED 1-1/2 PSI IN 24 HOURS. TEST PRESSURE TANKS AT NORMAL WATER LEVEL AND MEASURE AIR PRESSURE DROP WHICH SHALL NOT EXCEED 1-1/2 PSI IN 24 HOURS. ALL PIPING HYDROSTATICALLY TESTED AT 200 PSI FOR 2 HRS. IF NO, STATE REASON T;;;]SODIUM DRY PIPING PNEUMATICALLY TESTED 0 YES ❑NO ❑N/A EQUIPMENT OPERATES PROPERLY ®YES ❑NO ❑N/A KNIGHT FIRE PROTECTION, INC. CERTIFIES THAT ADDITIVES AND CORROSIVE CHEMICALS, SUCH AS SILICATE OR DERIVATIVES OF SODIUM SILICATE, BRINE, OR OTHER CORROSIVE CHEMICALS WERE NOT USED FOR STOPPING LEAKS. DRAIN I READING OF GAGE LOCATED NEAR THE RESIDUAL PRESSURE WITH MAIN DRAIN VALVE TEST MAIN DRAIN: _ PSI OPEN WIDE _65—E PSI UNDERGROUND MAINS AND LEAD INS TO THE SYSTEM RISERS WERE FLUSHED BEFORE CONNECTION 'WAS MADE TO THE ABOVEGROUND SPRINKLER PIPING. VERIFIED BY UNDERGROUND TEST CERTIFICATE 0 YES ❑ NO OTHER EXPLAIN FLUSHED BY KNIGHT FIRE PROTECTION 18(YES ❑ NO APPROVING AUTHORITY TITLE DATE TEST CAPS NUMBER SED LOCATIONS NUMBER REMOVED NyA WELDED PIPING ®YES ❑ NO WELDING IF YES...... KNIGHT FIRE PROTECTION CERTIFIES THAT WELDING PROCEDURES COMPLY WITH THE REQUIREMENTS OF AT LEAST AWS B2.1 AND D10.9, LEVEL AR-3 YES ❑NO KNIGHT FIRE PROTECTION CERTIFIES THAT THE WELDING WAS PERFORMED BY WELDERS QUALIFIED IN COMPLIANCE WITH THE REQUIREMENTS OF AT LEAST 14 YES ❑NO AWS B2.1 AND D10.9, LEVEL AR-3 KNIGHT FIRE PROTECTION CERTIFIES WELDING WAS CARRIED OUT IN COMPLIANCE WITH A DOCUMENTED QUALITY CONTROL PROCEDURE TO INSURE THAT ALL DISCS ARE RETRIEVED, THAT OPENINGS IN PIPING ARE SMOOTH, THAT SLAG AND OTHER WELDING RESIDUE ARE REMOVED, AND THAT THE INTERNAL DIAMETERS OF PIPING ARE NOT PENETRATED 0 YES ONO CUTOUTS KNIGHT FIRE PROTECTION CERTIFIES THAT THEY HAVE A CONTROL FEATURE TO ENSURE THAT ALL (DISCS) CUTOUTS_ (DISCS) ARE RETRIEVED. YES ❑ NO HYDRAULIC DATAPLATE PROVIDED IF NO, EXPLAIN DATAPLATE W YES ❑No REMARKS DATE LEFT IN SERVICE WITH ALL CONTROL VALVES OPEN: DOCUMENTS DOES THE OWNER HAVE A COPY OF NFPA #25 FOR THEIR REFERENCE. ©YES ❑ NO KNIGHT FIRE PROTECTION, INC. LICENSE# KNIGHFP044LK ACCEPTANCE PRqgERTY RE TITLE DATE KI FIRE" ROTECTION TITLE DATE '� (I'C 4 I D—)y vas APPR VI G AUTHORITY TITLE DATE - ' ram- ►`1kS�Ca D Z� -Q� I CERTIFY THAT THE INFORMATION HEREIN IS TRUE AND THAT THIS SPRINKLER SYSTEM WAS CERTIFICATION INSTALLED IN ACCORDANCE WITH THE RULES ADOPTED BY THE WASHINGTON ADMINISTRATIVE CODE AS ADMINISTERED BY THE STATE FIRE MARSHAL. RICHARD KNIGHT NAME OF CERTIFICATE OF COMPETENCY HOLDER SIGNATURE OF CERTIFICATE OF COMPETENCY HOLDER /�OTCIn sTC O�MCTOATl�AI ll 1:12�11��i)�22f KNIGHT FIRE PROTECTION, INC. 9702 LATHROP INDUSTRIAL DRIVE SW OLYMPIA, WA 98512-9188 (360) 786-8606 MATERIAL & TEST FAX 786-8722 REPORT FOR ABOVEGROUND PIPING •ON GUARD LICENSE NO. KNIGHFP044LK 24 HOURS A DAY" Procedure upon completion of work: Inspection and tests shall be made by the contractor's representative and witnessed by the Al All defects shall be corrected and system left in service before contractor's personnel finally leave the job. A certificate shall be filled out and signed by both representatives. Copies shall be prepared for approving authorities, owners, and contractor. It is understood the owner's representative's signature in no way prejudices any claim against contractor for faulty material, poor workmanship, or failure to comply with approving authority's requirements or local or nces. PROPERTY NAME MASON CO. PUBLIC WORKS & MAINT. FACILITY, Bldg. 6 DAT lo- "op PROPERTY ADDRESS SR 101 & SR 102, MASON COUNTY, WASHINGTON SYSTEM LOCATION OR ID 3" Riser in N.E. corner of building REVIEWED AND ACCEPTED BY MASON COUNTY FIRE MARSHAL PLANS ADDRESS Shelton, Washington INSTALLATION CONFORMS TO ACCEPTED PLANS 0 YES ❑ NO EQUIPMENT USED IS APPROVED 0 YES ❑NO IF NO, EXPLAIN HAS PERSON IN CHARGE OF FIRE EQUIPMENT BEEN INSTRUCTED AS TO 0 YES ❑ NO ,INSTRUCTIONS CARE AND MAINTENANCE OF THE NEW EQUIPMENT AND THE LOCATION OF ALL CONTROL VALVES? HAVE COPIES OF THE FOLLOWING BEEN LEFT ON THE PREMISES: 1. SYSTEM COMPONENT CARE, AND MAINTENANCE INSTRUCTIONS YES ONO 2. MAINTENANCE AGREEMENT j8[ YES O NO YEAR OF ORIFICE TEMPERATURE SPRINKLERS MAKE MODEL MANUFACTURE SIZE QUANTITY RATING Tyco Mod. TY-3131 Upright 2007 .50 15 155 Tyco Mod. TY-3131 Upright 2007 .50 1 212 Tyco Mod. .TY-3331 Sidewall 2007 .50 5 155 PIPE AND TYPE OF PIPE STEEL FITTINGS TYPE OF FITTINGS FLANGED, WELDED, CAST/MALLEABLE IRON, GROOVED, SOCK—IT WATER FLOW INDICATOR INFORMATION MAXIMUM TIME TO OPERATE THROUGH TEST CONNECTION ALARM LOCATION TYPE MAKE MODEL MIN. SEC. DEVICES. 1 DRY VALVE Q.O.D. MAKE I MODEL SERIAL NO. MAKE MODEL SERIAL NO. Vltcl,J&- F W oo3q o A- TIME TO TRIP * TIME WATER ALARM THROUGH TEST WATER AIR TRIP POINT REACHED OPERATED DRY PIPE CONNECTION PRESSURE PRESSURE AIR PRESSURE TEST OUTLET PROPERLY OPERATING MIN. SEC. PSI PSI PSI MIN. SEC. YES NO THOU TEST �0.0.D T 6 S L/5" -� I WITH Q.0.D. IF NO, EXPLAIN HYDROSTATIC: HYDROSTATIC TEST SHALL BE MADE AT NOT LESS THAN 200 PSI FOR TWO HOURS OR 50 PSI ABOVE STATIC PRESSURE IN EXCESS OF 150 PSI FOR TWO HOURS. DIFFERENTIAL DRY—PIPE VALVE CLAPPERS SHALL BE LEFT OPEN DURING TEST TO PREVENT DAMAGE. ALL ABOVEGROUND PIPE TEST LEAKAGE SHALL BE STOPPED. DESCRIPTION PNEUMATIC: ESTABLISH 40 PSI AIR PRESSURE AND MEASURE DROP WHICH SHALL NOT EXCEED 1-1/2 PSI IN 24 HOURS. TEST PRESSURE TANKS AT NORMAL WATER LEVEL AND MEASURE AIR PRESSURE DROP WHICH SHALL NOT EXCEED 1-1/2 PSI IN 24 HOURS. ALL PIPING HYDROSTATICALLY TESTED AT 200 PSI FOR 2 HRS. IF NO, STATE REASON TESTS DRY PIPING PNEUMATICALLY TESTED ®YES ❑ NO ❑N/A EQUIPMENT OPERATES PROPERLY ®YES ❑ NO ❑N/A KNIGHT FIRE PROTECTION, INC. CERTIFIES THAT ADDITIVES AND CORROSIVE CHEMICALS, SUCH AS SODIUM SILICATE OR DERIVATIVES OF SODIUM SILICATE, BRINE, OR OTHER CORROSIVE CHEMICALS WERE NOT USED FOR STOPPING LEAKS. DRAIN I READING OF GAGE LOCATED NEAR THE RESIDUAL PRESSURE WITH MAIN DRAIN VALVE TEST MAIN DRAIN: _�� PSI OPEN WIDE PSI UNDERGROUND MAINS AND LEAD INS TO THE SYSTEM RISERS WERE FLUSHED BEFORE CONNECTION WAS MADE TO THE ABOVEGROUND SPRINKLER PIPING. VERIFIED BY UNDERGROUND TEST CERTIFICATE 14 YES ❑NO OTHER EXPLAIN FLUSHED BY KNIGHT FIRE PROTECTION 14 YES ❑ NO APPROVING AUTHORITY TITLE DATE TEST CAPS NUMBER US D TOCATIONS NUMBER REMOVED WELDED PIPING 0 YES ❑NO WELDING IF YES...... KNIGHT FIRE PROTECTION CERTIFIES THAT WELDING PROCEDURES COMPLY WITH THE REQUIREMENTS OF AT LEAST AWS B2.1 AND D10.9, LEVEL AR-3 N YES ❑NO KNIGHT FIRE PROTECTION CERTIFIES THAT THE WELDING WAS PERFORMED BY WELDERS QUALIFIED IN COMPLIANCE WITH THE REQUIREMENTS OF AT LEAST 19 YES ❑NO AWS B2.1 AND D10.9, LEVEL AR-3 KNIGHT FIRE PROTECTION CERTIFIES WELDING WAS CARRIED OUT IN COMPLIANCE WITH A DOCUMENTED QUALITY CONTROL PROCEDURE TO INSURE THAT ALL DISCS ARE RETRIEVED, THAT OPENINGS IN PIPING ARE SMOOTH, THAT SLAG AND OTHER WELDING RESIDUE ARE REMOVED, AND THAT THE INTERNAL DIAMETERS OF PIPING ARE NOT PENETRATED 0 Y ES ONO CUTOUTS KNIGHT FIRE PROTECTION CERTIFIES THAT THEY HAVE A CONTROL FEATURE TO ENSURE THAT ALL (DISCS) CUTOUTS (DISCS) ARE RETRIEVED. 0 YES ❑ NO HYDRAULIC DATAPLATE PROVIDED IF NO, EXPLAIN DATAPLATE 9 YES ❑NO REMARKS DATE LEFT IN SERVICE WITH ALL CONTROL VALVES OPEN: DOCUMENTS DOES THE OWNER HAVE A COPY OF NFPA #25 FOR THEIR REFERENCE. WES ❑NO KNIGHT FIRE PROTECTION, INC. LICENSE# KATIGHFP044LK ACCEPTANCE PRO ERTY REP. TITLE DATE o-� ib-mil �p8 K �\ F I E P O✓TFe C T 10N TITLE DATE AP 0 NG AUTHORITY TITLE DATE d I CERTIFY THAT THE INFORMATION HEREIN IS TRUE AND THAT THIS SPRINKLER SYSTEM WAS CERTIFICATION INSTALLED IN ACCORDANCE WITH THE RULES ADOPTED BY THE WASHINGTON ADMINISTRATIVE CODE AS ADMINISTERED BY THE STATE FIRE MARSHAL. RICH"D MGHT NAME OF CERTIFICATE OF COMPETENCY HOLDER SIGNATURE OF CERTIFICATE OF COMPETENCY HOLDER nrn nrin�'rr orncTo rn► n 30-03-5020 r KNIGHT FIRE PROTECTION, INC. 9702 LATHROP INDUSTRIAL DRIVE SW OLYMPIA, WA 98512-9188 (360) 786-8606 MATERIAL & TEST FAX 786-8722 REPORT FOR ABOVEGROUND PIPING "ON GUARD LICENSE NO. KNIGHFP044LK 24 HOURS A DAY" Procedure upon completion of work: Inspection and tests shall be made by the contractor's representative and witnessed by the AHJ. All defects shall be corrected and system left in service before contractor's personnel finally leave the job. A certificote shall be filled out and signed by both representatives. Copies shall be prepared for approving authorities, owners, and contractor. It is understood the owner's representative's signature in no way prejudices any claim against contractor for faulty material, poor workmanship, or failure to comply with approving authority's requirements or local or ' ances. PROPERTY NAME MASON CO. PUBLIC WORKS & MAINT. FACILITY, Bldg. 4 DATE 10 PROPERTY ADDRESS SR 101 & SR 102, MASON COUNTY, WASHINGTON SYSTEM LOCATION OR ID 4" Riser in N.W. corner of building REVIEWED AND ACCEPTED BY MASON COUNTY FIRE MARSHAL PLANS ADDRESS Shelton, Washington . INSTALLATION CONFORMS TO ACCEPTED PLANS 19 YES ❑NO EQUIPMENT USED IS APPROVED 14 YES ❑NO. IF NO, EXPLAIN HAS PERSON IN CHARGE OF FIRE EQUIPMEI\LT BEEN INSTRUCTED AS TO IR YES ❑NO NSTRUCTIONS CARE AND MAINTENANCE OF THE NEW EQUIPMENT AND THE LOCATION OF ALL CONTROL VALVES? HAVE COPIES OF THE FOLLOWING BEEN LEFT ON THE PREMISES: 1. SYSTEM COMPONENT CARE, AND MAINTENANCE INSTRUCTIONS N YES ❑NO 2. MAINTENANCE AGREEMENT N YES ❑NO YEAR OF ORIFICE TEMPERATURE SPRINKLERS MAKE MODEL MANUFACTURE SIZE QUANTITY RATING Tyco Mod. TY-3131 Upright 2007 .50 55 155 Tyco Mod. TY-3131 Upright 2007 .50 6 200 Tyco Mod. TY-3131 Upright 2007 .50 5 212 PIPE AND TYPE OF PIPE STEEL FITTINGS TYPE OF FITTINGS FLANGED, WELDED, CAST/MALLEABLE IRON, GROOVED, SOCK—IT WATER FLOW INDICATOR INFORMATION MAXIMUM TIME TO OPERATE THROUGH TEST CONNECTION ALARM LOCATION TYPE MAKE MODEL MIN. SEC. DEVICES DRY VALVE Q.O.D. MAKE MODEL SERIAL NO. MAKE MODEL SERIAL NO. VIkING W 00.7Y7o;L1 TIME TO TRIP * TIME WATER ALARM THROUGH TEST WATER AIR TRIP POINT REACHED OPERATED DRY PIPE CONNECTION PRESSURE PRESSURE AIR PRESSURE TEST OUTLET PROPERLY OPERATING MIN. SEC. PSI PSI PSI MIN. SEC. YES NO TEST WITHOUT Q.O.D. WITH Q.O.D. IF NO, EXPLAIN r HYDROSTATIC: HYDROSTATIC TEST SHALL BE MADE AT NOT LESS THAN 200 PSI FOR TWO HOURS OR 50 PSI ABOVE STATIC PRESSURE IN EXCESS OF 150 PSI FOR TWO HOURS. DIFFERENTIAL DRY-PIPE VALVE CLAPPERS SHALL BE LEFT OPEN DURING TEST TO PREVENT DAMAGE. ALL ABOVEGROUND PIPE TEST LEAKAGE SHALL BE STOPPED. DESCRIPTION PNEUMATIC: ESTABLISH 40 PSI AIR PRESSURE AND MEASURE DROP WHICH SHALL NOT EXCEED 1-1/2 PSI IN 24 HOURS. TEST PRESSURE TANKS AT NORMAL WATER LEVEL AND MEASURE AIR PRESSURE DROP WHICH SHALL NOT EXCEED 1-1/2 PSI IN 24 HOURS. ALL PIPING HYDROSTATICALLY TESTED AT 200 PSI FOR 2 HRS. IF NO, STATE REASON TESTS DRY PIPING PNEUMATICALLY TESTED H YES ❑NO ❑N/A EQUIPMENT OPERATES PROPERLY ❑ YES ❑NO ❑N/A KNIGHT FIRE PROTECTION, INC. CERTIFIES THAT ADDITIVES AND CORROSIVE CHEMICALS, SUCH AS SODIUM SILICATE OR DERIVATIVES OF SODIUM SILICATE, BRINE, OR OTHER CORROSIVE CHEMICALS WERE NOT USED FOR STOPPING LEAKS. DRAIN I READING OF GAGE LOCATED NEAR THE RESIDUAL PRESSURE WITH MAIN DRAIN VALVE TEST MAIN DRAIN: _ 1_ PSI OPEN WIDE 6F PSI UNDERGROUND MAINS AND LEAD INS TO THE SYSTEM RISERS WERE FLUSHED BEFORE CONNECTION WAS MADE TO THE ABOVEGROUND SPRINKLER PIPING. VERIFIED BY UNDERGROUND TEST CERTIFICATE 0 YES ❑NO OTHER EXPLAIN FLUSHED BY KNIGHT FIRE PROTECTION 14 YES ❑NO APPROVING AUTHORITY TITLE DATE NUMBER USED LOCATIONS NUMBER REMOVED TEST CAPS N WELDED PIPING 1$YES ❑ NO WELDING IF YES...... KNIGHT FIRE PROTECTION CERTIFIES THAT WELDING PROCEDURES COMPLY WITH THE REQUIREMENTS OF AT LEAST AWS B2.1 AND D10.9, LEVEL AR-3 0 YES ❑NO KNIGHT FIRE PROTECTION CERTIFIES THAT THE WELDING WAS PERFORMED BY WELDERS QUALIFIED IN COMPLIANCE WITH THE REQUIREMENTS OF AT LEAST ®YES ❑NO A�WS B2.1 AND D10.9, LEVEL AR-3 KNIGHT FIRE PROTECTION CERTIFIES WELDING WAS CARRIED OUT IN COMPLIANCE WITH A DOCUMENTED QUALITY CONTROL PROCEDURE TO INSURE THAT ALL DISCS ARE RETRIEVED, THAT OPENINGS IN PIPING ARE SMOOTH, THAT SLAG AND OTHER WELDING RESIDUE ARE REMOVED, AND THAT THE INTERNAL DIAMETERS OF PIPING ARE NOT PENETRATED 0 YES ONO CUTOUTS KNIGHT FIRE PROTECTION CERTIFIES THAT THEY HAVE A CONTROL FEATURE TO ENSURE THAT ALL (DISCS) CUTOUTS (DISCS) ARE RETRIEVED. 0 YES ❑NO HYDRAULIC DATAPLATE PROVIDED IF NO, EXPLAIN DATAPLATE N YES ❑ NO REMARKS DATE LEFT IN SERVICE WITH ALL CONTROL VALVES OPEN: �o DOCUMENTS DOES THE OWNER HAVE A COPY OF NFPA #25 FOR THEIR REFERENCE. ® YES ❑NO KNIGHT FIRE PROTECTION, INC. LICENSE# KNIGHFP044LK ACCEPTANCE PR ERTY REP TITLE DATE KN T F RE . TION TITLE DATE APP V NG AUTHORITY TITLE DATE I CERTIFY THAT THE INFORMATION HEREIN IS TRUE AND THAT THIS SPRINKLER SYSTEM WAS CERTIFICATION INSTALLED IN ACCORDANCE WITH THE RULES ADOPTED BY THE WASHINGTON ADMINISTRATIVE CODE AS ADMINISTERED BY THE STATE FIRE MARSHAL. RICHARD MIGHT NAME OF CERTIFICATE OF COMPETENCY HOLDER SIGNATURE OF CERTIFICATE OF COMPETENCY HOLDER I KNIGHT FIRE PROTECTION, INC. 9702 LATHROP INDUSTRIAL DRIVE SW OLYMPIA, WA 98512-9188 (360). 786-8606 MATERIAL & TEST FAX 786-8722 REPORT FOR ABOVEGROUND PIPING "ON GUARD LICENSE NO. KNIGHFP044LK 24 HOURS A DAY" Procedure upon completion of work: Inspection and tests shall be made by the contractor's representative and witnessed by the AHJ. All defects shall be corrected and system left in service before contractor's personnel finally leave the job. A certificate shall be filled out and signed by both representatives. Copies shall be prepared for approving authorities, owners, and contractor. It is understood the owner's representative's signature in no way prejudices any claim against contractor for faulty material, poor workmanship, or•foilure to comply with approving outhority's requirements or local or i onces. PROPERTY NAME MASON CO. PUBLIC WORKS & MAINT. FACILITY, Bldg. 3 °ATE a y. oFr PROPERTY ADDRESS SR 101 & SR 102, MASON COUNTY, WASHINGTON SYSTEM LOCATION OR ID 3" Riser in N.E. corner of building REVIEWED.AND ACCEPTED BY MASON COUNTY FIRE MARSHAL PLANS ADDRESS Shelton, Washington INSTALLATION CONFORMS TO ACCEPTED PLANS 0 YES ❑NO EQUIPMENT USED IS APPROVED N YES ❑NO IF NO, EXPLAIN HAS PERSON IN CHARGE OF FIRE EQUIPMENT BEEN INSTRUCTED AS TO 0 YES ❑ NO NSTRUCTIONS CARE AND MAINTENANCE OF THE NEW EQUIPMENT AND THE LOCATION OF ALL CONTROL VALVES? HAVE COPIES OF THE FOLLOWING BEEN LEFT ON THE PREMISES: 1. SYSTEM COMPONENT CARE, AND MAINTENANCE INSTRUCTIONS 39 YES ❑ NO 2. MAINTENANCE AGREEMENT 19 YES ❑ NO YEAR OF - ORIFICE TEMPERATURE SPRINKLERS MAKE MODEL MANUFACTURE SIZE QUANTITY RATING Tyco Mod. TY-3131 Upright 2007 .50 50 155 Tyco Mod. TY-3131 Upright 2007 .50 2 200 Tyco Mod. TY-3131 Upright 2007 .50 1 212 Tyco Mod. TY-3331 Sidewall 2007 .50 1 155 Tyco Mod. TY-3231 Pendent 2007 .50 1 155 Tyco Mod. TY-5237 EC Pendent 2007 .75 1 155 PIPE AND TYPE OF PIPE STEEL FITTINGS TYPE OF FITTINGS FLANGED, WELDED, CAST/MALLEABLE IRON, GROOVED, SOCK—IT WATER FLOW INDICATOR INFORMATION MAXIMUM TIME TO OPERATE THROUGH TEST CONNECTION ALARM LOCATION TYPE MAKE MODEL MIN. SEC. DEVICES v- -� 3-57 DRY VALVE Q.O.D. MAKE MODEL SERIAL NO. MAKE MODEL SERIAL NO. V(K,nl(r- F-1 W ova LI70 R I N TIME TO TRIP * TIME WATER ALARM THROUGH TEST WATER AIR TRIP POINT REACHED OPERATED DRY PIPE CONNECTION PRESSURE PRESSURE AIR PRESSURE TEST OUTLET PROPERLY OPERATING MIN. I SEC. PSI PSI PSI MIN. SEC. YES NO TEST WITHOUT Q.O.D. a d �� ( 3 WITH Q.O.D. IF NO, EXPLAIN r HYDROSTATIC: HYDROSTATIC TEST SHALL BE MADE AT NOT LESS THAN 200 PSI FOR TWO HOURS OR 50 PSI ABOVE STATIC PRESSURE IN EXCESS OF 150 PSI FOR TWO HOURS. DIFFERENTIAL DRY-PIPE VALVE CLAPPERS SHALL BE LEFT OPEN DURING TEST TO PREVENT DAMAGE. ALL ABOVEGROUND PIPE TEST LEAKAGE SHALL BE STOPPED. DESCRIPTION PNEUMATIC: ESTABLISH 40 PSI AIR PRESSURE AND MEASURE DROP WHICH SHALL NOT EXCEED 1-1/2 PSI IN 24 HOURS. TEST PRESSURE TANKS AT NORMAL WATER LEVEL AND MEASURE AIR PRESSURE DROP WHICH SHALL NOT EXCEED 1-1/2 PSI IN 24 HOURS. ALL PIPING HYDROSTATICALLY TESTED AT 200 PSI FOR 2 HRS. IF NO, STATE REASON TESTS DRY PIPING PNEUMATICALLY TESTED 0 YES ❑NO ❑N/A EQUIPMENT OPERATES PROPERLY ❑ YES ❑NO ❑ N/A KNIGHT FIRE PROTECTION, INC. CERTIFIES THAT ADDITIVES AND CORROSIVE CHEMICALS, SUCH AS SODIUM SILICATE OR DERIVATIVES OF SODIUM SILICATE, BRINE, OR OTHER CORROSIVE CHEMICALS WERE NOT USED FOR STOPPING LEAKS. DRAIN READING OF GAGE LOCATED NEAR THE RESIDUAL PRESSURE WITH MAIN DRAIN VALVE TEST MAIN DRAIN: PSI OPEN WIDE PSI UNDERGROUND MAINS AND LEAD INS TO THE SYSTEM RISERS WERE FLUSHED BEFORE CONNECTION WAS MADE TO THE ABOVEGROUND SPRINKLER PIPING. VERIFIED BY UNDERGROUND TEST CERTIFICATE OYES ❑NO OTHER EXPLAIN FLUSHED BY KNIGHT FIRE PROTECTION 0 YES ❑NO APPROVING AUTHORITY TITLE DATE TEST CAPS NUMBER USED LOCATIONS NUMBER REMOVED N WELDED PIPING ®YES ❑NO WELDING IF YES...... KNIGHT FIRE PROTECTION CERTIFIES THAT WELDING PROCEDURES COMPLY WITH THE REQUIREMENTS OF AT LEAST AWS B2.1 AND D10.9, LEVEL AR-3 N YES ❑NO KNIGHT FIRE PROTECTION CERTIFIES THAT THE WELDING WAS PERFORMED BY WELDERS QUALIFIED IN COMPLIANCE WITH THE REQUIREMENTS OF AT LEAST 0 YES ❑NO AWS B2.1 AND D10.9, LEVEL AR-3 KNIGHT FIRE PROTECTION CERTIFIES WELDING WAS CARRIED OUT IN COMPLIANCE WITH A DOCUMENTED QUALITY CONTROL PROCEDURE TO INSURE THAT ALL DISCS ARE RETRIEVED, THAT OPENINGS IN PIPING ARE SMOOTH, THAT SLAG AND OTHER WELDING RESIDUE ARE REMOVED, AND THAT THE INTERNAL DIAMETERS OF PIPING ARE NOT PENETRATED 0 YES p NO CUTOUTS KNIGHT FIRE PROTECTION CERTIFIES THAT THEY HAVE A CONTROL FEATURE TO ENSURE THAT ALL (DISCS) CUTOUTS (DISCS) ARE RETRIEVED. 0 YES ❑NO HYDRAULIC DATAPLATE PROVIDED IF NO, EXPLAIN DATAPLATE 0 YES ❑ NO REMARKS DATE LEFT IN SERVICE WITH ALL CONTROL VALVES OPEN: Iv• �yvg DOCUMENTS DOES THE OWNER HAVE A COPY OF NFPA #25 FOR THEIR REFERENCE. RYES ❑NO KNIGHT FIRE PROTECTION, INC. T LICENSE# KNIGHFP044LK ACCEPTANCE PR ERTY REP. TITLE DATE KN T FI PROTECTION TITLE DATE _ T€ . , APPROVING AUTHORITY TITLE DATE I CERTIFY THAT THE INFORMATION HEREIN IS TRUE AND THAT THIS SPRINKLER SYSTEM WAS CERTIFICATION INSTALLED IN ACCORDANCE WITH THE RULES ADOPTED BY THE WASHINGTON ADMINISTRATIVE CODE AS ADMINISTERED BY THE STATE FIRE MARSHAL. RICHARD KMGHT NAME OF CERTIFICATE OF COMPETENCY HOLDER SIGNATURE OF CERTIFICATE OF COMPETENCY HOLDER KNIGHT FIRE PROTECTION, INC. 9702 LATHROP INDUSTRIAL DRIVE SW OLYMPIA, WA 9851 2-91 88 (360) 786-8606 MATERIAL & TEST FAX 786-8722 REPORT FOR ABOVEGROUND PIPING ON GUARD LICENSE NO. KNIGHFP044LK 24 HOURS A DAY" Procedure upon completion of work: Inspection and tests shall be mode by the contractor's representative and witnessed by the AHJ. All defects shall be corrected and system left in service before contractor's personnel finally leave the job. A certificate shall be filled out and signed by both representatives. Copies shall be prepared for approving authorities, owners, and contractor. It is understood the owner's representative's signature in no way prejudices any claim against contractor for faulty material, poor workmanship, or.foilure to comply with approving authority's requirements or local &�di onces. PROPERTY NAME MASON CO. PUBLIC WORKS & MAINT. FACILITY, Bldg 2 DAT�D o PROPERTY ADDRESS SR 101 & SR 102, MASON COUNTY, WASHINGTON SYSTEM LOCATION OR ID 4" Riser In Fire Sprinkler Room 226 REVIEWED AND ACCEPTED BY MASON COUNTY FIRE MARSHAL PLANS ADDRESS Shelton, Washington INSTALLATION CONFORMS TO ACCEPTED PLANS 0 YES ❑NO EQUIPMENT USED IS APPROVED 14 YES ❑NO IF NO, EXPLAIN HAS PERSON IN CHARGE OF FIRE EQUIPMENT BEEN INSTRUCTED AS TO 14 YES ❑NO NSTRUCTIONS CARE AND MAINTENANCE OF THE NEW EQUIPMENT AND THE LOCATION OF ALL CONTROL VALVES? HAVE COPIES OF THE FOLLOWING BEEN LEFT ON THE PREMISES: 1. SYSTEM COMPONENT CARE, AND MAINTENANCE INSTRUCTIONS )SI YES ❑NO 2. MAINTENANCE AGREEMENT 14 YES ❑NO YEAR OF ORIFICE TEMPERATURE SPRINKLERS MAKE MODEL MANUFACTURE SIZE QUANTITY RATING Reliable Mod. DH-56 Sidewall 2007 .50 3 155 T c6 Mod. TY-4332 EC Sidewoll 2007 .50 1 155 Tyco Mod. TY-5137 EC Upright 2007 .75 24 155 Tyco Mod. TY-3131 Upright 2007 .50 6 200 Tyco Mod. TY-3131 Upright 2007 .50 113 155 Two Mod. TY-3331 Sidewall 1 2007 .50 1 155 Tyco Mod. TY-3231 Pendent 1 2007 .50 13 155 Tyco Mod. TY-5237 EC Pendent 1 2007 .75 18 155 PIPE AND. TYPE OF PIPE STEEL PV FITTINGS TYPE OF FITTINGS FLANGED, WELDED, CAST/MALLEABLE IRON GROOVED SOCK—IT WATER FLOW INDICATOR INFORMATION MAXIMUM TIME TO OPERATE THROUGH TEST CONNECTION ALARM LOCATION TYPE MAKE MODEL MIN. SEC. DEVICES i � � rt,:qy-P- VSR P -a DRY VALVE Q.O.D. MAKE I MODEL SERIAL NO. MAKE I MODEL SERIAL NO. TIME TO TRIP * TIME WATER ALARM THROUGH TEST WATER AIR TRIP POINT REACHED OPERATED DRY PIPE CONNECTION PRESSURE PRESSURE AIR PRESSURE TEST OUTLET PROPERLY OPERATING X MIN. SEC. PSI PSI PSI MIN. SEC. YES I NO TEST WITHOUT Q.O.D. WITH NSA Q.O.D. IF NO, EXPLAIN it HYDROSTATIC: HYDROSTATIC TEST SHALL BE MADE AT NOT LESS THAN 200 PSI FOR TWO HOURS OR 50 PSI ABOVE STATIC PRESSURE IN EXCESS OF 150 PSI FOR TWO HOURS. DIFFERENTIAL DRY-PIPE VALVE CLAPPERS SHALL BE LEFT OPEN DURING TEST TO PREVENT DAMAGE. ALL ABOVEGROUND PIPE TEST LEAKAGE SHALL BE STOPPED. DESCRIPTION PNEUMATIC: ESTABLISH 40 PSI AIR PRESSURE AND MEASURE DROP WHICH SHALL NOT EXCEED 1-1/2 PSI IN 24 HOURS. TEST PRESSURE TANKS AT NORMAL WATER LEVEL AND MEASURE AIR PRESSURE DROP WHICH SHALL NOT EXCEED 1-1/2 PSI IN 24 HOURS. ALL PIPING HYDROSTATICALLY TESTED AT 200 PSI FOR 2 HRS. IF NO, STATE REASON TESTS DRY PIPING PNEUMATICALLY TESTED 0 YES ❑NO ❑N/A EQUIPMENT OPERATES PROPERLY ❑YES ❑NO ❑N/A KNIGHT FIRE PROTECTION, INC. CERTIFIES THAT ADDITIVES AND CORROSIVE CHEMICALS, SUCH AS SODIUM SILICATE OR DERIVATIVES OF SODIUM SILICATE, BRINE, OR OTHER CORROSIVE CHEMICALS WERE NOT USED FOR STOPPING LEAKS. DRAIN READING OF GAGE LOCATED NEAR THE RESIDUAL PRESSURE WITH MAIN DRAIN VALVE TEST MAIN DRAIN: PSI OPEN WIDE PSI UNDERGROUND MAINS AND LEAD INS TO THE SYSTEM RISERS WERE FLUSHED BEFORE CONNECTION WAS MADE TO THE ABOVEGROUND SPRINKLER PIPING. VERIFIED BY UNDERGROUND TEST CERTIFICATE 14 YES ❑ NO OTHER EXPLAIN FLUSHED BY KNIGHT FIRE PROTECTION 0 YES ❑ NO APPROVING AUTHORITY TITLE DATE NUMBER USED LOCATIONS NUMBER REMOVED TEST CAPS N WELDED PIPING 14 YES ❑NO WELDING, IF YES...... KNIGHT FIRE PROTECTION CERTIFIES THAT WELDING PROCEDURES COMPLY WITH THE REQUIREMENTS OF AT LEAST AWS B2.1 AND D10.9, LEVEL AR-3 0 YES ❑NO KNIGHT FIRE PROTECTION CERTIFIES THAT THE WELDING WAS PERFORMED BY WELDERS QUALIFIED IN COMPLIANCE WITH THE REQUIREMENTS OF AT LEAST 0 YES ❑NO AWS B2.1 AND D10.9, LEVEL AR-3 KNIGHT FIRE PROTECTION CERTIFIES WELDING WAS CARRIED OUT IN COMPLIANCE WITH A DOCUMENTED QUALITY CONTROL PROCEDURE TO INSURE THAT ALL DISCS ARE RETRIEVED, THAT OPENINGS IN PIPING ARE SMOOTH, THAT SLAG AND OTHER WELDING RESIDUE ARE REMOVED, AND THAT THE INTERNAL DIAMETERS OF PIPING ARE NOT PENETRATED 0 YES 0 NO CUTOUTS KNIGHT FIRE PROTECTION CERTIFIES THAT THEY HAVE A CONTROL FEATURE TO ENSURE THAT ALL (DISCS) CUTOUTS (DISCS) ARE RETRIEVED. 0 YES ❑NO HYDRAULIC DATAPLATE PROVIDED IF NO, EXPLAIN DATAPLATE 0 YES ❑No REMARKS DATE LEFT IN SERVICE WITH ALL CONTROL VALVES OPEN: Iv O g DOCUMENTS DOES THE OWNER HAVE A COPY OF NFPA #25 FOR THEIR REFERENCE. KYES ❑NO KNIGHT FIRE PROTECTION, INC. LICENSE# KATIGHFP044LK ACCEPTANCE P ERTY REP. TITLE, ^_ DATE KNIG FIRE R EC N TITLE DATE F� io,-act-ov AP RO AUTH ' TY TITLE T DATE I CERTIFY THAT THE INFORMATION HEREIN IS TRUE AND THAT THIS SPRINKLER SYSTEM WAS CERTIFICATION INSTALLED IN ACCORDANCE WITH THE RULES ADOPTED .BY THE WASHINGTON ADMINISTRATIVE CODE AS ADMINISTERED BY THE STATE FIRE -MARSHAL. RICHM MGHT NAME OF CERTIFICATE OF COMPETENCY HOLDER SIGNATURE OF CERTIFICATE OF COMPETENCY HOLDER -iug_m_nnga KNIGHT FIRE PROTECTION, INC. 9702 LATHROP INDUSTRIAL DRIVE SW OLYMPIA, WA 98512-9188 (360) 786-8606 MATERIAL & TEST FAX 786-8722 REPORT FOR ABOVEGROUND PIPING ON GUARD LICENSE .NO. KNIGHFP044LK 24 HOURS A DAY" - Procedure upon completion of work: Inspection and tests shall be mode by the contractor's representative and witnessed by the AHJ. All defects shall be corrected and system left in service before contractor's personnel finally leave the job. A certificate shall be filled out and signed by both representatives. Copies shall be prepared for approving authorities, owners, and contractor. It is understood the owner's representative's signature in no way prejudices any claim against contractor for faulty material, poor workmanship, or failure to comply with approving authority's requirements or local inonces. PROPERTY NAME MASON CO. PUBLIC WORKS & MAINT. FACILITY, Bld . 1 DATE o- p /08� PROPERTY ADDRESS SR 101 & SR 102, MASON COUNTY, WASHINGTO SYSTEM LOCATION OR ID 3" Riser in Fire Sprinkler Room 136 REVIEWED AND ACCEPTED BY MASON COUNTY FIRE MARSHAL PLANS ADDRESS Shelton, Washington INSTALLATION CONFORMS TO ACCEPTED PLANS 0 YES ❑ NO EQUIPMENT USED IS APPROVED 0 YES ❑ NO IF NO, EXPLAIN HAS PERSON IN CHARGE OF FIRE EQUIPMENT BEEN INSTRUCTED AS TO N YES ❑ NO NSTRUCTIONS CARE AND MAINTENANCE OF THE NEW EQUIPMENT AND THE LOCATION OF ALL CONTROL VALVES? HAVE COPIES OF THE FOLLOWING BEEN LEFT ON THE PREMISES: 1. SYSTEM COMPONENT CARE, AND MAINTENANCE INSTRUCTIONS YES ❑ NO 2. MAINTENANCE AGREEMENT N YES ❑ NO YEAR OF ORIFICE TEMPERATURE SPRINKLERS MAKE MODEL MANUFACTURE SIZE QUANTITY RATING Reliable Mod. DH-56 Sidewall 2007 .50 8 155 Tyco Mod. TY-3180 BB1 2007 .50 6 155 Tyco Mod. TY-5137 EC Upright 2007 .75 4 155 Tyco Mod. TY-3131 Upright 2007 .50 17 200 Tyco Mod. TY-3131 Upright 2007 .50 2 155 Tyco Mod. TY-3331 Sidewall 2007 .50 1 6 1 155 Tyco Mod. TY-3231 Pendent 2007 .50 1 29 1 155 Tyco Mod. •TY-5237 EC Pendent 2007 .75 1 39 1 155 PIPE AND TYPE OF PIPE STEEL , QV C FITTINGS TYPE OF FITTINGS FLANGED, WELDED, CAST/MALLEABLE IRON, GROOVED SOCK—IT WATER FLOW INDICATOR INFORMATION MAXIMUM TIME TO OPERATE THROUGH TEST CONNECTION ALARM LOCATION TYPE MAKE MODEL MIN. SEC. DEVICES T DRY VALVE Q.O.D. MAKE MODEL SERIAL NO. MAKE MODEL SERIAL NO. Nll{- TIME TO TRIP * TIME WATER ALARM THROUGH TEST WATER AIR TRIP POINT REACHED OPERATED DRY PIPE CONNECTION PRESSURE PRESSURE AIR PRESSURE TEST OUTLET PROPERLY OPERATING MIN. SEC. PSI PSI PSI MIN. SEC. YES NO TEST WITHOUT Q.0.D. WITH N/A Q.O.D. IF NO, EXPLAIN