HomeMy WebLinkAboutCOM2013-00102 Furnances - COM Permit / Conditions - 10/24/2013 ' MASON COUNTY DEPT. OF COMMUNITY DEVELOPMENT Inspection Line (360)427-7262
Mason County Bldg. 3 426 W. Cedar P.O. Box 186 Phone: (360)427-9670, ext. 352
Shelton, WA 98584
i�
COMMERCIAL BUILDING PERMIT COM2013-00102
OWNER: MASON CO FIRE DISTRICT#11 RECEIVED: 10/14/201c
CONTRACTOR: OLYMPIC HEATING & COOLING 360-426-9945 LICENSE: OLYMPHC986BA EXP: 1/1/2014 ISSUED: 10/24/2011:
SITE ADDRESS: 130 E ISLAND LAKE RD SHELTON EXPIRES: 4/24/2014
PARCEL NUMBER: 420121260010
LEGAL DESCRIPTION: TR 1 OF NW NE
PROJECT DESCRIPTION: DIRECTIONS TO SITE:
FURNACES ISLAND LAKE RD FIRE STATION
General Information Construction &Occupancy Information
Type of Use: Fire Hall Insp.Area: No. of Units: Type of Constr.:
No of Bathrooms: Occ. Group:
Valuation: .
Type Work: MEC Fire Dist.: 11 No. of Stories: Exit Design. Load:
Building Height:
Pre-Manufactured Unit Information Square Footage Information
Make: Length: Lot Size:
Model: Width: Building:
Year: Serial No.: Basement: Parking Spaces:
Setback Information
Shoreline& Planning Information
Front: Ft. Shoreline: Ft.
Rear: Ft. Slope: Ft. Water Body: Shoreline Desig.:
Side 1. Ft. SEPA?: Comp. Plan Desig.:
Side 2: Ft.
Fire Protection System Information
Auto Fire Alarm System?: Emergency Key Box?: Standpipe?:
Auto Fire Sprinkler System?: Access Road?: Fire Extinguishers?:
Fixed Fire Suppression System?: Fire Hydrants?: Fire Lanes?:
COM2013-00102 Please refer to the following pages for conditions of this permit. Page 1 of 4
Plumbing Fixtures Mechanical Fixtures FLEs
Type Qty. Type Qty. Type By Date Amount Receipt
Furnace<100K 2 Mechanical Permit Fee TIN in/lAoni a�F sn St?nj�nn
Mechanical Base Fee -nA1 inmA/?m �'?R rn st9minn
Total $65.10
CASE NOTES FOR
COM2013-00102
CONDITIONS FOR
COM2013-00102
1) Contractor registration laws are governed under RCW 18.27 and enforced by the WA State Dept of Labor and Industries, Contractor Compliance
Division. There are potential risks and monetary liabilities to the homeowner for using an unregistered contractor. Further information can be
obtained at 1-800-6 982. The person signing this condition is either the homeowner, agent for the owner or a registered contractor according to
WA state law. X
2) Owner/Agent i responsible to post the assigned address and/or purchase and post private road signs in accordance with Mason County Title
14.28.
X
3) ALL ONSTRUCTION MUST MEET OR EXCEED ALL LOCAL CODES AND THE INTERNATIONAL CODE REQUIREMENTS AND OCCUPANCY
IS L MITED TO THE PERMITTED AND APPROVED CLASSIFICATION. ANY CHANGE OF USE OR OCCUPANCY WOULD RESULT IN PERMIT
REVOCATION. CHANGE OF USE MUST BE APPROVED PRIOR TO CHANGE. x
4) All building permits shall have a final inspection performed and approved by the Mason County Building Department prior to permit expiration. The
failure to request a final inspection or to obtain approval will be documented in the legal property records on file with Mason County as being
non-c m liant with Mason County ordinances and building regulations.
X
5) All ermits expire 180 days after permit issuance, or 180 days after the last inspection activity is performed. The Building Official may extend the
time for action for a period not exceeding 180 days, upon the receipt of a written extension request indicating that circumstances beyond the control
of the er it holder have prevented action from being taken. No more than one extension may be granted.
X
COM2013-00102 Page 2 of 4
L) ALL FURNACE INS IALLAI IUNS SHALL MEL I I HE MINIMUM LFFICILNCIES SL I FUR I H IN I HL CUKLN I LUI I IUN OF I HL
WASHINGTON STATE ENERGY CODE (WSEC). ANY PORTION OF THE MECHANICAL SYSTEM THAT IS ALTERED OR REPLACED SHALL
MEET T E MINIMUM STANDARDS SET FORTH IN THE WSEC AND INTERNATIONAL MECHANICAL CODE.
X
I uildings of unusually tight construction, fuel-burning appliances (excluding cooking appliances and domestic clothes dryers) shall obtain
combu ti n air from outside in accordance with the international codes.
X
CajZn monoxide alarms, listed as complying with UL 2075 shall be installed in accordance with manufacturer specifications and in accordance
with IRC Section R315.
Alarms shall be installed outside of each separate sleeping area in the immediate vicinity of the bedrooms and on each level of the dwelling.
X l
Heating equipment shall be sized in accordance to ICC/WSEC, Section R403.6. Heating and design load calculations for the purpose of sizing
HVAC systems are required and shall be calculated in accordance with accepted practice, including infiltration and ventilation. Design calculations
shall be available for inspection during inspection.
Referencing IRC M1601.4, all ducts, air handlers, filter boxes, and building cavities shall be sealed. All joints of duct systems and seams shall be
made substantially air tight by means of tapes, mastics, liquid sealants, gasketing or other approved closure systems. Closure systems used with
rigid fibrous glass ducts shall comply with UL181A and shall be marked 181A-P for pressure-sensitive tape, 181A-M for mastic or 181 A-H for
heat-sensitive tape. Closure systems used with flexible air ducts and flexible air connectors shall comply with UL181 B and shall be marked
181 B-FX for pressure-sensitive tape or 181 B-M for mastic. Duct connections to flanges of air distribution system equipment or sheet metal fittings
shall be mechanically fastened. Mechanical fasteners for use with flexible nonmetallic air ducts shall comply with UL 181 B and shall be marked
181 B-C. Crimp joints for round metal ducts shall have a contact lap of at least 1-1/2 inches (38 mm) and shall be mechanically fastened by means
of at least three sheet-metal screws or rivets equally spaced around the joint. Closure systems used to seal metal ductwork shall be installed in
accordance with the manufacturer's installation instructions.
Duct tape is NOT permitted as a sealant on any ducts. When ducts are located in unheated spaces the ducts hall be insulated to R-8
DUCT TIGHTNESS TESTING shall be conducted by person(s)trained to perform such testing. A signed affidavit documenting test results in
accordance to IECC/WSEC Section R403.2.2 shall be provided to the Mason County Building Department prior to the final occupancy inspection.
Affidavit forms are available on at the WSU-Energy Program website titles, "Duct Leakage Affidavit" or"Duct Leakage Testing Results (Existing
Constr ction)." Duct tightness testing is not required if the air handler and all ducts are located within the heated space.
X
This permit ecomes null and void if work or construction authorized is not commenced within 180 days, or if construction or work is suspended for a period of 180 days at any
time after ork is commenced. Evidence of continuation of work is a progress inspection within the 180 day period. Final inspection must be approved before building can be
occupied. Proof of continuation of work is by means of a progress inspection. The owner or the agent on the owners behalf, represents that the information provided is accurate
and grants employees of Mon�ountyaccess he above described property and structure for review and inspection.
OWNER OR AGENT: DATE: `T3 1
COM2013-00102 Page 3 of 4
n
O
N CONCRETE MECHANICAL MANUFACTURED HOME D'
Footings i Setbacks Date By Ribbons O
Gas Piping Z
o Interior Date By Interior-Date By Date By 0
N Exterior Date By Exterior-Date Bt, O
I NS ULAT1 ON Seup m
Point Load!Isolated Footings Date By �
BG i SLAB INSULATION
Date By Data By FIRE DEPARTMENT m
Foundation Walls Floors Date By 0
N
Date By Data By DECKS
FRAMING walls Date By n
Date By Data By PROPANE TANKS
PLUMBING vautt Date By
Date BY OTHER
Groundwork Attic
Date By Date By Type
Date By
D.W.v DRYWALL Type: 0O
Int.Brace wall
Date BY Date B Oate By k
Y FINAL INSPECTION N
Water Line Fire Separation o
Date By Date By Date It I Z /� ByLL+O to
O
Pass or Request Inspect.
Type of Insp. Fail Date Date Done ByComments ,C1
I Ak( P,5, ,' I� 5'/3 11 Jz 13 1�101�
v
00
(n
ro
A
O
A
MASON COUNTY
Department of Community Development
INSPECTION CARD and
CERTIFICATE OF OCCUPANCY*
PO BOX 186, 426 W Cedar ST, Shelton WA 98584
General Questions: (360) 427-9670 ext 352 Inspection Requests: (360) 427-7262
Permit Number COM2013-00102 Date 10/24/2013 Issued By
Project FURNACES
Site Address 130 E ISLAND LAKE RD SHELTON
Applicant MASON CO FIRE DISTRICT#11
Contractor OLYMPIC HEATING & COOLING License Number OLYMPHC986BA
Con. Phone 360-426-9945 Expiration Date 01/01/2014
Primary Code Occupancy Division
Use Fire Hall Type of Construction Exit Design Load
Public Works Access /Driveway Other
Health Dept Septic Well
Planning Dept Site Inspection
Fire Marshal Fire Apparatus Access Fire Sprinkler
Auto Fire Alarm Hood and Duct
Other Final
Building Dept Building Official: Community Development Designee
Concrete Setbacks Slab
Footing Perimeter Ret. Wall / Bulkhead
Footing Interior Footing Decks/ Porches
Foundation Stem Walls Other
Rough-In Groundwork Plumbing Plumbing
Groundwork Mechanical Other
Groundwork Gas Pipe
Gas Piping
_Framing
Mechanical
Insulation Slab Ceiling
Floor Vaulted Ceiling
Walls Vapor Barrier
Other
Wallboard Nailing Interior Wall Brace Panels Fire walls
Other
Final Building
Manuf. Home Setbacks Setup
Concrete Foot/ Runners Final
Other
APPROVED PLANS MUST BE ONSITE FOR ALL INSPECTIONS
*THIS STRUCTURE MAY NOT BE USED FOR OCCUPANCY UNITL ALL APPLICABLE FINAL INSPECTIONS ARE
COMPLETED
DO NOT PROCEED BEYOND EACH STAGE OR COVER WORK UNTIL APPROVALS ARE GIVEN.
POST THIS CARD IN A CONSPICUOUS PLACE ON THE FRONT OF THE PREMISES CONVENIENT FOR MAKING
REQUIRED ENTRIES.
ALL PERMITS EXPIRE 180 DAYS AFTER PERMIT ISSUANCE OR 180 DAYS AFTER LAST INSPECTION ACTIVITY IS
PERFORMED.
OWNER/AGENT IS RESPONSIBLE FOR CALLING FOR ALL INSPECTIONS
PRIOR TO CALLING FOR FINAL INSPECTION, ALL CONDITIONS OF THE PERMIT MUST BE MET.