HomeMy WebLinkAboutFIR2008-00044 Commercial Sprinkler - FIR Permit / Conditions - 12/11/2008 MASON COUNTY DEPT. OF COMMUNITY DEVELOPMENT Inspection Line(360)327-7262
Mason County Bldg. 3 426 W. Cedar P.O. Box 186 Phone: (360)427-9670,ext. 352
br%0
Shelton, WA 98584
FIRE PROTECTION PERMIT FIR2008-00044
APPLICANT: SHELTON PRESBYTERIAN CHURCH
CONTRACTOR: KNIGHT FIRE PROTECTION RECEIVED: 6/6/2008
(360) 786-8606 LICENSE: KNIGHFP044LK SITE ADDRESS: 1430 E SHELTON SPRINGS RD SHELTON ISSUED: 12/11/2008
PARCEL NUMBER: 420122190002 EXPIRES: 6/11/2009
LEGAL DESCRIPTION: PCL 1 OF BLA#07-17 PTN TR C S 12/55
PROJECT DESCRIPTION: Commercial Sprinkler.
GENERAL INFORMATION System Information
Type of Use: COMM
Fire District: Sprinkler Heads: Audible Switches: Pull Stations:
Hood & Duct t: N Flow Switches: Visual Devices: Door Releases:
Dry Chemical?: N Pressure Switches:: Smoke Detectors: Duct Detectors:
Zones: Heat Detectors:
Wet Chemical?: N
SprinkleR: Y
Standpipe?: N SQUARE FOOTAGE FEES
Monitoring Company: First Floor:
Monitoring Phone No.:() - Second Floor: Type Amount Due Amount Paid
Auto Fire Alarm?:N Third Floor;: Sprinkler System Permit $552.85 $552.85
Sprinkler System Plan $359.35 $359.35
Total: $912.20 $912.20
FI R2008-00044 Please refer to the following pages for conditions of this permit. 1 of 4
` CASE NOTES
FIR2008-00044
CONDITIONS FOR
FIR2008-00044
1.) The system is required to be in full compliance with NFPA 13, a compliance report is required to be provided to the fire marshal at the time of the final
inspects,
X
The limited supply water supply system tank, foundation, piping and supply plans need to be submitted for review.
X_ - -
This permit becomes null and void if work or construction authorized is not commenced within 180 days,or if construction or work is suspended for a period of 180 days at anytime after work is
commenced. Evidence of continuation of work is a progress inspection within the 180 day period. Final inspection must be approved before building can be occupied. Proof of continuation of work is
by means of a progress inspection.The ownerorthe agent on the owners behalf, represents that the information provided is accurate and grants employees of Mason County access to the above
described property and structure for re vie nd inspection.
OWN ER OR AGENT: (ii/� J DATE:
v
FIR2008-00044 Please refer to the following pages for conditions of this permit. 2 of 4
MASON COUNTY FIRE MARSHAL
>I� Mason County Bldg.III 426 W Cedar St
PO BOX 186 Shelton,WA 98584
(360)427-9670 Ext.273 _
Permit#
Mason County Fire Protection System Permit Application
6A
Incomplete application will not be accepted
Owner: AM &kh", aaxl�hone#:
Mailing Address: City: State:1_&jA_Zip:as'T
15cz) L s s
Site Addre c State: Zip:
,,'ao1.a C/o oaa
Parcel #:412W)17S60Q,?0 Legal Description:
Lien/Title Holder:
Address: City: State: Zip: _
Contractor: r Phone #:
Address•��� Mo_f))D-V,_ City: C( State:JI , J� Zip:
Contractor Registration#: / Expiration DateS�G
Building Square Footage (existing&proposed): lst /1 2nd / 3rd /
Building Use: CJ,UA/ JA Occupancy Classification: Construction Type:
Type of System: Type of Work:
Sprinkler: Wet)L Dry New System:
Standpipe: Wet Dry Modification:
AFA:
Hood &Duct:
Dry Chem:
Wet Chem:
Fire Pump:
UL certified Monitorinompany: Phone#:
Contractors Bid Price: $
\\CLUSTERI_HOME_SERVER\HOME\COMMON\BUILDING\Fire Protection System Permit Application.doc
J
Plan Submittal Requirements
Your plan submittal shall include the following: r
• Plans shall be on standard 24"x 36"paper, drawn to scale with dimensions and north arrow.
• Site and Floor plan with cross sectional and exterior elevations.
• Location of occupancy and/or area separation walls,partitions, stairway enclosures, concealed spaces, etc.
• Cut sheets and/or references for all new devices.
• Location/description of all new and existing devices.
• Battery calculations.
• Wiring diagrams per floor or zone overlaid on an accurate floor plan.
• Electrical riser diagram showing all zones, circuits, devices, and end—of—line resistors.
• Hydraulic calculations.
• Copy of Contractors bid.
Fees
The permit fee will be assessed based on the submitted contractor bid for the project or a minimum of$150.00.
A plan review fee will be calculated at 65%of the permit fee and is due upon submittal of permit application.
Contractor's Affidavit
I certify that I am a currently registered contractor in the State of Washington. I am aware of the ordinance requirements regulating
the work for which the permit is issued and certify that all work will be in compliance with this ordinance. No changes will be made
without first obtaining approval from the Mason County Fire Marshal.
By: Date: —
\\CLUSTERI_HOME_SERVER\TOME\COMMON\BUILDING\Fire Protection System Permit Application.doc
MASON COUNTY FIRE MARSHAL
Mason County Bldg.III 426 W.Cedar
P.O.Box 186 Shelton,Washington 98584
(360)427-9670 Ext.273
CODE ENFORCEMENT FIRE INSPECTIONS FIRE INVESTIGATION PUBLIC EDUCATION
November 17, 2006
FIRE PROTECTION PLAN FOR SHELTON PRESBYTERIAN CHURCH
CONSTRUCTION TYPE: V-B
SQ. FEET: 10,844
OCC. CLASS: A-3
FIRE FLOW AVAILABLE: NO
FIRE FLOW DEMAND: 3025 GPM
FIRE PROTECTION OPTIONS:
1. Access fire flow from city water system, with automatic fire alarm
system.
2. Install limited supply fire sprinkler system combined with a fire
alarm system.
3. Divide the building into four areas with 2-hour firewalls, resulting in
four 2700 square foot (+/-) fire areas, 'th automatic fire alarm
system.
Craig ugen Dave Salzer
Mason County Fire Marshal City of Shelton Fire Marshal
Z TO BE KEPT IN THE
10 00 PARCEL FILE