HomeMy WebLinkAboutBLD2023-00208 Add cover Patio, Shearwall Upgrade - BLD Inspections - 4/9/2024 ` \\ MASON COUNTY 615 W.Alder St.Bldg 8,SHELTON,WA 98584
SHELTON:360-427-9670, EXT 352
COMMUNITY SERVICES
a% BELFAIR:360-275-4467, EXT 352
Buildin4 Plan nmg.Env ironmental Health.Community Health ELMA:360-482-5269,EXT 352
-` www.co.mason.wa.us
INSPECTION CARD AND CERTIFICATE OF OCCUPANCY"
To schedule an inspection call or visit http://www.co.mason.wa.us/community-services/bld-inspection.php ti
Permit Number BLD2023-00208 Date Issued 04/27/2023 Issued ByCIL
Project ADD ATTACHED COVERED PATIO&UPGRADE THE SHEARWALL AROUND ENTIRE SFR c� �{
Site Address 1069 W KAMILCHE LN
Applicant MARUCA AARON M&EMILY N
Contractor
Contractor Phone
Primary Code 201C8 IBC,IRC,IFC,IEC,IMC,& Type
UP
Permit Type CARPORT/DECK/COVERED Occupancy
-APPROVED PLANS MUST BE ONSITE FOR ALL INSPECTIONS.
-DO NOT PROCEED BEYOND EACH STAGE OR COVER WORK UNTIL APPROVAL IS GRANTED.
-THIS CARD MUST BE POSTED IN A CONSPICUOUS LOCATION, FRONT OF THE PREMISES IS BEST FOR MAKING ENTRY.
-ALL PERMITS EXPIRE 180 DAYS AFTER THE PERMIT IS ISSUED OR 180 DAYS AFTER DATE OF LAST INSPECTION.
-OWNER/AGENT IS RESPONSIBLE FOR REQUESTING ALL INSPECTIONS THROUGH FINAL INSPECTION.
"THIS STRUCTURE MAY NOT BE USED OR OCCUPIED UNTIL ALL APPROVALS ARE GRANTED.—
PRIOR TO CALLING FOR FINAL INSPECTION,ALL CONDITIONS OF THE PERMIT MUST BE MET
Public Works Access/Driveway Other
Health Septic Well
Deptartment
Planning Site Inspection
Department
Fire Marshall Fire Apparatus Access Fire Sprinkler
Auto Fire Alarm Hood and Duct
Other Final
Building
Department Building Official: Community Services Designee
Concrete Setbacks f,go -.23 DO Slab
Footing Perimeter Point load Footing
Footing Interior Footing Decks/Porches
Foundation Stem Walls Other
Rough-In Groundwork Plumbing Framing -10_2-3 t)
Groundwork Mechanical Plumbing
Groundwork Gas Pipe Mechanical
Gas Piping Shear Wall Nailing b6n
Underfloor
Other
Insulation Slab Ceiling
Floor Vaulted Ceiling
Walls Vapor Barrier
Other
Wallboard Interior Wall Brace Panels Fire Walls
Nailing
Other
Final Building 4— -at( pep
Manufactured Setbacks Setup
Home
Concrete Foot/Runners Final
Other
/7f
��� - f41 �_ l^a3 D� s�44
r
MASON COUNTY 360-427-9670 Shelton ext.352
COMMUNITY SERVICES 36 60-482-52 Belfair ext.352
360-482-5269 Elma ext.352
Building, Planning,Environmental Health,Community Health
615 W.Alder St.Bldg.8 - Shelton,WA 98584 www.masoncountywa.gov
CORRECTION/INSPECTION REPORT
PERMIT/CASE NUMBER: �TZ2.023-002O8'
ADDRESS/LOCATION: &I W K,anr�cHE
FINDINGS:
14cy-D how�-' A F-4ZY 1.E c'r�cLl� Pro j- CJC,ne.� 1<41r
rD^ti jEyjt Va-r o 1
-C rezo,'t �'hck cower} C,4j;4,o,, -are -tc 4- aQ.
6e U►��iTIGr4�jcJ� /� pi+llwtar o- - I� <t✓ /�M�n] wli�l
fltrrc�.� cQ:I
DDD,HSo�Q NIA-SonJ cv ANT y t��t.Ga
Items listed above must be corrected to gain compliance.
❑ THIS IS NOT A COMPLETE INSPECTION
❑ This structure has been inspected by Mason County Building Department and the items listed
above are in VIOLATION of Mason County laws and/or ordinances.
❑ Call for re-inspection when corrections are made before proceeding with any further work.
Make corrections, items will be checked on the next inspection.
OK to FAmi t Acwn tiTio., -6 eo-r,: ( 46o✓e-
Date: ,-)L7-23 ❑ Please contact our office regarding possible
Department: II09 structural damage incurred by recent
"natural/man made"disasters.This is NOT a
Inspector: �Eo CORRECTION NOTICE.
DO NOT REMOVE THIS TAG
MCC14.12
1 L
MASON COUNTY 360427-9670 Shelton ext.352
360-275-4467 Belfair ext.352
COMMUNITY SERVICES 360482-5269 Elma ext.352
Building,Planning, Environmental Health,Community Health
615 W.Alder St. Bldg.8 - Shelton,WA 98584 www.masoncountywa.gov
CORRECTION/INSPECTION REPORT
PERMIT/CASE NUMBER: 9W-2023-D0Xe
ADDRESS/LOCATION: 10j6qlj Af Jj L-CHE LA°
FINDINGS:
RAmxs N AIL SAS
rA
uo4 oS <Auws W-Tdi-1• 1ord, couei: ri-eid
conk ►on il— c //
/OV4- r i eGr O-A Fr171C.4d
a NAP5 AnFBC 1 ALI
Items listed above must be corrected to fain compliance.
❑ THIS IS NOT A COMPLETE INSPECTION
❑ This structure has been inspected by Mason County Building Department and the items listed
above are in VIOLATION of Mason County laws and/or ordinances.
Call for re-inspection when corrections are made before proceeding with any further work.
❑ Make corrections, items will be checked on the next inspection.
❑ OK to
Date: 8'1 ❑ Please contact our office regarding possible
Department: S&D structural damage incurred by recent
Inspector: "natural/man made" disasters.This is NOT a
CORRECTION NOTICE.
DO NOT REMOVE THIS TAG
MCC14.12
Mason County
Mason County - Division of Community Development
615 W.Alder St.
imp Building 8
Shelton, WA 98584
360-427-9670 ext 352
www.masoncountywa.gov
B DD2023-00208 CARPORT/DECK/ COVERED
PROJECT DESCRIPTION: ADD ATTACHED COVERED PATIO& ISSUED: 04/27/2023
UPGRADE THE SHEARWALL AROUND ENTIRE SFR
SITE ADDRESS: 1069 W KAMILCHE LN SHELTON EXPIRES: 10/24/2023
PARCEL: 319074490031
APPLICANT: MARUCA AARON M&EMILY N OWNER: MARUCA AARON M&EMILY N
1069 W KAMILCHE LN 1069 W KAMILCHE LN
SHELTON, WA98584 SHELTON,WA98584
1.253.985.3634
VALUATIONS: FEES: Paid Due
Project Valuation (BID, 6000.00 $6,000.00 Plan Check Fee $169.63 $0.00
ESTIMATION..) State Fee-Residential $6.50 $0.00
Covered Deck/Carport 374.00 $8,228.00 Technology Surcharge $8.61 $0.00
Planning Review Fee $240.00 $0.00
Building Permit Fee $260.97 $0.00
Total: $14,228.00 Totals : $685.71 $0.00
REQUIRED INSPECTIONS
Setback Inspection Shear Wall Nailing
Footing Inspection Framing Inspection
Foundation Wall Inspection BLD-Final Inspection
CONDITIONS
* All construction must meet or exceed all local and state ordinances in addition to the International Codes requirements as
adopted and amended by Mason County and the State of Washington. Occupancy is limited to the approved and permitted
classification. Any non-approved change of use or occupancy would result in permit revocation.
The foundation/footing must be placed on undisturbed, firm-native soil. Proper frost depth shall be observed below grade
in undisturbed soils.
Printed by:Genie Mcfarland on:04/27/2023 11:21 AM
Page 1 of 3
Mason County
Mason County - Division of Community Development
615 W. Alder St.
Building 8
Shelton, WA 98584
360-427-9670 ext 352
www.masoncountywa.gov
CARPORT/DECK/ COVERED BLD2023-00208
CONSTRUCTION PROCESS TO BE FIELD CORRECTED AS REQUIRED PER MASON COUNTY BUILDING
DEPARTMENT AND THE ADOPTED BUILDING CODE.
The construction of the permitted project is subject to inspections by the Mason County Building Department. All
construction must be in conformance with the international codes as amended and adopted by Mason County. Any
corrections, changes or alterations required by a Mason County Building Inspector shall be made prior to requesting
additional inspections.
Proposed structure(s) must maintain a minimum of a 5' setback from all property lines, easements and 25' from all County
and State Road right of ways. Setbacks are measured from the furthest projection of the structure.
X
* All RED stamped approved plans are required to be on-site for inspection purposes. If an inspection is called for and
plans are not available on site, then approval will not be granted. In addition, a re-inspection fee (refer to current fee
schedule, minimum 1 hour) will be charged and must be collected by the Building Department prior to any further inspections
being performed or approvals granted.
REQUIREMENTS FOR ROOF COVERINGS. Roof coverings shall be applied in accordance with the applicable
provisions of the current code and the manufacturer's installation instructions.
A drip edge shall be provided at eaves and gables of shingle roofs.
All building permits shall have a final inspection performed and approved by Mason County Building Department prior to
permit expiration. The failure to request a final inspection or to obtain approval will be documented in the legal property
records on file with Mason County as being non-compliant with Mason County ordinances and building regulations.
OWNER/BUILDER acknowledges submission of inaccurate information may result in a stop work order or permit
revocation. Acknowledgement of such is by signature below. I declare that I am the owner, owners legal representative, or
contractor. I further declare that I am entitled to receive this permit and to do the work as proposed. I have obtained
permission from all the necessary parties, including any easement holder or parties of interest regarding this project. The
owner or authorized agent represents that the information provided is accurate and grants employees of Mason County
access to the above described property and structure(s)for review and inspection. This permit/application becomes null &
void if work or authorized construction is not commenced within 180 days or if construction work is suspended for a period of
180 days. PROOF OF CONTINUATION OF WORK IS BY MEANS OF INSPECTION. INACTIVITY OF THIS PERMIT
APPLICATION OF 180 DAYS WILL INVALIDATE THE APPLICATION.
* PROOF OF CONTINUATION OF WORK IS BY MEANS OF INSPECTION. INACTIVITY OF THIS PERMIT APPLICATION
OF 180 DAYS WILL INVALIDATE THE APPLICATION.
* Any changes in proposed construction shall be reviewed by the engineer or architect of record and submitted in writing to
the Mason County Building Department prior to construction. All engineering and/or architectural documents are a part of
the approved set of plans and shall remain attached thereto. If documents are removed, approval will not be granted. In
addition, a re-inspection fee (refer to current fee schedule, minimum 1 hour)will be charged and shall be collected by the
Building Department prior to any further inspections being performed or approvals granted.
Printed by:Genie Mcfarland on:04/27/2023 11:21 AM
Page 2 of 3
Mason County
at Mason County - Division of Community Development
615 W. Alder St.
Building 8
Shelton, WA 98584
360-427-9670 ext 352
www.masoncountywa.gov
CARPORT/DECK/ COVERED BLD2023-00208
A separate inspection in addition to the inspections required in the IBC, Section 110 shall be required in accordance with
the 2018 IBC, Section 1705.12.2 and Section 1707.1. The additional inspection is required when shear wall fastener
spacing is required to be 4 inches or less. The shear wall schedule shown on sheet G100 designate TYPE 2 AND 3 WALLS
with fastener spacing 4 inches or less.
The required inspection may be performed by the Mason County Building Department, a WABO certified inspector, certified
to inspect lateral connections, the Engineer of record (EOR), or an authorized representative of the (EOR). The special
inspectors duties and responsibilities shall be as specified in Chapter 17. When a third party inspector is used to perform the
inspection, special inspection reports shall be submitted to the Mason County Building Department, 615 W Alder St, Shelton,
WA 98584 and also available on site for review by the Building Official. Inspection reports shall be completed and submitted
to the Mason County Building Department in a timely manner and shall be submitted prior to the framing inspection of said
project.
EPDXY INSPECTION IS REQUIRED PRIOR TO INSTALLATION. PRIOR TO INSPECTION ALL HOLES MUST BE
DRILLED, PROPERLY CLEANED, AND EPDXY AVAILABLE ONSITE. INSPECTION WILL OBSERVE EPDXY AND
ANCHOR INSTALLATION
• ALL STRAPS MUST BE VERIFIED PRIOR TO COVER
• PLANNING SETBACKS
Front: 25'
Rear and Side: 20'
Measured from furthest projection
Subject to EH setbacks
hereby certify that I have read and examined this application and know the same to be true and correct.
All provisions of Laws and Ordinances governing this type of work will be complied with whether
specified herein or not. The granting of a permit does not presume to give authority to violate or cancel
the provisions of any other state/local law regulating construction or the performance of construction.
Issued By:
Contractor or Authorized nt: Date: �7 3
Printed by:Genie Mcfarland on:04/27/2023 11:21 AM Page 3 of 3
1235 East 4`'Avenue Suite 101
Olympia,WA 98506
360-754-9339
Fax 360-352 2044
—� —� office@mc2-inc.com
MC SQUARED
INCunroltATE1)
July 3, 2023
Aaron Maruca
1069 West Kamilche Lane
Shelton, WA 98584
RE: Maruca Remodel, 1069 West Kamilche Lane, Shelton, WA 98584, MC Squared
Incorporated Project#2022-0368
Dear Aaron,
All holdowns have been installed correctly and at the locations indicated by the structural plans.
You have provided photos of each holdown installed and its location.
The current nailing of at least(2) 1Od nails per lx6 horizontal shiplap sheathing at each stud is
acceptable to meet the shearwall nailing requirements.
If you have any questions, please contact me at(360) 754-9339.
Sincerely,
MC Squared, Inc.
Ryan D. Egolf,PE
Engineer
� D •
of aoG,0
e
0 22094 0 �u 1
FS �FG]STER��
S�ONAL E�
07 / 03 / 23
STRUCTURAL.•FOUNDATION•MARINE