Loading...
HomeMy WebLinkAboutButane Refrigerant Room - OT General - 8/7/2015 &L Kl(.,HMONU Er-J [31NEEF' I E3 A division ofir�irnoaaa���u�e�rui; �r�a _. „ ._....... ..,.. www.RichmondSystems.com August 7, 2015 Revised February 2, 2016 Whole Cannabis, LLC 50 West Westfield Court Shelton, WA 98584 AT Steve Chamberlain Ref: Butane Refrigerant Use (Revision 1) Extractor Room Building E By: George M Richmond, P.E. This letter summarizes the results of a code investigation for use of a Butane based essential oils extractor application. Assumptions: The equipment contains 8 lbs of Butane used through the process equipment as a solvent with transfer of the Butane between containers,accomplished via a refrigeration type process. In other words, through phase changes. The Butane transfers as a gas and is collected, condensed, and recovered as a liquid. The code documents which appear to govern are: • ASHRAE Standard 15-2013 ASHRAE Standard 34-2013 • 2012 International Building Code • 2012 International Fire Code • 2012 International Fire Code Washington State Emergency Rule — Chapter 38 • 2012 International Mechanical Code • 2014 National Electrical Code Below are my findings from the code documents. Code Review 1. ASHRAE Standard 34; Designation and Safety Classifications of Refrigerants a. ASHRAE standard 34 identifies Butane and Iso-Butane as refrigerants 600 and 600a respectively. b. Both Butane refrigerants have safety classifications of A3. A indicates they are not toxic to humans and 3 indicates they are at the highest flammability classification for refrigerants. 8365 Hogum Bay Lane NE I Olympia,WA 98516 1 Office 360.956.0384 i Fax 360.352.1275 2. ASHRAE Standard 15; Safety Standard for Refrigeration a. Section 4, Occupancy Classification: I interpreted this use as Industrial and believe it falls under section 4.1 .6, Industrial Occupancy. i. Not open to the public. ii. Access by authorized persons only iii. used to manufacture, process, or store goods. b. Section 5; Refrigerating System Classification i. Section 5.1.1 A direct system where the evaporator or condenser is in direct contact with the space. ii. Section 5.2.1 High Probability System. Any system where a leakage of refrigerant will enter the occupied space. c. Section 6; Refrigerant Safety Classification, Section 6.1, Single Compound Refrigerant. Classification A3 as indicated above from Standard 34. d. Section 7, Restrictions on Refrigerant Use i. Section 7.2 limits Refrigeration Volumes based on table 4.1 and 4.2 in ASHRAE Standard 34. Table 4.1 limits Butane volumes to 0.15 Ibs / 1,000 cubic feet (Mcf). The processing space is 3.725 Mcf. This section limits the allowable refrigerant to 0.55 Ibs of Butane. ii. Section 7.2.2 Industrial Occupancies and Refrigerated Rooms 1. This section will allow higher volumes of refrigerant as long as seven conditions are met. a. The 31d condition requires the floor area per occupant of not less than 100 square feet OR the space is provided with egress directly to the outdoors or into approved building exits. b. The 6th condition requires Class I, Div 2 electrical equipment if the volume will exceed 25% of the lower flammability limit (LFL) for the flammable refrigerant. iii. Section 7.4 Location in a Machinery Room or Outdoors 1. This section allows higher volumes of refrigerant as long as ALL system components are located in a Machinery Room or Outdoors. a. The processing space appears to meet all code requirements for a Machinery Room. b. Section 7.4.2 Flammable Refrigerants requires Machinery Rooms to be constructed to Sections 8.11 and 8.12. i. Section 8.11 requires tight fitting, self closing doors opening to the outdoors or to an exit pathway. 8.11.2.1 requires a detector properly located which will provide audible and visual alarm in the event of refrigerant detection. More requirements in this section. RICHMOND ENGINEERING 8365 Hogum Bay Lane NE Olympia,WA 98516 Phone(360)956-0384 Fax(360)352-1275 Page 2 of 6 ii. 8.11.5 requires mechanical ventilation to flush the space should a leak be detected. Flushing air rates were calculated at 282 cfm. Makeup air source cannot be from an adjacent occupied space. In addition to the air flush required airflow, this section requires continuous airflow at 0.5 cfm per square foot or 20cfm per person while occupied. iii. Section 8.11.6 requires no open flames or combustion equipment within the Machinery Room. 2. Section 8.12 Machinery Room Special Requirements a. All of the following are REQUIRED i. No flame producing device or hot surface over 80OF installed in the room. ii. Doors communicating with the building shall be gasketed, labeled, fire doors. iii. Walls, floor, and ceiling shall be tight and non- combustible construction. One hour construction. iv. Must have a door that opens directly to the outdoors or through an exit vestibule. v. All pipes piercing the interior walls ceiling or floor shall be tightly sealed. vi. When refrigerants of class A3 are used, the machinery room shall conform to Class I, Div 2 of the National Electric Code. 3. 2012 International Fire Code a. Chapter 38, Marijuana Processing and Extraction Facilities (WAC Emergency Ruling) i. Location: Room dedicated to extraction process; not to be used for any other use, including storage. ii. Staffing: The space shall be continuously staffed by personnel trained in the extraction process and all emergency procedures. iii. Systems, Equipment and Process: 1. Listing/Certification: All equipment shall be listed for the specific use. If it is not listed, the system shall have a designer of record. If the designer of record is not licensed Washington State professional engineer, the system shall be peer reviewed by a licensed Washington professional engineer. iv. Construction Requirements: 1. Room Location and Egress: One or more exits shall be provided, swinging in the direction of travel and provided with an automatic closer and panic hardware. The room shall not RICHMOND ENGINEERING 8365 Hogum Bay Lane NE Olympia,WA 98516 Phone(360)956-0384 Fax(360)352-1275 Page 3 of 6 enter directly into an exit, exit passageway, horizontal exit or along the sole egress path from another portion of the building. 2. Ventilation: Room shall be provided with a dedicated hazardous exhaust system complying with Section 5004.3 for all solvents other than water. Operation of system shall be continuous. a. Ventilation rates shall limit concentration of solvents to below 25% of the lower flammability limit (See calculations below) OR Class I Division II electrical requirements shall apply to the entire room. 3. Electrical: a. All electrical components shall be interlocked with the hazardous exhaust system and the gas detection system. When system is not operational, all electrical devices and lighting shall be disabled. b. Emergency Power: Emergency power shall be provided for lighting, ventilation, gas detection systems, emergency alarm systems, and fire extinguishing systems, when provided. 4. Alarms: A gas detection system shall be provided with a threshold no greater than 25% of the lower flammability limit (LFL) of materials (25% of the LFL for butane is 0.4%). 5. Fume Hoods: A fume hood is not required for this process. Butane is not defined as a liquid per the IFC since it has a boiling point below 68 OF. b. Chapter 50, Hazardous Materials— General Provisions i. Section 5003.1.1 limits the maximum allowable quantity per control area to 150 pounds as liquefied flammable gas, or 1,000 cubic feet at NTP as a gaseous flammable gas per table 5003.1.1(1). The amounts used in this process are below these requirements and must meet the requirements of sections 5001 and 5003. 1. Equipment Requirements: a. Design Standards: 5003.2.1 and 5003.2.2 - All containers, cylinders, tanks piping, tubing, valves and fittings shall be designed and constructed in accordance with approved standards. Pressure vessels shall comply with ASME Boiler and Pressure Vessel Code. b. Installation: 5003.2.8 - Equipment shall be braced and anchored in accordance with seismic design requirements of the IBC. It is assumed no stationary tanks will be utilized during this process. c. Maintenance: 5003.2.6 - All equipment shall be maintained in an operable condition. Any defective RICHMOND ENGINEERING 8365 Hogum Bay Lane NE Olympia,WA 98516 Phone(360)956-0384 Fax(360)352-1275 Page 4 of 6 devices or equipment shall be removed from service, repaired or disposed of in an approved manner. d. Testing: 5003.2.9.2 - All alarms and gas detection systems shall be tested not less than annually. 2. MSDS Sheets: 5003.4— MSDS Sheets shall be readily available on site. 3. Signage: a. 5003.5 — Hazard Identification signs per NFPA 704 for butane (Health Hazard: 1, Flammability: 4, Instability: 0) shall be placed on all containers, tanks and at all entrances to locations where butane is stored, dispensed, used or handled. b. 5003.7 — No smoking signs shall be placed in extraction rooms. 4. Construction Requirements: a. Fire Separation: 5003.8.3.1 and 5003.8.3.4 - Room shall be separated from the remainder of the building by Fire Barriers with 1-hour rating per the IBC Section 707 and 711. Floors shall have a 2-hour rating. 5. General Safety Requirements: a. Specific safety and security requirements are listed in section 5003.9 b. Electrical equipment is required to be installed and maintained per NFPA 70. 6. Handling and Transportation: a. Protective caps are required on all valves per 5003.10.1. b. 5003.10.2 and 5003.10.3 - Whenever liquid containers are transported that are over 5 gallons, a cart or truck shall be used. Cart shall provide a stable base and have a means of restraining each individual container. Carts or trucks shall not be left unattended within any part of a means of egress. ii. Chapter 5004.3 (per section 3802.4.3): 1. Ventilation shall be 1 cfm per square foot, or 70 cfm (minimum) for the storage area and operate continuously. 2. Ventilation system shall have a manual shutoff control outside the room with a break-glass switch labeled "Ventilation System Emergency Shutoff". 3. Exhaust intake shall be within 12 inches of the finished floor. 4. Make-up air discharge and Exhaust inlet locations shall be in opposite corners of the room. 5. Exhaust air shall not be recirculated to occupied areas. 4. 2012 International Mechanical Code a. Chapter 5: Exhaust Systems RICHMOND ENGINEERING 8365 Hogum Bay Lane NE Olympia,WA 98516 Phone(360)956-0384 Fax(360)352-1275 Page 5 of 6 i. Hazardous Materials System Requirements 502.8.1.1 — Same requirements as listed in section 5004.3 of the 2012 IFC. 5. 2014 National Electrical Code a. Chapter 500: Hazardous (Classified) Locations i. 500.5 - Classifications of Locations. 1. This section specifically lists locations containing oil-extraction equipment using volatile flammable solvents as being a Class I, Division 1 . ii. 500.7 — Protection Techniques. 1. This section lists explosion proof equipment and Intrinsic Safety as a permitted protection techniques for this Class I Division 1 locations. Quick calculations for 8 Ibs of Butane in our 3275 cubic foot room and knowing that 1.6% by volume is the Butane LEL, leads to; 8lbs of butane will occupy 52.4 cubic feet at atmospheric pressure. 25% of 1.6% LEL = 0.4%. 0.4% of 3275 cubic feet = 13 cubic feet of Butane allowable. The 8 Ibs of Butane is more than four times the allowable. In summary, the space will be required to be constructed with 1-hour fire barriers with a 2- hour floor. All doors for the room shall be gasketed and labeled fire doors. The egress doors will need to open directly to the outdoors or into an exit vestibule. The space will be required to exhaust 70 CFM (minimum) continuously with an intake on the opposite side of the room as the exhaust and the exhaust intake shall be within 12 inches of the floor. Upon detection of butane concentrations above 0.4%, exhaust shall increase to 282 CFM (minimum) and all electrical devices shall be disabled. The exhaust system, alarm system and lighting will be required to be on emergency power. All electrical systems are required to be explosion proof or intrinsically safe. RICHMOND ENGINEERING 8365 Hogum Bay Lane NE Olympia,WA 98516 Phone(360)956-0384 Fax(360)352-1275 Page 6 of 6