HomeMy WebLinkAboutPAR2014-00013 - PAR Letters / Memos - 7/13/2016 MASON COUNTY (360) 427-9670 Shelton ext.352
® tea" DEPARTMENT OF COMMUNITY DEVELOPMENT (360) 275-4467 Belfair ext. 352
BUILDING•PLANNING• FIRE MARSHAL (360)482-5269 Elma ext. 352
Mason County Bldg, III, 426 West Cedar Street
Shelton, WA 98584 www.co.masonma.us
Date: 07/13/2016
RE: Pre-Submission Conference
PAR2014-00013
Parcel Number: 42\002-10-00020
Dear Applicant,
Please find enclosed a computer-generated report summarizing the results of your pre-submission
conference on 3/19/2014 If you have questions regarding the summary report, please do not hesitate to
call the appropriate staff member.
The various staff members, the departments they represen and their telephone extensions are listed
below:
DEPARTMENT STAFF MEM ER EXTENTSION INITIALS
Fire Inspector/Comm. Dev. Jeromy Hicks 282 JNH
Building/Comm. Dev. Debbera Coker - DLC
Environ. Health Spec./Public Health Cindy Waite 353 CEW
-Eng. Tech/Public Works Fred Perryman 625 FJP
Planner/Comm. Dev. Grace Miller 360 GBM
Planner/Comm. Dev. Rebecca Hersha 287 RDH
Planner/Comm. Dev. Allan Borden 365 AHB
Planner/Comm. Dev Michael MacSer is 571 MMS
Stormwater Eng./Public Works Loretta Swansor 769 LGS
The comments are based on the pro'ect discussed during t e pre-submission conference. Any changes or
alterations to the original proposal may significantly change the permit requirements. In this case a
second pre-submission conference will most likely be required to discuss the changes.
Information provided to the prospective applicant during t�e pre-submission conference is based on
Mason County regulations in effect 4t the time of the conference. Revised or new regulations could affect
a future development application. A�pre-submission conference does not vest a future development
application.
If further assistance is needed please contact us at 360.427.9670 ext. 352 or www.co.mason.wa.us.
016
/2
Case Activity Listing s7/1 7/133 AM
IF
Case #: PAR2014-00013
�� Parcel #: 420021000020
Description: CITY OF SHELTON IS PROPOSING TO EXPAND ITS EXISTING WATER SUPPLY SYSTEM THROUGH THE CONSTRUCTION
OF A NEW PRESSURE ZONE CALLED THE UPPER MOUNTAIN VIEW PRESSURE ZONE UMVPZ).
PARA10 Application Received 3/4/2014 None GMM 3/4/2014 GMM
PARB60 Fire Marshal Review 3/4/2014 3/19/2014 None DONE LAW 3/19/2014 LAW
A copy of title 14 chapter 14.18 of the Mason County Code for group A water systems(Fire Flow)and a copy of ordinace 04-31 title 14 chapter 14.17 of the Mason County Code for Fire apparatus access
road requirement.The plans submitted will need to comply with both standards A permit will be required
PARB40 Environ. Health Review 3/4/2014 3/19/2014 __ None_ ___I ONF. LB__ I B 3/21/2n t a GBM
No Environmental Health Department review is required for this proposal,per Lee Boad,Environmental Health Specialist.
PARB50 Public Works Review 3/4/2014 3/19/2014 None DONE FJP FJP 3/21/2014 GBM
A Road Access Permit(RAP)will be needed for the access to Public Works Dr.Access will need to be finalized prior to the final approval of the building permit
RAP was given to applicant and can be turned in to Public Works y
PARB20 Building Plan Review 3/4/2014 3/24/2014 None DONE LAW 3/24/2014 LAW
The structural design will need to be per chapter 16 of the International Buildind code,a soils report showing the barring capacity is required.
Pagel of 3 CaseActivity..rpt
Case Activity Listing 7/13/2016
8:40:17AM
Case #: PAR2014-00013
Parcel #: 420021000020
Description: CITY OF SHELTON IS PROPOSING TO EXPAND ITS EXISTING WATER SUPPLY SYSTEM THROUGH THE CONSTRUCTION
OF A NEW PRESSURE ZONE CALLED THE UPPER MOUNTAIN VIEW PRESSURE ZONE UMVPZ .
PARB10 Planning Review 3/4/2014 3/19/2014 None DONE GBM GBM 3/25/2014 GBM
Grace Miller attended meeting on behalf of the Planning Department The property is Zoned as Public Institutional.The applicable Planning Dept requirements include the following criteria and requirements:
1)Airport Overlay Zone-The property is located within an Airport Overlay Zone,regulated by the Airport Overlay Ordinance 17.16.010.The applicable criteria of section 17.60.070 Airspace Protection
Areas-Height Limitations(2)(B) 1 through 3 apply.Once you receive the documentation/approval from the FAA,please submit it to the Permit Assistance Center so that we may review and verify compliance
with this ordinance has been completed.This will be an administrative decision.
2) Aquifer Recharage Area-The project is located on a Class II(Highly Susceptible)Critical Aquifer Recharge Area.Aquifers are regulated by he Mason County Resource Areas Ordinance 17.01.080.The
Title -Form must be-completed and-recorded within the 'Office.-Then a copy to the Planting Dept for theme 3 hiscan be-done e
during the apptteattorrPracr'ss-off
either the Land Modification Permit or Building Permit.The project does not require a Special use or Mason Environmental Permit because of the use.
3)Resource Ordinance-Fish&Wildlife Habitat Critical Areas Ordinance Section 17.01.110:The pocket gopher is designated within this chapter as a state threatend species.Therfore,a Habitat Management
Plan addressing their presence on the site is to be submitted for review with the SEPA that the City will be processing and as part of the county applications or prior to county applications as part of the SEPA
process.
w
4)SEPA-The Planning Department concurs that the City of Shelton will be lead agency for the SEPA Determination.
5)Stormwater Plan-The Stormwater Plan and checklist is to be submitted to the Planning Department as part of the Land Modification Permit Application.It will then be routed to Public Works for review
for compliance with y's stormwater ordinance as part of the lion:Ysumay wish 44 ;_pt.iof to submittal,if you haveany qttestion& � --
Please let us know if you have any questions Thank you.
PARA910 Meeting 3/19/2014 None DONE PIB 4/18/2014 P1B
PAR2014-00013
APPLICANT: JERRY HAUTH-CITY OF SHELTON
MEETING DATE&TIME: WEDS,MAR 19TH,2014 10:45111:00- 12:00 pm
PARCEL NUMBER: 42002-10-00020
SITE ADDRESS: DAYTON AIRPORT ROAD
PROJECT DESCRIPTION: CONSTRUCTION OF(2)WATER TANKS
LOCATION: BLDG III,425 W.CEDAR STREET,SHELTON WA 98584
PLANNER: GRACE MILLER,ext 360
ENVIRONMENTAL HEALTH: LEE BOAD,ext 547
Notes sent.
Page 2 of 3 CaseActivity xpt
016
/2
Case Activity Listing 87/1 7/133 AM
Case #: PAR2014-00013
Parcel #: 420021000020
Description: CITY OF SHELTON IS PROPOSING TO EXPAND ITS EXISTING WATER SUPPLY SYSTEM THROUGH THE CONSTRUCTION
OF A NEW PRESSURE ZONE CALLED THE UPPER MOUNTAIN VIEW PRESSURE ZONE (UMVPZ).
PARA910 Meeting 10/6/2014 None DONE DLC 10/7/2014 DLC
Met with Jerry Hauth and Kelly Mayo to go over information that will be submitted soon to construct 1 water tower and an accessory shack less than 120 sf. Hoping to construct an additional water tower as
well.
1)Jery will provide engineer est of cost in order to calculate the permit fees Gave permit valuation info to Kelly M who may calculate fees
2)Based upon use of the structure the risk category in accordance with IBC 1604.5 is IV. As a result structural observation. In addition staff will verify that design is prepared for the risk category.
3)We agreed that the access road may be 12-ft wide in accordance with MCC 14.17.060 and 10-ft wide around water tank properly prepared will comply with access standards
The following are notes from J Hicks via email to DLC addressing fire code review.
Here are my notes from the plan meeting we had this afternoon
1. Fire Hydrants. These will need to be placed down Public Works Dr.every 300-500 feet depending on past notes from Larry. The hydrants will support 1750 gpm for buildings at 500 feet and 5500 gpw
300 feet. This will need to be evaluated for future growth since this spacing will change fire flow in the respective areas around Public Works Drive. Hydrants may need to be added in the future to meet fire
flow to address future development.
- 2 Install_Knox Box per
3. Install compact drive surface capable of supporting the weight of fire apparatus 10 feet wide with a 12'unobstructed width and 13.5'vertical clearance per MC Title 14.
4. Our office will review the water distribution to ensure that it meets current standards for fire flow. I imagine that a 12"main will be installed,but we can talk about this if there are any issues.
5. Install approved turn around at end of road at/around water tank.
If you have any questions please let me know.
Jeromy
PARA800 Documents Received 10/7/2014 None DONE DLC 10/7/2014 DLC
10.7.2014 emails between Hauth and DLC ioncluding recap sent to attendees from MC staff.see documents attached.
Page 3 of 3 CaseActivity..rpt