HomeMy WebLinkAboutMiles Sand Gravel Addition Alarm - FIR Plot / Site Plans - 1/5/2007Symbol Legend
Make / Model No.
Qty.
Li
4-6 N2.2
r:?EOL EOL
F.c�7`
any •110cd
LD
F•;
H
H
45 •
D&F•
D&FI
4-3
D&F'
D&F
{D28`F2
(H
(H
Fire Alarm Plan
1/8" = 1' - 0"
NEW
SHOP
From
FACP
D&F
110cd
N1-4
EOL
North
EXISTING
1-1
035
H
o-C2
03-4
O
o-E
N1-2
75cd
S
o-C2
2-1
EOL
60cd
01.3
0-A2
1-2
1-4
Efil F - ---• -�--
EOL
Building Data
ADDRESS: 3100 W. Franklin St.
Shelton, WA 98584
TAX PARCEL NUMBER: 420242400180
CODE:
2003 International Codes
with Washington State Amendments (WAC 51-50)
IMC 2003
UPC 2003
WSEC 2003
WSIAQ 2003
TYPE OF CONSTRUCTION: V-B
OCCUPANCY: Existing- S-1, M
New - S-1
BUILDING AREA:
Existing - 3,200
New - 3,200
Total - 6,400 SF
Vicinity Map
1235m_'
1160Oft
06 Yahoo! Ow
Wire Legend
A
ZONE #1
(2) #18 AWG. FPLR (FIRE RATED SOLID COPPER CABLE)
B
ZONE #2
(2) #18 AWG. FPLR (FIRE RATED SOLID COPPER CABLE)
C
ZONE #3
(2) #18 AWG. FPLR (FIRE RATED SOLID COPPER CABLE)
D
ZONE #4
(2) #18 AWG. FPLR (FIRE RATED SOLID COPPER CABLE)
E
N.A.C. #1
(2) #12 AWG. FPLR (FIRE RATED SOLID COPPER CABLE)
F
N.A.C. #2
(2) #12 AWG. FPLR (FIRE RATED SOLID COPPER CABLE)
G
DOOR RELEASE CKT.
(2) #18 AWG. FPLR (FIRE RATED SOLID COPPER CABLE)
Zone Descriptions
1. OFFICE DETECTION.
2. OFFICE ABOVE CEILING DETECTION.
3. EAST SHOP DETECTION.
4. WEST SHOP DETECTION.
5. -10. SPARES.
DEDICATED 120VAC CIRCUIT FOR
PRIMARY POWER
SILENT KNIGHT
5208
10 FIRE ALARM
CONTROL
PANEL
BATTERY
BATTERY
12 VDC
12 VDC
12 A.H.
12 AM.
Riser
Diagram
14:411zR-ct Rd
�Ft3�rrd to I_
tAilSeqflgt
Aim
Shalton-_MaRd:
.�r
Sequence
of
Operations
SMOKE DETECTOR
HEAT DETECTOR
MANUAL PULL STATION
SYSTEM TROUBLE
AUDIBLE & VISUAL ALARM INDICATION
@ FACP / ANNUCIATOR LCD DISPLAY
•
•
•
ACTIVATE NOTIFICATION DEVICES
TRANSMIT ALARM SIGNAL TO CENTRAL STATION
AUDIBLE & VISUAL TROUBLE INDICATION
@ FACP / ANNUCIATOR LCD DISPLAY
•
TRANSMIT TROUBLE SIGNAL TO
CENTRAL STATION
•
ACTIVATE CLOSURE OF COILING
OVERHEAD FIRE DOOR
•
•
•
TO ALARM CENTER, INC.
FOR UL CENTRAL STATION
MONITORING
RELAY OUTPUT#1
COILING FIRE DOOR RELEASE
RELAY OUTPUT #2 (SPARE)
RELAY OUTPUT #3 (SPARE)
RELAY OUTPUT #4 (SPARE)
STROBE
SYNC.
MODULE
01 8 800
[ I [ ]N.A.C. #2
N.A.C. #3 (SPARE)
N.A.C. #4 (SPARE)
N.A.C.#1
FACP
FIRE ALARM CONTROL PANEL
SILENT KNIGHT
5208
1
0
PHOTOELECTRIC SMOKE DETECTOR
ESL
429C
3
0
135° RATE OF RISE HEAT DETECTOR
EDWARDS
281 B-PL
10
194° FIXED TEMP. HEAT DETECTOR
LOCATED ABOVE CEILING
EDWARDS
284B-PL
1
I�
MANUAL PULL STATION
wall mount @ 48° A.F.F. to bottom of device
SILENT KNIGHT
PS -SA
4
HORN / STROBE COMBINATION
wall mount @ 80" A.F.F. to bottom of device
cd = candela rating of strobe light
GENTEX
GEC3-24WR
5
xxcd
STROBE LIGHT
wall mount @ 80" A.F.F. to bottom of device
cd = candela rating of strobe light
GENTEX
GES3-24WR
2
WP8xxcd
10" BELL WITH ADJACENT
WEATHERPROOF STROBE LIGHT
wall mount @ 12' -0" A.F.G. to bottom of device
cd = candela rating of strobe light
BELL MBA 10--24
STROBE GENTEX
WGES24-75WR
1
1
0
JUNCTION BOX
N/A
EOL
INDICATES END OF LINE DEVICE
N/A
N/A
Flag Notes
CONNECT COILING OVERHEAD DOOR TO CLOSE
UPON ACTIVATION OF GENERAL FIRE ALARM.
ALV13
k,1 l e__- : _ r-N 646_ t
fe_r- N r P'Pr 72- G d- .1) c- 4-k
ns�c_L�c��i'oY1
e_cl--?
ALL APP-;CA-_- CODES SHALL AP i.Y..
L_
V.Tt Mlle
PROJECT NAME: Miles Sand and Gravel
Building Addition
3100 W. Franklin St.
Shelton, WA 98584
DATE: 12/11 /06
SYSTEM TYPE: FIRE ALARM AND DETECTION
DRAWN BY: J. FOSSETi
SCALE: AS SHOWN CONTRACTORS ALARMCIO55CW
LICENSE NO.
DATE REVISION DATE
APPROVED BY:
REVISION
A
ACE
ACE FIRE & 1-800-354-1555
SECURITY SYSTEMS
A DIVISION OF ALARM CBTIER. MO
PO BOX 3363 - LACEY WA 98509-3363
SHEET NO.
FA7
1 of 1