HomeMy WebLinkAboutFIR Plot / Site Plans - 8/15/2023Ai Mason Co Fire Marshal
Approved with Conditions
08/01/2023 2:47:38 PM
NORTH MASON REGIONAL FIRE AUTHORITY -RESIDENCE
Conditions:
- System shall be subject to an acceptance test
which includes receiving print out from the central
station of all devices tested
1801 E TRAILS END DR
BELFAIR, WA 98528
FIRE ALARM SYSTEM
GENERAL NOTES
1. THESE DRAWINGS DEPICT GENERAL LOCATIONS OF LIFE SAFETY EQUIPMENT & FIELD DEVICES. EXACT
ROUTING OF CONDUITS TO BE DETERMINED IN THE FIELD BY THE INSTALLING CONTRACTOR TO SUIT
CONDITIONS.
2. ALL FIRE ALARM SYSTEM WIRING SHALL BE CLEAR FROM SHORTS, OPENS AND GROUNDS.
3. SHOULD ANY CONDITIONS EXIST THAT DIFFER FROM WHAT IS INDICATED ON THESE DRAWINGS WHICH
CAUSE MAJOR DEVIATIONS IN THE WORK SHOWN, THE CONTRACTOR SHALL CONTACT THE DESIGNER IN A
TIMELY MANNER SO AS NOT TO IMPAIR THE CONSTRUCTION SCHEDULE.
4. CONTRACTOR IS RESPONSIBLE FOR MAKING AND OBTAINING APPROVAL FOR ALL NECESSARY ADJUSTMENTS
IN CIRCUITING AS REQUIRED TO ACCOMMODATE THE RELOCATION OF EQUIPMENT AND/OR DEVICES WHICH
AREAFFECTED BY ANY AUTHORIZED CHANGE.
5. THE POWER CIRCUIT TO THE FACP AND TO THE FIRE ALARM POWER SUPPLIES SHALL BE ON A DEDICATED
120V, 20A BRANCH CIRCUIT BREAKER, AND SHALL HAVE A RED MARKING, LOCK -ON PROVISION AND SHALL BE
IDENTIFIED AS "FIRE ALARM CIRCUIT CONTROL." THE LOCATION OF THE CIRCUIT DISCONNECT MEANS
(CIRCUIT BREAKER) SHALL BE PERMANENTLY IDENTIFIED AT THE FIRE ALARM CONTROL UNIT.
6. ANY SMOKE DETECTOR HEAD INSTALLED BEFORE THE BUILDING IS CLEANED AND ACCEPTED SHALL BE
COVERED TO PROTECT FROM DUST.
7. INSTALLATION OF DEVICES SHALL BE IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS. POWER
LIMITED AND NON -POWER LIMITED FIELD WIRING MUST BE INSTALLED WITHIN THE FACP ENCLOSURE IN
ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS.
8. ALL WIRING SHALL BE INSTALLED ACCORDING TO NFPA 70 (NEC).
9. FIRE ALARM CIRCUITS EXTENDING BEYOND ONE BUILDING AND RUN OUTDOORS SHALL BE INSTALLED IN
ACCORDANCE WITH NFPA 70 ARTICLES 760, 770, 725 AND 800 WHERE APPLICABLE.
10. ALL WIRING, INCLUDING SHIELDS MUST BE DRY AND FREE OF SHORTS AND GROUNDS.
11. ALL SHIELDED WIRE MUST HAVE SHIELD CONTINUITY AT FULL LENGTH OF THE WIRE.
12. ONLY FIRE ALARM SYSTEM WIRING CAN BE RUN IN THE SAME CONDUIT.
13. MAINTAIN 40 PERCENT MAXIMUM CONDUIT FILL RATIO AS PER NEC REQUIREMENTS.
14. EXISTING CONDUITS MAY BE USED BY THE INSTALLATION CONTRACTOR AS DEEMED NECESSARY, HOWEVER,
ANY EXISTING CONDUIT WILL BE USED ONLY IF CONDUITS MEET CURRENT STANDARDS AND CODES.
15. THE FIRE ALARM SYSTEM SHALL BE MONITORED BY A CENTRAL UL LISTED MONITORING STATION.
16. ALL CEILINGS ARE ASSUMED TO BE 10' A.F.F., SMOOTH CONSTRUCTION UNLESS NOTED OTHERWISE.
SHEET INDEX
SHEET #
SHEET DESCRIPTION
FA-00
COVER SHEET
FA-01
PROJECT INFORMATION
FA-02
MAIN FLOOR PLAN
FA-03
WIRING DIAGRAM
SCOPE OF WORK
NEW MANUAL AND AUTOMATIC FIRE ALARM SYSTEM IN A NEW RESIDENTIAL SPACE. NEW FIRE ALARM PANEL IS
BEING INSTALLED ALONG WITH NOTIFICATION DEVICES AS PER THE APPLICABLE CODES. SPRINKLER
WATERFLOW SWITCH IS BEING MONITORED TO ACTIVATE NOTIFICATION DEVICES UPON ALARM.
CONTRACTOR INFO
SYSTEM DESIGNER/INSTALLER
NAME: INTELLISYSTEMS, INC.
EMAIL: info@intelli-systems.com
PHONE #: 360-895-7995
ADDRESS: 1950 Pottery Ave — Suite 19, Port Orchard, WA 98366
DRAWINGS PREPARED BY
JEM SECURITY LLC
hmadeira@jemsecurity.com
480-977-3555
MONITORING COMPANY
NAME: AvantGuard Monitoring
PHONE #: 877-206-9141
ADDRESS: 4699 Harrison Blvd, Ogden, UT 84403
APPLICABLE CODES
INTERNATIONAL BUILDING CODE - 2018 ED.
INTERNATIONAL MECHANICAL CODE - 2018 ED.
UNIFORM PLUMBING CODE - 2018 ED.
INTERNATIONAL FUEL GAS CODE - 2018 ED.
INTERNATIONAL ENERGY CONSERVATION CODE - 2018 ED.
NATIONAL ELECTRICAL CODE - 2017 ED.
INTERNATIONAL FIRE CODE - 2018 ED.
ADA STANDARDS FOR ACCESSIBLE DESIGN - 2010 ED.
NFPA 72 2019 EDITION
0
LEJ
0_
W
U
Z
W
0
W
Op00
_ N
I— 0 Ln
D Z
< W
W Cn Q
ce
Q
J � �
Q Q
ZWLL
J O�W
5cD
W-
oe
z
0
I—
O
Z
REVISION:
FIRST RELEASE
/\
SHEET DESCRIPTION:
FIRE ALARM SYSTEM
COVER SHEET
DRAWN BY: JEM SYSTEMS
DATE:
06.16.2023
SCALE:
N.T.S
SHEET:
FA-OO
1 OF 4
BUILDING DATA
OCCUPANCY GROUP: R3
WORK AREA: 2,039 SQFT
FIRE PROTECTION: FULLY SPRINKLERED
NUMBER OF STORIES: 1
TYPICAL MOUNTING HEIGHTS
1. NFPA 72 201917.15.6 THE OPERABLE PART OF EACH MANUAL FIRE ALARM BOX SHALL BE NOT LESS THAN
42in AND NOT MORE THAN 48in FROM THE FINISHED FLOOR.
2. NFPA 72 2019 17.15.9.4 MANUAL FIRE ALARM BOXES SHALL BE LOCATED WITHIN 5ft OF EACH EXIT
DOORWAY ON EACH FLOOR.
3. NFPA 72 2019 18.4.9.1 IF CEILING HEIGHTS ALLOW, AND UNLESS OTHERWISE PERMITTED BY 18.4.9.2
THROUGH 18.4.9.5, WALL -MOUNTED APPLIANCES SHALL HAVE THEIR TOPS ABOVE THE FINISHED FLOORS
AT HEIGHTS OF NOT LESS THAN 90in AND BELOW THE FINISHED CEILINGS AT DISTANCES OF NOT LESS
THAN 6in.
4. NFPA 72 2019 18.4.9.3 IF COMBINATION AUDIBLE/ VISIBLE APPLIANCES ARE INSTALLED, THE LOCATION OF
THE INSTALLED APPLIANCE SHALL BE DETERMINED BY THE REQUIREMENTS OF 18.5.5. (SEE NOTE 5).
5. NFPA 72 2019 18.5.5.1 WALL -MOUNTED APPLIANCES SHALL BE MOUNTED SUCH THAT THE ENTIRE LENS IS
NOT LESS THAN 80in. AND NOT GREATER THAN 96in ABOVE THE FINISHED FLOOR OR AT THE MOUNTING
HEIGHT SPECIFIED USING THE PERFORMANCE BASED ALTERNATIVE OF 18.5.5.7.
TOP
OF
CABINETS
MAX 6'
MIN 15"
BPS
ADA
MAX
(48")
'NOTE 1
ANN
MAX 5'
(60')
'NOTE 2
C '
FACP
FINISHED
FLOOR
NOT LESS
THAN 90"
AND
BELOW
CEILING
NOT LESS
THAN 6"
'NOTE 3
MAX 8' (96")
MIN 6'-8"
(80")
'NOTE 4 & 5
PANEL FACU-1 (6700) BATTERY CALCULATION
(SECONDARY POWER SOURCE REQUIREMENTS)
STANDBY CURRENT (AMPS)
SECONDARY ALARM CURENT (AMPS)
PANEL COMPONENTS
QTY
PART NO.
DESCRIPTION
CURRENT DRAW (A)
TOTAL (A)
CURRENT DRAW (A)
TOTAL
1
6700 Main Board
Main Board
0.165
0.165
0.31
0.31
CIRCUIT
SYMBOL
QTY
PART NO
DESCRIPTION
CURRENT DRAW (A)
TOTAL (A)
_
CURRENT DRAW (A)
TOTAL (A)
FACU-1 •AUX1
1
SLE-LTEV-FIRE
Sole Path Communicator,
Cellular 8dor IP, connected
by Verizon LTETM', ABS.
0.071
0.071
0.2
0.2
®
FACU-1 •DACT
1
SLE-LTEV-FIRE
Sole Path Communicator,
Cellular 8Jor IP, connected
by Verizon LTETMI, ABS.
0
0
0
0
®
FACU-1•L1
O
1
SK-HEAT-W - W/B300-6
ADDRESSABLE HEAT
DETECTOR, FIXED TEMP
W/ BASE B300-6
0.0002
0.0002
0.0045
0.0045
IM
1
SK-ISO
FAULT ISOLATOR
MODULE
0.00045
0.00045
0.005
0.005
C.
2
SK-MONITOR
ADDRESSABLE MONITOR
MODULE
0.000375
0.00075
0.000375
0.00075
O
6
SK-PHOTO-W w/B300-6
White, low -profile
photoelectric sensor w/Base
0.0002
0.0012
0.0045
0.027
1
SK-PULL-SA
ADDRESSABLE MANUAL
PULL STATION,
SINGLE-ACTION
0.000375
0.000375
0.000375
0.000375
�
I I
FACU-1'NI
WP
1
P2RK
Hom/Strobe, Wall, Red,
Outdoor 115cd
0
0
0.218
0.218
IF
1
SSM24-10
Alarm Bell 10" 24VDC, red
0
0
0.0535
0.0535
FACU-1 •N2
3
PC2WL-LF
Horn/Strobe, Ceiling, White,
Low Frequency 15cd
0
0
0.071
0.213
1
PC2WL-LF
Hom/Strobe, Ceiling, White,
Low Frequency 30cd
0
0
0.09
0.09
X
2
SCWL
Strobe, White 15cd
0
0
0.041
0.082
FACU-1•SBUS+
FM
1
6860
ANNUNCIATOR
0.02
0.02
0.025
0.025
TOTAL STANDBY (A)
0.258975
TOTAL ALARM (A)
1.229125
REQUIRED STANDBY TIME = 24 HOURS
REQUIRED ALARM TIME = 5 MINUTES
SECONDARY STANDBY LOAD (A)
0.258975
24
6.2154
SECONDARY ALARM LOAD (A)
1.229125
0.08333
0.10243
STANDBY AND ALARM SUBTOTAL (AMP HOURS)
6.31783
DEBATING FACTOR
1.25
rw
SECONDARY LOAD REQUIREMENTS (AMP HOURS) `� 7.89728
/'PROVIDE (2)12V 12AH BATTERIES
FACU-1 N1 LUMP SUM REPORT
CIRCUIT SETTINGS
TOTALS
Starting Calculation Voltage:
20.4
Max. Voltage Drop:
0.16354
Min. Operational Voltage:
16
End Of Line Voltage:
20.23646
Max. Circuit Current (A):
1
Voltage Drop Percent:
0.80 %
Wire Resistance (O/kFt):
2.6
Total Circuit Current (A):
0.2715
Circuit Wiring Properties: 'V' 14/2 FPLP (NAC) 14 AWG, NAC - 2 Cond. Solid Copper FPLP Analog Unshielded
Total Circuit Length (Ft):
116
Spare Current (A):
0.7285
Total Circuit Resistance (0):
0.602342
Spare Current (A) Percent:
72.85 %
DEVICE TOTALS
Symbol
Part No.
Description
Qty.
Device Current (A)
Total Current (A)
F
SSM24-10
Alarm Bell 10" 24VDC, red
1
0.0535
0.0535
WPOutdoor
P2RK
Hom/Strobe, Wall, Red,
115cd
1
0.218
0.218
FACU-1 N2 LUMP SUM REPORT
CIRCUIT SETTINGS
TOTALS
Starting Calculation Voltage:
20.4
Max. Voltage Drop:
0.23299
Min. Operational Voltage:
16
End Of Line Voltage:
20.16701
Max. Circuit Current (A):
1
Voltage Drop Percent:
1.14 %
Wire Resistance (D/kFt):
2.6
Total Circuit Current (A):
0.385
Circuit Wiring Properties: 'V' 14/2 FPLP (NAC) 14 AWG, NAC - 2 Cond. Solid Copper FPLP Analog Unshielded
Total Circuit Length (Ft):
116
Spare Current (A):
0.615
Total Circuit Resistance (0):
0.605177
Spare Current (A) Percent:
61.50 %
DEVICE TOTALS
Symbol
Part No.
Description
Qty.
Device Current (A)
Total Current (A)
X -
SCWL
Strobe, White 15cd
2
0.041
0.082
PC2WL-LF
Hom/Strobe, Ceiling, White,
Low Frequency 15cd
3
0.071
0.213
E
PC2WL-LF
Hom/Strobe, Ceiling, White,
Low Frequency 30cd
1
0.09
0.09
_
Calculation Methods:
Total Resistance (0) = Wire Resistance (0/Ft) x 2 x Total Circuit Length (Ft)
Total Voltage Drop = Total Resistance (0) x Total Circuit Current (A)
EQUIPMENT LIST
SYMBOL
QTY
MANUFACTURER
PART NO
DESCRIPTION
1
SILENT KNIGHT
6700
ADDRESSABLE FIRE ALARM CONTROL PANEL
MB
1
SPACE AGE
ELECTRONICS
SSU00689
FIRE ALARM DOCUMENT BOX
DoC
1
NAPCO
SLE-LTEV-FIRE
SOLE PATH COMMUNICATOR, CELLULAR &/OR IP
®
1
SILENT KNIGHT
6860
ANNUNCIATOR
FAA
1
SILENT KNIGHT
SK-PULL-SA
ADDRESSABLE MANUAL PULL STATION, SINGLE-ACTION
F
aM
2
SILENT KNIGHT
SK-MONITOR
ADDRESSABLE MONITOR MODULE
IM
1
SILENT KNIGHT
SK-ISO
FAULT ISOLATOR MODULE
Q
1
SILENT KNIGHT
SK-HEAT-W -
W/B300-6
ADDRESSABLE HEAT DETECTOR, FIXED TEMP W/ BASE B300-6
O
6
SILENT KNIGHT
SK-PHOTO-W
WB300-6
WHITE, LOW -PROFILE PHOTOELECTRIC SENSOR W/BASE
Lr
1
SYSTEM SENSOR
SSM24-10
ALARM BELL 10" 24VDC, RED
WP
1
SYSTEM SENSOR
P2RK
HORN/STROBE, WALL, RED, OUTDOOR
a4
SYSTEM SENSOR
PC2WL-LF
HORN/STROBE, CEILING, WHITE, LOW FREQUENCY
X
2
SYSTEM SENSOR
SCWL
STROBE, WHITE
CABLE AND WIRE LEGEND
LABEL
PART NO
AWG
RESISTANCE
(OJKFT)
DESCRIPTION
TOTAL
LENGTH
A
18/4 FPLP (ANN)
18
6.5
ANNUNCIATOR - 4 COND. SOLID COPPER FPLP ANALOG UNSHIELDED
19'
D
16/2 FPLP (SLC)
16
4.1
SLC - 2 COND. SOLID COPPER FPLP ADDRESSABLE UNSHIELDED
105'
E
RJ31X (PHL)
22
16.14
PHONE LINE - RJ31X SOLID COPPER TWISTED SHIELDED
4'
p
14/2 FPLP (AUX)
14
2.6
AUX POWER - 2 COND. SOLID COPPER FPLP UNSHIELDED
4'
V
14/2 FPLP (NAC)
14
2.6
NAC - 2 COND. SOLID COPPER FPLP ANALOG UNSHIELDED
135'
Z
18/2 FPLP (IDC)
18
6.5
IDC - 2 COND. SOLID COPPER FPLP ANALOG UNSHIELDED
11'
EVENT
2/-/C �2 1-3'�-0
SMOKE/HEAT DETECTOR
MANUAL PULL STATION
WATERFLOW SWITCH
TAMPER SWITCH
FACP AC POWER FAILURE
SYSTEM LOW BATTERY
•
•
OPEN CIRCUIT
GROUND FAULT
NOTIFICATION APPLIANCE CIRCUIT SHORT
CELLULAR DISCONNECT
NOTE: ALL SIGNALS WILL BE SENT TO A CENTRAL STATION
4d/
RISER DIAGRAM
N 1.02 EOL 4.7k
115cd
WP
F
N1.01
1V
N2.06 EOL 4.7k N2.05 N2.04 N2.03 N2.02 N2.01
30cd 15cd 15cd , 15cd 15cd 15cd
1 1"
ANNUNCIATOR
e
FIRE ALARM
CONTROL UNIT
FACU-1
CELLULAR
COMM
SBUS+•1
AUX1.01
DACT• 1
DACT•2
L1 •D005
N
L1 •D006 L1 •D007
L1 •I1 ' L1 •M001
ISOLATOR MODULE L1 •D001
IM
TAMPER SWITCH
AIM
L1 •M002
WATERFLOW SWITCH
L1 •M003
0
L1•D002 L1•D003
1D
v
v
0
L1 •D004
F
0
0
i0_
W
U
z
W
0
V J
NW
I.L
F-
I..L.. n/
o co
_ ACV^
L ,
Dzc
W Cn <
CC
V- g
ZWLL
O
W
5ca
W
Ce
z
0
QC
I
F-
0
z
REVISION:
FIRST RELEASE
/
/\
\
iN.
SHEET DESCRIPTION:
FIRE ALARM SYSTEM
PROJECT INFORMATION
DRAWN BY: JEM SYSTEMS
DATE:
06.16.2023
SCALE:
H _ DEDICATED 120V
G 20 AMP CIRCUIT
N.T.S
SHEET:
FA-Ol
2 OF 4
AUX1.01
DACT•1
DACT•2
1V
F
N1.01
1E
1P
J
J
W
0
U
U-
J
-1
U
0
FACU-1
1
UTILITY
1A
L1 •I1
ISOLATOR MODULE
\
\
\
\
L1•M001
TAMPER SWITCH
i `� \) .\%14N\
L1•M002
\ WATERFLOW SWITCH
\
\
\
\
\
\
\
\
\
DETAIL SCALE: 3/16" = 1'-0"
P
BEDROOM \ w
0)
\ 0
1v\
L1 •D007
\,
BEDROOM
N2.03
15cd
CLOSET
N2.04
15cd
BEDROOM
BATH
N2.01
5cd
1V
UTILITY
DINING
\
SBUS+•1
b
CLOSET
1D
1V \0/
/ \5
N2.05
15cd
FAA
1
V
F
1V 1V
L1 •M003
LIVING ROOM
L1 •D003
KITCHEN
L1 •D004
1D{ S
1V 1V
MAIN FLOOR PLAN
BATHROOM FAMILY ROOM
N2.06 EOL 4.7k
30cd
MAIN FLOOR PLAN
1'
5'
10'
1/4" = 1'-0"
N 1.02 EOL 4.7k
115cd
WP
DEVICE LEGEND
SYMBOL
DESCRIPTION
FIRE ALARM CONTROL PANEL
FACU
SOLE PATH COMMUNICATOR
CELL
ANNUNCIATOR
FM
F
ADDRESSABLE MANUAL PULL STATION
e
ADDRESSABLE MONITOR MODULE
IM
FAULT ISOLATOR MODULE
0
ADDRESSABLE HEAT DETECTOR
O
WHITE, LOW -PROFILE PHOTOELECTRIC SENSOR
ALARM BELL 10" 24VDC, RED
Li
WP
HORN/STROBE, WALL, RED, OUTDOOR
aHORN/STROBE,
CEILING, WHITE, LOW FREQUENCY
X
STROBE, CEILING, WHITE
FIRE ALARM DOCUMENT BOX
DOC
2
VALVE TAMPER SUPERVISORY SWITCH (BY OTHERS)
gWATERFLOW
SWITCH (BY OTHERS)
CABLE AND WIRE LEGEND
LABEL
AWG
DESCRIPTION
A
18
ANNUNCIATOR - 4 COND. SOLID COPPER FPLP ANALOG
UNSHIELDED
D
16
SLC - 2 COND. SOLID COPPER FPLP ADDRESSABLE
UNSHIELDED
E
22
PHONE LINE - RJ31X SOLID COPPER TWISTED
SHIELDED
P
14
AUX POWER - 2 COND. SOLID COPPER FPLP
UNSHIELDED
V
14
NAC - 2 COND. SOLID COPPER FPLP ANALOG
UNSHIELDED
Z
18
IDC - 2 COND. SOLID COPPER FPLP ANALOG
UNSHIELDED
ADDRESS & LABEL CLARIFICATION
L1 •D001
N1•01
SLC LOOP NUMBER
"D" FOR DETECTOR PM" FOR MODULE
DEVICE ADDRESS ON SLC LOOP
NOTIFICATION CIRCUIT NUMBER
DEVICE NUMBER ON CIRCUIT
CABLE QUANTITY
TYPE OF CABLE (CHECK CABLE AND WIRE LEGEND)
i u I
1D
0
0
0_
W
U
Z
LLI
0
W
F-
L.L
Oce
_ co
E-- LO
D Z < CO
LIJ
W C!) <
cc
•r<
a�Q
Z W LL
O r J
W
:5ca
LLl —
Z
0
Cl)
F-
DC
0
Z
REVISION:
FIRST RELEASE
%\
SHEET DESCRIPTION:
FIRE ALARM SYSTEM
MAIN FLOOR PLAN
DRAWN BY: JEM SYSTEMS
DATE:
06.16.2023
SCALE:
1 /4" = 1'-0"
SHEET:
FA-02
3 OF 4