Loading...
HomeMy WebLinkAboutFIR2021-00039 Fire Alarm System - FIR Permit / Conditions - 5/9/2022 INSPECTION CARD Mason County 615 W. Alder St. Bldg. 8, Shelton, WA 98584 360-427-9670 ext 352 www.co.mason.wa.us PERMIT# FIR2021-00039 PROJECT ADDRESS 490 NE Old Belfair Hwy Belfair, WA 98528 PARCEL# 123291100030 PROJECT DESCRIPTION Install complete Fire Alarm system for new construction fire station. OWNER NORTH MASON REGIONAL FIRE ADDRESS PO BOX 277 PHONE CONTRACTOR AHEARN ELECTRIC INC ADDRESS PO BOX 4058 PHONE 1.360.373.1900 CONTRACTOR LICENSE AHEAREI008PA LENDER INSPECTION INSP DATE Comments INSPECTION INSP DATE Comments Fire Marshal Final �%� ��"' Mason County Mason County - Division of Community Development MAI 615 W. Alder St. Bldg.8 Shelton, WA 98584 360-427-9670 ext 352 www.co.mason.wa.us E -00039 FIRE ALARMDESCRIPTION: INSTALL COMPLETE FIRE ALARM SYSTEM ISSUED: 09/28/2021 CONSTRUCTION FIRE STATION. ESS: 490 NE OLD BELFAIR HWY BELFAIR EXPIRES: 03/27/2022 PARCEL: 123291100030 APPLICANT: NORTH MASON REGIONAL FIRE AUTHORITY OWNER: NORTH MASON REGIONAL FIRE AUTHORITY (NMRFA) (NMRFA) PO BOX 277 PO BOX 277 BELFAIR, WA 98528 BELFAIR, WA 98528 CONTACT: AHEARN ELECTRIC INC PO BOX 4058 BREMERTON, WA98312-0058 1.360.373.1900 GENERAL CONTRACTOR'S LICENSE: AHEARN ELECTRIC INC License: AHEAREI008PA PO BOX 4058 Expires: 10/01/2022 BREMERTON, WA98312-0058 1.360.373.1900 VALUATIONS: FEES: Paid Due Project Valuation (BID, 36000.00 $36,000.00 Fire Protection Permit Fee $541.47 $0.00 ESTIMATION..) Technology Surcharge $10.83 $0.00 Fire Protection Plan Check $351.96 $0.00 Total: $36,000.00 Totals : $904.26 $0.00 REQUIRED INSPECTIONS Fire Marshal Final CONDITIONS Printed by:Amber Selby on:09/28/2021 01:49 PM Page 1 of 2 t i Mason County Mason County - Division of Community Development 615 W. Alder St. Bldg.8 Shelton, WA 98584 360-427-9670 ext 352 www.co.mason.wa.us FIRE ALARM FIR2021-00039 OWNER/BUILDER acknowledges submission of inaccurate information may result in a stop work order or permit revocation. Acknowledgement of such is by signature below. I declare that I am the owner, owners legal representative, or contractor. I further declare that I am entitled to receive this permit and to do the work as proposed. I have obtained permission from all the necessary parties, including any easement holder or parties of interest regarding this project. The owner or authorized agent represents that the information provided is accurate and grants employees of Mason County access to the above described property and structure(s)for review and inspection. This permit/application becomes null & void if work or authorized construction is not commenced within 180 days or if construction work is suspended for a period of 180 days. PROOF OF CONTINUATION OF WORK IS BY MEANS OF INSPECTION. INACTIVITY OF THIS PERMIT APPLICATION OF 180 DAYS WILL INVALIDATE THE APPLICATION. " Fire Marshal Comments I hereby certify that I have read and examined this application and know the same to be true and correct. All provisions of Laws and Ordinances governing this type of work will be complied with whether specified herein or not. The granting of a permit does not presume to give authority to violate or cancel the provisions of any ther s ate/lo al law regulating construction or the performance of construction. Issued Contractor or Authorized Agent: Date: Printed by:Amber Selby on:09/28/2021 01:49 PM Page 2 of 2 1 2 3 4 FIRE ALARM SYSTEM SHOP DRAWINGS Compliance September 27,2021 NORTH MASON RFA FIRE STATION OfficeMason County,WA - a of the Fire Marshal D 490 NE OLD BELFAIR HWY FIR2021-00039 D Subject to Field Inspection BELFAIR, WASHINGTON 98528 FIRE ALARM DEVICE LEGEND SHEET INDEX FIRE ALARM SYSTEM NOTES QTY SYMBOL DEVICE DESCRIPTION PART NUMBER/ SHEET DESCRIPTION 1. ALL FIRE ALARM WIRING MUST BE IN STRICT COMPLIANCE WITH MANUFACTURER NO. APPLICABLE SECTIONS OF THE NATIONAL ELECTRICAL CODE 1 FACP FIRE ALARM CONTROL PANEL S3/FCI FA-01 NORTH MASON RFA FIRE STATION-TITLE PAGE ARTICLE 760)AND ALL APPLICABLE NFPA STANDARDS. 1 HA77 FIRE ALARM/MASS NOT.BATTERY CABINET BB55F/FCI FA-02 NORTH MASON RFA FIRE STATION-SEQUENCE OF OPERATION MATRIX 2. INSTALLATION MUST COMPLY WITH ALL APPLICABLE FEDERAL, FARA FIRE ALARM REMOTE ANNUNCIATOR LCD-SLP/FCI FA-03 NORTH MASON RFA FIRE STATION-FIRE PROTECTION OVERVIEW STATE,OR LOCAL LAWS,REGULATIONS,CODES,AND 2 �R SPECIFICATIONS. 22 MC FIRE ALARM HORN/STROBE-CEILING MOUNT-WHITE PC2WL/SYSTEM SENSOR FA-04 NORTH MASON RFA FIRE STATION-FIRE PROTECTION PLAN-AREA 1 3. ALL INSTALLATIONS MUST BE APPROVED BY THE LOCAL 2 ['* FIRE ALARM HORN/STROBE-WALL MOUNT-WEATHERPROOF-WHITE P2RK/SYSTEM SENSOR FA-05 NORTH MASON RFA FIRE STATION-FIRE PROTECTION PLAN-AREA 2 AUTHORITY HAVING JURISDICTION. 15 © FIRE ALARM STROBE-CEILING MOUNT-WHITE SCWL/SYSTEM SENSOR FA-06 NORTH MASON RFA FIRE STATION-FIRE PROTECTION RISER DIAGRAM 4. TO AVOID CONTAMINATION AND DUST ACCUMULATION IN THE C 9 L,�JLF FIRE ALARM MINI HORN-WALL MOUNT-WHITE HWL-LF/SYSTEM SENSOR FA-07 NORTH MASON RFA FIRE STATION-BATTERY CALCULATION CHARTS SMOKE DETECTORS,IT IS RECOMMENDED THAT THE SMOKE C 3 Qf MANUAL PULL STATION MS-TAF!FCI FA-08 NORTH MASON RFA FIRE STATION-DEVICE DESCRIPTION CHARTS DETECTORS NOT BE INSTALLED UNTIL AFTER CONSTRUCTION IS COMPLETED AND THE SUBJECT AREA HAS BEEN CLEANED. 2 © CONTROL RELAY AOM-2RF!FCI FA-09 NORTH MASON RFA FIRE STATION-FIRE ALARM CONTROL PANEL DIAGRAM THE SUPPLIER IS NOT RESPONSIBLE FOR DUST 1 [t]S SUPERVISORY CONTROL RELAY AOM-2SF/FCI FA-10 NORTH MASON RFA FIRE STATION-SYSTEM DEVICE DIAGRAMS ACCUMULATION IN SMOKE DETECTORS AND WILL NOT 10 (] MONITOR MODULE AMM-0F/FCI WARRANTY DEVICES THAT HAVE NOT BEEN PROPERLY MAINTAINED.WHEN DETECTORS ARE INSTALLED,PROTECTIVE 16 ® SMOKE DETECTOR ASD-PL3&B300-6/FCI COVERS SHALL BE INSTALLED OVER EACH DETECTOR AND �1 9 ®LF SMOKE DETECTOR W/LOW FREQUENCY SOUNDER BASE ASD-PL3&B20OS-LF-WH I FCI REMOVED BY AUTHORIZED SERVICE PERSONNEL. al teal 1 r�1 1 7 ® CARBON MONOXIDE DETECTOR C01224TRI SYSTEM SENSOR 5. ALL FIRE ALARM SYSTEM WIRING SHALL BE CLEAR FROM eleCtFIC SHORTS,OPENS,AND GROUNDS. a�•Kcrec�o.�' 2 m0 DUCT DETECTOR DNR I FCI 2 REMOTE TEST SWITCH RTS-151/FCI 6. CONDUCTOR,RACEWAY,AND JUNCTION BOX LOCATIONS ARE s.`�E�ciu."�'NUMeea+vw RTS ��� DIAGRAMMATIC ONLY,EXACT LOCATIONS MAY VARY DUE TO •cos 2 ® SPRINKLER WATER FLOW SWITCH PROVIDED BY OTHERS FIELD CONDITIONS.ACTUAL INSTALLATION LOCATIONS SHALL 4 ® SPRINKLER TAMPER SWITCH PROVIDED BY OTHERS BE DETERMINED BY THE INSTALLING CONTRACTOR AND UPDATED ON AS-BUILT DRAWINGS. 2 ® SPRINKLER LOW AIR SWITCH PROVIDED BY OTHERS .on 1 mE) I SPRINKLER POST INDICATOR VALVE PROVIDED BY OTHERS 7. DO NOT LOCATE SMOKE OR HEAT DETECTORS WITHIN 3 FEET OF SUPPLY OR RETURN AIR VENTS. 1 Q SPRINKLER 24VDC BELL PROVIDED BY OTHERS -�O oR 8 17 2021 8. ALL CONDUCTORS SHALL BE PULLED SPLICE FREE. oFs TGE nmrDMW aM PIG 9. ALL NOTIFICATION DEVICES WILL BE SYNCHRONIZED. nao�awltn av dc/ww 10. FIRE ALARM CIRCUITS SHALL HAVE RED MARKING AND BE roc vxrnma B IDENTIFIED. OD B 11. FIRE ALARM TO INTERCONNECT WITH FIRE SPRINKLERS FOR UN WIRE LEGEND CIRCUIT LABELS AND DESIGNATORS PIV,BACKFLOW.AND WATER FLOW. 00 EXAMPLE:MANUAL PULL STATION 0) SYMBOL DESCRIPTION WIRE SIZE WIRE COLOR 12. WILL PROVIDE COMPLETION DOCUMENTS BY FINAL Q ADDRESSABLE © N1 L1:M 001 INSPECTION. Z > A SLC LOOP-SIGNALING LINE CIRCUIT #16-2 FPLR NON-SHIELDED NO STRIPE -BLACK/RED+ DEVICE Y`'�DESIGNATES DEVICE NUMBER(001-159) > LABELS �_ 13. WILL COORDINATE WALK-THROUGH WITH FIRE INSPECTOR B NAC CIRCUIT #14-2 FPLR NON-SHIELDED NO STRIPE NAC 1 -BLACK!RED+ 'M"DESIGNATES MODULE/"S'DESIGNATES SENSOR/ _ "IM'DESIGNATES ISOLATION MODULE PRIOR TO FINAL INSPECTION. Q NAC 2 -BLUE/YELLOW+ DESIGNATES LOOP NUMBER.(X2 LOOPS PER NODE) �' r L¢L. NAC 3 -PURPLE/ORANGE+ DESIGNATES NODE NUMBER 14. PRINTS ARE INTENDED TO MEASURE SIZE 22"X 34".IF SHEETS Z J NAC 4 -BROWN/PINK+ DO NOT MEASURE 22'X 34"IT IS A REDUCED PRINT.REDUCE W W CC U CO LLJ C COMMUNICATION #16.2 TWISTED NON-SHIELDED YELLOW STRIPE -BLACK/RED+ EXAMPLE:FIRE ALARM HORN/STROBE SCALE ACCORDINGLY. NAC CIRCUIT INDICATES PANEL CIRCUIT ORIGINATES FROM } D 24V AUX POWER #14-2 FPLR NON-SHIELDED BLUE STRIPE -BLACK/RED+ LABELS DESIGNATES NAC CIRCUIT(1-4) > d E INITIATION CIRCUIT (2) #14 THHN SOLID BLACK/BLACK DESIGNATES NUMBER IN CIRCUIT Cr U »= W ff] NAC1-1.01 z Q F CONTROL CIRCUIT (2) #14 THHN SOLID RED/RED 15cdl INDICATES TAPPED CANDELA SETTING p _ G 24V BATTERY POWER #12 THHN STRANDED •BLACK/RED+ FIRE ALARM DEVICE MOUNTING HEIGHTS U = Q F-- H CARBON MONOXIDE DETECTOR CIRCUIT #16-6 TWISTED NON-SHIELDED BLACK!RED/BROWN I LOCATE DEVICES AS NOTED BELOW.DEVICE HEIGHTS ARE CC J BLUE/YELLOW/GREEN MEASURED FROM THE FINISHED FLOOR TO THE CENTERLINE OZ LLI in THE DEVICE UNLESS OTHERWISE NOTED. J REMOTE TEST SWITCH (3) #14 THHN SOLID BLACK!RED/BLUE 0 1. PULL STATIONS +4 FEET CENTER PER FLAG 120VAC POWER (3) #12 THHN SOLID OR #12-2 NMB RATED HOT BLACK Z A GROUND GREEN NOTE NEUTRAL WHITE 2. FIREALARM +80 INCHES BOTTOM W HORN/STROBES, HORSTROBES, Z A HORNS,AND p STROBES O) 3. FIRE ALARM PANELS +6 FEET TO TOP sale AS NOTED Epxa¢r ra.: m1aiz r�rrc ro. srm 1 or 10 FA-01 1 2 3 4 5 1 2 3 4 Compliance September 27,2021 Mason County,WA a Office of the Fire Marshal D F I R2021-00039 D Subject to Field Inspection i7 SYSTEM OUTPUTS OQ- ��'�, 0� Q C Q�G. 5J �Q tS0 OQ �O �p�`J�G�QP G� �5��P C Q�OQ PG PG PG PG 0�Q GJJ ahearn SYSTEM INPUTS A B C D E F G I H I I I J K L M N O P Q ClrectrlC 1 MANUAL PULL STATION • • • 1 `"FaE` CH—" » .e 2 SMOKE DETECTOR • • • 2 3 INDIVIDUAL DORM ROOM SMOKE DETECTOR • • • 3 4 CARBON MONOXIDE(C.O.)DETECTOR • • • 4 5 DUCT DETECTOR • • • 5 6 HEAT DETECTOR • • • 6 am�mnn ea B 17 2021 ncs TGE orsw DMW a� PTG 7 SPRINKLER WATER FLOW SWITCH • • • • 7 w� 8 SPRINKLER TAMPER SWTICH • • 8 oEs Exc7u� 9 SYSTEM BYPASS ACTIVATED • • • 9 13 10 FIELD WIRING OR SYSTEM COMPONENT FAULT • • 1 1 10 � N 11 LOSS OF PRIMARY AC POWER • • 11 0000 12 OPEN CIRCUIT • • 12 Q x 13 NAC SHORT • • 13 11� Z 14 LOW BATTERY • • 14 O 15 15 cn Z J z 16 16 � O m O � U Q 17 17 Q Z w 18 18 _ 0- 19 19 ZO :�i a: 20 20 Q iE cr J O A B C D E F G H I J K L M N O P Q OZ LU w O O Z —1 �w O 1n A z A 0 rn v scue AS NOTED wroaEcr ra: cormrt car1m.ra. s"¢ 2 ar 10 FA-0-2- 1 2 3 4 5 1 1 2 1 3 1 4 © O O O G Compliance O 4 September 27,2021 7 - _ - - - - - — - - - - - ----- - --- - - - -- - - - - - -- - - Mason County,WA - - 7 a � a --- - Office of the Fire Marshal I -- -- n I "MIN 113 1 1 ASSISTANT `,,";SF CHIEF I - F I R2021-00039 Ly 6 - - - e — — - - . _ _ _ Subject to Field Inspection s E ADMIN rE . 112 I 117 I A ' a - ACP _ vuuc FILE j I VISER _ _ -4 COMMUNRY - -tIOSE 5 OUTREACH LL 2 STORAGE I _,i KITCHEN DINING DAY ROOM H I 111 1 110 ^CONFEREN 1 6 I I FF_OFFIC_E — € 120� 126 I 129 I 131 132 r__133 g g c B .:. € H WORKBE 184 I z NCH { e ANTRYISU PLY° HA B VESTIBULE aG8 eBHOP -1301 B A 1 A I; VOLUNT ER _ 1 9 a I 109 COPYIMAIL a — 106 ( APPARATUS �? B J A J B C REFUGE ItT.°U z c z c B lI�UNDRY JAN I B Y I; I .. �.. -.:l..129- —� f -T� RR e H L_� ..-H H C&D SCBA SCBA COMP OFFICE _ _ A .____...._.----- � — J I L ,�_ STORAGE i--t6� 106 WORKROOM 1 1 1 " t66 I 10� c OESTR06M �TH B 103 BAT .. B 1 J 1 z \.._.:. aern 137 �� I etrle EXAM I RECEPTION _._.»— _ HALL g' e e i 105 102 I B ( 139 B 136 13A I -- H .., zc 40 FITNESS MECH TURNOUT € A 104 !; 154 i ( 156 1 B g I 169 AA°® I c c B L._. I B B z z LOBBY 3 A 141 A g SSCaD B e H I 01 .; _ W. C8D A HAL' /an 4 - - - - - - - - - - - - - g A _ EQUIP-,- 4 1 samm'm � 8 17 2021 STORAGE _ 3 LOCKER B B �t B j — n_ SUPPLY TGE 1 17 DMW cxK PrG 123 12 H ' _ (I 144 I I A�'DORM B A - - - - - - - DE(ON _._ CO ,i L DOR LF EXTRACTOR LA - - 146_ 7 t r- co U A . I _Q 1 173 CA TRAINING i 0 B g Q 3 - i DOR DOR Z O > - - c - -� - L 48 A 143-, 49 - - - - - ¢ Q W J O W " DOR it tee' B e� I I LU Q O m g F J Iso I A - 1 L.L U A C B. ZO I A A A i I I I I CC U) = Z DORM, 1F LF" B DO O U) LLJ O HIr CO d O 0 � I I i I i I Z 0 U- © O O C� N � FIRE PROTECTION PLAN - OVERALL srxe AS NOTED SCALE 178 = "0' FA-03 • Z 8: mnsm.carte.no. ���� D• a, 18 -/- SCALE:118'=1'-0' sem 3 a 10 FA-03 1 2 3 4 5 1 2 1 3 1 4 Compliance � September 27,2021 l IIIIIII Ills it I I I B Mason County,WA a TQJ Office of the Fire Marshal ADMiN I IIi t13 ASSISTANT I ! CHIEF i CHIEF r ! F I R2021-00039 ! 1t5 t18 I I I _ _ I� Subject to Field Inspection _ ADMIN i € 112 A nl:sad+ 117 I B FILE i 119 I I COMMUNITY iI �Op 7scd (f OUTREACHONFEREN iALLE� HA LLKITCHEN DINING DAY ROOM FF OFFICE Il r 111 t10 1 8 I 126 129 I 131 I 132 A 120 1 133 i B I 1 _ g I i I xAc a F - ? B I xAczlz ANTRY/SUPPLY' HA L B yETIBULE KC 13Q_ A ; 1 A 151d102 VOLUNTEER i 10$_ usoo9 COPYIMAIL N a w 108.._i 134 B MRi�FU�GE ' t:It lA5 I B .I c � .s 7t zln C I—r 121 i 127 LAUNDRYtzla I x I , I RR OFFICE A xAc _....... L_ 128 nn *I' 1 11— =-- [159 —� — I- 10 i WORKROOM �- B a 'i I I L_107_; ? c RESTROGM xAc I _b �L__ xaB o 1� ( B 37 k�_ .Bx,L1: �z I NAc zw °� ai learn i x�° F I EXAM c u:s9o7 RECEPTION u:sml �-- ( X B: I E� ct P 1ALL 05 1 4.04 I 102� I �( fi e '� B �:H36�t� SAT I i e c L %c 1wz9�— 140 F FITNESS r. _ t_._._.,,--„ NAC 2QlF i� W1C 204 .. L . aq MEC_H_ i� F F FL 1Me'• g..��- A __. d% 4AC 1� i{ II J5d 15s I �1iiY g lif g �S a 4.0,NIMSMOB i_.. N1L1:N013 L BY 1(C^,47K➢E1a A L 141 N1U:5913 NAe3.07 N1L1:5025 q g xxy102 55O&D N1U:5012 15.d ---- NAC_ .• _ �e �. B 7(N1LI:YOI! 9c9f ' - A _ ,•. to M 8 17 2021 STORAGE 1--JAI. g g H.I t�l ID:S924 L_ B x �01 DEEsTGE —DMW CHK PTG 75<a� 12 I LOCKER 144 r xAc xts I I Its A 5 I a6 N/ua g 'jA t�t•: i rnE vamLl.Tox e A I —_ �__ I B — — 3.05 3 - — — — I I xt�� x�Ac 3.100 mu smil H _ 47 OD 0) i TRAINING Q E L147 g Q ",Oak .1 I Z N1L7: O Q NAC 4.02 c — �. 148.. + '`__1g09 — — wL1:500975cA 1fN0.1:5010 I-- - I — 2 z Q Q TO AHU �, J SHUTDOMB B I --S rR—TS1 ;z.. N1L1 S02t: W W NLFAC 112 H H m KACz (t j F J } �158 A +SD�� 1 151 LL C� _ ILI:M01 N1L1:5027 1—p -K:. 4 1� -4 --thF _ - ._ ( LL O 0,., HILM9A A A ---- I N16:OS8 RM F Z = = oNc3n O = - W C = 0o wZ Of - z m a O Qf w I I I I Z 0 N �Y FIRE PROTECTION PLAN -AREA A AS NOTED SCALE 1 8 = 10 FA-04 2, S, coKsrrt.wxm.Ko. — SCALE:11V=1'-0' sr¢T 4 Dv 10 FA-04 1 2 3 4 5 1 2 3 4 FQ © HO FLAG NO ES Compliance g September 27,2021 120V DICATED B � C�JT T DETERMIN D a 7 - - ---- - — - I- O AND U DATED ON 'AS LY 4fYAIN Office of the Fire Marshal i I I D I FI R2021-00039 O6 _ . - - - - - — _ g Subject to Field Inspection 2 : NiL,:NOif id F I '�. .,A :. I I N1 L1:M001 9 SU (`!DJl- I —H1O6S1 1l l N1L1:M02SA� E STORAGE ISER � N1L1:M04 f 6 D H A NAC 1.07 NAC LOS NAC,.09 — J M M M C FACP , 7kd B 75M B 47KO EOL E BATT c Cd AIR A X WORKBENCH H E i 163 164 N11-1: 005 M A N1L1:M006 M Sv _�BASHOP A N1L1:S001 9% B 165 N1L1:M007 M i YAC 101 N1LI M00B M Pry APPARATUS _ A C SAY N1L1:M009 M 1 _. N1L1:M010' M A \ e H H H C&D SCBA COMP A STORAGE 167 N11-1:M011 M R 166 H A B �bo ahearn B B elegtric: T-1 a EEcnox H JOcd Er+r4e+eiw.+�iEcn.,oioar FlRE PUHM Sv TURNOUT B B 169 *� B B X NAC 1.06 NAC t.05 NAC 1.04 75cd 75W 75cd _,m - B N HAL RISER ROOM 162- DETAIL — — — — — — — - - - — — >o � e ,�zoz, 168 SUPPLY SCALE 3/16' = 1'0' FA-05 oFs TGE onwDM, cNN PfG g I I aar Ow/AWI i DE I ELEC `RO L9M B 3 L.__ ,1772 O ........ C ,Scd - - - - - - - --- - V LO NAC,05 TOR 00 f73 0) m I I W � W I I g 1 I � o ° Z --- - - - - --- -- - - - - - � � L w J o F- 0 p J w I Z Q A O © OUJ N �t FIRE PROTECTION PLAN -AREA B AS NOTED SCALE: 1 8' = 1V FA-05 _ FPNOJ—NO.: CONSIR.CONtR N0. L - u 4' -�- SCALE:lir=r a 5 10 FA-05 1 2 3 4 5 1 1 2 3 4 FLAG NO ES Compliance 4 September 27,2021 AND U DATED ON WRPLY'DRAT�SNGS" DETERMIN D a Office of the Fire Marshal a D F I R2021-00039 Subject to Field Inspection g B B B B B B B B C C WP C C C C C X X X X X X X X NAC 4.01 NAC 4.02 NAC 4.03 NAC 4.04 NAC 4.05 NAC 4.06 NAC 4.07 NAC 4.08 30cd 75cd 75cd 15cd 15cd 30cd 15cd 47KO EOL 15cd B B B B B B B B B 13 B B B �B ��� B WP C C LF C LF �LF �C� LF LF LF LFLF X H X H HH H H H H H NAC 3.01 NAC 3.02 NAC 3.03 NAC 3.04 NAC 3.05 NAC 3.06 NAC 3.07 NAC 3.08 NAC 3.09 NAC 3.10 NAC 3.11 NAC 3.12 NAC 3.13 NAC 3.14 NAC 3.15 NAC 3.16 75cd 15cd 15cd 15cd 15cd 15cd 47KO EOL C 15cd B B B B B B B B B B B B B B B C C C C C C C C C C C C C C C X X X X X X X X X X X X X X X NAC 2.01 NAC 2.02 NAC 2.03 NAC 2.04 NAC 2.05 NAC Z06 NAC 2.07 NAC 2.08 NAC 2.09 NAC 2.10 NAC 2.11 NAC 2.12 NAC 2.13 NAC 2.14 NAC 2.15 • 15cd 15cd 15cd 15cd 15cd 15cd 15cd 15cd 15cd 15cd 15cd 15cd 15cd 15cd 47KO EOL ahearn B B B B B B B B B H H H H 75cdH electric C C C C C C C C C = X X X X X X X X X E1.1I EPoRGiECRVIXOG� FlRE.4PRM SrST' NAC 1.01 NAC 1.02 NAC 1.03 NAC 1.04 NAC 1.05 NAC 1.06 NAC 1.07 NAC 1.08 NAC 1.09 HE F MM�. 15cd 30cd 15cd 75cd 75cd 75cd 75cd 75cd 47KO EOL 75cd S PIV RTS D D D D D E E E E E E E E E H J �10 W B 17 2021 FARA C FARA C A A A A A A A A A A A A A A A A m TGE Io DMW ICHK PTG NAM LCD-SUP LCDSLP FACP C M M M M M M M MIJ M M F t p o rmnc n LOBBY 101 VESTIBULE 155 S3 N1L1:M001 N1L1:M002 NiL1:M003 N1Li:M004 NiL1:M005 N1Li:M006 N111:MD07 N1L1:M008 NiL1:M009 N1L1:M010 NiL1:MO11 N1L1:S001 N1Li:M012 NiLI:S002 N1L1:S026 B BELL ACTIVATION DRY#1 DRY#1 DRY#1 DRY#2 DRY#'2 DRY#2 PIV BACKFLOW#1 BACKFLOW#2 C.O.DETECTORS RISER 162 APPARATUS HALL 136 LAUNDRY 128 co 1 RISER 162 RISER 162 RISER 162 RISER 162 RISER 162 RISER 162 RISER 162 RISER 162 RISER 162 RISER 162 RISER 162 BAY 158 N TO AHU SHUTDOWN TO AHU SHUTDOWN 000 FCU-5 DOAS 0) RTS a z � � TO 120VAc Q DEDICATED CIRCUIT U F F O RISER 162 A A A A A A A A A A A A A A A Z p TO(2) DEDICATED G W LU 11� PHONE LINES Z 2 C Z F Z C m � N1L1:S012 N1L1:SO11 N1Li:SO10 N1LI:S026 N1L1:M016 N1L1:S009 N11-1:013 N1L1:S008 N1L1:S007 N1L1:S006 N1L1:S005 N1Li:SDO4 NiL1:S003 NiL1:MO15 B HALL 141 LOBBY 101 TRAINING 122 TRAINING 122 TRAINING 122 TRAINING 122 LOBBY 101 LOBBY 101 RECEPTION 102 COPY/MAIL 108 HALL 114 HALL 114 COPY/MAIL 108 LAUNDRY 128 Q 0 Z Q = O H Q F=- Lai LAJ D D D D D D D D O W d D z m O w OfA A A A A A A A A A A A A A z 0 �- 2 2 t Z Z t 2 2 2 2 Z Z F z A LF LF LF LF LF LF LF LF LF o NiL1:SO13 N1L1:SO14 NiL1:S015 N1L1:S016 N1L1:S017 N1L1:S018 N1L1:SO19 N1L1:S020 N1L1:S021 NW:S022 NiI:S023 NiL1:S024 N1L1:S025 N1L1:M014 0) HALL 141 HALL 143 HALL 146 DORM 148 DORM 150 DORM 152 HALL 143 DORM 153 DORM 151 DORM 149 DORM 147 DORM 145 HALL 141 VESTIBULE 155 d scut AS NOTED ERiP2Cf Ko.: mxsm.L1]KIR.Ko. 9EE 6 a 10 FA-06 1 2 3 4 5 1 2 3 4 Compliance Fire Alarm Control Panel(FA CP)Current Draw September 27,2021 Module/Device Part Number CITY Normal Alarm Normal Current- Alarm Current- Mason County,WA a Current Current Total Total Office of the Fire Marshal Main Board-Intelligent Loop Interface S3 1 0.111 0.243 0.111 0.243 Touchscreen Annunciator Display LCD-SLP 1 0.03 0.065 0.03 0.065 Dialer Module Dad-E3 1 0.03 0.065 0.03 0.065 D On-Board NAC Circuits N/A 1 0 3.025 0 3.025 F I R2021-00039 Fire Alarm Remote Annunciator LCD-SUP 2 0.03 0.065 0.06 0.13 Manual Pull Station MS-7AF 3 0."3 0.007 0.0009 0.021 Subject to Field Inspection Monitor Module AMM-4F 10 0.0035 0.06 0.035 0.6 Control Relay AOM-2RF 2 0,000375 0.0065 0.00075 0.013 Supervised Control Relay AOM-2SF 1 0.0003 0.006 0.0003 0.006 Smoke Detector ASD-PL3&B300-6 16 0.0002 0.0045 1 0.0032 0.072 Smoke Detector w/Low Frequency Base ASD-PL3&B20OS-LF-WH 9 0.0002 0.0135 0.0018 0.1215 C.O.Detector C01224TR 7 0.02 0.04 0.14 0.28 Duct Detector DNR 2 0.0002 0.0045 0.0004 0.009 Remote Test Switch RTS151 2 0 0.012 0 0.024 24VDC Electric Bell By Others 1 1 1 0 0.031 0 0.031 Total Current Draw 0.41335 4.7055 Current Total 0.41335 24hrs 9.9204 1 5min. =0.0831 0.3905565 10.3109565 x 125%=112.888695625AH Battery Required(48 Hour Standby-15 Minute Alarm) 12.888695625 AH Battery Selected 35 AH C On-Board S3 NAC Circuits-Current Draw Part Candela Normal Alarm Normal Current Alarm Current Circuit CITY Numbers Setting/Amps Current Current Total Total PC2WL 15cd-0.054A 2 0 0.108 0 NAC 1-1 PC2WL 30cd-0.071A 1 0 0.071 0 0.809 , PC2WL 75cd-0.137A 4 0 0.548 0 ahearn SCWL 15cd-0.041A 2 0 0.082 o 1 eleclriC PC2WL 15cd-0.054A 6 0 0.324 0NEEPo�GrEW, NAC 1-2 PC2WL 75cd-0.137A 1 0 0.137 0 0.789 EE EL I- - s I--.z,A.e SCWL 15cd-0.041A 8 0 0.328 0 PC2WL 15cd-0.054A 4 0 0.216 0 SCWL 15cd-0.041A 2 0 0.082 0 NAC 1-3 1.427 HWL-LF 0.108A 9 0 0.972 0 P2RK 75cd-0.157A 1 0 0.157 0 .�rnm to w a r7 2021 PC2WL 15cd-0.054A 1 0 0.054 0 m TGE lo DMW Jew PrG PC2WL 30cd-0.071A 2 0 0.142 0 , NAC 1-4 PC2WL 75cd-0.137A 1 0 0.137 0 0.613 B SCWL 15cd-0.041A 3 0 0.123 0 P2RK 75cd-0.157A 1 1 0 1 0.157 0 00 N Total Current Draw 0 3.025 u7 00 rn Q Voltage Drop Calculations z u7 A =3252.9588845 cEnd Of Line0Circuit Total CurrentDrop Wire Gauge VoltageNAC 1-1 0.8093195 14 22.8386805 LU Z JWNAC 1-2 0.7891752 14 22.1878248 m O NAC 1-3 1.4278845 14 21.0411155 ZO NAC i-4 0.6138136 15 22.2791864 Z = J O Q cn = Q c) "TOTAL CURRENT IS TAKEN FROM THE BATTERY CALCULATION CHARTS. < � LL J s LENGTH IS ANNOTATED AS THE DISTANCE FROM THE SOURCE TO THE LAST DEVICE ON THE CIRCUIT. Ir O p a J M z O c VOLTAGE DROP USES THE FOLLOWING FORMULA: W A I x 21, x R WHERE:VD=VOLTS DROPPED z VD= 1000 1=TOTAL AMPERAGE rn L=CIRUIT LENGTH R=RESISTANCE OF WIRE(Q/KF) As NOTED wiaccr do.: - THE RESISTANCE FOR 12 AWG IS 2.010/0,AND 3.190/0 FOR 14AWG PER NFPA 70TABLE 8 CHAPTER 9. END OF LINE VOLTAGE SHALL BE GREATER THAN 18.00 VOLTS DC 7 10 FA-07 1 2 3 4 5 1 2 3 4 Compliance � Fire Alarm Control Panel(FACP)-Device Description Chart Clubhouse-Fire Alarm Control Panel(FACP)-Device Description Chart a2021 NODE 1-LOOP 1-MODULES NODE 1-LOOP 1-SENSORS a a PASSOM nty,WA Device Device Address Device Description Part Number Location Address Device Description Part Number Lo ion Office of the Fire Marshal Supervisory Control Relay-Electric Bell ASD-PL3 w/ N1L1:M001 AOM-25F Riser 162 NIL1:S001 Smoke Detector Riser 162 Activation B300-6 Base N1L1:MO02 Monitor Module-Flow Switch Dry#1 AMM-4F Riser 162 ASD-PL3 w/ F I R2021-00 39 N1L1:S002 Smoke Detector Hall 136 N1L1:MO03 Monitor Module-Low Air Switch Dry#1 AMM-4F Riser 162 B300-6 Base N1L1:M004 MonitorModule-Tamper Switch Dry#1 AMM-4F Riser 162 N1L1:5003 Smoke Detector Co Mil �ASD-PL3w/ Py/ Aub'ect to Field Irispection N1L1:M005 Monitor Module-Flow Switch Dry#2 AMM-4F Riser 162 B300-6 Base N1L1:M006 Monitor Module-Low Air Switch Dry#2 AMM-4F Riser 162 ASD-PL3 w/ NiL1:5004 Smoke Detector Hall 114 N1L1:M007 Monitor Module-Tamper Switch Dry#2 AMM-4F Riser 162 B300-6 Base N1L1:M008 Monitor Module-PIV AMM-4F Riser 162 N1L1:S005 Smoke Detector ASD-PL3 w/ Hallil4 N1L1:M009 MonitorModule-Tamper Switch BackFlow#1 AMM-4F Riser 162 B300-6Base N1L1:M010 MonitorModule-Tamper Switch BackFlow#2 AMM-4F Riser 162 ASD-PL3w/ N1L1:S006 Smoke Detector Copy/Mail 108 N1L1:M011 Monitor Module-C.O.Detectors AMM-4F Riser 162 B300-6 Base N1L1:M012 Manual Pull Station MS-7AF Apparatus Bay 158 N1L1:S007 Smoke Detector ASD-PL3w/ Reception 102 N1L1:M013 Manual Pull Station MS-7AF Lobby 101 B300-6 Base N1L1:M014 Manual Pull Station MS-7AF Vestibule 155 N11.1:5008 Smoke Detector ASD-PL3w/ Lobby 101 N1L1:M015 Control Relay-AHU Shutdown-DOAS AOM-2RF Laundy 128 B300-6 Base N1L1:M016 Control Relay-AHU Shutdown-FCU-5 AOM-2RF Training 122 N1L1:S009 Smoke Detector ASD-PL3w/ Training 122 B300-6 Base N1L1:S010 Smoke Detector ASD PL3w/ Training 122 B300-6 Base C N1L1:S011 Smoke Detector 8300-6 Base Lobby 101 N1L1:S012 Smoke Detector ASD-PL3 w/B300-6B se Hall 141 N1L1:S013 Smoke Detector ASD-PL3w/ Hall 141 ahearn B300-6 Base ASD-PL3 w/ eletrl� N1L1:S014 Smoke Detector Hall 143 B300-6 Base E FlRE n1ARR 5• Ek+S V Smoke Detector w/Low Frequency Sounder ASD-PL3w/ N1L1:S015 Dorm 146 A1°® Base B20OS-LF-WH Base N1L1:S016 Smoke Detector w/Low Frequency Sounder ASD-PL3 w/ Dorm 148 Base B20OS-LF-WH Base MR Smoke Detector w/Low Frequency Sounder ASD-PL3 w/ N1L1:5017 Dorm 150 s�,m,o .E Base B200S LF-WH Base a 17 2021 oEss TGE �DA1W ICHK PTG Smoke Detector w/Low Frequency Sounder ASD-PL3 w/ N1L1:S018 Dorm 152 Base 62005-LF-WH Base ov do/�m N1L1:S019 Smoke Detector ASD-PL3w/ Hall 143 B B300-6 Base 00 Smoke Detector w/Low Frequency Sounder ASD-PL3 w/ N 1L1:S020 LO Base B20OS-LF-WH Base Dorm 153 00 N11.1:S021 Smoke Detector w/Low Frequency Sounder ASD-PL3 w/ Q Base B20OS-LF-WH Base Dorm 151 z 3. N1L1:5022 Smoke Detector w/Low Frequency Sounder ASD-PL3 w/ CL Base B20OS-LF-WH Base Dorm 149 Smoke Detector w/Low Frequency Sounder ASD-PL3 w/ W W N 1L1:S023 Base B20OS-LF-WH Base Dorm 147 LL OU En Zo Smoke Detector w/Low Frequency Sounder ASD-PL3 w/ Q Z I_ N1L1:S024 O a. Base B20OS-LF-WH Base Dorm 145 CC cn o 2 ASD-PL3 w/ N1L1:S025 Smoke Detector O CC V) B300-6 Base Hall 141 U) 2 Q wo ASD-PL3R w/ CC J w N1L1:5026 Duct Detector-AHUDOAS = O W 0 DNR Housing Laundry 128 F— Z CO j ASD-PL3R w/ CC C, p N1L1:S027 Duct Detector-AHU FCU-5 DNR Housing Training 122 0 p A z 0 rn scuE: AS NOTED EGROJER HD.: wRsm.m'rn.ra. s m 8 ar 10 FA-08 1 2 3 4 5 1 1 2 1 3 1 4 FLAG NO ES Compliance - September 27,2021 - / ]HORN/STROBE CIRCUIT-NAG 4 ry 0 ]SLC 1110 CUT ON ]HORN/STROBECIRCUIT-NAC2 AND U DATED120V DICATED B� pN DET ERMIN D n�?� 2Z Office 0T i Marshal/ ] - a O O nc snnatfn ]HORNISTROBE CIRCUIT-NAG 1 O O O O O ° D o 0 0 o 0 � �� � -00 F IR2021-00039 D 0 O O O 0 BL95YEZI� / / / [ff 0 © 0 0 Subject to Field Inspection 71 a K � ® O OTW ° ASSY, LCD-SLP a°FW A / ' L AUX POWER 1120-0938 REV N0 u / SLP-E3 - B 1 11200933 REV i T. � / 71I o O O envx. C a // / ® �\� ® C ®a ❑ Oo (FBI/ \/ At 0 0 a -E! LCD-SLP Ei oEi 0 o ahearn AUXILARY RS485� electric: O ¢ ¢ o ® TE 32 r�.l n / O O - O NICETIfl'EL IV.NUM6ER 133' i a m FARA(X2) ,,,o• z�w 2 DEDICATED / • TELEPHONE LINES / TO 120 VAC DEDICATED CIRCUIT BRANCH CIRCUIT °CIM >Iosiclm'1° nc 8 I7 2021 m TGE oawDMW C. PTG u � E.woi NNumI FARA on do%ww LOCATEDIN (EXTERI❑R CABINET VIEW) B VESTIBULE 155 00 B s T L0 CO O Q Z w LCD-SLP cc o m Q Z —J (EXTERIOR CABINET VIEW) � O = Q O Z 0 b b U = Q O FARA BB-55F BATTERY BOX Q LL EC J :E LOCATED IN " " " UZ EO Ly D_ s W LOBBY 101 C-) C+) C-) C+) 35AH BATTER 14' O Q s�. Z o W 35AH BATTER z `� q 35AH 35AH � 0) BATTERY BATTERY (INTERIOR CABINET VIEW) d BAT-12220 BAT-12220 n 24• srKe AS NOTED a� BMWECT No.: - LCD-SLP KEY PLAN vw sm 9 a 0 FA-09 1 C_- 2 3 4 Compliance September 27,2021 - Mason County,WA a INSTALL AOM-2SF RELAY MODULE IN P Office of the Fire Marshal TERMINAL I➢ FINSTALL THE AOM-2RF RELAY MODULE IN P 4'SQUARE%2-V8'DEEP BOX INSTALL THE MONITOR MODULE IN P T]-SLC LOOP C-) 4'SQUARE%2' 1-118'!8•DEEP BOX q'SQUARE X 2-i/B'DEEP BOX (-) $LD LOOP DDT T2-SLC LOOP(+) SLC LOOP IN VFROME SLR LOOP IN FROM (') NIXTUEVICE TO PREVIOUS nEvicE PREVIOUS DEVICE �I T3 NOT USED SLC LOOP IN FRO!( •� q T (.)n(-) PREVIOUS DEVICE 4- 7 - TS-NN0 USED ORMALLY OPEN 1 TO WP HORWSTROBE OR —I (') ELECTRIC BELL A D T6-NORMALLY CLOSED 1 T7-RELAY COMMON 1 O�° ® °o (�>n(-) O o ® °o �O ® °� F I R2021-00039 D O TB-NORMALLY OPEN 2 a T9-NORMALLY CLOSED 2 T10-RELAY COMMON 2 TD T 1D T Ts n 24FACPM ; TX U Subject to Field Inspection KEYEDCAT60 n r4 n r4 g ro AHU SHUMN d n n n �,�pp+�� n NOTE: _ TrY I�IJI-)tOB WILL HAVE FACTORYSUPPLIED Tew® ®s WEATHERPROOF BACKBOX �� o o f �NEXT�DPEVICETO *Op,,E�NDA LI �" V u SLC LOW GT TO NE%T➢EVICE SLC LOW OUT TO REARVIEW NEXT DEVICE NOTE �S-EMS CAN BE FLUSH MOUNTED ON A SINGLE GANG DEEP BOX OR CAN BE SURFACE AOM-2RF RELAY MODULE AOM-2SF SUPERVISORY CONTROL RELAY MODULE 47KMOUNTED ONAFCIS&10 BOX. RESISTR MM-4F MONITOR MODULE AHU SHUTDOWN ELECTRIC BELL ACTIVIATION FLOW SWITCH/TAMPER SWITCH I PIV MS-7AF MANUAL PULL STATION WIRING DETAIL WIRING DETAIL WIRING DETAIL WIRING DETAIL SLC Ot1I SLC IN CINSTALL IN A 4'SQUARE INSTALL IN A 4-SQUARE INSTALL IN A 4'SQUARE ® TEST COIL X 2-1/8'DEEP BOX FOR %2-1/8-DEEP BOX FOR X 2-1/8'DEEP BOX FUR SURFACE MOUNT.INSTALL SURFACE MOUNT.INSTALL SURFACE MOUNT.INSTALL ® - TEST COIL IN A SINGLE GANG DEEP IN A SINGLE GANG DEEP IN A SINGLE GANG DEEP BOX FOR FLUSH MOUNT. BOX FOR FLUSH MOUNT, BOX FOR FLUSH NUXK. ¢ IN/COMM. O O p M OUT CONY ONLY) o o e e Q - ICOMM- IY-^•CS 5 ahearn ® 12112C E fl RTS �i =a DNR ENC.INEERMGTECHNQLOGY _ _ M wa wu LR EV N MBERS Nk A HORN/STROBE STROBE HORN DNR DUCT DETECTOR DETAIL RTS-151 PC2WL SCWL HWL-LF �Y P2RK WIRING DETAIL WIRING DETAIL WIRING DETAIL AID RE B 17 202t DEs TGE —DMW cNK PTG PH/DH aunty uNunBB uEF fN0/AWI ♦1H PMIECIpN R BNOTE 3 NOTE 3 678 g DO N FAC�fP S BREAKPVAY TAB-MODULES HE WITH A L!7 SJ 4 11 ROT RRA n SWITCH.THIS BREAKAWAY ATAB NMUST BE WHO E➢ � H TO NEXT .3 FROM FACP \ 23 WHEN THE MODULE IS DN AN ES. THAT (WHEREC 3 USES MORE THAN 99 ADDRESSES. z + / APPLICABLE) NON-RESETABLE POWER / / \ DEVICE T TENS o 8 L Q NOTE I_.-J// NOTE 1, DETECTOR WIRING <SLC LOOP) TO BE 56 7 8 g Q Q INSTALLED USING TWISTED CABLE. // \ Z L.L NOTE 2- D❑ NOT LOOP WIRE UNDER ; \ 3 SETTING THE SLC ADDRESS W � w Q p TERMINALS 14 2. BREAK WIRE \ 2 Of � c m 0 (�) `*) RUN TO PROVIDE SUPERVISION - \ ) O LL OF CONNECTIONS. r ` Q Z LJ NOTE 3, OBSERVE POLARITY. DO NOT GROUND / APPLIED AND NO FAULT ) ONES O = >U & _ `s-J ■gym�� CONTROL WIRES. ) DETECTED. ) 47KD EOL z Q W T ) T I RESISTOR C) NOTE 4, SET THE ROTARY DIALS ON THE REAR to Rn 2 Q OF THE DETECTOR HEAD TO CORRESPOND @) o 1 ( I ¢ LL- TO THE LAST TWO DIGITS OF THE DEVICE Oo ASD-PL3 ASD PL3 � LOOP ADDRESS. N REFER TO THE FLOOR O W PLANS FOR THE DETECTOR DEVICE To rz \ / I I Z V- LOOP ADDRESS. rs Ta \ C / I N NOTE 5- RECORD THE LOOP ADDRESS S DEVICE n r4 \ / I I J TYPE IN THE SPACES PROVIDED ON m Te / I tN MIT Z O DETECTOR WIRING DETAIL \ NO / W THE DETECTOR BASE. m.®� I IN BUT IN pUT IN �T A NQTF, Q�O �° �� // L--1 CORRECT CORRECT INCORRECT z A EA H WITH MODULE ADD CANESS BE SET TO ONE OF 159 ADDRESSES(01-159)AND IS FACTORY PRESET C01224TR / TO SET AN SLC ADDRESS,USE A COMMON SCREWDRIVER TO ADJUST THE ROTARY SWITCHES ___ 0) ON THE MODULE TO THE DESIRED ADDRESS.WHEN FINISHED,MARK THE ADDRESS ON NOTE 6- INSTALL IN 4SQ RED DEEP BOX FOR ' 't THE MODULE FACE IN THE SPACE PROVIDED. SURFACE 3/0 BOX.MOUNT OR FLUSH MOUNT IN CO DETECTOR DETAIL WIRING METHODS MONITOR MODULE z+e AS NOTED AMM-4F - EPftX—NO.: coNslR.LTRm.ND. SHEE to o T FA-10 1 2 34 5