COM2021-00017 Fire Station - COM Permit / Conditions - 5/17/2021
} : 7 ! ' Mason County Mason County - Division of Community Development 615 W.Alder St. Bldg.8 ' Shelton, WA 98584 360-427-9670 ext 352 www.co.mason.wa.us FPROJECT 1-00017 NEW COMMERCIAL PERMIT ESCRIPTION: NEW FIRE STATION ISSUED: 05/17/2021 ESS: 490 NE OLD BELFAIR HWY BELFAIR EXPIRES: 11/13/2021 PARCEL: 123291100030 APPLICANT: NORTH MASON REGIONAL FIRE AUTHORITY OWNER: NORTH MASON REGIONAL FIRE AUTHORITY (NMRFA) (NMRFA) PO BOX 277 PO BOX 277 BELFAIR,WA 98528 BELFAIR,WA 98528 1.253.549.6949 ARCHITECT: ARCHITECTS WEST CONTRACTOR: TRICO COMPANIES LLC 210 E LAKESIDE AVE PO BOX 409 COEUR D ALENE, ID 83814 15066 JOSH WILSON RD 208.667.9402 BURLINGTON,WA98233 360.757.2373 VALUATIONS: FEES: Paid Due B VB Business 9933.00 $1,365,390.18 Pre-application meeting - Major $230.00 A-3 VB Assembly, general, 1482.00 $198,736.20 EH Plan Review community halls, libraries, Planning Commercial Review $380.00 museums Fee Covered Deck/Carport 1619.00 $35,618.00 Technology Surcharge $359.43 S-1 VB Storage, moderate 8408.00 $531,385.60 State Fee-Commercial $25.00 hazard Geo-Tech/Stormwater Review $300.00 Building Permit Fee $10,079.61 IFC Plan Check Fee $3,275.88 Plan Check Fee $6,551.75 Plumbing Fees $562.00 Mechanical Fees $778.00 Total: $2,131,129.9 Totals : $22,541.67 8 FIXTURES Printed by:Kate Campbell on:05/17/2021 01:07 PM Page 1 of 5 Mason County Mason County - Division of Community Development 615 W.Alder St. Bldg.8 . , Shelton, WA 98584 360-427-9670 ext 352 www.co.mason.wa.us NEW COMMERCIAL PERMIT COM2021-00017 y Mechanical Fixtures (sty Plumbing Fixtures 1.0000 Gas Outlets Each Additional 1.0000 Gas-piping systems (for first set of 1-5 outlets) 1.0000 Gas Outlet(s) (1-5) 1.0000 Number of Dishwashers 1.0000 Kitchen Exhaust Hood(s) 1.0000 FLOOR SINK 1.0000 For the installation of each hood which is served 1.0000 URINAL by mechanical exhaust, including the ducts for 1.0000 Number of Water Heaters and or Vent each hood 2.0000 Dryer Vent(s) 3.0000 Number of Hose Bibs 3.0000 Heat Pump(s) 3.0000 Number of Clothes Washers 4.0000 For each air-handling unit to and including 10,000 4.0000 Number of Kitchen Sinks cubic feet per minute (cfm) (4719L/s), including 4.0000 Number of Showers attached ducts. 6.0000 Additional gas-piping system outlet, per outlet 4.0000 Air Handlers- Miscellaneous 8.0000 Number of Toilets 8.0000 Spot Vent Fan(s) 9.0000 Bathroom Sink 8.0000 For each ventilation fan connected to a single 9.0000 For each repair or alteration of drainage or vent duct piping, each fixture 13.0000 For each appliance or piece of equipment 17.0000 For each plumbing fixture on one trap or a set of regulated by the Mechanical Code but not fixtures on one trap (including water, drainage classed in other Appliance categories, or for piping and associated backflow protection) which no other fee is listed in the table 15.0000 Other REQUIRED INSPECTIONS Setback Inspection Plumbing Inspection Underground Plumbing Insulation Inspection Footing Inspection HVAC Inspection-General Underground Inspections (Fire) HVAC- Ductwork Inspection Footing Inspection Commercial Sprinkler System Wet UNDERGROUND GAS LINE Foundation Wall-Pre-Pour Inspection SLAB INSPECTION Shearwall Inspection Slab Insulation Framing Inspection Masonry Inspection Rough- Plumbing Inspection Masonry Inspection Fire-stopping Inspection Shear Wall Nailing Mechanical Inspection Rough-Structural Inspection PW- Final Inspection Printed by:Kate Campbell on:05/17/2021 01:07 PM Page 2 of 5 Mason County � Tyr Mason County - Division of Community Development 615 W.Alder St. Bldg.8 Shelton, WA 98584 360-427-9670 ext 352 www.co.mason.wa.us NEW COMMERCIAL PERMIT COM2021-00017 Rough - HVAC Inspection Fire Marshal Final Rough- Plumbing Inspection Commercial Fire Alarm-Final Roof Sheathing Inspection BLD-Final Inspection Gas Piping Inspection CONDITIONS WIND LOADS- Roof coverings shall be designed and tested to withstand the maximum basic wind speed. The basic wind speed for Mason County is 85 MPH. * By definition, propane tanks and heatpumps are structures, which must meet setback conditions. Please check your "Approved Site Plan"to ensure these structures meet the setback conditions listed. * The international code requires a fire apparatus access road for every facility, building, or portion of a building that is more than 150'from an approved access road. Roads are required to meet the minimum Mason County Fire Marshal standards for Fire Apparatus Access Roads up to the point where such roads connect with a county maintained public road or to another fire apparatus access road which connects to a county maintained public road. * All surface water and potential runoff must be controlled on site and shall not adversely affect any adjacent properties nor increase the velocity flow entering or abutting to any state or county culverting/ditching system or road way. * CONSTRUCTION PROCESS TO BE FIELD CORRECTED AS REQUIRED PER MASON COUNTY BUILDING DEPARTMENT AND THE ADOPTED BUILDING CODE. The construction of the permitted project is subject to inspections by the Mason County Building Department. All construction must be in conformance with the international codes as amended and adopted by Mason County. Any corrections, changes or alterations required by a Mason County Building Inspector shall be made prior to requesting additional inspections. * Pressure treated wood manufactured after January 1, 2004 may contain high concentrations of copper which could quickly corrode metal fasteners, connectors, and flashing. Install metal connectors approved for contact with the new types of pressure treated material. * Owner/Agent is responsible to post the assigned address and/or purchase and post private road signs in accordance with Mason County Title 14.28 and 14.17. * When parcel development requires direct access to state road(s), a Road Access Permit or Approval must be granted and approved by the Washington State Department of Transportation. For more information contact Washington State Department of Transportation, at(206)357-2620, ext. 630. * Provisions for surface/subsurface drainage control must be implemented with new construction or development on site and MUST NOT adversely impact adjacent parcels. Under the requirements of Mason County Stormwater Ordinance, either private ditches and drains will meet requirements of the stormwater ordinance or prior approval will be granted to use an existing utility and drainage easement dedicated for that specific purpose. For further information regarding this ordinance and the REQUIREMENT to obtain an ACCESS PERMIT for the installation/construction of a driveway or access connecting from a Mason County Road, Contact the Mason County Public Works Department prior to construction at Ext 450. For any construction which is proposed to be located within 25' of a Mason County road right of way, it is suggested to contact that office to review future planned work which may affect your project. * All construction must meet or exceed all local and state ordinances in addition to the International Codes requirements as adopted and amended by Mason County and the State of Washington. Occupancy is limited to the approved and permitted classification. Any non-approved change of use or occupancy would result in permit revocation. Printed by:Kate Campbell on:05/17/2021 01:07 PM Page 3 of 5 � Mason County Mason County - Division of Community Development 615 W.Alder St. Bldg.8 Shelton, WA 98584 360-427-9670 ext 352 www.co.mason.wa.us NEW COMMERCIAL PERMIT COM2021-00017 " All permits expire 180 days after permit issuance, or 180 days after the last inspection activity is performed. The Building Official may grant a one time extention of 180 days, upon the receipt of a written extension request prior to permit expiration. Letter must indicating that circumstances beyond the control of the permit holder preventing action from being taken. No more than one extension may be granted. * REQUIREMENTS FOR ROOF COVERINGS. Roof coverings shall be applied in accordance with the applicable provisions of the current code and the manufacturer's installation instructions. A drip edge shall be provided at eaves and gables of shingle roofs. * The foundation/footing must be placed on undisturbed, firm-native soil. * All changes to"approved" building plans that effect compliance with the international codes as amended and adopted, or any other Mason County ordinance or regulation, must be reviewed and approved by Mason County prior to construction. * All property lines shall be clearly identified at the time of foundation inspection. * When parcel development requires direct access to county road(s), a Road Access Permit or Approval must be granted by the Mason County Department of Public Works. For more information contact Public Works, at(360)427-9670, ext.450 or 100 W Public Works Dr. Shelton. The building permit will not be finaled until the permit holder can show proof that the access permit from Public Works has been finaled and approved. * All RED stamped approved plans are required to be on-site for inspection purposes. If an inspection is called for and plans are not available on site, then approval will not be granted. In addition, a re-inspection fee (refer to current fee schedule, minimum 1 hour)will be charged and must be collected by the Building Department prior to any further inspections being performed or approvals granted. * The stamped approved site plan is required to be on-site for inspection purposes. If an inspection is requested and the approved site plan is not on site, approval will not be granted. In addition, a re-inspection fee (refer to current fee schedule, minimum 1 hour)will be charged and shall be collected by the Building Department prior to any further inspections being performed or approvals granted. * Contractor registration laws are governed under RCW 18.27 and enforced by the WA State Dept of Labor and Industries, Contractor Compliance Division. There are potential risks and monetary liabilities to the homeowner for using an unregistered contractor. Further information can be obtained at 1-800-647-0982. The person signing this condition is either the homeowner, agent for the owner or a registered contractor according to WA state law. * Approved per dimensions and setbacks on submitted site plan. Setbacks are measured from the furthest projection of the structure. * All building permits shall have a final inspection performed and approved by Mason County Building Department prior to permit expiration. The failure to request a final inspection or to obtain approval will be documented in the legal property records on file with Mason County as being non-compliant with Mason County ordinances and building regulations. * Concrete encased grounding electrodes must be installed and used at each new building or structure that is built upon a permanent concrete foundation. In Mason County the electrical code is regulated by Washington State Department of Labor & Industries (L&I). For more information contact L&I for additional information. In Olympia call (360)902-6350 and in Bremerton call (360)415- 4000. * Application acknowledges that the structure is only permitted for a use consistent with the current zoning of the parcel. * Comply with updated landscape plan added to file. Printed by:Kate Campbell on:05/17/2021 01:07 PM Page 4 of 5 � Mason County I � Mason County - Division of Community Development 615 W. Alder St. Bldg.8 Shelton, WA 98584 360-427-9670 ext 352 www.co.mason.wa.us NEW COMMERCIAL PERMIT COM2021-00017 " Deferral Conditions: 1. Panic Hardware at all Assembly area doors and fire wall locations including front entry. 2.All fire damper locations shall be confirmed with the Architect of Record PRIOR to installation and shall be listed and located for inspections, testing and servicing. 3. The Mezzanine ship ladder detail shall be submitted for clarification as access to an Equipment Platform using the exception in the IBC. " On-site Septic System final installation approval required prior to temporary/final occupancy of the residence. * Applicant/Owner assumes all responsibility if On-site Sewage Components are encumbered. A.) Drainfield/Reserve requires a 1 Oft setback from all footing/foundations. B.) Septic tank(s)requires 5ft setback from all footing/foundations. C.) No foundation/Perimeter Drains within 30ft, down gradient of Drainfield/Reserve area. D.) No Cut Bank(s) (greater than 5ft and over 45 degrees)within 50ft, down gradient of Drainfield/Reserve area. " From Richard Dickinson (Deputy Director of Utilities and Waste Management): Mason County has plenty of wastewater treatment plant capacity to serve this proposed project. An engineered main extension would be required to connect this property. The nearest connection point is approximately 2200 lineal feet away. - If sanitary sewer is extended to serve this property it will be at the cost of the proponent of this project. - Payment of Capital Facility Fee, design/project review fee &associated permit costs. -The proponent of this project could be eligible for a latecomer's agreement, as described in Mason County Code 13.32, to help offset the cost of construction. If an on-site septic system is the direction you plan to go please be aware this property is still subject to the following conditions: - Per Mason County Code 13.31.030; the property will still be required to connect to sewer when it becomes available and would then be required to decommission the on-site septic system along with any associated permits that may be required at that time. - Payment of a Sanitary Sewer System Capital Facility Charge will still be required per Mason County Code 17.03.030(2)(a) (ii)(7-8). I hereby certify that I have read and examined this application and know the same to be true and correct. All provisions of Laws and Ordinances governing this type of work will be complied with whether specified herein or not. The granting of a permit does not presume to give authority to violate or cancel the provi 'ons a o state/local law r g construction or the performance of construction. J Issued By: _ f' Contractor or Authorized Agent: Date: Printed by:Kate Campbell on:05/17/2021 01:07 PM Page 5 of 5 615 W.Alder St.Bldg 8,SHELTON,WA 98584 MASON COUNTY SHELTON:360-427-9670,EXT 352 l COMMUNITY SERVICES BELFAIR:360-275-4467,EXT 352 Building,Planning.Environmental Health,Community H"It 7 ELMA:360-482-5269,EXT 352 —Y www.co.mason.wa.us INSPECTION CARD AND CERTIFICATE OF OCCUPANCY** - To schedule an inspection call or visit http://www.co.mason.wa.us/community-services/bid-inspection. ,hp Permit Number COM2021-00017 Date Issued 05/17/2021 Issued Project NEW FIRE STATION Site Address 490 NE Old Belfair Hwy Applicant NORTH MASON REGIONAL FIRE AUTHORITY(NMRFA) Contractor Contractor Phone Primary Code UPC IBC,IRC,IFC,IEC,IMC,& Type Permit Type NEW COMMERCIAL PERMIT Occupancy -APPROVED PLANS MUST BE ONSITE FOR ALL INSPECTIONS. -DO NOT PROCEED BEYOND EACH STAGE OR COVER WORK UNTIL APPROVAL IS GRANTED. -THIS CARD MUST BE POSTED IN A CONSPICUOUS LOCATION, FRONT OF THE PREMISES IS BEST FOR MAKING ENTRY. -ALL PERMITS EXPIRE 180 DAYS AFTER THE PERMIT IS ISSUED OR 180 DAYS AFTER DATE OF LAST INSPECTION. -OWNER/AGENT IS RESPONSIBLE FOR REQUESTING ALL INSPECTIONS THROUGH FINAL INSPECTION. **THIS STRUCTURE MAY NOT BE USED OR OCCUPIED UNTIL ALL APPROVALS ARE GRANTED.** PRIOR TO CALLING FOR FINAL INSPECTION,ALL CONDITIONS OF THE PERMIT MUST BE MET Public Works Access/Driveway Other Health Septic Well Deptartment Planning Site Inspection Department Fire Marshall Fire Apparatus Access Fire Sprinkler Auto Fire Alarm Hood and Duct Other Final Building Building Official: Community Services Designee Department Concrete Setbacks LA--L/ V7Z. Slab Footing Perimeter t d'7Z_ Point load Footing Footing Interior Footing Decks/Porches Foundation Stem Walls Other Rough-In Groundwork Plumbing V -Zj j-rL_ Framing to — (q-Z( J T-L, Groundwork Mechanical Plumbing ZI JTL Groundwork Gas Pipe Mechanical 2. _j_Z Gas Piping 1ImIct) /1_8.44 JZZ Shear Wall Nailing Underfloor CVAV t✓attS Other Insulation Slab c J r Ceiling 2.Z JTL. Floor Vaulted Ceiling Walls Vapor Barrier (p..t u Other Wallboard Interior Wall Brace Panels Fire Walls I�(7_2 J-� Nailing Other Final Building Manufactured Setbacks Setup Home Concrete Foot/Runners Final Other Dk / c.� S l� ��7 f6 It � ld L�( ,Q_,�,��'('�S 5� �o �j.C. (�w��t� a rl' � �et�✓ a�`�. a �4d $�p��'"f 1pc�tX ?e..�t �g J4c�t"tfrt ir,Q1� ay.� c1,�-�1��/�,eK.k✓cv✓ S� 74,(W �` `3�e.� �� sf�i'���r✓-r - r4- r• �Irtd-t s2. - o �'7✓ovKc� vNti�i --F�/-? G Z-tf .jZ ., 7 G -u-2 JZ b-�ct,'Z� J'tZ -f-t�'I�t✓tv✓ 1'�u-i-�uS S H�IM«t �� r� - �J- �SS�Z l �T2_ r�t-fGticu�.i �crJ-�-e�,,.5 � yyt.c c G+�`rlu � S rv�t l t/'�.�-..,� 5.,y✓za.,� ( S/hg 1Ze�4 �+w.� r J-R— S ('4 � Ca H,.�(.�� ©tit f+.9i Wrc�c d—�NI,CL� . S'tt�•L(s�� , ^2^2( C eavx+-A-c� rh5jZct�r� �-✓ /�n -P(A Ct �rt �Iv✓ lJl�<� Q f fl�'µf tom' �Olh f f'Os o> -�-21 SAS LMU �5 oy, o-F -j s IC�..,41s q 1,0- gfeel 1l...4— C-► e-� 5 tip �oL,4 �a ��titL , c'oluVKv, CvHtin ✓i�� �� g kc( r v► -71*c c aSn�c_ 1 sa' (oo-v - 3 7-LA-Zt �C5 lam"io lt3, ; Mt3l�;,ty �s C6 Y-41 O --au- -7-7.ss-Z4 .t�z col mow► a+ wt 4- a to./. Gt 5- ( ,Lt 4x�oeH s d-A.57 / S�� o 4 l�l.�- 4c f-c.�. �� C W O l *4— Svtrfir t u t1« LIAl ICA-C K rc r✓�i t o �'o I1o,w OF OV, �.2-2( _ ��� �.a.w. �� �- Sa�i't^ Wa.�l I�` d- Z�` eivw�• - tie. �` tnx v �� c�K +7)e-I ✓b� c i3ov C( 1740,4. g-a"x t „� Sw- we.l<s A-(50 51,t -� 2t j1.��� r„�.1� 6c.4 ✓ a►aµ�� rtrcrw� fi � s C'-��,.� hws A � � t's+{c � -17� �rhlcuct�nrc4(' Accl� vt�t(r c���k— e�•� /G,-k�����"Z . Co rf(.e rvaM A _ r A Q*# - - 4 Ya t� �{ao�•/S O�.t,/ {C.�l� ae�c.a.. �tJ��`. (/�C rat� I/�6 p�� /�cwr�fr.-4.d,.►1 is ^f1'✓h/��llct 7�v` a-�- y�C� rod A u 5� ��r� g_Z(,-z. l �'�,�.c-k.•� � 4`c'v+er�l� k i,.►>"�� �' 1�d� '�t' '�?�''� c17L �✓'��'S -b 00 CaAo I Z-1 -1,1Qc - l7Nal txwsL% C kf �Gu�(' !K '-f I�or�tt t ✓Ouv�; l / —s'-'LL �.is `ti c w4✓ 40 Co,µ' U It C��c�.� v�� S��►� tu.S4-w1( IOU asJtcrC �S `,( �'t �'`� �van�Gt � ht r�vS rrS� �` �-r�-,�+-,-..c • GiKrazan & ASSOCIATES, INC. GEOTECHNICAL ENGINEERING • ENVIRONMENTAL ENGINEERING CONSTRUCTION TESTING & INSPECTION May 2, 2022 KA Project No.: 10621094 Mr.Joshua Luck Email: jluck@co.mason.wa.us Mason County (Lead Building Inspector) 615 W Alder Street Shelton,Washington 98584 Project: North Mason RFA Fire Station 490 NE Old Belfair HWY Belfair,WA 98528 Subject: Final Special Inspection Letter Mason County BLDG Permit No.: COM2021-00017 Dear Mr. Luck, In response to the request and authorization of Ms. Renee Wassenaar representing North Mason Regional Fire Authority, Krazan &Associates has provided special inspection and related construction materials testing services for the North Mason RFA Fire Station project located at 490 NE Old Belfair HWY in Belfair, Washington. Our services were performed by our staff from April 28, 2022 through May 2, 2022, under the supervision of a State of Washington registered engineer. Our observations were documented in our inspector's daily field reports which have been submitted the owner,structural engineer of record,contractor and Mason County building department. Krazan provided special inspection for the following type of construction at the project site: Soils and Foundations Reinforced Concrete Reinforced Concrete Masonry Units Structural Steel Welding including NDT(UT) Structural Wood (Shearwall Nailing) In accordance with Chapter 17 of the 2018 International Building Code,the work requiring special inspection was performed in conformance with approved plans and applicable standards of workmanship at the time of completion. LIMITATIONS We have performed our services in a manner consistent with the standard of care and skill ordinarily exercised by forms of our type practicing under similar conditions at the time and locality our inspection was performed. Please recognize that construction monitoring is a technique employed to reduce the risk of problems arising during construction. Provision of construction monitoring by Krazan& Associates personnel is not insurance, nor does it guarantee the construction of any type. In all cases the contractor shall retain sole responsibility for the quality of there work, adhering to the approved project plans and specifications and for repairing any defects, deficiencies or omissions, regardless of when they are found. Our services were limited to the work documented in our reports. We do not With Offices Serving The Western United States 1230 Finn Hill Road NW,Suite A•Poulsbo,WA 98370•(360)598-2126•Fax:(360)598-2127 KA No. 10621094 Page No.2 undertake the guarantee of construction or completion of a completed project conforming to the plans and specifications. No warranty expressed or implied. CLOSING We trust that this report is sufficient to meet your needs and appreciate the opportunity of working with you on this project. Should you have any questions, comments or if we may be of additional service to you, please feel free to contact us at your convenience. Respectfully Submitted, K��ra/zan&Associates, INC. Wes A. Mahan Operations Manager Peninsula Division Krazan&Associates,Inc. Offices Serving The Western United States