AN ORDINANCE ADOPTING A CROSS CONNECTION CONTROL PROGRAM FOR ALL
WATER SYSTEMS OWNED AND OPERATED BY MASON COUNTY
WHEREAS, WAC 246-290-490 Establishes cross connection control regulations;
WHEREAS, Purveyors (in this case Mason County) have the responsibility to protect
public water systems from contamination due to cross connections . Cross connections which
can be eliminated shall be eliminated;
WHEREAS, Mason County shall develop and implement a cross connection control
program acceptable to the State Department of Health;
WHEREAS, this ordinance replaces ordinance no . 21-03 and which limits the existing
cross connection program to the Beards Cove Water System and ordinance no. 128-98 which
references Hartstene Pointe and is in the Mason County Code under chapter 13.19;
WHEREAS, this ordinance will replace those that are currently found in the County Code
in chapter 13 .19;
WHEREAS, The Board of County Commissioners held a public hearing on December 4,
2012 to consider the recommendations of the Department of Public Works and Utilities to
change the coverage of the cross connection program from Beards Cove and Hartstene Pointe
to all public water systems owned and operated by the Mason County;
WHEREAS, this hearing was advertised in the legal newspaper for Mason County;
NOW THEREFORE IT BE ORDAINED that the Board of County Commissioners of Mason
County hereby adopts the cross connection control program for all public water systems owned
and operated by Mason County.
This ordinance shall be in full force effective on this date
LJn; DATED this :1 day of December, 2012
APPROVED AS TO FORM
~~~Z TIM WHITEHEAD,
Ch . Deputy Prosecuting Attorney
BOARD OF COUNTY COMMISSIONERS
MASON COUNTY, WASHINGTON
.--rz:. '
TIM SHELDON, Commissioner
MASON COUNTY DRINKING WATER SYSTEMS
Cross-Connection Control Ordinance
PURPOSE
The purpose of a Cross Connection Control Program is to protect the health of water consumers
and the potability of the water system. This program is designed to maintain the quality of
Mason County public water supplies by the elimination and prevention of cross connections
between the distribution system and other sources of water or liquids used for other purposes.
The policies and procedures presented in this program are designed in compliance with WAC
246-290-490
GENERAL
Except where specifically designated herein, all words used in this program shall carry their
customary meanings. Words used in the present tense shall include the future, and all plural
words shall include the singular. The word "shall" indicates a mandatory action, and the word
"may" denotes a use of discretion in making a decision.
DEFINITIONS
Air Gap Separation {AG}: Shall mean the unobstructed vertical distance through the free
atmosphere between the lowest opening from any pipe or faucet supplying water to a tank,
plumbing fixture, or other assembly, and the maximum flood level rim of the receptacle. This
gap shall be at least double the diameter ofthe supply pipe measure vertically above the flood
rim of the vessel. In no case shall this gap be less than 1 inch.
Approved Backflow Prevention Assembly: Shall mean any assembly to prevent backflow that
has been approved for use by the System Manager and DOH. Approved assemblies shall be
those that have successfully passed performance tests of the University of Southern California
Engineering Center or another approved testing laboratory.
Atmospheric Vacuum Breaker (AVB): Shall mean a backflow prevention assembly which is
operated by atmospheric pressure in combination with the force of gravity. The unit is so
designed to work on a vertical plane only. The moving part consists of a poppet valve, which
must be carefully sized to slide in a guided chamber and effectively shut off the reverse flow of
water when a negative pressure exists in the supple system. An AVB is designed to protect
against back siphonage events only.
Auxiliary Supply: Shall mean any water supply on or available to the premises other than the
County public water supply/
Backflow: Shall mean the flow, other than in the intended direction of flow, of any foreign
liquids, gasses or other substances {including water} into the distribution system of the public
water supply.
Backflow Assembly Tester: Shall be a person certified by Washington State in the inspection
and testing of approved backflow prevention devices.
Back Pressure: Shall mean any induced pressure caused by a pump, elevated tank, boiler,
pressure vessel, or any other means that could create pressure within a customer's system
greater than the operating pressure of the public water supply distribution system.
Back Siphonage: Shall mean backflow of water due to a negative or reduced pressure within
the water system.
Building Inspector: Shall be a Building Inspector of Mason County.
County Inspector: Shall be that person or persons employed by the County that have been
trained and are qualified to perform the designated inspection work.
Cross Connection: Shall mean any actual or potential connection whereby w public water
supply is connected directly or indirectly, with any other water supply system, sewer, drain,
conduit, pool, storage reservoir, plumbing fixture or other assembly which contains, or may
contain, contaminated water, sewage or other waste or liquid of unknown or unsafe quality,
which may be capable of imparting contamination to the public water supply system as a result
of backflow {reversed flow}.
Customer: Shall mean any person, persons, firm or corporation that is furnished potable water
from the public water supply system through a legal service connection to the public water
supply distribution system.
Double Check Detector Assembly (DCDA): Shall mean an assembly composed of two {2} single,
independently acting, approved check valves, including resilient seated shut-off valves located
at each end of the assembly and properly located tests cocks to test the water tightness of each
check valve. Double check valve assemblies are designed to protect the water supply system
from both back siphonage and back pressure events. They are not suitable for use in protecting
the water system from health threatening substances.
Hazards:
Degree: Shall express the results of an evaluation of a health, system, or plumbing
hazard.
Health: Shall mean any condition, assembly, or practice in a water supply system and/or
its operation that creates, or may create, a danger to the health and well-being of a
customer.
Plumbing: Shall mean a potential or existing cross connection in a customer's water
system that may permit back siphonage in the event of a negative or reduced pressure
in the supply line.
System: Shall mean a threat to the physical properties of the public or the customers
potable water system by a material not dangerous to health, but aesthetically
objectionable and having a degrading effect on the quality of the potable water within
the system.
Industrial Fluids: Shall mean any fluid or solution which may be chemically, biologically, or
otherwise contaminated or polluted in a form or concentration that would constitute a health
or plumbing hazard if introduced into a potable water supply. This may include, but is not
limited to, all types of processed waters originating from the public water or auxiliary supply,
which may deteriorate in sanitary quality. Types processed waters include chemicals in fluid
form, circulated cooling waters that are chemically or biologically treated or stabilized with
toxic substance, and contaminated natural waters, as from springs, stream, or ponds.
Liquids: Shall mean any substance that flows readily but does not expand indefinitely, such as
water and industrial fluids.
Mason County DCD: Shall also be referred to and the County, herein.
Pressure Vacuum Breaker Assembly (PVBA): Shall mean a backflow prevention assembly which
consists of a spring-loaded check valve, an independently operating air-inlet valve, inlet and
discharge shut-off valves, and properly installed test cocks. The air-inlet valve is internally
loaded to the open position, normally by means of a spring. This internally loading allows the
device to be installed on the pressure side ofthe shut-off valve. A PVBA is designed to protect
against back siphonage events only.
Public Health Officer: Shall be the duly appointed Public Health Officer ofthe Southwest
Washington Health District. Any act in this program required or authorized by the public Health
Officer may be done on his/her behalf by an authorized representative of DOH.
Public Water Supply: Shall be the system operated and maintained by the County, which is a
water supply intended or used for human consumption or other domestic use. The public water
supply system included source, storage, transmission and distribution facilities where water is
furnished by the County to the customers of the County.
Reduced Pressure Principal Backflow Prevention Assembly (RPBA): Shall mean an assembly
containing a minimum of two (2) independently acting, approved check valves, together with
an automatically operated pressure differential relief valve located between the two check
valves. During normal flow the pressure between these two checks shall be less than the
upstream (supply) pressure. In case of a leakage of either check valve, the differential valve, by
discharging to the atmosphere, shall operate to maintain not less than two psi of pressure
between the supply pressure and the zone between the two check valves. The unit must
include resilient seated shut-off valves located at each end of the assembly, and each assembly
shall be fitted with properly located test cocks.
Service Connection: Shall mean a connection between the public water supply distribution
system and the customers system.
System Manager: Shall mean the Water System Manager, Mason County, Washington. Any act
in this program required or authorized by the System Manager may be done on his/her behalf
by the authorized representative of Mason County.
CODE AUTORITY AND ENFORCEMENT
The enforcement of this Cross Connection Program, in the area served by the Mason County
Owned and Operated Drinking Systems, shall be in accordance with the Uniform Plumbing
Code, latest Edition, and WAC 246-290, Rules and Regulations of the State Board of Health
relating to public water supplies.
GENERAL POLICY
It is the intention of this program to provide for the permanent abatement or control of all
cross connections. Where it is physically and economically infeasible to find or to permanently
eliminate all cross connection of the customers water systems, and when it is deemed
necessary by the appropriate inspector, there shall be installed at the service connection a
suitable backflow prevention assembly commensurate with the degree of hazard to the public
water supply.
The following methods of cross connection control are considered minimum protection at the
service connection.
1. The public water supply to a premises having auxiliary water supply from an additional
public supply with no known cross connection shall require an approved DCVA at the
service connection.
2. The public water supply to a premises on which is handled a substance that is
objectionable (not a health hazard) in a manner constituting a potential cross
connection shall require a DCVA at the service connection.
3. The public water supply to a premises on which there is an auxiliary water supply and
internal cross connections that are not correctable or intricate plumbing arrangements
which make it impractical to ascertain whether or not cross connection exist, shall
require a RPBA at the service connection.
4. The public water supply to a premises on which material dangerous to health or toxic
substances are handled shall have installed a RPBA at the service connection.
5. The public water supply to a premises where entry is restricted so that inspection for
cross connection cannot be made at a sufficient frequency or sufficient short notice to
assure that cross connection do not exist shall have installed a ROBA at the service
connection.
6. The public water supply to a premises on which any substance is handled under
pressure so as to permit entry into the public water supply, or where a cross connection
could reasonably be expected to occur, shall have installed a RPBA or DCVA, according
to the health hazard at the service connection.
7. The public water supply to a premises having a repeated history of cross connections
being established or re-established, shall have installed a RPBA at the service
connection.
SURVEILLANCE PROGRAM
The County is charged with the responsibility of ensuring that the public water supply is not
compromised by events resulting from cross connections. As such, a Surveillance Program
based on proper management, adequate record keeping, and aggressive inspections must
be properly implemented by the County.
Such a program for cross connections initially requires the inspection of all new and existing
buildings, structures, and grounds. The procedure requires the County Inspector(s) and the
Building Inspector(s) to assist with the requirements of DOH. Each must be knowledgeable
in the field of plumbing and building inspection, pipe arrangements, and cross connection
control.
The systematic program of inspection shall be established with priority given on the basis of
risk to public health and shall be conducted according to the following outline:
A. New and Proposed Construction
1. Upon application for a building permit, the Building Inspector shall require a detailed
set of plans and specifications for the plumbing installations, and shall make such
detailed plans and specifications available to the County Inspector.
2. The Building Inspector and the County Inspector shall review these plans and
specifications to determine the probability of cross connections, the availability of
the auxiliary water supplies, the handling of substances which, if introduced into the
water system, would constitute a health, plumbing, or system hazard. If, upon
review, it is determined that any of these conditions will exist, the County Inspector
shall coordinate with the property owner to ensure such cross connections are
properly controlled, or eliminated.
3. During the construction phase of any new building, structure, or ground
installations, and during the regular plumbing inspections, the County Inspector shall
perform the required cross connection control inspection. Upon completion of the
inspection, but prior to the approval of any water service connection, the County
Inspector shall advise the customer in writing that further backflow preventing
testing is, or is not required. The customer shall also be notified that Washington
State certified backflow assembly tester must test the backflow assembly, and that
the test report form completed by the certified tester must be received by the
County Inspector prior to the regular use of the customer's water system.
4. Upon receipt of an application for new water service, but prior to the installation of
such new service, a cross connection inspection shall be made by the County
Inspector and required backflow prevention assemblies shall be installed at the time
the new service is installed.
B. Existing Buildings, structures, and Grounds
1. An initial survey of the water system customers shall be conducted by the County to
determine if any cross connections currently exist. The initial cross connection
determination shall proceed according to the following steps:
a) A survey form shall be sent to each customer explaining the program and
stressing the relationship between the cross connections and water-borne
disease epidemics, types of health hazards, and cross connections. The survey
shall also include a brief questionnaire with desired information, such as a
auxiliary water supply, any chemicals used, and certain types of fixtures installed.
This survey shall be returned by the water system customer to the County.
b) Based upon the responses received from the questionnaire, if the County
determines that a customer has a potential cross connection, a letter requesting
an appointment for inspection by the County Inspector shall be sent to the
waters system customer.
c) Upon completion of the inspection, the County Inspector shall orally brief the
customer or his/her representative of the inspection findings.
d) The County Inspector shall prepare a written report for the water system
customer and the System Manager that shall include the following information:
1. Complete identifying information contained in heading.
2. List of all potential or actual cross connections found, including the location
and options for method of control for each.
3. List of any industrial fluids, chemicals or other contamination liquids used or
pumped under pressure, the use of each, and an indication of the probability
of cross connection.
4. Any applicable drawings, sketches, blueprints, etc. used in support of the
inspection.
5. A summary of the findings of the inspection.
6. Recommendations for actions to be taken by the customer.
e) The System Manager, upon completion of review of the report, shall prepare a
letter to the customer outlining the corrective action required, and the time
period in which the corrective action must be completed. A copy of this letter
shall be send to the customer (return receipt requested), and a copy shall be
maintained at the County.
f) When all required actions have been completed, the file copy of the completed
actions shall be placed in the County's cross connection control file.
g) Each premises required to be in compliance with the program shall be re-
inspected annually, or more often if the degree of hazard so indicates.
2. The backflow prevention devices at the wastewater treatment plant and the
Community Center shall be inspected and tested annually by certified backflow
assembly tester.
CORRECTIVE MEASURES
Corrective measures for cross connections shall follow the guidelines in the most recently
published Accepted Procedure and Practice in Cross Connection Control of the Pacific Northwest
Section (PNWS) of the AWWA.
CODE
The following are the abbreviations for assembles or methods used to prevent of eliminate
cross connections:
1. Air Gap
2. Reduced Pressure Backflow Assembly
3. Double Check Valve Assembly
4. Double Check Detector Assembly
5. Pressure Vacuum Breaker Assembly
6. Atmospheric Vacuum Breaker
AG
RPBA
DCVA
DCDA
PVBA
AVB
PROCEDURES FOR INSTALLATION, INSPECTION, AND MAINTENANCE OF BACKFLOW-
PREVENTION ASSEMBLIES
A. Initial Installation
1) When it is determined that a RPBA, DCVA, DCDA, PVBA, or AVB is required, the
County shall inform the owner/manager of the need for a device.
2) Approved assemblies shall be installed as specified in the Uniform Plumbing Code,
the PNWS-AWWA Cross Connection Control Manual, or the Mason County Owner
and Operated Drinking Systems Design Standards, whichever is the more restrictive.
3) Upon completion of the installation of the backflow assembly, a certified backflow
assembly tester shall make such tests as are required to ensure proper operation of
the assembly. If the assembly fails any portion of the test, the assembly shall be
rejected until such time that a repaired or a replaced assembly passes all portions of
the tests. The test results shall then be supplied in the County.
B. Inspection and Maintenance
1) All backflow prevention assemblies shall be tested not less that annually. The testing
shall be made by a certified backflow prevention assembly tester, and the results are
to the forwarded to the County.
2) Maintenance
a) When a backflow prevention assembly is determined to be defective, the tester
shall notify the County immediately.
b) Upon receipt of notification of the defective assembly, the customer shall take
the necessary steps to repair or replace the defective assembly. The defective
assembly shall be repaired or replaced by the qualified person, who has specific
training in backflow prevention assembly repair.
c) Upon completion of repair or replacement, the backflow prevention assembly
shall be tested by a certified backflow prevention assembly tester.
RECORDS AND REPORTS
following information shall be available through the County's record keeping
program.
1. Information regarding installations.
2. Test results for installations.
3. Information about testers.
4. Tester's certifications histories.
5. Mailing addresses of installation owners.
6. Device manufacturers and model and approved status.
MASON COUNTY
DRINKING WATER SYSTEMS
In order to protect the public potable water supply from possible contamination or pollution
due to backflow from a customer's private internal system, Mason County has established a
Cross Connection Control Program. The County recognizes that there are varying degrees of
risks associated with different types of uses and will consider this when determining if a cross
connection exists and what, if any backflow prevention device will be required.
Please complete the following survey and return it to _______________ _
Name ----------------------------------
Address ---------------------------------
Phone Number ___________ Alt. Phone Number ___________ _
1. Please indicate if your home has or will have any of the following fixtures, equipment, or
areas on site:
Yes No
Fire sprinkler system
Irrigation system
Air conditioning system
Bathtub, below rim filter
Bidets
Boiler feed lines
Decorative ponds
Dialysis Equipment
Floor Drains
Flushing floor drains
Heat exchangers
Heat pumps
Hose Bibbs
Hot tub
Sumps
Photo developing sinks
Sewer connected equipment
2. Please provide the following information on any existing backflow protection that you
are aware of:
Existing Cross Connection Protection
Assembly Testing
Hazard/Location Type Make Model Serial No. Information
3. Please provide the name of any products or chemicals that you mix with water for use in
your home, such as fertilizers, etc.