Loading...
HomeMy WebLinkAboutCOM2021-00013 ShearWall Modification - COM Engineering / Geo-Tech Reports - 2/23/2021 y WALSH ,711 CONSTRUCTION CO. BUILDING VALUE I www.waishconstruction.com Request For Information Project: 122020-014 Prelim-Aldertarook Spa Refresh RFI Number: 15 RFI Type: Preconstruction RFI Date: 02/23/21 Revision: Priority: Status: Open Date Sent: 02/23/21 Due Back: 03/02/21 Sent By: Tracy Ann Michel To Firm: SkB Architects To: Meg Taylor From Firm: Walsh Construction Co./Washington Contact: Tracy Ann Michel Subject: Retail Structural Wall Question: During investigation of the retail wall that currently divides the retail from admin offices,it was discovered the wall is structural and upgrades to the wall will be necessary in order to open the wall as defined on A2.1. Please advise what modifications will be necessary.Preliminary definition has been provided and further research is being investigated.Using the RFI system to document and not lose sight of item in the works. Thank you. Impact: Days: TBD ROM: TBD References: 6/A9.3,A2.1 Notes: Response: SEE ATTACHED STRUCTURAL DETAILS AND CALCULATIONS FOR REINFORCEMENT OF SHEAR WALL AT RETAIL OPENING, Answered By: M.TAYLOR/SkB ARCHITECTS Date: 02.25.21 Distribution: Sent To Finn Sent To Contact Date Required ----------------—------------------------------------------—--------------------—-----------------------—-------------- 2 Walsh Construction CoAVashington John Lennox 3 Walsh Construction Co./Washington Randy Cossette 4 Walsh Construction Co./Washington Tracy Ann Michel 5 North Forty Lodging,LLC dba Alderbrook Resort&Sp Laurie Kenneth 6 SkB Architects Louie Caldwell 1 SkB Architects Meg Taylor Version 20180219 Page 1 of 1 02/23/21 11:30:06 AM PORTLAND,OREGON SEATTLE,WASHINGTON TACOMA,WASHINGTON 2905 SW First Ave,Parkland,OR 97201 315 Fifth Ave S,Suite 600,Seattle.WA 98104 301 S 28th St,Tacoma,WA 98402 O 503.222.437'5 I F 503.274.7676 O 206,547,4008 I F 206.547.3SO4 a 253.572,4245 0RCC6147267/WAL5HCC962LD WALSHCC99001 WALSHCCO90DI s 6A QM) (2)2x trim studs for new header _ (2)2x Studs ETAIL I' — 281 I I Simpson HDUB-SDS2.5.Install with 7/8'dia ssK A___threaded rod F1554 Gc36.with HIM HIT-HY b oa I 200 epoxy and T-0"embed depth.Note 1. h tmCOLLM ® I j �, ' SOUND < I C� • v — — I Fasten new HDU8 to(E)studs.Verify there are A93 ssK_ a min of(2)existing studs.Install(2)new studs if none existing.Note 2. fESERVATIONS 17 278 F 1 SSK-02 for anchor bobs.---'"�- Assumed(E)studs for bearing point above I SSK-01, Verify(E)studs are at Woo Modified Add sheathing to this side of Shear Wall shear wall,full height. (E)Shear wall sheathing is assumed to be on Use 15132"Structural I — this side of wall.Contractor to Verify nailing in sheathing,nail all panel _existing sheathing as:4"oc at panel edges and edges with 10d @ 3"oc,and at 12"oc in field. D 12"oc at field.Notify FOR if nailing is other. 2nd Floor Partial Plan from A2.1 {2}2x studs at new HDU,Note 2, Simpson HDU8-SDS2.5.Install with 7/8"dia threaded rod F1554 Gr.36.with HIM HIT-HY 200 epoxy and V-0"embed depth.Note 1. (E)HDU to remain (E)HSS Column to remain Modified Shear Wall Ian NOTES: 1,Do not harm existing foundation reinforcement when drilling 2.Nail new studs into existing shear wall sheathing with 10d @4"oc at panel edges and 12"oc field. 3.New studs are DF no.1 10 4 UND ,,,�„Alderbrook TI HL Print noColor Existing Shear Wall Modification-Partial Plan SAH o,�Knae.zl-o21-01 0„"02/24n021 S_SK_U1 A2.1 six NTS SE~6- r.J Cl't' 1, NSA 144 -L& Pc-rH i r` 6- . . - 5 r M P sa:ti1 � ..... siteA7tirxjc (2 tot' r oec- STA6(TQ, 71f P. a Cal 6-LB, I �Z,x '-RL> C)pErj}�J&- HEA00-k 1+5S.D Fug 14 E4 GH T. H f�P, 'T.P;1 F'Ffi� ARCH Tb FRAME ' �j i✓W OPEt l r Q(,- �- (r=) R55 Co t SaE Oers '1,, NOTES: TO , REMAtr-,4. 1. Contractor to verify GLIB Hanger is present before cutting opening. Notify FOR if GLB hanger does not exist. 2. Existing shear wall sheathing to remain in place. Install trim stud, header and blocking from opposite side of wall. Nail existing sheathing to new framing with 10d @ 6" oc. I Protect Alderbrook TI UND Existing Shear Wall Modification - Header detail 4S)AHL Project No. 21-021-01 Date 02/24/2021 1201 Fast Avenge South,Sane 310 S S K 0 3 Seattle.Washington 93139 zosao2 slss wwwaanaopsaht.com Reference A2.1 scale NTS P qea Alderbrook TI Sheet za,n�ezc Existing Shear Wall Modification Page No 4kSAHL NDArchitects, _ . t<t��t SKB nra�eclt�lo �;� 021-01, oesiyner RN R _ gaze 2/24/2021 www.lundopsahl,com Tel:206.402.5156 to rV= _ U t yr rye -} 0." -> cS- s rtt't� at 1405 ib) = 6 LtS 2 I t 1,35 g - � P ..._-Alderbrook TI Sheet SIM Existing Shear Wall Modification P eNa. .._. �( ND j cu.., SKB Architects P�oKt�+o 21-021-01 U SAHL °� ....._.. .. _..,.. .._..__—Oate 2/24/2021 www.lundopsahl.com Tel:206.402.5156 -t ram,5+ p* 4 841106 r L{34 + 6 4 a -- S cr 3'8 16 r � 4- 1 x ra - 2N3 ��3 Ise = -- 5 2 1b e-e- zkW,c &ed,,. N1141' Pepo r+ rc2) s«'�s®r� Iu- ' Tc� = 2 (C, 75b' = 1 = j VD �(�-74�15 Ib) J� L 2-9 6. 7 (1.. r2 t=D s 0 0 jo 15,2-i ct 1 Z�..q 'Ys c'L SG�CtG 3-T to I r p l� �tj 1i F 3Cr C-.Q.. I F}" eta fi4 (5 G� � = t Alderbrook TI sheet subjec, Existing Shear Wall Modification Pa�e�o_ 6 NDc31,. SKB Architects pro)ec„ 21-021-01. Designer RNR m...__ Date,2/24/2021 IaSIAHL j www.lundopsahl.com Te1:286.482.5156 c411 e }c�r Lc cd P ' SaC,101-P 5�1 7 tom`/ _ � I I � l gam' 5 S SimpsonRestoration Gas- and Powder-Actuated Fasteners Design Information - Steel 1 s Powder-Actuated and Gas-Actuated Fasteners - * ~ Allowable Shear Loads in Steel' ABC MW y / / 410 365 389 3851 3254 PDPA,PDPAT, 0.157 0.5 1 A36 - (1.82) (1,62) (1.71) (1.71) (1.45) 0C PDPAWL (4.0) (13) (25) A572 Gr.50 _ 420 290' 275' 2757 or A992 (1,87) (1.62) (1.29) (1.22) (1.22) Powder PINW 0.145 0.5 1 A36 _ 395 Actuated PINWP (3.7) (13) (25) (1.76) - - - - PSLV3 0.205 1 11Fz A36 - 770 1,120 _ _ _ a Smooth shank (5.2) (25) (38) (3.43) (4.98) PSLV3-12575K 0.205 1 11h 930 1,130 _ Knurled shank (5.2) (25) (38) A36 (4.14) (5.03) - - - 0.5 1 285 225 A36 205 GDP 0.106 (13) (25) (1.27) (1.00) (0,91) - - - (2,7) 0.5 1 A572 Gr.50 _ 250 145 (13) (25) or A992 (1.11) (0.64) - - - f 0.5 1 A36 _ 180 265 2258 2251 _ Gas GDPS 0.118/0.102 (13) (25) (0.80) (1,18) (1.00) (1.00) Actuated (3.0/2.6) 0.5 1 A572 Gr 50 _ 205 305 2058 (13) (25) or A992 (0.91) (1.36) (0.91) - 400 345 3109 0.128/0.110 (13) (25) A36 GW-50 (1,78) (1,53) (1,38) 3.3/2.8 ( ) 0.5 1 A572 Gr.50 _ 380 3259 3509 _ s 113) 1. The entire pointed portion of the fastener must penetrate through the steel to obtain the tabulated values,unless otherwise indicated. 2. The allowable shear values are for the fastener only.Members connected to the steel must be investigated separately in accordance with accepted design criteria. 3. Steel strength must comply with the minimum requirements of ASTM A 36(Fy=36 ksi,Fu=58 ksi), ASTM A 572,Grade 50(Fy=50 ksi,Fu=65 ksi),or ASTM A992(Fy=50 ksi,Fu=65 ks). 4. Based upon minimum penetration depth of 0.46'(11.7 mm). 5. Based upon minimum penetration depth of 0.58"(14.7 mm). 6. Based upon minimum penetration depth of 0.36'(9.1 mm). 7. The fastener must be driven to where the point of the fastener penetrates through the steel. 8. Based upon minimum penetration depth of 0.35'(8.9 mm). 9. Based upon minimum penetration depth of 0.25"(6.4 mm). z 10.For stepped shank fasteners:(Diameter of shank above the step)/(Diameter of shank below the step). 11.The allowable load values listed are for static load conditions.Refer to ICC-ES ESR-2138 and ESR-2811 code reports for seismic load conditions. a M 0 0 F Spiral Knurl Pin Allowable Tension and Shear Loads z in Cold-Formed Steel Studs z r / & f 0 33 30 70`_ ) ® (20) (0.13) (0.31) T N 43 48 89 ci GDPSK 138 0,109 WIG 4 (18) (0.21) (0.40) � (2.8) (2.1) (102) 54 92 150 t 1 (16) (0.41) (0.67) 1 1 k 68 73 218 (14) (0.32) (0.97) 1.Entire pointed portion of the fastener must penetrate through the cold-formed steel to obtain tabulated values. 2.The allowable tension and shear values are for the fastener only.Members connected to the cold-formed steel must be investigated separately in accordance with accepted design criteria. 3.Fastener is to be installed in the center of the stud flange. 4.Loads are based on cold-formed steel members with a minimum yield strength,Fy=33 ksi and tensile strength, Typical GDPSK Fu=45 ksi for 33 mil(20 ga.)and 43 mil(18 ga.),and minimum yield strength,Fy=50 ksi and tensile strength, Fu=65 ksi for 54 mil(16 ga.)and 68 mil(14 ga.) Installation See p.12 for an explanation of the load table icons. 197 IIIIELIIIIIIIIIIIIIIIII Hilti PROMS Engineering 3.0.67 www.hilti.com Company: Page: 2 Address: Specifier: Phone I Fax: E-Mail: Design: SW in-plane shear anchor bolts Date: 2/22/2021 Fastening point: 1.1 Design results Case Description Forces[lb]/Moments[in.lb] Seismic Max.Util.Anchor[%] 1 Combination 1 N=0;Vx=0;Vy=4,200; yes 69 Mx=0;My=0;Mz=0; Nsus=0;Mx,sus=0;My,sus=0; i Input data and results must be checked for conformity with the existing conditions and for plausibility! PROFIS Engineering(c)2003-2021 Hilti AG,FL-9494 Schaan Hilti is a registered Trademark of Hilti AG,Schaan 2 111�I� Hilti PROFIS Engineering 3.0.67 www.hilti.com Company: Page: 4 Address: Specifier: Phone I Fax: E-Mail: Design: SW in-plane shear anchor bolts Date: 2/22/2021 Fastening point: 4 Remarks; Your Cooperation Duties • Any and all information and data contained in the Software concern solely the use of Hilti products and are based on the principles,formulas and security regulations in accordance with Hilti's technical directions and operating,mounting and assembly instructions,etc.,that must be strictly complied with by the user. All figures contained therein are average figures,and therefore use-specific tests are to be conducted prior to using the relevant Hilti product. The results of the calculations carried out by means of the Software are based essentially on the data you put in. Therefore,you bear the sole responsibility for the absence of errors,the completeness and the relevance of the data to be put in by you. Moreover,you bear sole responsibility for having the results of the calculation checked and cleared by an expert,particularly with regard to compliance with applicable norms and permits,prior to using them for your specific facility. The Software serves only as an aid to interpret norms and permits without any guarantee as to the absence of errors,the correctness and the relevance of the results or suitability for a specific application. • You must take all necessary and reasonable steps to prevent or limit damage caused by the Software. In particular,you must arrange for the regular backup of programs and data and,if applicable,carry out the updates of the Software offered by Hilti on a regular basis.If you do not use the AutoUpdate function of the Software,you must ensure that you are using the current and thus up-to-date version of the Software in each case by carrying out manual updates via the Hilti Website. Hilti will not be liable for consequences,such as the recovery of lost or damaged data or programs,arising from a culpable breach of duty by you. Input data and results must be checked for conformity with the existing conditions and for plausibility! PROFIS Engineering(c)2003-2021 Hilti AG,FL-9494 Schaan Hilti is a registered Trademark of Hilti AG,Schaan 4 Hilti PROMS Engineering 3.0.67 www.hilti.com Company: Page: 2 Address: Specifier: Phone I Fax: E-Mail: Design: SW new HDU epoxy anchor bolt-North Date: 2/22/2021 Fastening point: 1.1 Design results Case Description Forces[lb]/Moments[in.lb] Seismic Max.Util.Anchor[%] 1 Combination 1 N=15,299;Vx=0;Vy=0; yes 91 Mx=0;My=0;Mz=0; Nsus=0;Mx,sus=0;My,sus=0; Input data and results must be checked for conformity with the existing conditions and for plausibility! PROFIS Engineering(c)2003-2021 Hilti AG,FL-9494 Schaan Hilti is a registered Trademark of Hilb AG,Schaan 2 IIIIIII 1 111 II�1111�1�1�II Hilti PROMS Engineering 3.0.67 www.hilti.com Company: Page: 4 Address: Specifier: Phone I Fax: E-Mail: Design: SW new HDU epoxy anchor bolt-North Date: 2/22/2021 Fastening point: 4 Remarks; Your Cooperation Duties • Any and all information and data contained in the Software concern solely the use of Hilti products and are based on the principles,formulas and security regulations in accordance with Hilti's technical directions and operating,mounting and assembly instructions,etc.,that must be strictly complied with by the user. All figures contained therein are average figures,and therefore use-specific tests are to be conducted prior to using the relevant Hilti product. The results of the calculations carried out by means of the Software are based essentially on the data you put in. Therefore,you bear the sole responsibility for the absence of errors,the completeness and the relevance of the data to be put in by you. Moreover,you bear sole responsibility for having the results of the calculation checked and cleared by an expert,particularly with regard to compliance with applicable norms and permits,prior to using them for your specific facility. The Software serves only as an aid to interpret norms and permits without any guarantee as to the absence of errors,the correctness and the relevance of the results or suitability for a specific application. • You must take all necessary and reasonable steps to prevent or limit damage caused by the Software. In particular,you must arrange for the regular backup of programs and data and,if applicable,carry out the updates of the Software offered by Hilti on a regular basis.If you do not use the AutoUpdate function of the Software,you must ensure that you are using the current and thus up-to-date version of the Software in each case by carrying out manual updates via the Hilti Website. Hilti will not be liable for consequences,such as the recovery of lost or damaged data or programs,arising from a culpable breach of duty by you. Input data and results must be checked for conformity with the existing conditions and for plausibility! PROFIS Engineering(c)2003-2021 Hilti AG,FL-9494 Schaan Hilti is a registered Trademark of Hilb AG,Schaan 4 IIet7M Hilti PROMS Engineering 3.0.67 www.hilti.com Company: Page: 2 Address: Specifier: Phone I Fax: E-Mail: Design: SW new HDU anchor bolt-South Date: 2/24/2021 Fastening point: 1.1 Design results Case Description Forces[lb]/Moments[in.lb] Seismic Max.Util.Anchor[%] 1 Combination 1 N=11,500;Vx=0;Vy=0; yes 58 Mx=0;My=0;Mz=0; Nsus=0;Mx,sus=0;My,sus=0; Input data and results must be checked for conformity with the existing conditions and for plausibility! PROFIS Engineering(c)2003-2021 Hilti AG,FL-9494 Schaan Hilti is a registered Trademark of Hilti AG,Schaan 2 IIII IIII II�1�11��I Hilti PROMS Engineering 3.0.67 www.hilti.com Company: Page: 4 Address: Specifier: Phone I Fax: E-Mail: Design: SW new HDU anchor bolt-South Date: 2/24/2021 Fastening point: 4 Remarks; Your Cooperation Duties • Any and all information and data contained in the Software concern solely the use of Hilti products and are based on the principles,formulas and security regulations in accordance with Hilti's technical directions and operating,mounting and assembly instructions,etc.,that must be strictly complied with by the user. All figures contained therein are average figures,and therefore use-specific tests are to be conducted prior to using the relevant Hilti product. The results of the calculations carried out by means of the Software are based essentially on the data you put in. Therefore,you bear the sole responsibility for the absence of errors,the completeness and the relevance of the data to be put in by you. Moreover,you bear sole responsibility for having the results of the calculation checked and cleared by an expert,particularly with regard to compliance with applicable norms and permits,prior to using them for your specific facility. The Software serves only as an aid to interpret norms and permits without any guarantee as to the absence of errors,the correctness and the relevance of the results or suitability for a specific application. • You must take all necessary and reasonable steps to prevent or limit damage caused by the Software. In particular,you must arrange for the regular backup of programs and data and,if applicable,carry out the updates of the Software offered by Hilti on a regular basis.If you do not use the AutoUpdate function of the Software,you must ensure that you are using the current and thus up-to-date version of the Software in each case by carrying out manual updates via the Hilti Website. Hilti will not be liable for consequences,such as the recovery of lost or damaged data or programs,arising from a culpable breach of duty by you. Input data and results must be checked for conformity with the existing conditions and for plausibility! PROFIS Engineering(c)2003-2021 Hilti AG,FL-9494 Schaan Hilti is a registered Trademark of Hilti AG,Schaan 4