Materials Testing & Consulting, Inc.
Geotechnical Engineering&Consulting•Special Inspection•Materials Testing•Environmental Consulting
Water Stain - 19S298 - Field Report: Other: Report #F220032
CLIENT Alta Forest Products DATE 11/18/2019
PROJECT LOCATION 780 West State Route 108 Shelton WA PERMIT#COM20-0049
Inspection Information:
Inspection Date: Time Onsite: 8:00 Weather Mid 40's Cloudy
11/18/2019 am Conditions:
Inspection Performed: 1 Other
.. .... .w.aeeeme e _m _ ... __....�._.
Comments:
MTC Inspector,on site,as requested for pull-testing of the Stain Shack.
After arriving on site I spoke with Alta rperesentatives&Vector Engineer who directed me to the testing location.
The 3/4"anchor bolts were tested to a load of 3200 lbs.
This was observed by everyone mentitoned above.
See picture below for more information.
__
To the best of MTC inspector's knowledge,the above-described work was performed in general accordance with project
specifications and approved plans.
Images:
b
t . 8 3
_.. � .
UPLOADED: 11/19/2019 20:04:32
REPORTED BY:Ben Erskine REVIEWED BY:Michael Houser,Project Manager
Corporate - 777 Chrysler Drive • Burlington, WA 98233 • Phone 360.755.1990 • Fax 360.755.1980
Regional Offices: Olympia Bellingham Silverdale Tukwila
360.534.9777 360.647.6111 360.698.6787 206.241.1974
Visit our website: www.mtc-inc.net
Water Stain-19S298,1111812019,#F220032,Page 1 of 1
MTC
Materials Testing. & Consulting, Inc.
Geotechnical Engineering&Consulting•Special Inspection•Materials Testing•Environmental Consultinge+�n•��
Water Stain - 19S298 - Field Report: Structural Steel, Job site: Report #F216418
CLIENT Alta Forest Products DATE 10/04/2019
PROJECT LOCATION 780 West State Route 108 Shelton WA PERMIT #COM20-0049
Inspection Information:
Inspection Date: Time Onsite: 8:00 Weather
10/04/2019 am Conditions: 50 s Partly Cloudy
._ ___. .
Inspection Performed: Structural Steel Job site
Report Profile:
®Any Deficiencies Noted 0 Needs Engineer's Approval
Comments:
Sheet(s): S-1 thru S-5
Location(s):Water Stain Shack Support Framing-No Gridlines Available
Elevation(s):Platform-Varies
Detail(s):Section Cuts,Details,&Elevations on Provided Sheets
s
MTC Inspector on site,as requested,for as-built inspection for Water Stain Shack Support Framing.
Upon arrival I met with Alta Rep Dan&Ben with Vector Engineering.
Current permit drawings were provided&the structure was walked with the individuals noted above.
Building conditions varied from drawing&inspection requirements&Alta intends to put together updated As-Built
drawings&submit to vector&the jurisdication for finalapproval.
Items that varied from plan included:
• Welders did not possess WABO certification nor was a Weld Procedure Specification available,all welds were
previuosly welded.
• Steel connections did not match the structural drawings&welds were used in lieu of high-strength bolts,
shear tabs were excluded,beams coped,etc.
• Anchor rods varied in embed depth but were stated to all be at 7"or greater.Epoxy used was common
HY-200&a P.O.was given for the product but no special inspection performed.
• Weld quality did not meet AWS Table 6.1 visual acceptance criteria.Weld size was deemed a consistent 1/8"
Fillet at best but possesed undercut,underun,undersize,excessive convexity/cold-roll,&fit-up potentially in
question per above.
• Columns were not welded 1/4"fillet, all-around per detail B/S-5 due to fit-up,nor was a seam weld provided.
MTC report is provided to cover basic Q.A.&Special Inspection requirements of the building and will provide report,and
'defer to Vector Engineering for review&acceptance.
.—... __. __ _ .
REPORTED BY:Ben Erskine REVIEWED BY:Michael Houser,Project Manager
Corporate • 777 Chrysler Drive • Burlington, WA 98233 • Phone 360.755.1990 • Fax 360.755.1980
Regional Offices: Olympia Bellingham Silverdale Tukwila
360.534.9777 360.647.6111 360.698.6787 206.241.1974
Visit our website: www.mtc-inc.net
Water Stain-19S298,1010412019,#F216418,Page 1 of 1
FN
cr�.v r
..
6 1 N E E ! I N 6 \ l N E
2724 Black Lake Blvd. SW Suite 202
Tumwater WA 98512
Phone: 360-352-2477 Fax: 360-352-0179 Toll Free:844 204-5179
Technical Memorandum
To: Dan Florek
CC: File
From: VEI Staff
Date: 11/18/2019
Re: Final Project Acceptance for Water Stain Booth (Reviewed by Engineer of Record)
Dan,
This technical memorandum is pursuant to the meeting that took place on site October 4th,
2019. Parties present for this meeting were Materials Testing and Consulting (MTC)
personnel, Dan Florek of Alta Forest Products (Alta FP), and Benton Cook of Vector
Engineering (Engineer of Record). The purpose of the meeting was to address required
special inspections for the project. MTC provided a field report regarding this meeting that
deferred to Vector Engineering Incorporated (VEI) for final acceptance of the project due to
differences between planned and as-built conditions. Specifically; the epoxy anchor rods,
welding, and final project acceptance (see attached MTC Field Report #F216418).
VEI staff returned for another on site meeting/inspection November 18th, 2019. The
meeting's purpose was to address the issues noted in MTC's initial report, and to perform an
in-situ load test on the post installed epoxy anchor rods. MTC personnel, along with Dan
Florek and Brad Prihoda of Alta FP were present for this meeting as well. A post-installed
epoxy anchor rod was tested by MTC personnel to a tensile force of 3,200 pounds, which is
greater than the maximum factored design load (see attached MTC Field Report #F220032).
VEI personnel performed a non-invasive visual inspection of the welds and deemed them
acceptable, besides a few minor issues noted on the Welding Procedure Forms completed by
VEI personnel during the inspection (see attached WPS Forms). The minor issues noted on
the WPS forms were corrected by Alta FP personnel. VEI personnel then updated the
original project drawings to reflect the project's as-built conditions (see attached as-built
drawings).
The field welding of this project was completed by Alta FP employees prior to inspection. In
lieu of the standard special inspections for welding, the welds were inspected for general
conformance by VEI staff, then reviewed by the engineer of record Benton Cook for final
acceptance. Special inspections for this project are in general compliance with the Mason
County Special Inspections &Testing Agreement (see attached copy), except the field
welding and post installed anchorage as previously noted. The Table of Special Inspections
in the approved plan set complies with the Mason County Special Inspections &Testing
Agreement as well.
Welding was done in general accord with the WPS provided by VEI and approved by the
engineer of record. Inspection was visual only. The inspected work appeared adequate
after execution.
It appears the work substantially conforms with the intent of the design and that the
building is suitable for occupancy.
x:\2018 jobs\a1ta02(spray room)\communication\tech memos\final acceptance of project.docx
Please feel free to call or email if you care to discuss.
Sincerely, VEI Staff
Reviewed By: Benton S. Cook (Engineer of Record)
17984 w
ICISTL-ti����y1�
S��NAi 12.05.19
X:\2018 Jobs\AIta02(Spray Room)\Communication\Tech Memos\Final Acceptance of Project.docx
Page 2 of 2