Loading...
HomeMy WebLinkAboutBLD94-0794 Finished Basement - BLD Permit / Conditions - 2/20/1997 i MASON COUNTY DEPARTMENT of GENERAL SERVICES Mason County Bldg.III 426 W.Cedar P.O.Box 186 Shelton,Washington 98584 (360)427-9670 BUILDING PARKS&RECREATION FAIR/CONVENTION CENTER ADMINISTRATION MASON COUNTY NON-RESIDENTIAL ENERGY CODE REVIEW COMMENTS RE: BLD 94-0794 Belfair Assembly of God Finish lower floor ENVELOPE REQUHURMENTS: Slab on grade, R-10 2x6 walls, R-19 Doors, U- .60 maximum R-19 trade-off allowed for walls) Below grade walls, R-0 (note Windows, U- .90 maximum MECHANICAL SYSTEM: The mechanical system was installed when the building was originally constructed. Any changes/alterations to the existing system will require compliance to the 1994 Non- Residential Energy Code. LIGHTING: 1. Each space enclosed by walls, temporary partitions, or ceiling height partitions shall have lighting controls capable of turning of all lights in that space. The switches shall be readily accessible and located at the point of entry/exit. 2 . All daylighted zones shall be switched independently from lights in the general lighting area. Daylighted zones extend into the space 15 feet from the glazed wall . See notes on plans, "J-5 . " 3 . Each classroom shall be equipped with automatic controls to shut off the lighting during unoccupied hours. Automatic controls may be an occupancy sensor, time switch, or other device capable of automatically shutting off lighting. NOTE: If an occupancy sensor lights no more than 30 minutes is s h capable of turning off g after the area is vacated. If automatic time switches are installed the time switches beingshall sethave for 7 different day clock, and be capable day types per week. Time switches must also have program back-up capabilities which prevent the loss of power and time settings for at least 10 hours, if power is interrupted. R MASON COUNTY DEPARTMENT of GENERAL SERVICES Mason County Bldg.III 426 W.Cedar P.O.Box 186 Shelton,Washington 98584 (360)427-9670 FAIR/CONVENTION CENTER ADMINISTRATION BUILDING PARKS&RECREATION 4 . Based upon the plans submitted the maximum light wattage are listed for each room. Prior to the final inspection of each room a detailed lighting plan of all lights installed must be submitted to the Mason County Building Dept. The lighting plan shall include the light wattage for lamps AND ballast. Entry #2/Stairwell 308 watts Corridor 1362 watts Mens restroom 96 watts Storage #7 75 watts Ladies restroom 200 watts Classroom #1 486 watts Stairwell 270 watts Classroom #2/storage #6 1102 watts Classroom #3 632 watts Classroom #4 475 watts Classroom #5, 6, 7, 8, & 9 5103 watts Kitchen EXEMPT Entry #3 152 watts to the 1994 If you have questionsode callding Toni Hermanseneor Debbera Coker Non- residential energy at 427-9670 ext. 284 . MASON COUNTY DEPARTMENT of GENERAL SERVICES Mason County Bldg.III 426 W.Cedar P.O.Box 186 Shelton,Washington 98584 (360)427-9670 BUILDING PARKS&RECREATION FAIR/CONVENTION CENTER ADMINISTRATION "MASON COUNTY STRUCTURAL REVIEW CONIl EUM" RE: BLD94-0794/COM[M ERCIAL BELFAIR ASSEMBLY OF GOD 1) (Per table 5-A) Occupancy Classification: A-3 2) (Per table 33-A #3 UBC) Max. occupancy load = Basement Room / 266 max 3) Proposed Floor area = 9000 Square Feet 4) (Chapter 22 UBC) Type'of construction = V ONE HOUR, DUE TO SQUARE FTG. 5) Occupancy specific requirements: A) (Sec. 602 (D): A-3 Located in basements or above the first floor shall not be of less than one-hour fire resistive construction. Div. 3 occupancies with a occupant load of 50 or more above usable space shall be separated from such space by a one-hour fire resistive construction. B) (Sec. 605) Light, Ventilation, Sanitation: All enclosed.portions of Group A occupancies customarily used by human beings and all dressing rooms shall be provided with natural light by means of exterior glazed openings not less than one tenth of the total floor area, or shall be provided with artificial light. C) (Sec. 1703) Usable space under floors: Usable space under first story shall be enclosed when constructed of wood or metal shall be protected on the side of the usable space by a one-hour fire resistive construction. Doors shall be self closing, non-combustible construction or solid wood core, not less than 1 3/4" thickness. D) (Sec. 1705)Folding, Portable, Movable Partitions: Need not have a fire resistive rating provided: 1). Do not block required exits or establish a corridor. 2). Location is restricted by means of permanent tracks, guides, or other methods. 3). Flammability shall be limited to table 42-B for flame spread. E) (Sec. 4305 (B) Ceiling membrane protection: When a ceiling forms a protective membrane for a floor ceiling fire resistive. The floor shall be without openings to protect structural elements. (See Exceptions) Page 2-3 Belfair Assembly of God F) (Sec. 4306 (C)Identification of Fire Door, Fire Windows, and Fire Dampers, shall have a label or other identification showing the fire protection rating. label shall be permanently affixed. G) (Sec. 4306 (n Fire Dampers: Shall comply with UBC #43-7 and shall be installed and be accessible for servicing in the following locations: 1). Duct penetrations of the ceiling of a fire resistive floor ceiling assembles. , 2). Duct penetrations of ceiling and fire rated corridors walls shall be fire/smoke dampers with a class III leakage. 6) Exits: A) (Sec. 3303 (C) Posting Room Capacity: Main assembly basement must have max occupant load posted in a conspicuous place on an approved sign near main exits from the room. B) (Sec. 3303 (D) Distance To Exits: Max travel distance to an exit door, horizontal exit is 150 feet in un-sprinkled building. This is why a rated corridor must be provided travel distance is over 150 feet. C) (Sec. 3304) (C) Exit Doors: Exit doors shall be operable from the inside without the use of a key or any special knowledge or effort. Manually operated edge or surface mounted flush bolts and surface bolts are PROHIBITED. When exit doors are used in pairs and approved automatic flush bolts are used, the door leaf having the automatic flush shall have no door knob or surface-mounted hardware. The unlatching of any leaf shall not require more than one operation. D) (Sec. 3304 (D) Panic Hardware: If installed shall comply with the requirements of UBC Standard No. 33-4. The activating member shall be mounted a height of not less than 30" inches or more than 44" inches above the floor. The unlatching force is same as regular doors 15 pounds in direction of travel. Panic Hardware shall be of the push pad type and the pad shall not extend across more than one half of the width of the door measured from the latch side. E) (Sec. 3304 (I) Floor Level at Doors: Regardless of the occupant load, there shall be a floor or landing on each side of door. The floor or landing shall not be more than 1/2 inch lower than the threshold of the doorway. F) (Sec. 3305 (B) Corridor width: Min 44" wide. Page 3-3 Belfair Assembly of God G) (Sec 3305 (C) Corridor height: Clear height of not less than 7' measured from lowest projection of ceiling. H) (See 3305 (H) Openings in Corridors: Every interior door opening shall be protected by a tight-fitting smoke-and draft-control assembly having a fire-protection rating of not less than 20 minutes when tested in accordance with U.B.C. Standard No. 43-2. Said doors shall not have louvers. The door and frame shall bear an approved label or other identification showing the rating thereof, the name of the manufacturer and the identification of the service conducting the inspection of materials and workmanship at the factory during fabrication and assembly. Doors shall be maintained self-closing or shall be automatic closing by actuation of a smoke detector in accordance with Section 4306 (b). 8) See Attached A.D.A. Requirements for all Handicapped Accessibility. 3 > 77, ZE m 'ro -4 M cfj Z 0 0 > 0 0 0 fS z z m ml 1.1) S 5) a m I-M VI CIO ml > C C -M R 0 V) a Ln --i 0 -j ?I OD w w -is > 0 cp tll> r, 0 C 0 -4 0 -4 0 -4 -4 Tr" v > m — Inm W -4m -1 aS -ar trt 0 a 0 > S C/) < 01" - 'r ," -.4 > ct) > m co en Ir — 0 Sri 0 05 > 0 z z co In D . . — --i cu Z,7 co x m ars0 C) PS! Fo In -n ell z z z 2w M z M CA rr- z z 10 OL > C) Ivs to 10 z z co C) zwr e, IZ 0 10 02 ha 46 am:= M G6 0�2 xrt 11117, 31 C z In 4w rr, 4D CONCRETE MECHANICAL MOBILE HOME Footings-Setback date by Ribbons date by Gas Piping date b Foundation Walls date by Set Up date by INSULATION date by BG/SLAB Insulation Floors Final date by date by date by FRAMING Walls FIRE DEPT. date by date by date by PLUMBING Attic OTHER Groundwork d date by ate b D.W.V. WALLBOARD NAILING !*1CC- 7—/d date aj by date by Water Line FINAL INSPECTION date by date by date by ^-- CA- w 9 j 2 �I //�3 cc- w� o��}�SS /fzv-Z 600, wh//�Nf-c�S,,�J Sff�Er O� //+�Ti4E.L,E,O .l�i�'/�//�'D !.✓f�EA�' Z2? ep r Xm> X Xx 3 mr- n mZAC t3ccrw - M =-5 Cf) /' <= jw j to 0 c MMZ> mw —0 Za >> to mr- C7 0 o e+ omzo=M —0 0 a<o w !U)0 m -oz zrnc=zto — I AD (D A Q6 CL J) 9) rn CD c m < ITA 03.T; Imz CY-,a M7 71 > 0 cv Pti > LO 17. CLZ 0 z r." a 0 M 00 0 0 U) ml 0> cn Z, 000 st > —41n=rll ow--io< OD 0 Cc Pet u) 4 rr z >ca-ozo--4 17 > lk 1+ (D :Z 0 OL 0 mlnm= w 0< 0 iRJ m4w = a z 5 (P 0 4=M 3E rm o"o 0 UP > c CA N) <fW nco z In rm Z" 000cozo 10 OL 00 0 0 11 -i > ODIC z = 0 0 mm a w (LIZM Ow-- zolDr-zo ID C to zo 0 T W- 06 9D z W T-N) Xo m -n cr 0 -nz a >0 Q 0 =--4 Z-<<< No Von o 4 C*)1-1 a xmm M Az < Co 2 r-C7 a z rn to z a)> cz Xrn Z6 0 c7m = L. Mi ' 4 t�� � o � � x n O >M owOD as Enz F In 0, C C; Z-< Cr 0 =r Z CD z C') M o 00 F+0 0 OL :r -C 4 0-4 0 --+ 0 oz (P zcn -7 C4 v zz Z 00 M (c) m ZO (r, zr > 7 (D z 0 V, z 10 Q. OD Q CYI > > =Z z fi - r+ CD I to 0 zr > z z