August 27 , 1999
Ted Tollefson
Belfair LLC
606 110th Ave N.E.
Bellevue, WA. 98004
Re . Belfair Valley Plaza, Retail shop A, Permit # bld99-0554
Your plan for the building permit referenced above has been
reviewed. This review letter contains only those comments related
to the Building Department plan review and does not reflect
additional needs of the other county departments . Please review the
following project data, assumptions, and the plan review comments .
It is important that you read the re-submittal instructions located
at the end of this letter.
PROJECT DATA
Owner Belfair Center L.L.C.
606-110th Ave N.E. , Suite 206
Bellevue, WA. 98004
Ph (425) 455-2848
Contact : Ted Tollefson
I
} Architect C.D.A. Architects Inc.
P.O. Box 55429
Seattle, WA. 98155
Ph (206) 368-9668
—.Fx(206) 368-9558
Contact : Heather Mertes
Structural Engineer Richard Hudson & Assoc.
1605 12th Ave. Suite 18
Seattle, WA. 98122
Ph (206) 324-6100
Fx (206) 324-6248
Contact : Rick Hudson, P. E.
Contractor NOT SHOWN
Assumptions 4000 sq. ft . retail facility
Occupancy - M
Construction - III-N as stated
on permit .
a
i
i
1
i
i
C
Assumptions Continued Occupant load - 127 persons
Exits required - 2
Restrooms required - 2
fully sprinkled
Code Editions 1997 Uniform Building Code
WAC 51-40
1997 Uniform Plumbing Code
WAC 51-46 , 51-47
1997 Uniform Mechanical Code
WAC 51-42
Please provide the following information
1997 UNIFORM BUILDING CODE & WAC 51-40
i
1 . Plan sheet A-2 . 1A indicates a two hour area separation wall and
parapet located at the south east side where the proposed retail
area connects with the existing Safeway. Section 504 . 6 . 2 of the UBC
requires that area separation walls in type III-N structures be not
less than 4 hour fire resistive construction. Please include your
listing number for the 4 hour fire resistive assembly and revise
the construction drawings to reflect .
2 . The occupant load calculated for the "M" occupancy of 127
persons will require that there be two exits from this area.
Section 1004 . 2 .4 requires that there be a minimum separation of 1/2
the diagonal dimension, this will require one of the rear doors be
used as a required exit . Please verify that there will be an
accessible route of travel back to the public way / ADA parking
area.
3 . Section 1107 and Table 11-F . I am unable to find the accessible
parking areas to show compliance to these sections . Please indicate
the area that will be used to show compliance with this section.
See plan sheet A-1 . 1
UNIFORM PLUMBING CODE & WAC 51-46 / 51-47
4 . Please provide a plumbing riser diagram and information showing
compliance with the above mentioned code. Additional permit will be
required, the application has been enclosed with this letter.
i
UNIFORM MECHANICAL CODE & WAC 51-42
i
5 . Please provide mechanical drawings and information demonstrating
compliance with the above mentioned code. Additional permit
required, the application has been enclosed with this letter.
6 . The general notes on the submitted plan- on sheet A-0 . 1 and sheet
S-4 indicate the engineers request for special inspection, please
complete the attached special inspection sheet and return it with
your re-submittal .
a. High strenght bolting
b. Rebar placement
c . Concrete
d. Masonary
e. Welding
f . Anchor bolts
g. Expantion bolts
Please make the requested corrections and submit two set of
plans showing the revisions . If only specific pages are affected in
the revisions, only those pages need to be re-submitted. Voided
sheets shall be removed from the collated sets . Be sure to include
any additional changes that have been made since the plans were
originally submitted. All corrections must be detailed in a
transmittal letter and the plan revision numbers must follow the
Isame order as the plan review letter.
Prior to re-submittal you must call the Plans Examining
Department to make arrangements for re-submittal , if a meeting is
needed or if you have any questions regarding this review you may
contact me at (360) 5427-9670 extension 595 . It is required that you
f notify the department that the re-submittal is being sent by mail
to aid in a timely review service . Meetings and intake of re-
submitted plans without prior arrangements will be denied.
The issuance or granting of a building permit or approval of
plans, specifications and computations shall not be construed to be
a permit for , or an approval of, any violations of any of the
provisions of this code, or of any other ordinances of this
jurisdiction, per UBC section 106 .4 . 3 .
Re-submittals are normally reviewed within (5) working days
after the revisions are received in our office.
Sincerely
i, Kelly Mayo
Mason County Building Department
Plans Examining
attached special inspection form.
Mechanical / Plumbing permit
wp/99-0554
3
r
r p� Tollef sonDavidson a
�U1. 2 319 JUL 2
SON
July 22 , 1991
Ms . Grace Miller , Planner
MASON COUNTY DEPT. of GENERAL SERVICES
P. 0. Box 186
Shelton , Washington 98584
Re: Belfair Valley Plaza
Dear Grace:
It was a pleasure talking with you earlier this morning. I am
enclosing a second site plan for the above captioned property
which can be " stamped approved" by the Planning Department and
returned to my office.
This procedure will permit me to deed property to the County for
construction of the proposed road between SR 3 and the Old
Belfair Highway.
Thank you for your time and co-operation .
Very truly yours ,
TO SON-DAVIDSON PROPERTIES
C/v�
BarclayYP
son
BT/tg
Enclosure