HomeMy WebLinkAboutBLD99-0554 Belfair Valley Plaza - COM Permit / Conditions - 8/27/1999 s August 27 , 1999 Ted Tollefson Belfair LLC 606 110th Ave N.E. Bellevue, WA. 98004 Re . Belfair Valley Plaza, Retail shop A, Permit # bld99-0554 Your plan for the building permit referenced above has been reviewed. This review letter contains only those comments related to the Building Department plan review and does not reflect additional needs of the other county departments . Please review the following project data, assumptions, and the plan review comments . It is important that you read the re-submittal instructions located at the end of this letter. PROJECT DATA Owner Belfair Center L.L.C. 606-110th Ave N.E. , Suite 206 Bellevue, WA. 98004 Ph (425) 455-2848 Contact : Ted Tollefson I } Architect C.D.A. Architects Inc. P.O. Box 55429 Seattle, WA. 98155 Ph (206) 368-9668 —.Fx(206) 368-9558 Contact : Heather Mertes Structural Engineer Richard Hudson & Assoc. 1605 12th Ave. Suite 18 Seattle, WA. 98122 Ph (206) 324-6100 Fx (206) 324-6248 Contact : Rick Hudson, P. E. Contractor NOT SHOWN Assumptions 4000 sq. ft . retail facility Occupancy - M Construction - III-N as stated on permit . a i i 1 i i C Assumptions Continued Occupant load - 127 persons Exits required - 2 Restrooms required - 2 fully sprinkled Code Editions 1997 Uniform Building Code WAC 51-40 1997 Uniform Plumbing Code WAC 51-46 , 51-47 1997 Uniform Mechanical Code WAC 51-42 Please provide the following information 1997 UNIFORM BUILDING CODE & WAC 51-40 i 1 . Plan sheet A-2 . 1A indicates a two hour area separation wall and parapet located at the south east side where the proposed retail area connects with the existing Safeway. Section 504 . 6 . 2 of the UBC requires that area separation walls in type III-N structures be not less than 4 hour fire resistive construction. Please include your listing number for the 4 hour fire resistive assembly and revise the construction drawings to reflect . 2 . The occupant load calculated for the "M" occupancy of 127 persons will require that there be two exits from this area. Section 1004 . 2 .4 requires that there be a minimum separation of 1/2 the diagonal dimension, this will require one of the rear doors be used as a required exit . Please verify that there will be an accessible route of travel back to the public way / ADA parking area. 3 . Section 1107 and Table 11-F . I am unable to find the accessible parking areas to show compliance to these sections . Please indicate the area that will be used to show compliance with this section. See plan sheet A-1 . 1 UNIFORM PLUMBING CODE & WAC 51-46 / 51-47 4 . Please provide a plumbing riser diagram and information showing compliance with the above mentioned code. Additional permit will be required, the application has been enclosed with this letter. i UNIFORM MECHANICAL CODE & WAC 51-42 i 5 . Please provide mechanical drawings and information demonstrating compliance with the above mentioned code. Additional permit required, the application has been enclosed with this letter. 6 . The general notes on the submitted plan- on sheet A-0 . 1 and sheet S-4 indicate the engineers request for special inspection, please complete the attached special inspection sheet and return it with your re-submittal . a. High strenght bolting b. Rebar placement c . Concrete d. Masonary e. Welding f . Anchor bolts g. Expantion bolts Please make the requested corrections and submit two set of plans showing the revisions . If only specific pages are affected in the revisions, only those pages need to be re-submitted. Voided sheets shall be removed from the collated sets . Be sure to include any additional changes that have been made since the plans were originally submitted. All corrections must be detailed in a transmittal letter and the plan revision numbers must follow the Isame order as the plan review letter. Prior to re-submittal you must call the Plans Examining Department to make arrangements for re-submittal , if a meeting is needed or if you have any questions regarding this review you may contact me at (360) 5427-9670 extension 595 . It is required that you f notify the department that the re-submittal is being sent by mail to aid in a timely review service . Meetings and intake of re- submitted plans without prior arrangements will be denied. The issuance or granting of a building permit or approval of plans, specifications and computations shall not be construed to be a permit for , or an approval of, any violations of any of the provisions of this code, or of any other ordinances of this jurisdiction, per UBC section 106 .4 . 3 . Re-submittals are normally reviewed within (5) working days after the revisions are received in our office. Sincerely i, Kelly Mayo Mason County Building Department Plans Examining attached special inspection form. Mechanical / Plumbing permit wp/99-0554 3 r r p� Tollef sonDavidson a �U1. 2 319 JUL 2 SON July 22 , 1991 Ms . Grace Miller , Planner MASON COUNTY DEPT. of GENERAL SERVICES P. 0. Box 186 Shelton , Washington 98584 Re: Belfair Valley Plaza Dear Grace: It was a pleasure talking with you earlier this morning. I am enclosing a second site plan for the above captioned property which can be " stamped approved" by the Planning Department and returned to my office. This procedure will permit me to deed property to the County for construction of the proposed road between SR 3 and the Old Belfair Highway. Thank you for your time and co-operation . Very truly yours , TO SON-DAVIDSON PROPERTIES C/v� BarclayYP son BT/tg Enclosure 606-110th Avenue N.E.,Suite 206 Bellevue,WA 98004 (206)455-2848