HomeMy WebLinkAboutFire Alarm System Certification - FIR Letters / Memos - 9/14/1998 FIRE ALARM SYSTEM CERTIFICATION AND DESCRIPTION
Complete Parts 1 and 3 through 9 after the system is installed, and the installation wiring has been checked.
Complete Part 2 after the operational tests have been performed.
PROTECTED SYSTEM SYSTEM SERVICE
PROPERTY INSTALLER SUPPLIER ORGANIZATION
Name Bisyak Commercial Building S&S Security Inc. same same
Address 24160 N.Hwy 3 610 1121'Street East some same
Belfair,Washington 98528 Tacoma,WA 98445
Representative Joanne&Neil Bisyak David E.Oliver some same
Telephone (360)372-2628
(360)698-5000 same same
Location of As-Built Drawings-At the"Protected Property'
Location of Owner's Manuals-At the"Protected Property'.
Location of Test Reports-Fire Marshall(Authority Having Jurisdiction) Alarm&Telecom Inc
1. CERTIFICATION OF SYSTEM INSTALLATION: (Fill out after installation is complete and wiring checked for opens,shorts,ground faults,and improper
branching,but prior to conducting operational acceptance tests.)
This system installation was inspected by James D.Stoddard,Sr Alarm Technician on 09/14/1998 and found to comply with the installation
requirements of:
i
X NFPA 72A,72B,72C,72D,V2E,72F
Article 760 of NFPA 70,National Electrical Code®
NFPA 72H
X Manufacturer's Instructions
Other(specify)
Signed Date September 14,1998
Organization S&S Security,Inc.
i
2. CERTIFICATION OF SYSTEM OPERATION:
All operational features and functions of this system were tested by James D.Stoddard,Sr.Alarm Technician on 09/04/1998 and found to be
operating in accordance with the requirements of:
X NFPA 72A,72B,72C,72D,72E,72F
Job Specifications
X Manufacturer's Instructions f
Other(specify)
Signed Date September 21 1998
Organization S&S Security Systems,Inc.
Test Witness for the Authority Having Jurisdiction Mason County Fire Marshall
3. TYPE(S)OF SYSTEM OR SERVICE:
NFPA 72A-Local. If alarm is transmitted to location(s)off premises,list where received: Alarm&Telecom,Inc.
NFPA 72B-Auxiliary. Indicate type of connection:
Local Energy Shunt Parallel Telephone Cellular Telephone
Location and telephone number for receipt of signals Alarm&Telecom,Inc. (360)698-5000
NFPA 72C-Remote Statioh:
Location and telephone number for receipt of signals
Alarm Alarm&telecom,Inc.(360)698-5000
Supervisory Alarm&telecom,Inc.(360)698-5000
NFPA 72D-Proprietary. If alarms are re-transmitted to Public Fire Service Communications Center or Central Station,indicate location
and telephone number of the organization receiving alarm
Indicate how alarm is retransmitted
NFPA 72F-Emergency Voice/Alarm Service:
Quantity of voice/alarm channels Single Multiple(specify)
Quantity of speakers installed Quantity of speaker zones
Quantity of telephones or telephone jacks included in system
F,
4. ALARM INITIATING DEVICES AND CIRCUITS:
Quantity and style(See NFPA 72A,Table 2-12.1)of initiating device circuits connected to system:
Quantity 8 Style Class"B"
Types and quantities of alarm initiating devices installed:
5 Manual Stations Non-Coded Coded
12 Smoke Detectors Ion Photo
Duct Detectors Ion Photo
1 Sprinkler Water Flow Switches
Other(list)
i
5. ALARM INDICATING APPLIANCES AND CIRCUITS:
Quantity of indicating appliance circuits connection to system
Q
Types and quantities of alarm indicating appliances installed:
1 Bells Size I Z'
6 Horns
Chimes
Other(specify)
12 Visible Signals Type ADA
Indicate whether: 6 combined with audible 6 mounted separately
6. SUPERVISORY SIGNAL INITIATING DEVICES AND CIRCUITS:
Quantity and style(see NFPA 72A,Table 2-12.1)of supervisory circuits: Quantity Style
Types and quantities of supervisory and signal initiating devices installed:
2 Sprinkler Control Valve Engine Fire Pump:
Building Temperature Fire Pump Power Quantity
Site Water Temperature Fire Pump Running Quantity
1 Site Water Supply PIV
Electric-Driven Fire Pump: Selector in Auto.Position Quantity
Selector in Auto.Position Quantity Control Panel Trouble Quantity
Engine or Control Panel Trouble Quantity Transfer Switch Quantity
Fire Pump Running Quantity Engine Running Quantity
Other Supervisory Function(specify): Quantity
7. SIGNALLING LINE CIRCUITS:
Quantity and style(See NFPA 72A,Table 2-13.1))of signaling line circuits connected to system:
Quantity 2 Style(s) Standard Telephone Line
8. SYSTEM POWER SUPPLIES:
a. Primary(Main): Normal Voltage 110 VAC Amps 2.5
Overcurrent Protection: Type 15 Amps
Location
b. Secondary(Standby):
2 Storage Battery: Amp-Hr.Rating 7 Amp/Hr
Calculated capacity to operate system,in hours XX 24 60
Engine-driven generator dedicated to fire alarm system
Location of fuel storage
c. Emergency or Standby System used as backup to Primary Power Supply,instead of using a Secondary Power Supply:
Emergency System described in NFPA 70,Article 700
Legally Required Standby System described in NFPA 70,Arficle 701
Optional Standby System described in NFPA 70,Article 702,which also meets the performance requirements of Article 700 or 701
9. SYSTEM DEVIATIONS FROM THE REFERENCED NFPA STANDARDS:
None
As per attached sheet(describe fully):