HomeMy WebLinkAboutWater Dist. #1 Pressure Zone #2 Water Storage Tank Concrete Report - BLD Engineering / Geo-tech Reports - 7/1/2002 " Krazan & A S S O C I A T E S INC .
GEOTECHNICAL ENGINEERING • ENVIRONMENTAL ENGINEERING
CONSTRUCTION TESTING & INSPECTION
July 1, 2002 KA Project No.: 106-02015
T. Bailey, Inc.
Ms. Bonnie Brodie
12441 Bartholomew Rd.
Anacortes, WA 98221
RE: Belfair Water Dist.#1, Pressure Zone#2, Water Storage Tank/Belfair, WA
Dear Ms. Brodie:
In accordance with your request and authorization, the following test data are presented on the following reports,
which are enclosed:
April 2 Concrete Report No. 2782
April 2 Concrete Report No. 2783
April 2 Concrete Report No. 2784
Referenced concrete reports and compressive strength data will be mailed following 28-day tests, if applicable.
If you have any questions, or if we can be of further assistance, please do not hesitate to contact our office.
Respectfully submitted,
Penn Seely, Laboratory Manager
Peninsula Division
PS:jm
Enclosures
Cc: Mason Cty.Bldg.Dept.—Mr.Larry Waters
Belfair Water Dist.- Mr.Jerry Hukill
RECEIVED
JUL 0 8 2002
426 W. CEDAR STlI
With Eleven Offices Serving The Western United States
20714 State Hwy. 305 NE, Suite 3C 0 Poulsbo, Washington 98370 • (360)598-2126 9 Fax: (360)598-2127
Krazan & Associates, Inc. 20714 State Hwy. 305 N.E. Suite 3C, Poulsbo, WA 98370 (360)-598-2126
Project No. 106-02015 Cyl. Code P3180 Pour Date 4-2-2002 Report No. 2782
Weather O'CAST Jurisdiction MASON COUNTY Permit No. COM 2002-00007
Project BELFAIR ZONE 2 TANK Engineer
Location BELFAIR, WA Architect
Client Contractor T. BAILEY INC.
Field Data Site Mix Reported Batch Data
Supplier FRED HILL Plant No. 4 Cement Type TIL 1 - II
j Concrete X Mortar Grout Flex Beams i Design Actual
jl
Prisms Grouted Ungrouted Other Mix No. ND6000PT
Conc. Air Cem.lbs. 653
Temp. Temp. Unit F.Ash lbs. 101
Time Truck# Ticket# %Air Slump (F) (F) wt.
8:15 58 42997 --- 5.5 58 55 C.agg.Ibs.
C.agg.lbs.2 3/8 595
C.agg.lbs.3 7/8 1383
Sand lbs. 1135
Water 20.7 GAL
Placement Area ! Admixture POLY 38.0 OZ .
j
Footings X Walls Columns Grade Beams other RHEOB 29.4 OZ
Slab/Deck Slab X Pilings Other
j iAir Ent.(oz/cwt.) .11 OZ
Grids FOOTING/SLAB FOR WATER TOWER.
Water Added on
Job(gals.) 0
Remarks PLACED BY PUMP/BOOM. VIBRATED.
RESTEEL PREVIOUSLY INSPECTED. ! Items Inspected
SAMPLED 40/342 CY W/C=0.26 X Conforming
Inspector J. GORDON Reviewed By Non-Conforming
Laboratory Data Design Strength 6000 Date Specimens Rec'd. 3 APR 02
Cyl. Test Dia Length Max. Comp. j Tested Break Test Method
Code Date Age Dim. Area Load Str. 'psi) set# y Type
P3180-1 4/9/2002 7 4X8 12.57 64670 5,140 TR 1 j ASTM C39 X
P3180-2 4/30/2002 28 4X8 12.55 84270 6,710 TR 2 j C-1231 X
P3180-3 4/30/2002 28 4X8 12.56 86060 6,850 TR 1
Other
P3180-4 4/30/2002 28 4X8 12.54 85640 6,830 TR 1
P3180-5 Compressive X
P3180-6 Flexural
P3180-7
P3180-8
Test Results
X Conforming
Remarks SET#1 FR#6064 Non-Conforming
Results Reviewed By Date Reviewed
Codes for Break Types: 1. Cone j 2. Cone&Split R/1
3. Cone&Shear F1
4. ShearF1 5. Columnar(Split)
Krazan & Associates, Inc. 20714 State Hwy. 305 N.E. Suite 3C, Poulsbo, WA 98370 (360)-598-2126
Project No. 106-02015 Cyl. Code P3188 Pour Date 4-2-2002 Report No. 2783
Weather O'CAST Jurisdiction MASON COUNTY Permit No. COM 2002-00007
Project BELFAIR ZONE 2 TANK Engineer
Location BELFAIR, WA Architect
Client Contractor T. BAILEY INC.
Field Data Site Mix Reported Batch Data
Supplier FRED HILL Plant No. 4 Cement Type TIL 1 - II
Design Actual
Concrete X Mortar Grout Flex Beams
Prisms Grouted Ungrouted Other Mix No. ND6000PT
Conc. Air Cam.lbs. 654
Temp. Temp. Unit F.Ash lbs. 103
Time Truck# Ticket# %Air Slump (F) (F) wt.
10:30 70 43032 --- 5.0 58 55 C.agg.lbs.
C.agg.lbs.2 3/8 595 '
I
C.agg.lbs.3 7/8 1370
I it
Sand lbs. 1137
Water 19.9 GAL
Placement Area
Admixture POLY 37.7 OZ .
Footings X Walls Columns Grade Beams other RHEOB 29.4 OZ
Slab/Deck Slab X Pilings Other
j IAir Ent.(oz/cwt.) .11 OZ 1
Grids FOOTING/SLAB FOR WATER TOWER.
Water Added on
Job(gals.) 0
Remarks PLACED BY PUMP/BOOM. VIBRATED. Items Inspected
RESTEEL PREVIOUSLY INSPECTED.
SAMPLED 203/342 CY W/C=0.31 X Conforming
Inspector J. GORDON Reviewed Byte'' Non-Conforming
Laboratory Data Design Strength 6000 Date Specimens Rec'd. 3 APR 02
Cyl. Test Dia Length Max. Comp. Tested Break Test Method
Code Date Age Dim. Area Load Str. (psi) Set# By Type
P3188-1 4/9/2002 7 4X8 12.55 71460 5,690 TR 1 ASTM C39 X
P3188-2 4/30/2002 28 4X8 12.55 90460 7,210 TR 1 C-1231 X
P3188-3 4/30/2002 28 4X8 12.55 89140 7,100 TR 2
Other
P3188-4 4/30/2002 28 4X8 12.55 91820 7,320 TR 1 1
P3188-5 Compressive X
P3188-6 Flexural
P3188-7
Test Results
P3188-8
X Conforming
Remarks SET#2 FR#6064 Non-Conforming n
Results Reviewed By � Date Reviewed
Codes for Break Types: 1. Cone 2. Cone&Split 3. Cone&Shear 4. Shear 5. Columnar(Split)
Krazan & Associates, Inc. 20714 State Hwy. 305 N.E. Suite 3C, Poulsbo, WA 98370 (360)-598-2126
,Project No. 106-02015 Cyl. Code P3189 Pour Date 4-2-2002 Report No. 2784
Weather O'CAST Jurisdiction MASON COUNTY Permit No. COM 2002-00007
Project BELFAIR ZONE 2 TANK Engineer
Location BELFAIR, WA Architect
Client Contractor T. BAILEY INC.
Field Data Site Mix Reported Batch Data
Supplier FRED HILL Plant No. 4 Dement Type TIL I - II
Concrete X Mortar Grout Flex Beams
Design Actual
Prisms Grouted Ungrouted Other
Mix No. ND6000PT
Conc. Air Cem.lbs. 650
Temp. Temp. Unit F.Ash lbs. 99
Time Truck# Ticket# %Air Slump (F) (F) Wt.
11:30 384 43045 --- 5.75 58 55 C.agg.lbs.
ii
C.agg.lbs.2 3/8 595
C.agg.lbs.3 7/8 1370
I i
Sand lbs. 1137
- Water 19.9 GAL
Placement Area Admixture POLY 38 OZ
Footings X Walls Columns Grade Beams Other RHEOB 29.6
Slab/Deck slab X Pilings Other -
lAir Ent.(oz/cwt.) .11 OZ
Grids FOOTING/SLAB FOR WATER TOWER.
Water Added on
Job(gals.)
I
Remarks PLACED BY PUMP/BOOM. VIBRATED. Items Inspected
RESTEEL PREVIOUSLY INSPECTED.
SAMPLED 300/342 CY W/C=0.32 X Conforming
Inspector J. GORDON Reviewed Byq` Non-Conforming
Laboratory Data Design Strength 6000 Date Specimens Rec'd- 3 APR 02
Cyl. Test Dia Length Max. Comp. Tested Break Test Method
Code Date Age Dim. Area Load Str. (psi) Set# By Type
P3189-1 4/9/2002 7 4X8 12.56 58340 4,640 TR 1 ASTM C39 X
P3189-2 4/30/2002 28 4X8 12.55 81660 6,510 TR 1
C-1231 X
P3189-3 4/30/2002 28 4X8 12.55 78160 6,250 TR 1 Other
P3189-4 4/30/2002 28 4X8 12.55 77730 6,160 TR 1
P3189-5 Compressive X
P3189-6 Flexural
P3189-7
Test Results
P3189-8
X Conforming
Remarks SET#3 FR#6064 Non-Conforming
Results Reviewed By Q 1 Date Reviewed
Codes for Break Types: 1. ConeF1 2. Cone&Split / 3. Cone& ShearF1 4. ShearF1 5. Columnar(Split)