HomeMy WebLinkAboutAutomatic Sprinkler System - FIR Inspections - 2/26/2007 KNIGHT FIRE PROTECTION, INC. �/�
9702 Lathrop Industrial Drive SW i�/ �'o. �� Y�14-ZI
Olympia, WA 98512 JURISDICTION
(360) 786-8606
FAX 360-786-8722 TECHNICIANS
�.2 P
LICENSE NO.#KMGBFP044LK DATE
"ON GUARD
24 HOURS A DAY" 1
AU
TOMATIC
C SPRINKLE
R SYSTEM S EM
i
CERTIFICATION INSPECTION
FACILITY c1d
Contact V Phone
Address
System# Size Type: Wet Preaction/ System#_ Size_ Type: Wet/Dry/Preaction/
System# Size ` Type et Dry/Preaction/ System#_ Size_ Type: Wet/Dry/Preaction/
A. GENERAL INFO TION
1. Occupancy: ssem-b Mercantile Office Storage High Rise (7 stories or more)
Use or Storage of azar ous Materials Stock Piled Over 12' High the3� /ti(uc
2. Describe fire protection modifications since last inspection /Joa
3. Describe any fires since last inspection {V 0N-E.
4. Date sprinkler system installed(approximate if unknown)
5. Previous type of occupancy at that time(if known)
6. When was the system piping last checked for stoppage, corrosion or foreign material ( AIe-NQ,-1J,J
B. INSPECTOR'S SECTION (All responses reference current inspection) YES NO N/A
1. GENERAL
a. Is the system hydraulically designed
b. If hydraulically designed, are risers properly marked per NFPA 13
C. If not hydraulically designed indicate the piping schedule:
Light Ordinary Extra _ Special _
d. Are all areas of buildin ovided with sprinkler protection per NFPA 13
e. Height of buildm stories r feet)
£ Is the building occ '
g. In areas protected by wet system, does building appear to be properly heated
in all areas, including blind attics and perimeter areas where accessible
h. Do all exterior openings appear to be protected against freezing
i. Does the exterior condition of the sprinkler system appear to be satisfactory
2. CONTROL VALVES
a. Are all control valves in the appropriate position and locked, sealed or
equipped with a tamper switch
3. FIRE DEPARTMENT CONNECTIONS
a. Are fire department connections in good condition and properly maintained
b. Are fire department connection couplings free, caps in place, check valves
tight, and ball drips functional
c. Date fire department connection was last backflushed 6MKNoo)A/
O:\Templalesl.Senice Pape—kUnspection Forms Masks\Certificate of Inspection AFSS.dw
A
FACILITY: h7-'0kE6PSVK
4. ANTIFREEZE/WARM WEATHER SYSTEMS YES NO N/A
a. Are all cold weather valves in appropriate open or closed position
b. Have antifreeze solutions been tested
c. Were the antifreeze test results satisfactory
5. ALARMS
a. Did water motor gong/electric bell test satisfactorily
b. Did electric alarm test satisfactorily
c. Is system monitored
By whom --C Az.&ajZ . C-F �N
Phone Xd6--7Tj- 2g90 Aect# Ss 9 a I
d. Is the monitoring center receiving signals satisfactorily
e. Water flow alarm \e<- Test Satisfactorily
f. Valve tamper monitoring_� ` / Test Satisfactorily
g. Dry system low/high-low air pressure sensor 7� Test Satisfactorily
6. SPRINKLERS I A w'_
a. Are all sprinklers free from corrosion, loading or obstruction to spray discharge ?�
b. Are sprinklers less than 50 years old NdSw 1
c. Is a complete stock of spare sprinklers and required wrenches available — ns
d. Are sprinkler temperature ratings proper for their location
e. Are sprinkler deflectors proper distances from structure and/or storage
IK-
7. DRY SYSTEMS
a. Is the dry valve in service
b. Are air pressure and priming water in accordance with mfg.'s instructions
c. Has the operation of the air supply been tested and is it in service
Automatic_ Manual
d. Were low points drained during inspection
e. Did quick opening devices operate satisfactorily
f. Did dry valve trip properly during this testing
g. Did heating equipment in valve room operate at the time of inspection
h. Date piping last checked for proper pitch VNWiNW41
i. Internal exam of piping conducted in LN ori,w (Required every 10 years)
j. Date dry pipe valve trip tested, control valve open .Z 26 v 7 (Required every 3 years)
k. Date quick opening device tested 0 26 a 7 (Required every year)
DRY VALVE Q.O.D.
MAKE MODEL SERIAL NO. MAKE MODEL SERIAL NO.
DRY PIPE
OPERATING
TEST DATA
WATER INITIAL TIME TO TRIP TRIP POINT TIME OF WATER Q.O.D.
PRESSURE AIR PRESS. THRU TEST PIPE AIR PRESS. TO TEST OUTLET 3 � ALARM ALARM .TRIP
PSI PSI MIN. SEC. PSI MIN. SEC. FULL TRIP LOCAL REMOTF. O.K.
SYSTEM
# Ins � � I 3 ! 18 5s Yes x �Vo
SYSTEM
#
SYSTEM
SYSTEM
FACILITY: 4-2—,p�gS 0 ao4 jNAJ
8. MAIN DRAIN WATER FLOW TESTS MADE AT SPRINKLER RISERS
Sys. Test Pipe Size Static Pressure Before Residual (Flow) Static Pressure
# Location Test Pipe (Above Clapper) Pressure After
ser 2 ' 1 1/4"/3/4"
s r 2' 1 1/4"/3/4"/ p �O
Riser/ "/ 1 1/4"/3/4"/—
Riser/ 2"/ 1 1/4"/3/4"/
9. EXPLAIN APPLICABLE "NO" ANSWERS AND COMMENTS
Si£ D F c r`v /IV
10. ADJUSTMENTS OR CORRECTIONS MADE DURING THIS INSPECTION
11. ALTHOUGH THESE COMMENTS ARE NOT THE RESULT OF AN ENGINEERING REVIEW,
THE FOLLOWING DESIRABLE IMPROVEMENTS ARE RECOMMENDED
System# is: System# ?, is:
❑ operational ❑ operational
operational with defects 'operational with defects
❑ not operational ❑ not operational
System# is: System# is:
❑ operational ❑ operational
❑ operational with defects ❑ operational with defects
❑ not operational ❑ not operational
This is to certify that this automatic sprinkler system has been inspected and tested in accordance with the
standard adopted by the Wa hington State Fire Marshal and NFPA Standards 13 and 25.
Name Title
I F56c - 6r $D Date
(Signatur of Contractor)
�. Title �+��'�. Date
4&gnatu`reofwner's Representative)
KNIGHT FIRE PROTECTION, INC.
9702 LATHROP INDUSTRIAL DRIVE SW
OLYMPIA, WA 98512-9188
(360) 786-8606
FAX 786-8722
LICENSE NO. KNIGHFP044LK
"ON GUARD
24 HOURS A DAY"
FIRE SPRINKLER INSPECTION
FIELD NOTES
Date: February 26, 2007 Technician(s): JMF/SDK
Contact: Steve Phone: 360-490-6102
Facility: Alderbrook Inn Address: 7101 Highway 106
Monitoring Company: The Alarm Center Inc. Shelton, WA
Riser Room
1. No HS W head in spare head box.
Restaurant Area
1. SSP next to surface mount light in banquet office.
2. Missing escutcheons in walk-in cooler and freezer.
1"Floor
1. Missing escutcheons in several areas.
3`a Floor
1. Missing escutcheon(s) in bathroom of room 308.
2. Recommend changing 155'head to 200'head in electrical room by room 335.
4`h Floor
1. Painted head in room 420 by sink.
2. Recessed heads by surface mount light in laundry room and in hall by laundry(AAI).
Recommend repairing the star exhauster that did not operate and recommend installation of an
accelerator to help the DPV trip more quickly.
"QUALITY IS REMEMBERED... LONG AFTER PRICE IS FORGOTTEN!"
0AWordWS\Fie1d NdesMlderbrook 022607.dm